PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The...

16
Metroll Newcastle ABN 97 001 446 439 268 Macquarie Road WARNERS BAY NSW 2282 AUSTRALIA P: +61 (0)2 4954 5799 F: +61 (0)2 4954 0891 [email protected] www.metrollnewcastle.com.au 1 PURLINS & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa 3. The loads have been based on the use of approved Metroll sections & bridging systems. 4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal). 5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150 Span (mm) Overall purlin length = span + 70mm Table S100-Single Spans for Z/C100 Sections - Limit state capacity (kN/m) SECTION 10010 LOADING Inward Outward Def BRIDGING 0,1,2,3 0 1 2 3 2100 2400 2700 3000 3300 3600 3900 4200 4500 4800 5100 5400 5700 6000 6300 6600 3.53 2.70 2.13 1.73 1.43 1.20 1.02 0.88 0.77 0.67 0.60 0.53 0.48 0.43 0.39 0.36 2.99 1.81 1.15 0.76 0.53 0.37 3.53 2.70 2.13 1.73 1.43 1.11 0.84 0.63 0.48 3.53 2.70 2.13 1.73 1.43 1.20 1.02 0.88 0.77 0.67 0.58 0.47 3.53 2.70 2.13 1.73 1.43 1.20 1.02 0.88 0.77 0.67 0.60 0.53 0.48 3.73 2.50 1.75 1.28 0.96 0.74 0.58 0.47 0.38 0.31 0.26 0.22 0.19 0.16 0.14 0.12 Table S100-Single Spans for Z/C100 Sections - Limit state capacity (kN/m) SECTION 10012 LOADING Inward Outward Def BRIDGING 0,1,2,3 0 1 2 3 2100 2400 2700 3000 3300 3600 3900 4200 4500 4800 5100 5400 5700 6000 6300 6600 4.69 3.59 2.83 2.30 1.90 1.59 1.36 1.17 1.02 0.90 0.79 0.71 0.64 0.57 0.52 0.47 3.51 2.12 1.35 0.90 0.62 0.44 4.69 3.59 2.83 2.30 1.82 1.32 0.98 0.74 0.57 0.44 4.69 3.59 2.83 2.30 1.90 1.59 1.36 1.17 1.02 0.86 0.69 0.56 0.46 4.69 3.59 2.83 2.30 1.90 1.59 1.36 1.17 1.02 0.90 0.79 0.71 0.64 0.57 0.52 0.47 4.63 3.10 2.18 1.59 1.19 0.92 0.72 0.58 0.47 0.39 0.32 0.27 0.23 0.20 0.17 0.15

Transcript of PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The...

Page 1: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 1

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S100-Single Spans for Z/C100 Sections - Limit state capacity (kN/m)

SECTION 10010

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

2100240027003000330036003900420045004800510054005700600063006600

3.532.702.131.731.431.201.020.880.770.670.600.530.480.430.390.36

2.991.811.150.760.530.37

3.532.702.131.731.431.110.840.630.48

3.53 2.702.131.731.431.201.020.880.770.670.580.47

3.532.702.131.731.431.201.020.880.770.670.600.530.48

3.732.501.751.280.960.740.580.470.380.310.260.220.190.160.140.12

Table S100-Single Spans for Z/C100 Sections - Limit state capacity (kN/m)

SECTION 10012

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

2100240027003000330036003900420045004800510054005700600063006600

4.693.592.832.301.901.591.361.171.020.900.790.710.640.570.520.47

3.512.121.350.900.620.44

4.693.592.832.301.821.320.980.740.570.44

4.693.592.832.301.901.591.361.171.020.860.690.560.46

4.693.592.832.301.901.591.361.171.020.900.790.710.640.570.520.47

4.633.102.181.591.190.920.720.580.470.390.320.270.230.200.170.15

Page 2: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 2

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S100-Single Spans for Z/C100 Sections - Limit state capacity (kN/m)

