PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING...
Transcript of PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING...
![Page 1: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/1.jpg)
16D5292-0072No.
Central Mechanical Inc3774 Puritan Way Erie CO 80516
TO:
01/05/2016DATE:
230000-HVACRE:
Ryan HadawayATTN:
Shop Drawings
Letter
Prints
Change Order
Plans
Samples
Specifications / Product Data
Other:
Approval
Your Use
As Requested
Review and Comment
Attached
Separate Cover Via:
Approved as Submitted
Approved as Noted
Returned After Loan
Resubmit
Submit
Returned
Returned for Corrections
Due Date: 01/05/2016
WE ARE SENDING: SUBMITTED FOR:
SENT VIA:
ACTION TAKEN:
TRANSMITTAL
James GettmanSigned:
PROJECT: ACSD50-Flynn Elementary HVAC Upgrade & Addition
01/05/2016
Date
232100.01
Code
HVAC Hydronic Systems
Description
Revise andResubmit
Status
JOB: 16D5292
CC:
Item
Submittal 230000
Package
1
Rev. Copies
Ph/Fax: 303-833-2271 303-833-2625
NOTES: resubmit on items with notes 1,3 and 4 only.
5995 Greenwood Plaza Blvd.Suite 100Greenwood Village, CO 80111-4710303-571-5377303-629-7467 (fax)
![Page 2: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/2.jpg)
SUBMITTAL REVIEW
Q:\15\15076\Construction\Submittals\HVAC\Hydronic Systems\15-12-29, reviewed hydronic systems.doc
Lakewood: 2525 South Wadsworth Blvd., Suite 200 Lakewood, CO 80227 P: 303-988-4514 F: 303-988-4517 Fort Collins: 4730 South College Ave., Suite 203 Fort Collins, CO 80525 P: 970-568-8762 F: 303-988-4517
www.TheBallardGroup.com
To: DAO Architecture
3843 W. 73rd
Avenue
Westminster, CO 80030
Date: 12-29-15
TBG Project No: 15076.00
Attention: Tom Rafferty / Dan Orecchio
Project: ACSD #50 – Flynn Elementary School
We are transmitting the following shop drawings with comments listed below.
NET: No Exceptions Taken MCN: Make Corrections Noted RX: Rejected
RR: Revise and Resubmit SSI: Submit Specified Item
CMT: See Comment Below
Copies Item Manufacturer NET MCN RR RX SSI CMT
PDF Manual Air Vent Valves Bell & Gossett X
PDF Automatic Air Vent Valves Bell & Gossett X
PDF Air Separator AS-1 Wessels X X 1
PDF Expansion Tank ET-1 Amtrol X
PDF Pump Suction Diffuser Bell & Gossett X 2
PDF Pressure Relief Valve Watts X
PDF Pumps P-1 & P-2 Taco X X 3
PDF Pumps P-3 & P-4 Bell & Gossett X
PDF Pump P-5 Bell & Gossett X
PDF Inhibited Propylene Glycol Huntsmen X X 4
PDF Glycol Feeder GF-1 Sage X
PDF Pre-Startup Cleaner PreClean X
PDF Bypass Chemical Pot Feeder Wingert X 5,6
Comments:
1. Provide approved manufacturer.
2. Provide adjustable support foot, either from the manufacturer or field fabricated.
3. Pump P-1 shall be capable of flowing 90 GPM at 20 ft of head, while pump P-2 shall be
capable of flowing 60 GPM at 20 ft of head.
4. Provide “uninhibited” propylene glycol as provided by “Industrial Chemical
Corporation” as this is the District’s standard.
5. Provide Bypass Chemical Pot Feeder with ¾” NPT female drain pipe connection.
6. Bypass Chemical Pot Feeder shall have a continuous threaded closure requiring 2 ½
turns, as opposed to ¼ turn closure.
Signed: Don Beaglehole
![Page 3: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/3.jpg)
Submittal Cover Sheet
Project Name Flynn ES
Project Number 16D5292
Date 12-21-15
Architect DAO Architecture
Contractor GH Phipps Construction Companies
Prepared by/Subcontractor Central Mechanical
Supplier
Manufacturer
Submittal Number 232100.01 HVAC Hydronic Systems
Specification Section 232100
Drawing Number/Location
Contractor Review
A/E Review:
Contractor Notes:
![Page 4: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/4.jpg)
MANUAL AIR VENT VALVE
![Page 5: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/5.jpg)
A-310
Air Vents
A full line of manual and automatic air vents designed to remove troublesome air in the system.
