PSAS Lab Manual
-
Upload
mukesh80125 -
Category
Documents
-
view
392 -
download
12
Transcript of PSAS Lab Manual
-
7/28/2019 PSAS Lab Manual
1/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
1
PRACTICAL NO.1
Aim: Introduction to FEMM
1. Introduction
Finite Element Method Magnetics (FEMM) is a finite element package for solving 2D planar and
axisymmetric problems in low frequency magnetics and electrostatics. The program runs under
runs under Windows 95, 98, ME, NT, 2000 and XP. The program can be obtained via the FEMM
home page athttp://femm.foster-miller.com.
The package is composed of an interactive shell encompassing graphical pre-and postprocessing;
a mesh generator; and various solvers. A powerful scripting language, Lua 4.0, is integrated with
the program. Lua allows users to create batch runs, describe geometries parametrically, perform
optimizations, etc. Lua is also integrated into every edit box in the program so that formulas can
be entered in lieu of numerical values, if desired. (Detailed information on Lua is available from
http://www.lua.org.) There is no hard limit on problem sizemaximum problem size is limited
by the amount of available memory. Users commonly perform simulations with as many as amillion elements.
The purpose of this document is to present a step-by-step tutorial to help new users get "up and
running" with FEMM. In this document, the solution for the field of an air-cored coil is
considered.
2. Model Construction and Analysis
This will take you through a step-by-step process to analyze the magnetic field of an aircoredsolenoid sitting in open space. The coil to be analyzed is pictured in Figure 1. The coil has an
inner diameter of 1 inch; an outer diameter of 3 inches; and an axial length of 2 inches. The coil
is built out of 1000 turns of 18 AWG copper wire. For the purposes of this example, we will
consider the case in which a steady current of 1 Amp is flowing through the wire.
http://femm.foster-miller.com/http://femm.foster-miller.com/http://femm.foster-miller.com/http://femm.foster-miller.com/ -
7/28/2019 PSAS Lab Manual
2/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
2
In FEMM, one models a slice of the axisymmetric tric problem. By convention, the r = 0 axis is
understood to run vertically, and the problem domain is restricted to the region where r 0. In
this convention, positive-valued currents flow in the into-the-page direction.
Figure 1: Air-cored coil to be analyzed in first example.
2.1 Create a New Model
Run the FEMM application by selecting femm 4.0 from the femm 4.0 section of the Start Menu.
The default preferences will bring up a blank window with a minimal menu bar. Select New
from the main menu. A dialog will pop up with a drop list allowing you to select the type of new
document to be created. Select the Magnetics Problem entry and hit the OK button. A new blank
magnetics problem will be created, and a number of new toolbar buttons will appear.
2.2 Set Problem Definition
The first task is to tell the program what sort of problem is to be solved. To do this, select
Problem from the main menu. The Problem Definition dialog will appear. Set Problem Type to
Axisymmetric. Make sure that Length Units is set to Inches and that the Frequency is set to 0.
When the proper values have been entered, hit the OK button.
-
7/28/2019 PSAS Lab Manual
3/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
3
2.3 Draw Boundaries
The first task is to draw boundaries for the solution region. Fundamentally, finite element solversmesh and find a solution over a finite region of space that contains the objects of interest. In this
case, we will choose our solution region to be a sphere with a radius of 4 inches.
First, we can adjust the view so that it will contain the entire solution region. Select
View|Keyboard off of the main menu to bring up a dialog that allows you to specify the extents
of the visible screen. In this dialog, specify Bottom to be -4, Left to be 0, Right to be 4, and Top
to be 4 and hit the OK button. The screen will then be rescaled to the smallest rectangle that
contains the specified region.
Next, node points need to be defined that bound the sphere. To draw these node points, select the
Operate on nodes button from the from the tool bar (this is the farthest button on the left with a
small black box :). Place nodes at the top and bottom of the sphere, at (0, 4) and (0-4), and at the
origin (0,0). One can place nodes either by moving the mouse pointer to the desired location and
pressing the left mouse button, or by pressing the key and manually entering the point
coordinates via a popup dialog.
Select the Operate on segments toolbar button (second button from the left with a blue line: ). To
select a node to be the endpoint of a line, click near the desired endpoint with the left mouse
button. Draw a line down the axis of symmetry by selecting the point at (0,-4) and then the point
at (0, 4). A line will appear linking the nodes as soon as the second point is selected.
Select the Operate on arc segments toolbar button (third button from the left with a blue arc :).
Draw an arc down the axis of symmetry by selecting the point at (0,-4) and then the point at (0,
4). A dialog will appear asking you for some attributes of the arc. In FEMM, arc are
approximated by a series of small, straight lines. The Max. Segment specifies the coarseness
with which the arc is divided into sections. Enter 2.5 into this edit box to get a fairly fine
representation of the arc. Put 180 in the Arc Angle edit box to denote that a half circle is being
drawn.
-
7/28/2019 PSAS Lab Manual
4/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
4
2.4 Draw Coil
Now, the coil itself can be drawn. Switch back to Nodes mode by pressing the Operate on nodestoolbar button. Place nodes at (0.5,-1), (1.5,-1), (1.5,1) and (0.5,1) defining the extents of the
coil. Select the Operate on segments toolbar button so that lines can be drawn connecting the
points. By selecting the nodes defining the coil in sequence, one obtains lines between each of
the nodes and result in a large connected box.
2.5 Place Block Labels
Now click on the Operate on Block Labels toolbar button denoted by concentric green circles .
Place a block label in the coil region, and place one in the air outside the coil region. Like node
points, block labels can be placed either by a click on the left mouse button, or via the
dialog. The program uses block labels to associate materials and other properties with various
regions in the problem geometry. Next, we will defined some material properties, and then we
will go back and associate them with particular block labels.
NOTE: If snap-to-grid is enabled then it may be sometimes be difficult to place the block label
in the empty space. If this is the case, disable snap-to-grid by de-selecting the tool bar button
with the point and arrow.
2.6 Add materials to the model
Select Properties|Materials Library off of the main menu. The drag-and-drop Air from Library
Materials to Model Materials to add it to the current model. Go into the Copper AWG Sizes
folder and drag 18 AWG into Model Materials. Click on OK.