SECTION 10015

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

210024002700300033003600390042004500480051005400570060006300660069007200

6.174.733.733.022.502.101.791.541.341.181.050.930.840.760.690.620.570.53

4.372.641.691.120.780.55

6.174.733.733.022.251.641.220.920.710.56

6.174.733.733.022.502.101.791.541.341.070.860.700.570.47

6.174.733.733.022.502.101.791.541.341.181.050.930.840.760.690.620.560.48

5.943.982.792.041.531.180.930.740.600.500.410.350.300.250.220.190.170.15

Table S100-Single Spans for Z/C100 Sections - Limit state capacity (kN/m)

SECTION 10019

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

210024002700300033003600390042004500480051005400570060006300660069007200 75007800

8.356.405.054.093.382.842.422.091.821.601.421.261.131.020.930.850.770.710.650.61

5.543.362.141.430.990.700.51

8.356.405.053.902.852.081.551.170.900.710.560.45

8.356.405.054.093.382.842.422.071.691.351.090.880.720.600.500.42

8.356.405.054.093.382.842.422.091.821.601.421.261.131.020.930.810.710.610.520.46

7.444.983.502.551.921.481.160.930.760.620.520.440.370.320.280.240.210.180.160.15

Page 3: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 3

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S100-Single Spans for Z/C100 Sections - Limit state capacity (kN/m)

SECTION 15012

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

210024002700300033003600390042004500480051005400570060006300660069007200750078008100

7.345.624.443.602.972.502.131.841.601.411.251.111.000.900.820.740.680.620.580.530.49

7.345.623.992.731.891.350.990.740.570.44

7.345.624.443.602.972.502.131.841.601.311.050.860.700.570.47

7.345.624.443.602.972.502.131.841.601.411.251.111.000.900.820.740.650.560.48

7.345.624.443.602.972.502.131.841.601.411.251.111.000.900.820.740.680.620.580.530.49

13.208.846.214.533.402.622.061.651.341.110.920.780.660.570.490.430.370.330.290.260.23

Table S150-Single Spans for Z/C150 Sections - Limit state capacity (kN/m)

SECTION 15015

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

21002400270030003300360039004200450048005100540057006000630066006900720075007800810084008700900093009600

10.828.296.555.304.383.683.142.712.362.071.841.641.471.331.201.101.000.920.850.780.730.680.630.590.550.52

10.827.825.063.402.371.691.240.930.710.550.44

10.828.296.555.304.383.683.142.712.111.661.331.070.870.720.590.500.42

10.828.296.555.304.383.683.142.712.362.071.841.641.471.331.150.970.820.700.600.520.45

10.828.296.555.304.383.683.142.712.362.071.841.641.471.331.201.101.000.920.850.780.730.680.630.590.540.48

17.2611.568.125.924.453.432.692.161.751.451.201.010.860.740.640.560.490.430.380.340.300.270.240.220.200.18

Page 4: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 4

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S150-Single Spans for Z/C150 Sections - Limit state capacity (kN/m)

SECTION 15019

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

300033003600390042004500480051005400570060006300660069007200750078008100840087009000930096009900

1020010500

7.536.225.234.463.843.352.942.612.322.091.881.711.561.421.311.201.111.030.960.900.840.780.740.690.650.61

4.323.002.151.581.180.900.700.55

7.536.225.234.463.442.682.111.681.351.100.910.750.630.530.45

7.536.225.234.463.843.352.942.612.322.091.741.461.231.050.890.770.660.570.500.44

7.536.225.234.463.843.352.942.612.322.091.881.711.561.421.311.201.111.030.960.880.780.700.620.550.500.45

7.635.734.423.472.782.261.861.551.311.110.950.820.720.630.550.490.430.390.350.310.280.260.230.210.190.18

Page 5: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 5

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S150-Single Spans for Z/C150 Sections - Limit state capacity (kN/m)

SECTION 15024

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

300033003600390042004500480051005400570060006300660069007200750078008100840087009000930096009900

10200105001080011100

10.248.477.116.065.234.554.003.543.162.842.562.322.121.941.781.641.521.411.311.221.141.071.000.940.890.840.790.75