• Available in 1/8”, 1/2” and 3/4” connections
• Cast iron, brass and steel construction with
non-ferrous internals
![Page 6: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/6.jpg)
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.© 2012 Xylem Inc. A-310 May 2006
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379www.xyleminc.com/brands/bellgossett
![Page 7: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/7.jpg)
AUTOMATIC AIR VENT VALVE
![Page 8: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/8.jpg)
SUBMITTALHS-103(C)
JOB: Flynn Elementary HVAC Upgrade REPRESENTATIVE: McNevin Co
UNIT TAG: ORDER NO. DATE: 11/13/2015ENGINEER: SUBMITTED BY: DATE: CONTRACTOR: APPROVED BY: DATE:
Hoffman SpecialtyModel 792High PressureWater MainVent Valve
Materials of Construction
Part Specifications
Body Cast Iron
Cover Cast Iron
Float Stainless Steel
Seat Stainless Steel
Pin Stainless Steel
Capacities
Water Pressure psig (bar)
Air Discharge to Atmospherecu. ft./min.(S(m³/min))
100(6.9)
10(.28)
150(10.3)
15(.42)
200(13.8)
20(.57)
250(17.3)
25(.70)
RATINGS
Model
NPT Bottom Inlet Sizein.
NPT Side Inlet Sizein.
NPT Outlet Sizein.
Maximum Operating Pressurepsig (bar)
Maximum Hydrostatic
Pressurepsig (bar)
Maximum Operating Temperature
ºF (ºC)792 3/4 1/2 1/2 250 (17.3) 350 (24.2) 300 (149)
SCHEDULEMODEL
NUMBERPART
NUMBER TAGGING INFORMATION QTY.
792 401494 1
Xylem Inc.8200 N. Austin AvenueMorton Grove, IL 60053Phone (847)966-3700Facsimile (847)966-9052www.hoffmanspecialty.com
![Page 9: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/9.jpg)
AS-1 AIR SEPARATOR
![Page 10: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/10.jpg)
SUBMITTAL SPA-SERIES AIR SEPARATOR
Models: SPA-2 thru SPA-24 Submittal Sheet No. D-1003A Date: 7/13
Job Name ______________________________ Submitted By _______________ Date ________
Location ______________________________ Approved By _______________ Date ________
______________________________ Order No. _______________ Date ________
Engineer ______________________________ Notes __________________________________
Contractor ______________________________ __________________________________
Sales Rep. ______________________________ __________________________________
101 TANK ST ● GREENWOOD, IN 46143 ● (317) 888-9800 ● (317) 888-9988 FAX ● www.westank.com
Typical Specification Furnish and install, as shown on plans, a vortex type air separator model SPA __________ sized for ___________GPM, with __________” (NPT/Flanged) tangential connections, as manufactured by Wessels Company. A blowdown connection shall be provided to facilitate routine cleaning of the unit. The tank must be constructed in accordance with most recent addendum of Section VIII Division 1 of the ASME Boiler and Pressure Vessel Code, and shall be constructed and stamped for 125 PSI working pressure @ 450°F.
Each air separator shall be Wessels model number SPA-______________ or approved equal.
Description Wessels SPA ASME Vortex type Air Separators eliminate air quickly and efficiently from open and closed loop heating/cooling systems. Water enters and exits through unique “tangential” connections, which promote a low velocity swirling effect in the center of the unit. Natural centrifugal forces allow the heavier air-free water to move toward the outer edges while entrained air is captured within the “eye” of the vortex and released out of the top of the separator. The bubble-free water then exits near the bottom of the unit, protecting the systems against the noise, corrosion, and damage commonly caused by entrained air.
Construction Shell: Carbon Steel Heads: Carbon Steel Exterior: Primer Painted
Performance Limitations Maximum Design Temperature: 450°F Maximum Design Pressure: 125 PSIG*
*200 & 250 PSIG available
SPA-2 72006019 56SPA-2.5 72006025 90SPA-3 72006030 190SPA-4 72006035 300SPA-5 72016036 530SPA-6 72001060 850SPA-8 72016080 1900SPA-10 72030010 3200SPA-12 72030012 4800SPA-14 72072014 6100SPA-16 72072016 8000SPA-18 72072018 9700SPA-20 72072020 12000SPA-22 72072022 15000SPA-24 72072024 17000
Model Number
Part Number
Max Flow (GPM) Tagging Information Quantity
Flynn Elementary HVAC Upgrade
Central Mechanical
McNevin Company
Ferguson 11/13/15
33
3
AS-1 1
![Page 11: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/11.jpg)
D-1003A 7/13
101 TANK ST ● GREENWOOD, IN 46143 ● (317) 888-9800 ● (317) 888-9988 FAX ● www.westank.com
Notes Available with mounting clips.