2.7 Add a "Circuit Property" for the coil
Select Properties|Circuits off of the main menu. On the dialog that appears, push the Add
Property button to create a new circuit property. Name circuit by replacing the new circuit name
with Coil. Specify that the circuit property is to be applied to a wound region by selecting the
Series radio button. Enter 1 as the Circuit Current. The j edit box denotes the imaginary
-
7/28/2019 PSAS Lab Manual
5/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
5
component of the current, which is used in time harmonic problems to denote the phase of the
current. In this case, the problem is magnetostatic, so the imaginary component is ignoredjust
put zero in the j edit box. Click on OK for both the Circuit Property and Property Definition
dialogs.
2.8 Associate properties with block labels.
Right click on the block label node in the air region outside the coil. The block label will turn
red, denoting that it is selected. Press space to open the selected block label (Instead of
pressing the space bar, one can use the Open up Properties Dialog toolbar button). A dialog will
pop up containing the properties assigned to the selected label. Set the Block type to Air.
Uncheck the Let Triangle choose Mesh Size checkbox and enter 0.1 for the Mesh size. The mesh
size parameter defines a constraint on the largest possible elements size allowed in the associated
section. The mesher attempts to fill the region with nearly equilateral triangles in which the sides
are approximately the same length as the specified Mesh size parameter. When the Let Triangle
choose Mesh Size box is checked, the mesher is free to pick its own element size, usually
resulting in a somewhatcoarse mesh. Click on OK. The block label will then be labeled as Air,
and a circle will appear about the block label indicating the approximate mesh size in the
associated region.
Repeat the same for the block label node inside the coil region, changing the mesh size to 0.1.
However, set this Block type to Copper. We want to assign currents to flow in this region, so
select the Coil circuit from the In Circuit drop list. The Number of turns edit box will become
activated if a series-type circuit is selected for the region (e.g. the Coil property that was
previously defined). Enter 1000 as the number of turns for this region, denoting that the region if
filled with 1000 turns wrapped in a counter-clockwise direction (i.e. positive turns in the right-hand-screw rule sense). Click on OK.
NOTE: If we wanted to denote that the turns are wrapped in a counter-clockwise direction
instead, we could have specified the number of turns to be1000.
-
7/28/2019 PSAS Lab Manual
6/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
6
2.9 Create Boundary Conditions
Select Properties|Boundary from the menu bar, then click on the Add Property button. Replacethe name New Boundary with ABC and change the BC Type to Mixed. The ABC name is meant
to denote that we are creating an "asymptotic boundary condition" that approximates the
impedance of an unbounded, open space. In this way, we can model the field produced by the
coil in an unbounded space while still only modeling a finite region of that space. When the
Mixed boundary condition type is selected the c0 coefficient and c1 coefficient boxes will
become enabled. These entries are meant to represent coefficients in a boundary condition of the
form:
where A is magnetic vector potential, r is the relative magnetic permeability of the region
adjacent to the boundary, o is the permeability of free space, and n represents the direction
normal to the boundary. For our asymptotic boundary condition, we need to specify:
where R is the outer radius of a spherical problem domain. To enter these values into the dialog
box, enter 0 as the c1 coefficient and 1/(uo*4*inch) as the c0 coefficient. The Lua scripting
language processes the contents of each edit box automatically when the dialog is closed,
substituting the numerical value of the permeability of free space for uo and 0.0254 for inch and
evaluating the result.
-
7/28/2019 PSAS Lab Manual
7/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
7
To assign this boundary condition, switch to operate on arc segments mode. Select the arc
defining the outer boundary by clicking on the arc with the left mouse button and push the space
bar to open the arc's properties for editing. Select ABC from the Boundary cond. drop list and
click on OK. You have now defined enough boundary conditions to solve the problem, since a
zero potential is automatically applied along the r = 0 line for axisymmetric problems.
You have now completed modeling the coil. The finished pre-processor geometry should look as
pictured in Figure 2.
Figure 2: Completed coil model, ready to be analyzed.
-
7/28/2019 PSAS Lab Manual
8/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
8
2.10 Generate Mesh and Run FEA
Now save the file and click on the toolbar button with yellow mesh. This action generates atriangular mesh for your problem. If the mesh spacing seems to fine or too coarse you can select
block labels or line segments and adjust the mesh size defined in the properties of each object.
Once the mesh has been generated, click on the turn the crank button to analyze your model.
Processing status information will be displayed. If the progress bars do not seem to be moving
then you should probably cancel the calculation. This can occur if insufficient boundary
conditions have been specified. For this particular problem, the calculations should be completed
within a second. There is no confirmation for when the calculations are complete, the status
window just disappears when the processing is finished.
3. Analysis Results
Click on the glasses icon to view the analysis results. A post-processor window will appear. The
post-processor window will allow you to extract many different sorts of information from the
solution.
3.1 Point values
Just like the pre-processor, the post-processor window has a set of different editing modes: Point,
Contour, and Area. The choice of mode is specified by the mode toolbar buttons, i.e. where the
first button corresponds to Point mode, the second to Contour mode, and the third to Area mode.
By default, when the program is first installed, the post-processor starts out in Point mode. By
clicking on any point with the left mouse button, the various field properties associated with that
point are displayed in the floating FEMM Output window. Similar to drawing points in the pre-
processor, the location of a point can be precisely specified by pressing the button and
entering the coordinates of the desired point in the dialog that pops up. For example, if the point
(0, 0) is specified in the pop-up dialog, the resulting properties displayed in the output window
are as pictured in Figure 3.
-
7/28/2019 PSAS Lab Manual
9/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
9
Figure 3: Display of field values at the point (0,0).
3.2 Coil terminal properties
With FEMM, it is straightforward to determine the inductance and resistance of the coil as seen
from the coil's terminals. Press the button to display the resulting attributes of each Circuit
Property that has been defined. For the Coil property defined in this example, the resulting dialog
is pictured in Figure 4.
Figure 4: Circuit Property results dialog.
-
7/28/2019 PSAS Lab Manual
10/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
10
Since the problem is linear and there is only one current, the Flux/Current result can be
unambiguously interpreted as the coil's inductance (i.e. 22.9 mH). The resistance of the coil is
the Voltage/Current result (i.e. 3.34 ).
3.3 Plotting field values along a contour
FEMM can also plot values of the field along a user-defined contour. Here, we will plot the flux
density along the centerline of the coil. Switch to Contour mode by pressing the Contour Mode
toolbar button. You can now define a contour along which flux will be plotted. There are three
ways to add points to a contour:
1. Left Mouse Button Click adds the nearest input node to the contour;
2. Right Mouse Button Click adds the current mouse pointer position to the contour;
3. Key displays a point entry dialog that allows you to enter in the
coordinates of a point to be added to the contour.