5.473.802.722.001.501.140.890.700.560.45

10.248.477.115.624.353.392.672.131.721.401.150.950.800.670.570.490.42

10.248.477.116.065.234.554.003.543.092.632.201.851.561.321.130.970.840.730.630.550.49

10.248.477.116.065.234.554.003.543.162.842.562.322.121.941.781.641.521.381.241.110.990.880.780.700.630.560.510.46

9.607.215.554.373.502.842.341.951.651.401.201.040.900.790.690.610.550.490.440.390.360.320.290.270.240.220.210.19

Page 6: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 6

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S200-Single Spans for Z/C200 Sections - Limit state capacity (kN/m)

SECTION 20015

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

300033003600390042004500480051005400570060006300660069007200750078008100840087009000930096009900

10200105001080011100114001170012000

6.365.264.423.763.252.832.492.201.961.761.591.441.311.201.101.020.940.870.810.760.710.660.620.580.550.520.490.460.440.420.40

6.365.103.712.732.051.571.220.970.770.620.510.42

6.365.264.423.763.252.832.492.201.961.761.541.291.080.920.780.660.570.49

6.365.264.423.763.252.832.492.201.961.761.591.441.311.201.101.020.940.870.810.740.660.580.520.46

6.365.264.423.763.252.832.492.201.961.761.591.441.311.201.101.020.940.870.810.760.710.660.620.580.550.520.490.460.440.420.40

12.529.417.255.704.563.713.062.552.151.831.571.351.181.030.910.800.710.640.570.510.460.420.380.350.320.290.270.250.230.210.20

Page 7: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 7

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S200-Single Spans for Z/C200 Sections - Limit state capacity (kN/m)

SECTION 20019

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

3000.003300.003600.003900.004200.004500.004800.005100.005400.005700.006000.006300.006600.006900.007200.007500.007800.008100.008400.008700.009000.009300.009600.009900.00

10200.0010500.0010800.0011100.0011400.0011700.0012000.00

11.099.167.706.565.664.934.333.843.423.072.772.512.292.101.921.771.641.521.411.321.231.151.081.020.960.900.860.810.770.730.69

9.846.904.973.672.762.111.641.301.040.840.690.570.47

11.099.167.706.565.664.934.333.803.092.532.091.741.461.231.040.890.770.660.580.500.44

11.099.167.706.565.664.934.333.843.423.072.772.512.292.101.921.731.501.311.141.000.880.780.690.620.550.49

11.099.167.706.565.664.934.333.843.423.072.772.512.292.101.921.771.641.521.411.321.231.151.081.020.960.900.860.810.740.670.61

16.7312.579.687.626.104.964.083.412.872.442.091.811.571.381.211.070.950.850.760.690.620.560.510.470.430.390.360.330.300.280.26

Page 8: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 8

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S200-Single Spans for Z/C200 Sections - Limit state capacity (kN/m)

SECTION 20024

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

300033003600390042004500480051005400570060006300660069007200750078008100840087009000930096009900

10200105001080011100114001170012000

16.1013.3011.189.528.217.156.295.574.974.464.023.653.333.042.792.582.382.212.051.911.791.671.571.481.391.311.241.181.111.061.01

12.628.866.394.713.542.722.111.671.341.080.880.730.61

16.1013.3011.189.528.217.156.064.883.963.242.682.231.871.581.341.150.990.850.740.650.570.500.44

16.1013.3011.189.528.217.156.295.574.974.464.023.653.332.992.582.221.931.681.471.291.131.000.890.790.710.630.570.510.46

16.1013.3011.189.528.217.156.295.574.974.464.023.653.333.042.792.582.382.212.051.911.791.671.571.481.391.281.161.050.950.870.79

21.6216.2412.519.847.886.415.284.403.713.152.702.332.031.781.561.381.231.100.980.890.800.730.660.600.550.500.460.430.390.360.34

Page 9: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 9

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S250-Single Spans for Z/C250 Sections - Limit state capacity (kN/m)

SECTION 25019

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

300033003600390042004500480051005400570060006300660069007200750078008100840087009000930096009900