Dimensions & Weights
SPA-2 thru SPA-24
SPA-2 2 NPT 34SPA-2.5 2.5 NPT 37SPA-3 3 25 6 1/4 8 19 3/4 45SPA-4 4 80SPA-5 5 125SPA-6 6 175SPA-8 8 210SPA-10 10 460SPA-12 12 577SPA-14 14 36 78 22 31 1/2 46 3/8 30 850SPA-16 16 48 108 30 40 60 38 1858SPA-18 18 54 124 33 50 66 44 2490SPA-20 20 60 138 35 60 72 50 3346SPA-22 22 66 78 3879SPA-24 24 66 80 4211
Model Number A B C
Approx. Shipping Wt (lbs)D E F G
Dimensions in InchesConnection
Size
24
12
14
20
30
32
44
60 1/2
22 1/2 5 1/2
150
9 1/8
13 1/4
19
38 56
1 1/4
1 1/2
2
66
16 5/8
21 3/4
28
41
8 1/2
10 3/4
14 1/2
20
9 1/2
11 1/2
18
![Page 12: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/12.jpg)
ET-1 EXPANSION TANK
![Page 13: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/13.jpg)
MC 4400 (06/15)Amtrol Inc., 1400 Division Road, West Warwick, RI 02893 USA T: 401.884.6300 www.amtrol.com50
B
A
AX-120V THROUGH AX-240V
ConstructionShell ASME Approved SteelDiaphragm Heavy Duty Butyl/EPDM
System ConnectionNPTF1 Malleable Iron CenterNPTF2 Malleable Iron BottomNPTM3 Malleable Iron Top Offset
Finish Red Oxide PrimerAir Valve Schrader Valve w/EPDM SeatsFactory Precharge 12 PSIG (.8 bar)
PerformanceMaximum Operating Temperature 240°F (115°C)Maximum Working Pressure 125 PSIG (8.6 bar)Warranty 1 Year
125 PSIG Working Pressure
EXTROL®
Hydronic Expansion Tanks: Vertical AX Series ASME
Vertical ASME ModelsModel
Number
TankVolume
Max.Accept. Volume
ATank Diameter
BTank Height
Sys. Conn
ShippingWeight
Gal Lit Gal Lit In mm In mm In Lbs Kg
AX-15V 8.0 30.3 2.4 9.1 12 305 20 508 ½1 39 18
AX-20V 10.9 41.3 2.4 9.1 12 305 27 686 ½1 47 21
AX-40V 21.7 82.2 11.3 42.8 16 356 30 762 ½1 76 34
AX-60V 33.6 127.2 11.3 42.8 16 356 45 1143 ½1 98 44
AX-80V 44.4 168.1 22.6 85.5 24 610 29 737 11 155 70
AX-100V 55.7 211.8 22.6 85.5 24 610 34 864 11 176 80
AX-120V 68.0 257.4 34.0 128.7 24 610 47 1194 12 214 97
AX-144V 77.0 291.5 34.0 128.7 24 610 52 1321 12 230 104
AX-180V 90.0 340.7 34.0 128.7 24 610 60 1524 12 271 123
AX-200V 110.0 416.4 34.0 128.7 24 610 66 1676 12 290 132
AX-240V 132.0 500.0 46.0 174.0 30 762 58 1473 12 401 182
AX-260V 159.0 600.0 56.0 212.0 30 762 65 1651 1¼3 460 209
AX-280V 211.0 800.0 84.0 318.0 30 762 82 2083 1¼3 590 268
All dimensions and weights are approximate.
B
A
AX-15V THROUGH AX-100V
B
A
AX-260V THROUGH AX-280V
120°
F
E
HOLE SIZE "G"ON
BOLT CIRCLE "D"
BOTTOM VIEW
Optional Seismic RestraintsTank
DiameterBolt
Circle Dim. Dim. HoleSize
B D E F G12 12¾ 2 2 9⁄16
16¼ 14¾ 2 2 9⁄16
24 18 2 2 9⁄16
30 27 3 3 ¾
Job Name _____________________________________
Engineer _____________________________________
Contractor _____________________________________
P.O. No. _____________________________________
Sales Rep. _____________________________________
Model No. _____________________________________
Notes _________________________________
_______________________________________
_______________________________________
_______________________________________
_______________________________________
_______________________________________
Application• For use in closed, non-potable
hydronic heating and chilled water systems.
• Designed to meet all ASMECode Section VIII, Division 1 standards.
