Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data...

26
Contents Description Page Table 1. Revision notes ................................................................ 2 Table 2 Breaker catalog number convention ............................................... 3 Table 3. Electronic trip unit catalog number convention....................................... 3 Table 4. Symmetrical RMS interruption ratings I cu (kA) for each breaker frame ..................... 4 Table 5. Curve notes .................................................................. 4 Labels Figure 1. Power Defense frame 6 trip unit front labels. ....................................... 4 PXR electronic trip unit curves Figure 2. 1600A/2000A frame PXR 20D / PXR 25 - I 2 t long delay and flat short delay . . .............. 5 Figure 3. 2500A frame PXR 20D / PXR 25 - I 2 t long delay and flat short delay . .................... 6 Figure 4. 1600A/2000A frame PXR 20 - I 2 t long delay and flat short delay . ........................ 7 Figure 5. 2500A frame PXR 20 - I 2 t long delay and flat short delay . . ............................. 8 Figure 6. 1600A/2000A frame PXR 20D / PXR 25 - I 2 t long delay and I 2 t short delay . ................ 9 Figure 7. 2500A frame PXR 20D / PXR 5 - I 2 t long delay and I 2 t short delay . ...................... 10 Figure 8. 1600A/2000A frame PXR 20 I 2 t long delay and I 2 t short delay . ........................ 11 Figure 9. 2500A frame PXR 20 I 2 t long delay and I 2 t short delay . . .............................. 12 Figure 10. 1600A/2000A frame PXR 20D / PXR 25 - I 4 t long delay and flat short delay . . ............ 13 Figure 11. 2500A frame PXR 20D / PXR 25 - I 4 t long delay and flat short delay . ................... 14 Figure 12. PXR 20D / PXR 25 ground (earth) flat delay . . ..................................... 15 Figure 13. PXR 20D / PXR 25 - ground (earth) I 2 t delay .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Figure 14. PXR 20 - ground (earth) flat delay . .............................................. 17 Figure 15. PXR 20 - ground (earth) I 2 t delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Figure 16. 1600A frame PXR 20D / PXR 25 - instantaneous and override.. . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 17. 2000A frame PXR 20D / PXR 25 - instantaneous and override. . ....................... 20 Figure 18. 2500A frame PXR 20D / PXR 25 - instantaneous and override. . ...................... 21 Figure 19. 1600A frame PXR 20 - instantaneous and override. ................................ 22 Figure 20. 2000A frame PXR 20 - instantaneous and override. ................................ 23 Figure 21. 2500A frame PXR 20 - instantaneous and override. ................................ 24 Figure 22. PXR 20 / PXR 20D / PXR 25 - maintenance mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Effective November 2019 Supersedes February 2019 Technical Data TD012068EN Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

Transcript of Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data...

Page 1: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

ContentsDescription Page

Table 1. Revision notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Table 2 Breaker catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Table 3. Electronic trip unit catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Table 4. Symmetrical RMS interruption ratings Icu (kA) for each breaker frame . . . . . . . . . . . . . . . . . . . . . 4Table 5. Curve notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

LabelsFigure 1. Power Defense frame 6 trip unit front labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

PXR electronic trip unit curves Figure 2. 1600A/2000A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . 5Figure 3. 2500A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . 6Figure 4. 1600A/2000A frame PXR 20 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 5. 2500A frame PXR 20 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Figure 6. 1600A/2000A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . 9Figure 7. 2500A frame PXR 20D / PXR 5 - I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . 10Figure 8. 1600A/2000A frame PXR 20 I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 9. 2500A frame PXR 20 I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 10. 1600A/2000A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. . . . . . . . . . . . . . 13Figure 11. 2500A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . 14Figure 12. PXR 20D / PXR 25 ground (earth) flat delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Figure 13. PXR 20D / PXR 25 - ground (earth) I2t delay.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 14. PXR 20 - ground (earth) flat delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 15. PXR 20 - ground (earth) I2t delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Figure 16. 1600A frame PXR 20D / PXR 25 - instantaneous and override.. . . . . . . . . . . . . . . . . . . . . . . . 19Figure 17. 2000A frame PXR 20D / PXR 25 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 18. 2500A frame PXR 20D / PXR 25 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . 21Figure 19. 1600A frame PXR 20 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Figure 20. 2000A frame PXR 20 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Figure 21. 2500A frame PXR 20 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Figure 22. PXR 20 / PXR 20D / PXR 25 - maintenance mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Effective November 2019Supersedes February 2019Technical Data TD012068EN