Here, method 1 can be used. Click near the node points at (0, 4), (0, 0), and (0,-4) with the left
mouse button, adding the points in the above order. Then, press the Plot toolbar button . Hit OK
in the X-Y Plot of Field Values pop-up dialogthe default selection is magnitude of flux
density. If desired, different types of plot can be selected from the drop list on this dialog.
NOTE: It is often the case in the solution to magnetic problems that the field values are
discontinuous across a boundary. In this case, FEMM determines which side of the boundary
will be plotted based on the order in which points are added. For example, if points are added
around a closed contour in a counterclockwise order, the plotted points will lie just to the inside
of the contour. If the points are added in a clockwise order, the plotted points will lie just to the
outside of the contour. The implication to our example problem is that the contour along the r=0
should be defined in order of decreasing z (i.e. counterclockwise so that the plotted points will lie
inside the solution domain instead of outside it, where the field values are not defined).
-
7/28/2019 PSAS Lab Manual
11/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
11
3.4 Plotting Flux Density
By default, when the program is first installed, only a black-and-white graph of flux lines isdisplayed. Flux density can be plotted as a color density plot, if you so desire. To make a color
density plot of flux, click on the purple shaded toolbar button to generate a color flux density
plot. When the dialog box comes up, select the Flux density plot radio button and accept the
other default values. Click on OK. The resulting solution view will look similar to that pictured
in Figure 5.
Figure 5: Color flux density plot of solution.
-
7/28/2019 PSAS Lab Manual
12/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
12
Figure 6: Flux density (Tesla) versus length (Inches)
4. Conclusions
You have now completed your first model of a magnetic problem with FEMM. From this basic
introduction, you have been exposed to the following concepts:
How to draw a model using nodes, segments, arc, and block labels;
How to add material to your model and how to assign them to regions;
How to specify the finite element mesh size;
How to define boundary for your model;
How to define and apply boundary conditions;
How to analyze a problem;
How to inspect local field values;
How to plot field values along a line;
-
7/28/2019 PSAS Lab Manual
13/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
13
How to compute inductance and resistance;
How to display color flux density plots.
Hopefully, this tutorial has presented you with enough of the basics of FEMM so that you can
explore more complicated problems without getting sidetracked by the mechanics of how a
problem is drawn and analyzed.
-
7/28/2019 PSAS Lab Manual
14/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
14
PRACTICAL NO. 2
Aim: Calculation of Leakage reactance of transformer winding.
Problem Statement: 31.5 MVA, 132 KV/33KV, Y/, Transformer, Ampere-turns: 137780, the
dimensions of the transformer are given in Figure 1.
All dimensions are in mm.
Figure 1: Transformer dimensions
Dimensions:
Core Diameter : 560 mm
Core-LV gap : 23 mm
LV radial depth : 70 mm
-
7/28/2019 PSAS Lab Manual
15/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
15
LV-HV gap : 50 mm
HV radial depth : 100 mm
rof core = 3000
N1 turns =1000
N2 turns =433
Calculate % reactance of transformer using FEM software (attach flux plot) and comment on
result. Also reduce HV winding height by 2% at one end and do the same.
Simulation:
Calculation:
Current density = mmf/area A/mm2
Find on LV as well as HV side. Here we have taken Short circuit on HV side.
-
7/28/2019 PSAS Lab Manual
16/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
16
Using FEM plot, Magnetic field energy W=..Joules
Find current I=AT/(N) Ampere-turn/turns on both side of transformer.
W=(1/2) LI2
From above equation find L and on both side.
XL=2fL
Zb =V2/MVA
% Leakage Reactance %X = XL/ Zb * 100 %
Do same calculation for reduce HV height.
CONCLUSION:
-
7/28/2019 PSAS Lab Manual
17/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
17
PRACTICAL NO.- 3
Aim: Find the Force on Plunger of an actuator.
Problem Statement: Obtain the magnetic flux density plot in a solenoid and force applied to the
plunger for d= 0.02.
Find the force on the plunger for various values of d and plot same.
All dimensions are in meter.
Figure 1: Problem sketch
Relative Permeability of air and coil 1
Current Density in coil 1e6 Amp/m
-
7/28/2019 PSAS Lab Manual
18/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
18
The B-H curve for the core and plunger
H (A/m) 460 640 720 890 1280 1900 3400 6000
B(T) 0.8 0.95 1 1.10 1.25 1.40 1.55 1.65
SIMULATION:
Figure: Axysymmetric simulation of Plunger of an actuator
-
7/28/2019 PSAS Lab Manual
19/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
19
Figure: B-H curve of core and plunger
Find force on plunger using FEMM.
Plot the graph for force on the plunger V/S gap length d
CONCLUSION:
-
7/28/2019 PSAS Lab Manual
20/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
20
PRACTICAL NO.- 4
Aim: Simulation on Basic Electrical Engineering Application.
Problem Statement:
(1)Construct a simulink model in order to obtain Sine, Square and Sawtooth waves.(2)Construct a simulink model for average and RMS values(3)Construct a simulink model for (i) CCCS (ii) CCVS (iii) VCCS (iv) VCVS(4)Construct a simulink model for (i) Series Resonance (ii) Parallel Resonance
Simulation and Result:
(1)Construct a simulink model in order to obtain Sine, Square and Sawtooth waves.
Figure 4.1 Model for Sine, Square and Sawtooth waves
-
7/28/2019 PSAS Lab Manual
21/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
21
Figure 4.2 Plot for sine, square and sawtooth waves
(2)Construct a simulink model for average and RMS values
Figure 4.3 Circuit model for average and RMS values
-
7/28/2019 PSAS Lab Manual
22/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
22
Figure 4.4 Plot showing the peak values of the current and voltage
(3)Construct a simulink model for (i) CCCS (ii) CCVS (iii) VCCS (iv) VCVS
(i) CCCS (Current Controlled current source)
Figure 4.5 Model of current controlled current source
-
7/28/2019 PSAS Lab Manual
23/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
23
Figure 4.6 Input and Output currents of CCCS
(ii) CCVS (Current Controlled voltage source)
Figure 4.7 Model of current controlled voltage source
-
7/28/2019 PSAS Lab Manual
24/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
24
Figure 4.8 Input voltage and Output current of CCVS
(iii) VCCS (Voltage Controlled Current source)
Figure 4.9 Model for voltage controlled current source
-
7/28/2019 PSAS Lab Manual
25/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
25
Figure 4.10 Input voltage and output current of VCCS
(iv) VCVS (Voltage controlled voltage source)
Figure 4.11 Model of voltage controlled voltage source
-
7/28/2019 PSAS Lab Manual
26/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
26
Figure 4.12 Input and Output voltages of VCVS
(4) Construct a simulink model for (i) Series Resonance (ii) Parallel Resonance
(i) Series Resonance
Figure 4.13 Series Resonance Circuit
-
7/28/2019 PSAS Lab Manual
27/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
27
Figure 4.14 Supply voltage and current waveforms for series resonance
(ii) Parallel Resonance
Figure 4.15 Parallel Resonance
-
7/28/2019 PSAS Lab Manual
28/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
28
Figure 4.16 Supply voltage and current for parallel resonance
CONCLUSION:
-
7/28/2019 PSAS Lab Manual
29/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
29
PRACTICAL NO.- 5
Aim: Simulation on (I) Measurement of Apparent, Active and Reactive Powers (II) ThreePhase source and load simulation.