• Available with optional sightglass and seismic restraints.
![Page 14: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/14.jpg)
PUMPS P-3 & P-4 SUCTION DIFFUSERS
![Page 15: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/15.jpg)
SUBMITTAL
B-826JOB: Flynn Elementary HVAC Upgrade REPRESENTATIVE: McNevin Co
UNIT TAG: ORDER NO. DATE: 11/13/2015ENGINEER: SUBMITTED BY: DATE: CONTRACTOR: APPROVED BY: DATE:
B&G Suction Diffuser PlusCentrifugal Pump Accessories
DESCRIPTIONThe Bell & Gossett Suction Diffuser Plus is designed for direct application to the pump suction and provides ideal flow conditions for the pump, providing NPSH requirements are met. Its integrated Flow Cone directs flow through the unit and into the pump suction while working with the full length straightening vanes to create a more uniform flow profile. The orifice cylinder has a free area equal to five times the cross section of the pump suction opening and serves as a coarse strainer to protect the pump from large sediment. The disposable start-up strainer helps to clean the system during the first 24-48 hours of operation before it is removed. Its optional pressure temperature ports allow you to verify that the start-up strainer has been removed without the need to take the unit apart. OPERATING DATAOperating Temperature: 250?F (121?C)Working Pressure: 175 psi (1,207 kPa)
MATERIALS OF CONSTRUCTION
Type Body Inlet VanesOrifice
CylinderStart-UpStrainer
X Cast Iron Steel 16 Mesh Bronze
Z Cast Iron Stainless Steel 16 Mesh Bronze
NOTES: Type X-For Closed Systems.Type Z-For Domestic Water and Tower Systems.
SCHEDULEMODEL
NUMBERDIMENSIONS INCHES (mm)
TAGGING INFORMATIONX
QUANTITYZ
QUANTITYSYSTEM SIDE PUMP SIDEBA-3X/BA-3Z 2 (50.8) FPT 1-1/2 (38.1) FPTBB-3X/BB-3Z 2 (50.8) FPT 2 (50.8) FPTCB-3X/CB-3Z 2-1/2 (63.5) FPT 2 (50.8) FPTCC-3X/CC-3Z 2-1/2 (63.5) FLG 2-1/2 (63.5) FLGDA-3X/DA-3Z 3 (76.2) FPT 1-1/2 (38.1) FPTDB-3X/DB-3Z 3 (76.2) FPT 2 (50.8) FPT
DC-3X/DC-3Z
3 (76.2) FLG 2-1/2 (63.5) FLG P-3&4 2
DD-3X/DD-3Z 3 (76.2) FLG 3 (76.2) FLGEC-3X/EC-3Z 4 (101.6) FLG 2-1/2 (63.5) FLGED-3X/ED-3Z 4 (101.6) FLG 3 (76.2) FLGEE-3X/EE-3Z 4 (101.6) FLG 4 (101.6) FLGFE-3X/FE-3Z 5 (127) FLG 4 (101.6) FLGFF-3X/FF-3Z 5 (127) FLG 5 (127) FLGGE-3X/GE-3Z 6 (152.4) FLG 4 (101.6) FLGGF-3X/GF-3Z 6 (152.4) FLG 5 (127) FLGGG-3X/GG-3Z 6 (152.4) FLG 6 (152.4) FLGHG-3X/HG-3Z 8 (203.2) FLG 6 (152.4) FLGHH-3X/HH-3Z 8 (203.2) FLG 8 (203.2) FLGJH-3X/JH-3Z 10 (254) FLG 8 (203.2) FLGJJ-3X/JJ-3Z 10 (254) FLG 10 (254) FLG
![Page 16: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/16.jpg)
SUCTION DIFFUSER PLUS B-826
DIMENSIONS − INCHES (mm)
Model No. System Side Pump Side A B C D E F G H JOrifice Cylinder Free
Area in2 (cm2)Approx. Shpg.Wt. Lbs. (Kg)
BA-3 2(50.8) T 1-1/2
(38.1) T 5.96(151)
3(76)
2.25(57)
2.37(60)
3/4(19)
3.81(97)
5.25(133)
5.15(130.8) N/A 11
(71)13(6)
BB-3 2(50.8) T 2
(50.8) T 7.56(192)
3.87(98)
2.75(70)
2.75(70)
3/4(19)
4.38(111)
5.75(146)
6.75(171.5) N/A 20-1/2
(132)14(6)
CB-3 2-1/2(63.5) T 2
(63.5) T 7.56(192)
3.87(98)
2.75(70)
2.75(70)
3/4(19)