Time current curves Power Defense MCCBFrame 6 PXR electronic trip unitsStandards: UL, CSA, IEC, CCC

Page 2: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

2

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 1. Revision notes

ote: N Unless noted below, all curves remain unchanged from their prior revision.

Revision Curve number Page Date1 Power Defense frame 6 initial release 12/14/2018

2 Edits to curve notes 02/06/2019

3 Short delay tolerances adjusted Ground delay tolerance adjusted

11/07/2019

Page 3: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

3

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 2. Breaker catalog number convention

ote: N 1 See catalog for ## (protection type and available configured options).

Table 3. Electronic trip unit catalog number convention

ote: N IEC standard breakers include the CE mark; GB standard breakers include the CCC mark.

This information is provided only as an aid to understand the catalog numbers.

It is not to be used to build catalog numbers for circuit breakers or trip units as all combinations may not be available.

Poles

2 = 2 pole

3 = 3 pole

4 = 4 pole (programmable N)

Interrupting rating designator

kA at 480 V (UL)

M = 65

N = 85

P = 100

Continuous current rating

1600 = 1600 A

2000 = 2000 A

2500 = 2500 A

Terminals included

N = No terminals (imperial tapped conductors)

M = No terminals (metric tapped conductors)

Breaker family

PDG6 = Frame 6 global UL / CSA / IEC / GB

PDF6 = Frame 6 global-100% UL / CSA / IEC / GB (uses PDG trip units)

Trip unit type

E## = PXR 20 (1)

D## = PXR 20D (1)

P## = PXR 25 (1)

KNS = Molded case switch

PDG6 3 M 2500 P2M N

Poles

3 = 3 poles

4 = 4 poles with programmable neutral protection

Trip unit

PXR = Electronic trip unitAmpere frame rating

1600 = 1600 A frame

2000 = 2000 A frame

2500 = 2500 A frame

ETU trip unit style

E = PXR 20

D = PXR 20D

P = PXR 25

Style family

PDG6 = Frame 6 global UL / CSA / IEC / GB for PDG and PDF breakers

Features

N = None

R = Relays

Z = ZSI, relays

M = Modbus, relays

C = CAM interface, relays

D = Modbus, CAM interface, relays

W = ZSI & Modbus

X = ZSI, CAM interface. relays

Y = ZSI, Modbus, CAM interface, relays

ETU protection style

1 = -

2 = LSI

3 = LSIG

4 = LSI ARMS

5 = LSIG ARMS

PDG6 x PXR 3 1600 D 2 W

Accessories

x = Breaker accessory

Page 4: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

4

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 4. Symmetrical RMS interruption ratings Icu (kA) for each breaker frame

UL / CSA IEC / CCC

Voltage Frame 240V 480V 600V 240V 415V 440V 480V 525V 690V

Globally Rated

PDG6xM 125 65 35 135 70 50 50 30 15

PDG6xN 150 85 50 150 70 70 65 35 20

PDG6xP 200 100 65 200 100 100 85 40 35

Globally Rated

(UL 100%)

PDF6xM 125 65 35 135 70 50 50 30 15

PDF6xN 150 85 50 150 70 70 65 35 20

PDF6xP** 200 100 65 200 100 100 85 40 35

** 1600A and 2000A frames only.

Table 5. Curve notes

1. These curves apply for 50Hz and 60Hz applications

2. The maximum voltage rating for the frame style is stated in Table 4

3. These curves are comprehensive for Power Defense style circuit breakers including frame sizes, ratings and constructions stated.