Problem Statement:
Construct Matlab Simulink Model for Measurement of Apparent, Active and Reactive Powers:
An AC voltage source of 500 V, 50 Hz in series with a resistance of 10 and an inductance of
10mH in one branch. This branch is in series with two parallel branches; one branch with a
resistance of 35 an capacitance of 40 F, and another having a resistance of 20 and an
inductance of 10 mH and a load resistance of 35 .
Three Phase source and load simulation: The peak voltage amplitude of each phase is 315 V and
frequency 50 Hz. The resistance and inductance of the transmission lines are assumed to be zero.
All the three voltage sources are star connected, i.e., line currents and phase currents are equal.
The phase voltages of this three-phase voltage source are shown in figure. The transmission line
feeds a three-phase star connected balanced load resistance 50 and inductance 40 mH.
-
7/28/2019 PSAS Lab Manual
30/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
30
SIMULATION AND RESULT:
(I) Measurement of Apparent, Active and Reactive Powers
Figure 5.1 Measurement of active and reactive powers
Figure 5.2 Waveforms of active and reactive powers
-
7/28/2019 PSAS Lab Manual
31/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
31
(II) Three Phase source and load simulation.
Figure 5.3 Star Connected three phase source
Figure 5.4 Three phase active and reactive powers
-
7/28/2019 PSAS Lab Manual
32/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
32
Figure 5.5 Three phase symmetrical supply
CONCLUSION:
-
7/28/2019 PSAS Lab Manual
33/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
33
PRACTICAL NO.- 6
Aim: Simulation of Transformers- (I) Single Phase (II) Three Phase.
Problem Statement:
Construct Matlab Simulink Model for
Single phase transformer: The primary winding parameters of the transformer are V1(rms) =110
KV, R1(pu)= 0.02 , and L1(pu) =0.08 H and secondary winding parameters are V2(rms) = 220 KV,
R2(pu)= 0.02 , and L2(pu) =0.08 H. The primary winding is supplied with a voltage source of 200
V, 50 Hz. A resistance of 10 is connected in series with primary winding ad of 120 in series
with the secondary winding.
Three Phase transformer: A circuit containing a three phase transformer having two star
connected winding is shown in figure. The primary winding is fed by a three phase supply of 300
V, 50 Hz. The primary winding parameters are V1(rms) =300 V, R1(pu)= 0.002 , and L1(pu) =0.08H and secondary winding parameters are V2(rms) = 600 KV, R2(pu)= 0.02 , and L2(pu) =0.08 H.
The nominal power and frequency of transformer are 250 KW, 50 Hz. The resistances connected
to the primary windings are of 5 each and connected to the secondary windings are of 10
each.
-
7/28/2019 PSAS Lab Manual
34/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
34
SIMULATION AND RESULT:
Simulation of Single phase transformer:
Figure 6.1 Single phase transformer
Figure 6.2 Primary (V1) and Secondary (V2) winding voltages
-
7/28/2019 PSAS Lab Manual
35/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
35
Figure 6.3 Primary (I1) and Secondary (I2) winding currents
Simulation of Three phase transformer
Figure 6.4 Three Phase Transformer
-
7/28/2019 PSAS Lab Manual
36/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
36
Figure 6.5 Three phase primary and secondary winding voltages
Figure 6.6 Three phase primary and secondary winding currents
CONCLUSION:
-
7/28/2019 PSAS Lab Manual
37/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
37
PRACTICAL NO.- 7
Aim: Simulation of Transmission line model.
Problem Statement:
Medium Transmission Line: A 345 KV, three phase transmission line is 130 km long. The
resistance per phase is 0.036 per km and the inductance per phase is 0.8 mH per km. The shunt
capacitance is 0.0112 F per km. The receiving end load is 270 MVA with 0.8 power factor
lagging at 325 kV. Use the medium transmission line model to find the voltage and power at the
sending end and the voltage regulation.
Medium Transmission Line: A 345 KV, three phase transmission line is 130 km long. The
series impedance is z = 0.036 + j0.3 per phase per km, and the shunt admittance is y =
j4.22*10e-6 siemens per phase per km. The sending end voltage is 345 kV, and the sending end
current is 400 A at 0.95 power factor lagging. Use the medium line model to find the voltage,
current and power at the receiving end and the voltage regulation.
Long Transmission Line: A 500 kV, three phase transmission line is 250 km long. The series
impedance is z = 0.045 + j0.4 per phase per km and the shunt admittance is y = j4*10e -6
siemens per phase per km. Evaluate the equivalent model and the transmission matrix.