10200105001080011100114001170012000

13.7611.389.568.147.026.125.384.764.253.813.443.122.842.602.392.202.041.891.761.641.531.431.341.261.191.121.061.010.950.900.86

13.099.186.614.873.662.812.181.721.381.120.910.750.630.530.44

13.7611.389.568.147.026.125.384.764.113.362.772.311.941.631.391.191.020.880.770.670.590.520.46

13.7611.389.568.147.026.125.384.764.253.813.443.122.842.602.392.202.001.741.521.331.171.040.920.820.730.650.590.530.48

13.7611.389.568.147.026.125.384.764.253.813.443.122.842.602.392.202.041.891.761.641.531.431.341.261.191.121.061.010.950.900.82

28.2921.2516.3712.8810.318.386.915.764.854.123.543.052.662.332.051.811.611.441.291.161.050.950.860.790.720.660.610.560.520.480.44

Page 10: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 10

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S250-Single Spans for Z/C250 Sections - Limit state capacity (kN/m)

SECTION 25024

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

300033003600390042004500480051005400570060006300660069007200750078008100840087009000930096009900

10200105001080011100114001170012000

20.8117.2014.4512.3110.629.258.137.206.425.765.204.724.303.933.613.333.082.852.652.472.312.172.031.911.801.701.611.521.441.371.30

16.7911.788.496.264.713.612.812.221.771.431.170.970.810.680.570.49

20.8117.2014.4512.3110.629.258.086.495.274.313.562.962.482.101.781.521.311.130.980.860.750.660.580.520.46

20.8117.2014.4512.3110.629.258.137.206.425.765.204.724.303.933.432.962.562.231.951.711.511.331.181.050.940.840.750.680.610.550.50

20.8117.2014.4512.3110.629.258.137.206.425.765.204.724.303.933.613.333.082.852.652.472.312.172.031.911.801.701.541.401.271.151.05

36.5727.4821.1716.6513.3310.848.937.446.275.334.573.953.433.012.652.342.081.861.671.501.351.231.121.020.930.850.780.720.670.620.57

Page 11: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 11

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S300-Single Spans for Z/C300 Sections - Limit state capacity (kN/m)

SECTION 30024

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

4500480051005400570060006300660069007200750078008100840087009000930096009900

102001050010800111001140011700120001230012600129001320013500138001410014400147001500015300156001590016200165001680017100174001770018000

12.5811.059.798.737.847.076.425.855.354.914.534.193.883.613.363.142.942.762.602.452.312.182.071.961.861.771.681.601.531.461.401.341.281.231.181.131.091.051.010.970.940.900.870.840.810.79

8.536.685.304.253.452.832.341.951.641.391.181.010.870.760.660.580.510.45

12.5811.059.798.737.847.076.425.734.874.163.573.092.682.332.041.791.581.401.241.110.990.890.800.720.650.590.540.49

12.5811.059.798.737.847.076.425.855.354.914.534.193.883.613.363.142.942.722.432.181.961.761.591.441.311.191.080.990.900.830.760.700.640.590.550.500.47

12.5811.059.798.737.847.076.425.855.354.914.534.193.883.613.363.142.942.762.602.452.312.182.071.961.861.771.681.601.531.461.401.341.281.221.131.050.980.910.850.790.740.690.650.610.570.53

18.5915.3212.7710.769.157.846.785.895.164.544.023.573.192.862.572.322.111.911.751.601.461.341.241.141.060.980.910.850.790.740.690.640.600.570.530.500.470.450.420.400.380.360.340.320.310.29

Page 12: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 12

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S300-Single Spans for Z/C300 Sections - Limit state capacity (kN/m)

SECTION 30030

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

4500480051005400570060006300660069007200750078008100840087009000930096009900

102001050010800111001140011700120001230012600129001320013500138001410014400147001500015300156001590016200165001680017100174001770018000

18.0315.8514.0412.5211.2410.149.208.387.677.046.496.005.565.174.824.514.223.963.723.513.313.132.962.812.672.542.412.302.192.102.001.921.841.761.691.621.561.501.441.391.341.291.251.211.171.13