4. The total clearing times shown include the response time for the trip unit, the breaker opening and the interruption of the current. The bottom of the time band is the minimum commit to trip time.

5. The end of the curve is determined by the application or the interrupting rating of the circuit breaker.

6. All electronic trip units have an over temperature protection feature that will trip the breaker when the internal temperature of the ETU is over 105ºC

7. All time current data based on 3 phase testing.

Labels

PXR 20 - unit with LSIG protection and maintenance mode pictured.

Figure 1. Power Defense frame 6 trip unit front labels.

PXR 25 and PXR 20D - unit with LSIG protection and maintenance mode pictured.

ote: N Trip unit drawings in Figure 1 are representative of the face plates provided. Values on the trip unit dials will change based upon the specific breaker and trip unit. Refer to the time current curve of the breaker or the PXR User Guide for the specific settings.

Page 5: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

5

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Curves

Figure 2. 1600A/2000A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 1600A/2000A PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5 9

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG/PDF 1600 A

PDG/PDF 2000 A

Min. 700 A 1000 AMax. 1600 A 2000 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 24s at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 9x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as follows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 6: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

6

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 3. 2500A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 2500A PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5 6

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG2500 A

Min. 1600 AMax. 2500 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 24s at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 6x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as follows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 7: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

7

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 4. 1600A/2000A frame PXR 20 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 1600A/2000A PXR20 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5

6

54

3

9

2

8

0.4

0.05

0.1

0.2

0.3

0.15

7

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Irsetting

PDG/PDF 1600 A

PDG/PDF 2000 A

1 700 A 1000 A2 800 A 1100 A3 900 A 1200 A4 1000 A 1250 A5 1100 A 1400 A6 1200 A 1600 A7 1250 A 1700 A8 1400 A 1800 A9 1500 A 1900 A10 1600 A 2000 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0% /-

30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short time delay slopes are shown with

tolerance. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.7.

Page 8: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

8

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 5. 2500A frame PXR 20 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 2500A PXR20 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5

3.5

5

4

3

6

2

4.5

0.4

0.05

0.1

0.2

0.3

0.15

2.5

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Irsetting

PDG 2500 A

1 1600 A2 1700 A3 1800 A4 1900 A5 2000 A6 2100 A7 2200 A8 2300 A9 2400 A10 2500 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0% /-

30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short time delay slopes are shown with

tolerance. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maxi-mum of 60ms for 60Hz and 63ms for 50Hz..

Page 9: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

9

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 6. 1600A/2000A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 1600A/2000A PXR20D / PXR25 - I2t Long Delay and I2t Short Delay Curves

1.5

0.067

0.3

8

tr setting range

Isdsetting range

tsd setting range

9

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Irsetting

PDG/PDF 1600 A

PDG/PDF 2000 A

Min. 700 A 1000 AMax. 1600 A 2000 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 24s at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 9x at steps of 0.1x with ±5% tolerance.

5. Short delay I2t slope time settings adjustable from 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have tolerances of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, trip-ping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 10: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

10

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 7. 2500A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 2500A PXR20D / PXR25 - I2t Long Delay and I2t Short Delay Curves

1.5

0.067

0.3

tr setting range

Isdsetting range

tsd setting range

6

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Irsetting

PDG 2500 A

Min. 1600 AMax. 2500 A

Notes: 1. Long delay pickup is 110% of the Ir setting with ±5%

tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 24s at steps of 0.1s with +0%/-30% tolerance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 6x at steps of 0.1x with ±5% tolerance.