SIMULATION AND RESULT:
Medium transmission line:
m-file:
r = .036; g = 0; f = 60;
L = 0.8; % milli-Henry
C = 0.0112; % micro-Farad
Length = 130; VR3ph = 325;
-
7/28/2019 PSAS Lab Manual
38/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
38
VR = VR3ph/sqrt(3) + j*0; % kV (receiving end phase voltage)
[Z, Y, ABCD] = rlc2abcd(r, L, C, g, f, Length);
AR = acos (0.8);
SR = 270*(cos (AR) + j*sin (AR)); % MVA (receiving end power)
IR = conj (SR)/ (3*conj (VR)); % kA (receiving end current)
VsIs = ABCD* [VR; IR]; % column vector [Vs; Is]
Vs = VsIs (1);
Vs3ph = sqrt (3)*abs (Vs); % kV (sending end L-L voltage)
Is = VsIs (2); Ism = 1000*abs (Is); % A (sending end current)
pfs= cos (angle (Vs) - angle (Is)); % (sending end power factor)
Ss = 3*Vs*conj (Is); % MVA (sending end power)
REG = (Vs3ph/abs (ABCD (1, 1)) - VR3ph)/VR3ph *100;
fprintf (' Is = %g A', Ism), fprintf(' pf = %g\n', pfs)
fprintf(' Vs = %g L-L kV\n', Vs3ph)
fprintf(' Ps = %g MW', real(Ss)),
fprintf(' Qs = %g Mvar\n', imag(Ss))
fprintf(' Percent voltage Reg. = %g\n', REG)
-
7/28/2019 PSAS Lab Manual
39/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
39
Result:
Enter 1 for Medium line or 2 for long line --> 1
Nominal pi model
----------------
Z = 4.68 + j 39.2071 ohms
Y = 0 + j 0.000548899 Siemens
ABCD =
Is = 421.132 A pf = 0.869657
Vs = 345.002 L-L kV
Ps = 218.851 MW Qs = 124.23 Mvar
Percent voltage Reg. = 7.30913
Medium transmission line:
m-file:
z = .036 + j* 0.3; y = j*4.22/1000000; Length = 130;
Vs3ph = 345; Ism = 0.4; %KA;
As = -acos (0.95);
Vs = Vs3ph/sqrt (3) + j*0; % kV (sending end phase voltage)
0.98924 + j 0.0012844 4.68 + j 39.207
-3.5251e-007 + j 0.00054595 0.98924 + j 0.0012844
-
7/28/2019 PSAS Lab Manual
40/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
40
Is = Ism*(cos (As) + j*sin (As));
[Z,Y, ABCD] = zy2abcd (z, y, Length);
VrIr = inv (ABCD)* [Vs; Is]; % column vector [Vr; Ir]
Vr = VrIr (1);
Vr3ph = sqrt (3)*abs (Vr); % kV (receiving end L-L voltage)
Ir = VrIr (2); Irm = 1000*abs (Ir); % A (receiving end current)
pfr= cos (angle (Vr) - angle (Ir)); % (receiving end power factor)
Sr = 3*Vr*conj (Ir); % MVA (receiving end power)
REG = (Vs3ph/abs (ABCD (1, 1)) - Vr3ph)/Vr3ph *100;
fprintf(' Ir = %g A', Irm), fprintf(' pf = %g\n', pfr)
fprintf(' Vr = %g L-L kV\n', Vr3ph)
fprintf(' Pr = %g MW', real (Sr))
fprintf(' Qr = %g Mvar\n', imag(Sr))
fprintf(' Percent voltage Reg. = %g\n', REG)
-
7/28/2019 PSAS Lab Manual
41/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
41
Result:
Enter 1 for Medium line or 2 for long line --> 1
Nominal pi model
----------------
Z = 4.68 + j 39 ohms
Y = 0 + j 0.0005486 Siemens
ABCD =
Ir = 441.832 A pf = 0.887501
Vr = 330.68 L-L kV
Pr = 224.592 MW Qr = 116.612 Mvar
Percent voltage Reg. = 5.45863
0.9893 + j 0.0012837 4.68 + j 39
-3.5213e-007 + j 0.00054567 0.9893 + j 0.0012837
-
7/28/2019 PSAS Lab Manual
42/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
42
Long transmission line:
m-file:
z = 0.045 + j*.4; y = j*4.0/1000000; Length = 250;
gamma = sqrt (z*y); Zc = sqrt (z/y);
A = cosh (gamma*Length); B = Zc*sinh (gamma*Length);
C = 1/Zc * sinh (gamma*Length); D = A;
ABCD = [A B; C D]
Z = Zc * sinh (gamma*Length)
Y = 2/Zc * tanh (gamma*Length/2)
Result:
ABCD =
Z =
10.8778 +98.3624i
Y =
0.0000 + 0.0010i
CONCLUSION:
0.9504 + 0.0055i 10.8778 +98.3624i
-0.0000 + 0.0010i 0.9504 + 0.0055i
-
7/28/2019 PSAS Lab Manual
43/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
43
PRACTICAL NO.- 8
Aim: Simulation of power system for different fault condition.
Problem Statement: Construct a simulink model of power system for different fault condition.
SIMULATION AND RESULT:
Figure 8.1 Power system model for different fault conditions
Following program is used to set the values of various parameters of the power system model.
% This program sets the parameters for three phase power system model under different fault
% conditions.
-
7/28/2019 PSAS Lab Manual
44/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
44
clear all;
clc;
% Three phase power system parameters
f= 50; % frequency of the power system in Hz
T =1/f; % Time period in seconds
R1 = 1; % Resistance of the transmission line in ohms
L1 = 10e-6; % Inductance of the transmission line in H
R2 =50; % Load resistance in ohms
Ton = 0.02; % On time of the power supply in seconds
% Three voltage source
Pia = 0; % Phase angle of the voltage source Va in degrees
Pib = 120; % Phase angle of the voltage source Vb in degrees
Pic = 240; % Phase angle of the voltage source Vc in degrees
V =230; % Peak voltage per phase
% Under voltage, continuous Reduction parameters
k1 = 20.0; % Under voltage, continuous reduction of voltage in
V1 = (k1/100) * V; % Voltage to be reduced
Va = VV1; % Actual reduced peak voltage
-
7/28/2019 PSAS Lab Manual
45/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
45
% Voltage Unbalance Parameters
UF = 0.5; % Voltage Unbalance factor
Vneg = Va * UF; % Negative sequence voltage
% Voltage Sag/Swell parameters
N = 3.0; % Duration of sag/swell for number of fundamental cycles
T1 = 0.05; % Time in sec at which sag will be initiated
k = 50; % Reduction in magnitude in % for + values sag
% will be there & forive values will be there
Vu = Va * (k/100); % 50% reduction in phase voltage
T3 = T * N; % end of sag after N cycles
T = T1 + T3;
% Parameters for Harmonics Distortion
h5 = 0.05; % Harmonic Factor of 5th harmonic
h7 = 0.03; % Harmonic Factor of 7th harmonic
f5 = f * 5; % 5th harmonic frequency
f7 = f * 7; % 7th harmonic frequency
Vh5 = V * h5; % 5th harmonic, 5% of fundamental component
Vh7 = V * h7; % 7th harmonic, 3% of fundamental component
% End of the program
-
7/28/2019 PSAS Lab Manual
46/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
46
Figure 8.2 Source, Negative sequence and fifth harmonic voltage
Figure 8.3 The 7th harmonic, sag voltages, and line (Ra, La) current
-
7/28/2019 PSAS Lab Manual
47/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
47
Figure 8.4 Power line (Rb, Lb, Rc, Lc) currents, load voltage, and rectifier output voltage
CONCLUSION:
-
7/28/2019 PSAS Lab Manual
48/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
48
PRACTICAL NO.- 9
Aim: Simulation of Separately excited DC motor.