4.38(111)
5.75(146)
6.75(171.5) N/A 20-1/2
(132)16(7)
CC-3 2-1/2(63.5) F 2-1/2
(63.5) F 8.44(214)
4.75(121)
4.75(121)
3.5(89)
3/4(19)
5.77(147) N/A 7.63
(193.7)3.5(89)
26(168)
36(16)
DA-3 3(76.2) T 1-1/2
(38.1) T 7.44(189)
3.87(98)
2.75(70)
2.75(70)
3/4(19)
4.38(111)
5.75(146)
6.63(168.3) N/A 20-1/2
(132)17(8)
DB-3 3(76.2) T 2
(50.8) T 7.56(192)
3.87(98)
2.75(70)
2.75(70)
3/4(19)
4.38(111)
5.75(146)
6.75(171.5) N/A 20-1/2
(132)17(8)
DC-33
(76.2) F 2-1/2(63.5) F 8.75
(222)5
(127)5
(127)3.50(89)
3/4(19)
5.77(147) N/A 7.63
(193.7)3.75(95)
26(168)
44(20)
DD-3 3(76.2) F 3
(76.2) F 9.56(243)
5.50(140)
5.50(140)
3.75(95)
3/4(19)
7.0(178) N/A 8.75
(222.3)3.75(95)
37-1/2(242)
48(22)
EC-3 4(101.6) F 2-1/2
(63.5) F 11(279)
6.50(165)
6.50(165)
3.50(95)
3/4(19)
5.77(147) N/A 7.63
(193.7)4.50(114)
26(168)
42(19)
ED-3 4(101.6) F 3
(76.2) F 11(279.4)
6.50(165)
6.50(165)
3.75(95)
3/4(19)
7.93(201) N/A 10
(254)4.5
(114)37-1/2(242)
55(25)
EE-3 4(101.6) F 4
(101.6) F 11.5(292)
6.50(165)
6.50(165)
4.50(114)
3/4(19)
7.87(200) N/A 10.69
(271.5)4.50(114)
65(419)
72(33)
FE-3 5(127) F 4
(101.6) F 12.5(318)
7.50(191)
7.50(191)
4.50(114)
3/4(19)
7.87(200) N/A 10.69
(271.5)5
(127)65
(419)84
(38)
FF-3 5(127) F 5
(127) F 13.67(347)
7.50(191)
7.50(191)
5(127)
3/4(19)
10.44(265) N/A 12.84
(326.1)5
(127)90
(581)100(45)
GE-3 6(152.4) F 4
(101.6) F 13.5(343)
8(203)
8(203)
4.50(114)
3/4(19)
7.87(200) N/A 10.69
(271.5)5.50(140)
65(419)
90(41)
GF-3 6(152.4) F 5
(127) F 15.67(398)
8(203)
8(203)
5(127)
3/4(19)
10.46(266) N/A 13.84
(351.5)5.50(140)
90(581)
105(48)
GG-3 6(152.4) F 6
(152.4) F 15.82(402)
8(203)
8(203)
5.50(140)
3/4(19)
11(279) N/A 14.75
(374.7)5.50(140)
127(819)
134(61)
HG-3 8(203.2) F 6
(152.4) F 15.82(402)
9(229)
9(229)
5.50(140)
3/4(19)
11(279) N/A 14.75
(374.7)6.75(171)
127(819)
150(68)
HH-3 8(203.2) F 8
(203.2) F 19.55(497)
9(229)
9(229)
6.75(171)
3/4(19)
12.62(321) N/A 18.25
(463.6)6.75(171)
218(1406)
250(113)
JH-3 10(254) F 8
(203.2) F 19.55(497)
10(254)
11(279)
6.75(171)
3/4(19)
12.62(321) N/A 18.25
(463.6)8
(203)218
(1406)290
(132)
JJ-3 10(254) F 10
(254) F 22.80(579)
11(279)
11(279)
8(203)
3/4(19)
15.68(398) N/A 21.50
(546.1)8
(203)338
(2180)415
(188)(T) Threaded - FPT (F) Flanged *Dimensions include orifice cylinder + 2-1/2 (64) inch clearance.Dimensions are subject to change. Not to be used for construction purposes unless certified.
![Page 17: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/17.jpg)
SUCTION DIFFUSER PLUS B-826
TYPICAL SPECIFICATIONSProvide with each pump a Bell & Gossett Suction Diffuser Plus of the size noted on drawings.Units shall consist of angle type body, flanged system connection, integrated Flow Cone, carbon/stainless steel straightening vane and combination diffuser-strainer-orifice cylinder with 3/16" diameter openings for pump protection. The unit shall include a disposable fine mesh strainer which shall be removed after system start-up. Unit shall have pressure/temperature ports at the suction and discharge to allow for measurement of differential pressure across the unit.