5. Short delay I2t slope time settings adjustable from 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay set-tings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have tolerances of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 11: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

11

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 8. 1600A/2000A frame PXR 20 I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 1600A/2000A PXR20 - I2t Long Delay and I2t Short Delay Curves

1.5 6

0.067

0.3

0.15

3 42

7

8

5 9

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release

-PXR 20

Irsetting

PDG/PDF 1600 A

PDG/PDF 2000 A

1 700 A 1000 A2 800 A 1100 A3 900 A 1200 A4 1000 A 1250 A5 1100 A 1400 A6 1200 A 1600 A7 1250 A 1700 A8 1400 A 1800 A9 1500 A 1900 A10 1600 A 2000 A

Notes: 1. Long delay pickup is 110% of the Ir setting

with ±5% tolerance.2. Long delay time settings as shown have +0%

/-30% tolerance.3. If thermal memory is enabled, trip times may

be shorter than indicated in this curve.4. Short delay pickup settings as shown have

±5% tolerance.5. Short Delay I2t slope time settings are as fol-

lows: I2t slope time delay setting 0.300s has a tolerance of +0/-30%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay setting 0.300s has a tolerance of +0/-20%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 12: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

12

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 9. 2500A frame PXR 20 I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD6 2500A PXR20 - I2t Long Delay and I2t Short Delay Curves

1.5 5

0.067

0.3

0.15

3 42

2.5 3.5 4.56

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Irsetting

PDG 2500 A

1 1600 A2 1700 A3 1800 A4 1900 A5 2000 A6 2100 A7 2200 A8 2300 A9 2400 A10 2500 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0%

/-30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short Delay I2t slope time settings are as follows:

I2t slope time delay setting 0.300s has a tolerance of +0/-30%, time delay setting 0.150s has a toler-ance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay setting 0.300s has a tolerance of +0/-20%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maxi-mum of 60ms for 60Hz and 63ms for 50Hz.

Page 13: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

13

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 10. 1600A/2000A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Pickup (Ir)

PD6 1600A/2000A PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 9Isd

setting range

tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release

-PXR 20D / PXR 25

Irsetting

PDG/PDF 1600 A

PDG/PDF 2000 A

Min. 700 A 1000 AMax. 1600 A 2000 A

Notes: 1. Long delay pickup is 110% of the Ir setting

with ±5% tolerance. Ir is set from min to max at steps of 10 A

2. Long delay time settings adjustable from 0.5s - 7s at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 9x at steps of 0.1x with ±5% toler-ance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as follows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have toler-ances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 14: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

14

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 11. 2500A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Pickup (Ir)

PD6 2500A PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 6Isd

setting range

tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG2500 A

Min. 1600 AMax. 2500 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 7s at steps of 0.1s with +0%/-30% tolerance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 6x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as follows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 15: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

15

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 12. PXR 20D / PXR 25 ground (earth) flat delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Seco

nds

Current in Multiples of 1200A

PXR20D / PXR25 - Ground (Earth) Flat Delay Curves

0.2 1.0

0.1

1.0

Igsetting range

tg setting range

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. Ground pickup settings adjustable from 0.2x -

1.0x at steps of 0.010x for residual sensing with a tolerance of ± 10%.

2. Ground time delay settings adjustable from 0.100s – 1.00s at steps of 0.010s with tolerances as follows: time delay settings 1.00s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40%.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 16: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

16

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 13. PXR 20D / PXR 25 - ground (earth) I2t delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of 1200A

PXR20D / PXR25 - Ground (Earth) I2T Delay Curves

0.2 1.0

0.067

0.300

①Ig

setting range

tg setting range

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. Ground pickup settings adjustable from 0.2x -

1.0x at steps of 0.01x are for residual sensing with a tolerance of ± 10%.