11.098.686.895.544.493.693.052.542.141.811.541.321.140.990.860.750.660.580.520.460.41

18.0315.8514.0412.5211.2410.148.787.426.315.404.644.013.483.032.662.332.061.821.621.441.291.161.040.940.850.770.700.640.580.530.48

18.0315.8514.0412.5211.2410.149.208.387.677.046.496.005.565.174.824.443.953.523.152.822.542.292.071.871.701.541.401.281.171.070.990.910.830.770.710.660.610.560.520.49

18.0315.8514.0412.5211.2410.149.208.387.677.046.496.005.565.174.824.514.223.963.723.513.313.132.962.812.672.542.412.302.192.101.991.841.711.581.471.361.271.181.101.030.960.900.840.790.740.69

23.9919.7716.4813.8811.8010.128.747.606.655.865.184.614.113.693.323.002.722.472.252.061.891.741.601.481.361.271.171.091.020.950.890.830.780.730.690.650.610.580.540.510.490.460.440.410.390.37

Page 13: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 13

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S350-Single Spans for Z/C350 Sections - Limit state capacity (kN/m)

SECTION 35030

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

4500480051005400570060006300660069007200750078008100840087009000930096009900

102001050010800111001140011700120001230012600129001320013500138001410014400147001500015300156001590016200165001680017100174001770018000

21.7019.0716.8915.0713.5212.2111.0710.099.238.487.817.226.706.235.815.425.084.774.484.223.993.773.573.383.213.052.902.772.642.522.412.312.212.122.031.951.881.811.741.671.611.561.501.451.401.36

21.7018.2214.6111.819.637.936.585.514.643.943.362.892.492.161.891.651.451.281.141.010.900.810.720.650.590.53

21.7019.0716.8915.0713.5212.2111.0710.099.238.487.817.226.706.235.574.934.373.883.463.092.772.492.242.031.831.661.511.381.261.151.060.970.890.820.760.700.650.600.560.520.48

21.7019.0716.8915.0713.5212.2111.0710.099.238.487.817.226.706.235.815.425.084.774.484.223.993.773.573.383.213.052.902.682.472.272.091.931.781.641.521.411.311.211.131.050.980.920.860.800.750.70

21.7019.0716.8915.0713.5212.2111.0710.099.238.487.817.226.706.235.815.425.084.774.484.223.993.773.573.383.213.052.902.772.642.522.412.312.212.122.031.951.881.811.741.671.611.561.501.451.401.36

38.6331.8326.5422.3619.0116.3014.0812.2410.729.438.347.426.625.945.354.834.383.983.633.323.042.792.572.382.202.041.891.761.641.531.431.341.261.181.111.040.980.930.880.830.780.740.700.670.630.60

Page 14: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 14

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S400-Single Spans for Z/C350 Sections - Ultimate load capacity (KN/M)

SECTION 30024

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

60006300660069007200750078008100840087009000930096009900

102001050010800111001140011700120001080011100114001170012000

8.607.807.116.515.975.515.094.724.394.093.823.583.363.162.982.812.662.512.382.262.152.662.512.382.262.15

6.535.484.613.883.302.812.422.091.811.581.381.221.070.950.850.760.680.610.550.490.450.680.610.550.490.45

8.607.807.116.515.975.515.094.724.394.093.823.473.102.782.512.262.041.852.381.531.392.041.852.381.531.39

8.607.807.116.515.975.515.094.724.394.093.823.583.363.162.982.812.662.512.382.262.152.662.512.382.262.15

8.607.807.116.515.975.515.094.724.394.093.823.583.363.162.982.812.662.512.382.262.152.662.512.382.262.15

12.7210.999.568.377.366.515.795.174.644.173.773.423.112.832.592.372.182.011.861.721.592.182.011.861.721.59

Page 15: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 15

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S400-Single Spans for Z/C400 Sections - Ultimate load capacity (KN/M)

SECTION 40024

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

60006300660069007200750078008100840087009000930096009900

102001050010800111001140011700120001230012600129001320013500138001410014400147001500015300156001590016200165001680017100174001770018000