Problem Statement: Construct a simulink model of Separately excited DC motor.
SIMULATION AND RESULT:
In case of separately excited DC motors, V = Ea + I*Ra. The speed of a DC motor can be given
by = (V-I*Ra)/K, where K is the machine constant and is the flux per pole. So, the speed
of the DC motor can be varied by varying the armature resistance (which varies Ia) or by varying
the field resistance (which varies the flux per pole). The armature resistance control method
consists of a variable resistance connected in series with the armature as shown in figure 9.1. The
speed of the motor can be reduced to any desired value depending on the armature resistance.
The field current remains unaffected as it is connected to a separately excited DC motor is shown
in figure 9.2. As the circuit breakers connected in parallel are turned ON, the resistances
connected in parallel to them gets short circuited. Initially, all the CBs are OFF and are turned
ON one by one as can be seen from figure 9.2. The supply given to the armature of the DC motor
is 180 V and to the field winding is100 V. The initial speed of the motor is taken as 1 rad/s and is
fed back to the motor torque (input terminal TL) by multiplying it by a gain of 0.405. When the
ideal switch is turned ON at 0.01 s, the 180 V DC supply gets connected with the armature of
the motor through the series resistance. Initially, all the CBs are OFF so the voltage supplied to
the armature is low (20 V) as can be seen in figure 9.3. After 6 s when all the CBs are turned
ON, the voltage at the armature terminal become 180 V. The speed of the motor in rad/s,
armature current in A and electromagnetic torque developed in N.m are shown in figure 9.4. The
graphs of armature current (Ia) versus speed (), and speed () versus electromagnetic torque
(Te) are shown in figure 9.5 and 9.6 respectively. If the mechanical torque input, i.e., TL, to the
motor is negative it acts as a generator.
-
7/28/2019 PSAS Lab Manual
49/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
49
In the field control method of speed control, a variable resistance is connected in series with the
field winding of the motor as shown in 9.7. As the field resistance increases, the field current
decreases with a consequent reduction in flux which is inversely proportional to the motor speed.
Thus, as the field resistance increases, the speed of the motor also increases. This method of
speed control does not depend on the motor load and therefore permits the remote control of the
motor speed. The different parameters of the model in figure 9.7 are same as that of figure 9.1,
except that the series resistances are now connected in series with the field winding. Also the
subsystem1 of this model is same as shown in figure 9.2, expect that all the CBs are initially
ON and are turned OFF one by one. Thus, initially the field winding resistance is low and is
increased in steps of 1 s. The voltage at the field winding terminal is shown in figure 9.8. The
motor speed in rad/s, armature current in A, field current in A, and electromagnetic torque in
N*m are shown in figure 9.9. The graphs of armature current (Ia) versus speed (), and speed
() versus electromagnetic torque are shown in figure 9.10 and 9.11 respectively.
Figure 9.1 Separately excited DC motor armature control
-
7/28/2019 PSAS Lab Manual
50/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
50
Figure 9.2 Subsystem for varying the armature resistance
Figure 9.3 Armature Voltage
-
7/28/2019 PSAS Lab Manual
51/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
51
Figure 9.4 Motor Speed (rad/s), armature current (A) and electromagnetic torque (N m ) of the
motor
Figure 9.5 Graph of armature current versus speed
-
7/28/2019 PSAS Lab Manual
52/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
52
Figure 9.6 Graph of speed versus electromagnetic torque
Figure 9.7 Field control of Separately excited DC motor
-
7/28/2019 PSAS Lab Manual
53/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
53
Figure 9.8 Field winding voltage
Figure 9.9 Speed (rad/s), armature current (A), field current (A), and
electromagnetic torque (N m)
-
7/28/2019 PSAS Lab Manual
54/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
54
Figure 9.10 Armature current versus speed
Figure 9.11 Speed versus electromagnetic torque
CONCLUSION
-
7/28/2019 PSAS Lab Manual
55/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
55
PRACTICAL NO.- 10
Aim: Simulation of transmission line for load compensation.
Problem Statement: Simulation of transmission line for load compensation.
A three phase, 60 Hz, 550 kV transmission line is 300 km long. The line parameters per phase
per unit length are found to be
r = 0.016 /km L = 0.97mH/km C =0.0115 F/km
SIMULATION AND RESULT:
(A) Determine the line performance when load at the receiving end is 800 MW, 0.8 power factor
lagging at 500 KV.
(Note:Use lineperf and run in command window)
lineperf
TRANSMISSION LINE MODEL
Type of parameters for input Select
Parameters per unit length
r(ohms), g(siemens) L(mH) & C (micro F) 1
Complex z and y per unit length
r+j*x (ohms/length), g+j*b (siemens/length) 2
Nominal pi or Eq. pi model 3
A, B, C, D constants 4
-
7/28/2019 PSAS Lab Manual
56/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
56
Conductor configuration and dimension 5
To quit 0
Select number of menu --> 1
Enter Line length = 300
Enter Frequency in Hz = 60
Enter line resistance/phase in ohms per unit length r = 0.016
Enter line inductance/phase in millihenry per unit length L = 0.97
Enter line capacitance/phase in micro F per unit length C = 0.0115
Enter line conductance/phase in siemens per unit length g = 0
Enter 1 for Medium line or 2 for long line --> 2
Equivalent pi model
-------------------
Z' = 4.57414 + j 107.119 ohms
Y' = 6.9638e-007 + j 0.00131631 siemens
Zc = 290.496 + j -6.35214 ohms
alpha l = 0.00826172 neper beta l = 0.377825 radian = 21.6478
0.9295 + j 0.0030478 4.5741 + j 107.12
ABCD =
-1.3341e-006 + j 0.0012699 0.9295 + j 0.0030478
-
7/28/2019 PSAS Lab Manual
57/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
57
Hit return to continue ENTER
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu -->1
Enter receiving end line-line voltage kV = 500
Enter receiving end voltage phase angle (for Ref. enter 0 ) = 0
Enter receiving end 3-phase real power MW = 800
-
7/28/2019 PSAS Lab Manual
58/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
58
Enter receiving end 3-phase reactive power(+ for lagging & - for leading power factor) Mvar =
600
Line performance for specified receiving end quantities
-------------------------------------------------------
Vr = 500 kV (L-L) at 0
Pr = 800 MW Qr = 600 Mvar
Ir = 1154.7 A at -36.8699 PFr = 0.8 lagging
Vs = 623.511 kV (L-L) at 15.5762
Is = 903.113 A at -17.6996 PFs = 0.836039 lagging
Ps = 815.404 MW Qs = 535.129 Mvar
PL = 15.404 MW QL = -64.871 Mvar
Percent Voltage Regulation = 34.1597
Transmission line efficiency = 98.1108
Hit return to continue ENTER
-
7/28/2019 PSAS Lab Manual
59/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
59
(b) Determine the receiving end quantities and the line performance when 600 MW and 400
Mvar are being transmitted at 525 KV from the sending end.