Orifice cylinder shall be designed to withstand pressure differential equal to pump shut-off head (maximum ______ PSI) and shall have a free area equal to five times cross section area of pump suction opening. Vane length shall be no less than 2-1/2 times the pump connection diameter. Unit shall be provided with adjustable support foot to carry the weight of suction piping. Unit shall be rated for 175 psi (1,207kPa) maximum working pressure and 250F (121C) macimum working temperature.
![Page 18: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/18.jpg)
RELIEF VALVES
![Page 19: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/19.jpg)
For Pressure Protection of Hot Water Heating Boilers
Sizes: 3⁄4" – 2" (20 - 50mm)
Series 174ABronze body safety relief valves for pressure protection only of all types of hot water heating boiler equipment. Pressure range 30 to 150psi (2.1 - 10 bar) with corresponding high rat-ings from 650,000 to 14,370,000 BTU/hr. Female inlet and outlet connections. Sizes 3⁄4" - 2" (20 - 50mm).
Series 374AIron body with forged brass inlet, 550,000 BTU/hr rating. 3⁄4" (20mm) only.
Series 740Iron body with expanded outlets for hot water space heating boilers. Pressure range 30 to 75psi (2 to 5 bar) with corre-sponding high ratings from 925,000 to 10,700,000 BTU/hr.
Features• Seatlocatedabovedrain;watercan’tbetrappedand
sedimentcan’tfoulseat.• Non-mechanicalseat-to-discalignmentwillnotstick
or freeze.• Watersealofhightemperatureresistingmaterialisolatesspring
workingpartsfromwaterduringrelief.
SpecificationsBoiler Relief ValvesAn ASME Section IV certified pressure relief valve shall be installed on each boiler as noted. The valve shall have a BTU ratinginexcessoftheBTUratingoftheboiler’sheatingoutput.Each hot water space heating boiler shall be equipped with a pressure relief valve set to relieve below the maximum boiler workingpressure.Thevalveshallfeaturearaisedseatandnon-mechanicaldiscalignment.Workingpartsandspringshallbe isolated from any discharge by a high temperature resistant material.ValveshallbeaWattsSeries174A,374Aor740.
OperationAs thermal expansion conditions develop, pressure builds up to the setting of the relief valve. This will cause discharging of small quantity of water.
Should operating controls fail, permitting runaway firing, the boiler water may reach steam temperatures. The valve will then open to discharge steam at the rate or faster than the boiler can generate it, thus restoring system pressure to a safer level.
NOTICEThe discharge line must be the same size as the valve outlet, and must pitch downward from the valve to a safe place for disposal.
Valve lever must be tripped at least once a year to ensure that waterways are clear. This device is designed for emergency safety relief and shall not be used as an operating control.
For Hot Water Boiler ApplicationsES-174A-740
Series 174A Series 740
Series 174A, 374, 740ASME Water Pressure Relief Valves
JobName ––––––––––––––––––––––––––––––––––––––––––– Contractor ––––––––––––––––––––––––––––––––––––––––––––
Job Location ––––––––––––––––––––––––––––––––––––––––– Approval –––––––––––––––––––––––––––––––––––––––––––––
Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’sP.O.No. ––––––––––––––––––––––––––––––––––
Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
It is illegal to use this product in any plumbing system providing waterforhumanconsumption,suchasdrinkingordishwashing,in the United States. Before installing standard material product, consult your local water authority, building and plumbing codes.
WARNING!The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before begin-ning the installation of this product.
NOTICE
![Page 20: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/20.jpg)
Materials
Series 174A• Bronzebodyconstruction
• Nonmetallicdisc-to-metalseating
Series 740• Ironbodyconstruction
• Nonmetallicdisc-to-metalseating
Pressure – Temperature
Series 174APressure range: 30psi to 150psi (2 to 10 bar) with correspond-ing high BTU/hr ratings from 650,000 to 14,370,000 BTU/hr. Maximum Temperature: 250 ºF (121 ºC)
Series. 374APressure range: rated up to 550,000 BTU/hr at a 30psi (2 bar) setting.(Othersettingsavailable)
Series 740Pressure range: 30psi to 75psi (2 to 5 bar) with corre-sponding high ratings from 925,000 to 10,700,000 BTU/hr. Maximum Temperature: 250 ºF (121 ºC)
Standards
TestedandratedbytheNationalBoardofBoilerandPressureVessel Inspectors to the requirements of ASME. Meets Military Spec. MIL-V-18634B, Type I, Class 3A, Style A (Bronze Body), Style B (Iron Body).