9.638.737.967.286.696.165.705.284.914.584.284.013.763.543.333.142.972.812.672.532.412.292.182.081.991.901.821.741.671.601.541.481.421.371.321.271.231.191.141.111.07

7.786.535.494.623.923.352.882.492.161.881.651.451.281.131.010.900.800.720.650.590.53

9.638.737.967.286.696.165.705.284.914.584.284.013.713.322.992.702.442.212.011.831.661.511.371.251.151.050.970.890.820.760.700.650.600.560.520.48

9.638.737.967.286.696.165.705.284.914.584.284.013.763.543.333.142.972.812.672.532.412.292.182.081.991.901.821.701.581.471.371.271.191.111.040.970.910.850.800.750.70

9.638.737.967.286.696.165.705.284.914.584.284.013.763.543.333.142.972.812.672.532.412.292.182.081.991.901.821.741.671.601.541.481.421.371.321.271.231.191.141.111.07

17.4615.0813.1211.4810.108.947.957.106.365.735.174.694.263.893.553.262.992.762.552.352.182.031.891.761.641.531.441.351.261.191.121.050.990.940.890.840.800.750.720.680.65

Page 16: PURLINS & GIRTS - SINGLE SPAN - Metroll Newcastle & GIRTS - SINGLE SPAN Single Span NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method 2.

Metroll NewcastleABN 97 001 446 439268 Macquarie Road WARNERS BAY NSW 2282AUSTRALIAP: +61 (0)2 4954 5799F: +61 (0)2 4954 [email protected] 16

PURLINS & GIRTS - SINGLE SPAN

Single Span

NOTES: 1. The loads have been based on the Standard AS/NZS 4600:1996 using Limit State method

2. Following values of Fy considered for calculating the ultimate loads • 1.0 mm BMT Grade AS1397/G550 Z350 - Fy = 550 Mpa • 1.2 mm BMT Grade AS1397/G500 Z350 - Fy = 500 Mpa • 1.5, 1.9, 2.4, 3.0 mm BMT Grade AS1397/ G450 Z350 - Fy = 450 Mpa

3. The loads have been based on the use of approved Metroll sections & bridging systems.

4. The BOLD HORIZONTAL LINE marks where the overall length of the sections exceeds the normal delivery length (12000 mm nominal).

5. IN = Inward load capacity. OUT = outward load capacity. DEF. = Load required to give a deflection of SPAN/150

Span (mm)

Overall purlin length = span + 70mm

Table S400-Single Spans for Z/C400 Sections - Ultimate load capacity (KN/M)

SECTION 40030

LOADING Inward Outward Def

BRIDGING 0,1,2,3 0 1 2 3

60006300660069007200750078008100840087009000930096009900

102001050010800111001140011700120001230012600129001320013500138001410014400147001500015300156001590016200165001680017100174001770018000

14.4313.0911.9310.9110.029.248.547.927.366.876.426.015.645.304.994.714.464.224.003.803.613.433.273.122.982.852.732.612.512.402.312.222.142.061.981.911.841.781.721.661.60

9.698.056.745.684.824.113.533.052.652.312.021.781.571.391.241.100.990.890.800.720.65

14.4313.0911.9310.9110.029.248.547.927.366.796.025.344.744.233.783.393.042.742.482.242.041.851.691.541.411.291.191.091.010.930.860.790.740.680.640.59

14.4313.0911.9310.9110.029.248.547.927.366.876.426.015.645.304.994.714.464.224.003.803.613.433.273.012.772.552.352.172.011.861.721.601.481.381.291.201.121.050.980.920.86

14.4313.0911.9310.9110.029.248.547.927.366.876.426.015.645.304.994.714.464.224.003.803.613.433.273.122.982.852.732.612.512.402.312.222.142.061.981.911.841.781.721.661.60

22.4919.4316.9014.7913.0211.5210.249.148.207.386.666.045.495.014.584.203.863.553.283.032.812.612.432.262.111.971.851.731.631.531.441.361.281.211.141.081.020.970.920.880.83