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu --> 2
Enter sending end line-line voltage kV = 525
Enter sending end voltage phase angle (for Ref. enter 0 ) = 0
-
7/28/2019 PSAS Lab Manual
60/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
60
Enter sending end 3-phase real power MW = 600
Enter sending end 3-phase reactive power(+ for lagging & - for leading power factor) Mvar =400
Line performance for specified sending end quantities
-----------------------------------------------------
Vs = 525 kV (L-L) at 0
Ps = 600 MW Qs = 400 Mvar
Is = 793.016 A at -33.6901 PFs = 0.83205 lagging
Vr = 417.954 kV (L-L) at -16.3044
Ir = 1002.6 A at -52.16 PFr = 0.810496 lagging
Pr = 588.261 MW Qr = 425.136 Mvar
PL = 11.739 MW QL = -25.136 Mvar
Percent Voltage Regulation = 35.1383
Transmission line efficiency = 98.0435
Hit return to continue ENTER
-
7/28/2019 PSAS Lab Manual
61/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
61
(C) Determine the sending end quantities and the line performance when the receiving end load
impedance is 290 at 500 kV.
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu -->3
Enter receiving end line-line voltage kV = 500
Enter receiving end voltage phase angle (for Ref. enter 0 ) = 0
-
7/28/2019 PSAS Lab Manual
62/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
62
Enter receiving end complex load impedance Rload + j*Xload in /phase Zload = 290 + j*0
Line performance for specified load impedance
---------------------------------------------
Vr = 500 kV (L-L) at 0
Ir = 995.431 A at 0 PFr = 1
Pr = 862.069 MW Qr = 0 Mvar
Vs = 507.996 kV (L-L) at 21.5037
Is = 995.995 A at 21.7842 PFs = 0.999988 leading
Ps = 876.341 MW Qs = -4.290 Mvar
PL = 14.272 MW QL = -4.290 Mvar
Percent Voltage Regulation = 9.30464
Transmission line efficiency = 98.3714
Hit return to continue ENTER
-
7/28/2019 PSAS Lab Manual
63/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
63
(d) Find the receiving end voltage when the line is terminated in an open circuit and is energized
with 500 kV at the sending end. Also, determine the reactance and the Mvar of a three-phase
shunt reactor to be installed at the receiving end in order to limit the no-load receiving end
voltage to 500 kV.
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu --> 4
-
7/28/2019 PSAS Lab Manual
64/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
64
Enter sending end line-line voltage kV = 500
Enter receiving end voltage phase angle (for Ref. enter 0 ) = 0
Open line and shunt reactor compensation
----------------------------------------
Vs = 500 kV (L-L) at 0
Vr = 537.92 kV (L-L) at -0.00327893
Is = 394.394 A at 89.8723 PFs = 0.0022284 leading
Desired no load receiving end voltage with shunt reactor compensation kV (L-L) =500
Desired no load receiving end voltage = 500 kV
Shunt reactor reactance = 1519.4 ohm
Shunt reactor rating = 164.538 Mvar
Hit return to continue ENTER
The voltage profile for the uncompensated and the compensated line is also found as shown in
figure 10.1.
-
7/28/2019 PSAS Lab Manual
65/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
65
Figure 10.1 Compensated and uncompensated voltage profile of open ended line.
(e) Find the receiving end and the sending end currents when line is terminated in a short circuit.
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
-
7/28/2019 PSAS Lab Manual
66/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
66
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu --> 5
Enter sending end line-line voltage kV = 500
Enter sending end voltage phase angle (for Ref. enter 0 ) = 0
Line short-circuited at the receiving end
-----------------------------------------
Vs = 500 kV (L-L) at 0
Ir = 2692.45 A at -87.5549
Is = 2502.65 A at -87.367
Hit return to continue ENTER
-
7/28/2019 PSAS Lab Manual
67/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
67
(f) The line loading in part (a) resulted in a voltage regulation of 34.16 percent, which is
unacceptably high. To improve the line performance, the line is compensated with series and
shunt capacitors. For the loading condition in (a):
(1) Determine the Mvar and the capacitance of the shunt capacitors to be installed at the
receiving end to keep the receiving end voltage at 500 kV when the line is energized with 500
kV at the sending end.
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu --> 6
-
7/28/2019 PSAS Lab Manual
68/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
68
CAPACITIVE COMPENSATION
Analysis Select
-------- ------
Shunt capacitive compensation 1
Series capacitive compensation 2
Series & Shunt capacitive compensation 3
To quit 0
Selectr number of menu--> 1
Enter sending end line-line voltage kV = 500
Enter desired receiving end line-line voltage kV = 500
Enter receiving end voltage phase angle (for Ref. enter 0 ) = 0
Enter receiving end 3-phase real power MW = 800
Enter receiving end 3-phase reactive power (+ for lagging & - for leading power factor) Mvar =
600
Shunt capacitive compensation
-----------------------------
Vs = 500 kV (L-L) at 20.2479
-
7/28/2019 PSAS Lab Manual
69/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
69
Vr = 500 kV (L-L) at 0
Pload = 800 MW Qload = 600 Mvar
Load current = 1154.7 A at -36.8699 PFl = 0.8 lagging
Required shunt capcitor: 407.267 ohm, 6.51314 micro F, 613.849 Mvar
Shunt capacitor current = 708.811 A at 90
Pr = 800.000 MW Qr = -13.849 Mvar
Ir = 923.899 A at 0.991732 PFr = 0.99985 leading
Is = 940.306 A at 24.121 PFs = 0.997716 leading
Ps = 812.469 MW Qs = -55.006 Mvar
PL = 12.469 MW QL = -41.158 Mvar
Percent Voltage Regulation = 7.58405
Transmission line efficiency = 98.4653
Hit return to continue ENTER
-
7/28/2019 PSAS Lab Manual
70/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
70
(2) Determine the line performance when the line is compensated by series capacitors for 40
percent compensation with the load condition in (a) at 500 kV.