ASME
Dimensions – Weights
Capacity*BTU/hr Steam Pressure Discharge CapacitiesAs tested and rated by the National Board of Boiler and Pressure Vessel Inspectors
SerieS 174A
Size (Dn) Height Length Weight
Model in. mm Model in. mm in mm lbs. kg.374A 3⁄4 x 3⁄4 20 x 20 – 31⁄2 90 21⁄2 64 1.2 0.5
174A 3⁄4 x 3⁄4 20 x 20 M3 41⁄2 116 23⁄4 67 1.2 0.5
174A 1 x 1 25 x 25 M1 53⁄4 144 3 76 1.9 0.9
174A 11⁄4 x 11⁄4 32 x 32 M1 81⁄2 213 41⁄4 109 4.6 2.1
174A 11⁄2 x 11⁄2 40 x 40 M 91⁄4 232 43⁄4 122 6.9 3.1
174A 2 x 2 50 x 50 M 111⁄2 290 61⁄2 162 14.4 6.5
SerieS 740
740 3⁄4 x 1 20 x 25 M1 55⁄8 143 3 76 1.88 9
740 1 x 11⁄4 25 x 32 M 71⁄4 184 31⁄2 89 3.13 1.4
740 11⁄4 x 11⁄2 32 x 40 M 83⁄4 222 45⁄8 117 6.13 2.8
740 11⁄2 x 2 40 x 50 M 91⁄4 235 51⁄4 133 7.50 3.4
740 2 x 21⁄2 50 x 65 M 115⁄8 295 63⁄4 171 16.50 7.5
SerieS 174A
Set Pressure
3⁄4” x 3⁄4” 1” x 1” 11⁄4” x 11⁄4” 11⁄2” x 11⁄2” 2” x 2”20 x 20mm 25 x 25mm 32 x 32mm 40 x 40mm 50 x 50mm
psi bar Model M3 Model M1 Model M1 Model M Model M30 2.07 650,000 1,005,000 1,682,000 2,020,000 3,815,000
33 2.27 695,000 1,075,000 1,788,000 2,150,000 4,080,000
35 2.41 725,000 1,125,000 1,877,000 2,250,000 4,250,000
36 2.48 740,000 1,145,000 1,916,000 2,310,000 4,344,000
40 2.76 800,000 1,240,000 2,071,000 2,490,000 4,690,000
45 3.1 875,000 1,355,000 2,265,000 2,720,000 5,130,000
50 3.45 950,000 1,470,000 2,459,000 2,950,000 5,575,000
55 3.79 1,025,000 1,590,000 2,653,000 3,190,000 6,010,000
60 4.13 1,100,000 1,702,000 2,847,000 3,425,000 6,450,000
65 4.58 1,170,000 1,820,000 3,041,000 3,660,000 6,890,000
70 4.82 1,245,000 1,935,000 3,325,000 3,890,000 7,330,000
75 5.17 1,320,000 2,055,000 3,429,000 4,125,000 7,770,000
80 5.51 1,400,000 2,166,000 3,605,000 4,360,000 8,215,000
85 5.86 1,470,000 2,285,000 3,817,000 4,590,000 8,650,000
90 6.6 1,545,000 2,400,000 4,011,000 4,825,000 9,090,000
95 6.55 1,620,000 2,520,000 4,205,000 5,060,000 9,530,000
100 6.89 1,695,000 2,635,000 4,399,000 5,290,000 9,970,000
105 7.23 1,770,000 2,750,000 4,593,000 5,525,000 10,410,000
110 7.58 1,845,000 2,865,000 4,787,000 5,760,000 10,850,000
115 7.92 1,920,000 2,980,000 4,981,000 5,990,000 11,290,000
120 8.27 1,995,000 3,100,000 5,175,000 6,225,000 11,730,000
125 8.61 2,070,000 3,215,000 5,370,000 6,460,000 12,170,000
130 8.96 2,145,000 3,330,000 5,564,000 6,690,000 12,610,000
135 9.3 2,220,000 3,445,000 5,758,000 6,925,000 13,050,000
140 9.65 2,295,000 3,565,000 5,952,000 7,160,000 13,490,000
145 9.99 2,370,000 3,680,000 6,146,000 7,390,000 13,390,000
150 10.34 2,445,000 3,795,000 6,340,000 7,630,000 14,370,000
SerieS 740
Set Pressure
3⁄4” x 1” 1” x 11⁄4” 11⁄4” x 11⁄2” 11⁄2” x 2” 2” x 21⁄2”20 x 25mm 25 x 32mm 32 x 40mm 40 x 50mm 50 x 65mm
psi bar Model M1 Model M Model M Model M Model M30 2.07 925,000 1,300,000 2,105,000 2,900,000 5,250,000
33 2.27 989,000 1,390,000 2,250,000 3,100,000 5,613,000