2. Ground I2t slope time settings are adjustable from 0.067s – 0.300s at steps of 0.010s with tol-erances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay set-tings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have tolerances of +0/-50%. After approximately 1x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 17: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

17

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 14. PXR 20 - ground (earth) flat delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Seco

nds

Current in Multiples of 1200A

PXR20 - Ground (Earth) Flat Delay Curves

0.2

0.2 0.4 0.6 0.8 1.0

0.1

0.3

0.75

0.5

0.3

0.15

1.0

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release - PXR 20

Notes: 1. Ground pickup settings as shown are for residual

sensing with a tolerance of ± 10%. 2. Ground slope flat time setting are shown with

tolerances.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve. 4. With ZSI enabled and no auxiliary power, tripping

times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz

Page 18: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

18

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 15. PXR 20 - ground (earth) I2t delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of 1200A

PXR20 - Ground (Earth) I2T Delay Curves

0.150

0.2 0.5 1.0

0.067

0.300

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release - PXR 20

Notes: 1. Ground pickup settings as shown are for residual

sensing with a tolerance of ± 10%. 2. Ground slope flat time setting are shown with

tolerances.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve. 4. With ZSI enabled and no auxiliary power, tripping

times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz

Page 19: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

19

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 16. 1600A frame PXR 20D / PXR 25 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 1600A Frame Instantaneous Curves

Max10.92

IiSetting range

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

1600A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D /PXR 25

Notes: 1. The instantaneous pickup settings adjustable from

2x – 10.9x (max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 17500 A and has a ±15% tolerance.

Page 20: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

20

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 17. 2000A frame PXR 20D / PXR 25 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 2000A Frame Instantaneous Curves

2

Max8.8

IiSetting range

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

2000A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D /PXR 25

Notes: 1. The instantaneous pickup settings adjustable from

2x – 8.8x (max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 17500 A and has a ±15% tolerance.

Page 21: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

21

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 18. 2500A frame PXR 20D / PXR 25 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 2500A Frame Instantaneous Curves

2

Max7

IiSetting range

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

2500A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D /PXR 25

Notes: 1. The instantaneous pickup settings adjustable from

2x – 7x (max) at steps of 0.10x with a ±10% toler-ance.

2. For high fault current levels a fixed instantaneous override is provided at 17500 A and has a ±15% tolerance.

Page 22: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

22

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 19. 1600A frame PXR 20 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 1600A Frame Instantaneous Curves

2

Max10.9

8

7 10

6

5

43

9

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

1600A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release - PXR 20

Notes: 1. The instantaneous pickup settings as shown with a

±10% tolerance. 2. For high fault current levels a fixed instantaneous

override is provided at 17500 A and has a ±15% tolerance.

Page 23: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

23

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 20. 2000A frame PXR 20 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 2000A Frame Instantaneous Curves

2

Max8.8

8

7.5

8.5

6

5

43

7

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

2000A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release - PXR 20

Notes: 1. The instantaneous pickup settings as shown with a

±10% tolerance. 2. For high fault current levels a fixed instantaneous

override is provided at 17500 A and has a ±15% tolerance.

Page 24: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

24

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 21. 2500A frame PXR 20 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20 2500A Frame Instantaneous Curves

2

Max7

4.52.5 6.5

6

5

43

3.5

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

2500A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release - PXR 20

Notes: 1. The instantaneous pickup settings as shown with a

±10% tolerance. 2. For high fault current levels a fixed instantaneous

override is provided at 17500 A and has a ±15% tolerance.

Page 25: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

25

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 22. PXR 20 / PXR 20D / PXR 25 - maintenance mode. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR 20 / PXR 20D / PXR 25 - Maintenance Mode Curves

10

8

6

4

2.5

Time current curves Power Defense circuit breakersStyle: Frame 6Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20 / PXR 20D / PXR 25

Notes: 1. Reduction Pickup settings have a ±20%

tolerance.

Page 26: Power Defense time current curve Frame 6 - PD6 - Eaton · 2020-05-04 · 2 Technical Data TD012068EN Effective November 2019 Time current curves Power Defense MCCB Frame 6 PXR electronic

Eaton 1000 Eaton BoulevardCleveland, OH 44122United States877-ETN-CARE (877-386-2273)Eaton.com

© 2019 Eaton All Rights ReservedPrinted in USAPublication No. TD012068EN / TBG001425November 2019

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Technical Data TD012068ENEffective November 2019

Time current curves Power Defense MCCB Frame 6 PXR electronic trip units

Standards: UL, CSA, IEC, CCC