CAPACITIVE COMPENSATION
Analysis Select
-------- ------
Shunt capacitive compensation 1
Series capacitive compensation 2
Series & Shunt capacitive compensation 3
To quit 0
Select number of menu --> 2
Enter receiving end line-line voltage kV = 500
Enter receiving end voltage phase angle (for Ref. enter 0 ) = 0
Enter receiving end 3-phase real power MW = 800
Enter receiving end 3-phase reactive power(+ for lagging & - for leading power factor) Mvar =
600
Enter percent compensation for series capacitor(recommnded range 25 to 75% of the line
reactance) = 40
-
7/28/2019 PSAS Lab Manual
71/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
71
Series capacitor compensation
-----------------------------
Vr = 500 kV (L-L) at 0
Pr = 800 MW Qr = 600 Mvar
Required series capacitor: 42.8476 ohm, 61.9074 micro F, 47.4047 Mvar
Subsynchronous resonant frequency = 37.9473 Hz
Ir = 1154.7 A at -36.8699 PFr = 0.8 lagging
Vs = 571.904 kV (L-L) at 9.95438
Is = 932.258 A at -18.044 PFs = 0.882961 lagging
Ps = 815.383 MW Qs = 433.517 Mvar
PL = 15.383 MW QL = -166.483 Mvar
Percent Voltage Regulation = 19.4322
Transmission line efficiency = 98.1134
Hit return to continue ENTER
(3)
(3) The line has 40 percent series capacitor compensation and supplies the load in (a). Determine
the Mvar and the capacitance of shunt capacitors to be installed at the receiving end to keep the
receiving end voltage at 500 kV when line is energized with 500 kV at the sending end.
-
7/28/2019 PSAS Lab Manual
72/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
72
CAPACITIVE COMPENSATION
Analysis Select
-------- ------
Shunt capacitive compensation 1
Series capacitive compensation 2
Series & Shunt capacitive compensation 3
To quit 0
Select number of menu --> 3
Enter sending end line-line voltage kV = 500
Enter desired receiving end line-line voltage kV = 500
Enter receiving end voltage phase angle (for Ref. enter 0 ) = 0
Enter receiving end 3-phase real power MW = 800
Enter receiving end 3-phase reactive power(+ for lagging & - for leading power factor) Mvar =
600
Enter percent compensation for series capacitor(recommended range 25 to 75% of the line
reactance) = 40
Series and shunt capacitor compensation
---------------------------------------
Vs = 500 kV (L-L) at 12.0224
Vr = 500 kV (L-L) at 0
-
7/28/2019 PSAS Lab Manual
73/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
73
Pload = 800 MW Qload = 600 Mvar
Load current = 1154.7 A at -36.8699 PFl = 0.8 lagging
Required shunt capcitor: 432.736 ohm, 6.1298 micro F, 577.72 Mvar
Shunt capacitor current = 667.093 A at 90
Required series capacitor: 42.8476 ohm, 61.9074 micro F, 37.7274 Mvar
Subsynchronous resonant frequency = 37.9473 Hz
Pr = 800 MW Qr = 22.2804 Mvar
Ir = 924.119 A at -1.5953 PFr = 0.999612 lagging
Is = 951.165 A at 21.5977 PFs = 0.986068 leading
Ps = 812.257 MW Qs = -137.023 Mvar
PL = 12.257 MW QL = -159.304 Mvar
Percent Voltage Regulation = 4.41619
Transmission line efficiency = 98.491
Hit return to continue ENTER
(g) Construct the receiving end circle diagram.
CAPACITIVE COMPENSATION
Analysis Select
-------- ------
Shunt capacitive compensation 1
Series capacitive compensation 2
-
7/28/2019 PSAS Lab Manual
74/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
74
Series & Shunt capacitive compensation 3
To quit 0
Select number of menu --> 0
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu --> 7
-
7/28/2019 PSAS Lab Manual
75/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
75
Receiving end power circle diagram
----------------------------------
Enter receiving end line-line voltage kV = 500
Figure 10.2 Receiving End circle diagram
A plot of the receiving end circle diagram is obtained as shown in figure 10.2.
-
7/28/2019 PSAS Lab Manual
76/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
76
(h) Determine the line voltage profile for the following cases: no-load, rated load, line terminated
in the SLL, and short-circuited line.
TRANSMISSION LINE PERFORMANCE
----------Analysis---------- Select
To calculate sending end quantities
for specified receiving end MW, Mvar 1
To calculate receiving end quantities
for specified sending end MW, Mvar 2
To calculate sending end quantities
when load impedance is specified 3
Open-end line & inductive compensation 4
Short-circuited line 5
Capacitive compensation 6
Receiving end circle diagram 7
Loadability curve and voltage profile 8
To quit 0
Select number of menu --> 8
-
7/28/2019 PSAS Lab Manual
77/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
77
Voltage profile and line loadability
Analysis Select
--------- ----------
Voltage profile curves 1
Line loadability curves 2
To quit 0
Select number of menu -->1
Voltage profile for line length up to 1/8 wavelength
----------------------------------------------------
Enter sending end line-line voltage kV = 500
Enter rated sending end power, MVA = 1000
Enter power factor = 0.8
-
7/28/2019 PSAS Lab Manual
78/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
78
A plot for the voltage profile is shown in figure 10.3.
Figure 10.3 Voltage profile for length up to 1/8 wavelength
Obtain the line loadability curves.
Voltage profile and line loadability
Analysis Select
--------- ----------
Voltage profile curves 1
Line loadability curves 2
To quit 0
Select number of menu --> 2
-
7/28/2019 PSAS Lab Manual
79/79
PARUL INSTITUTE OF ENGINEERING & TECHNOLOGYDepartment of Electrical Engineering Power System Analysis
and Simulation
SUB CODE: 150902
Loadability curve of a lossless line (up to 1/4 wavelength
----------------------------------------------------------
Enter sending end line-line voltage kV = 500
Enter receiving end line-line voltage kV = 500
Enter rated line-line voltage kV = 500
Enter line current-carrying capacity, Amp/phase = 3500
The line loadability curve is shown in figure 10.4.
Figure 10.4 Line loadability curve for length up to wavelength.