35 2.41 1,032,000 1,450,000 2,345,000 3,235,000 5,855,000
36 2.48 1,053,000 1,480,000 2,395,000 3,300,000 5,975,000
40 2.76 1,139,000 1,600,000 2,590,000 3,569,000 6,461,000
45 3.10 1,245,000 1,750,000 2,830,000 3,903,000 7,067,000
50 3.45 1,352,000 1,899,000 3,075,000 4,237,000 7,672,000
55 3.79 1,459,000 2,049,000 3,315,000 4,572,000 8,277,000
60 4.13 1,566,000 2,200,000 3,560,000 4,907,000 8,883,000
65 4.58 1,672,000 2,349,000 3,800,000 5,241,000 9,488,000
70 4.82 1,779,000 2,499,000 4,045,000 5,575,000 10,093,000
75 5.17 1,886,000 2,649,000 4,285,000 5,909,000 10,700,000
ES-174A-7401442 ©2014Watts
USA:Tel:(978)689-6066•Fax:(978)975-8350•Watts.comCanada: Tel:(905)332-4090•Fax:(905)332-7068•Watts.ca
Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091•Watts.com
A Watts Water Technologies Company
![Page 21: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/21.jpg)
P-1 & P-2 PUMPS
![Page 22: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/22.jpg)
Submittal Data1600 Series Pumps (Stock Models)
301-001
EFFECTIVE: October 4, 2013 SUPERSEDES: July 1, 2011 1750 RPM MODELS
ITEM NO. MODEL NO. IMPELLER DIA. G.P.M. T.D.H. H.P. ELEC. CHAR.
B (Approximate)
DC
A
TAPPEDHOLE
1/4” NPT
TAPPEDHOLE
1/4” NPT
English dimensions are in inches. Metric dimensions are in millimeters. Metric data is presented in ( ).Do not use for construction purposes unless certified.
NOTE: Individual Submittal Data sheets are available for CUSTOM models.
WEIGHT PUMP/MOTOR
DIMENSIONS: * 1⁄4 HP AVAILABLE IN 1 PHASE ONLY
JOB ENGINEER
CONTRACTOR REP.
MODEL NUMBER FLANGESIZE
POWERHP (KW)
DIMENSIONS
STOCK 1600 CUSTOM 1600 A B C D
1600
1611 11⁄2 (38)
1⁄4 (0.19) *
3 (76)
16.0 (419)
101⁄4 (260) 127⁄8 (327)1610 1⁄3 (0.25) 16.0 (419)1⁄2 (0.37) 17.0 (432)
1615 11⁄2 (38)
1⁄3 (0.25)
31⁄8 (79)
18.0 (457)
131⁄2 (343) 161⁄8 (410)1612 1⁄2 (0.37) 18.5 (470)
1614 3⁄4 (0.56) 19.0 (483)
1 (0.75) 19.5 (495)
1619 2 (51)
3⁄4 (0.56)
3 (76)
18.5 (470)
141⁄2 (368) 173⁄8 (441)1616 1 (0.75) 19.0 (483)
11⁄2 (1.10) 21.0 (533)
2 (1.50) 23.0 (584)
1630
1635 2 (51)
1⁄2 (0.37)
31⁄2 (89)
18.0 (457)
131⁄2 (343) 161⁄8 (410)1632 3⁄4 (0.56) 18.5 (470)
1634 1 (0.75) 19.0 (483)
11⁄2 (1.10) 21.0 (533)
1636
1641 2 (51)
11⁄2 (1.10)
35⁄8 (92)
21.0 (533)
161⁄2 (419) 191⁄2 (495)1638 2 (1.50) 23.0 (584)
3 (2.37) 24.0 (610)
![Page 23: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/23.jpg)
Comments: ____________ ____________________________
MOTORS1750 RPM, Three Phase 200V or 230/460V, 60Hz.Also available in Single Phase with overload protection except3HP (2238 Watts).
BODY Flanged in-line connections. Companion flanges are included.
FLANGES Flanges are tapped for gauges (1⁄4" NPT).
IMPELLER Closed, dynamically balanced
DRIVE COUPLING Non-Metallic, vibration dampening
FRAME Ball bearing type, permanently lubricated.REMOVABLE BEARING CARTRIDGE FITS ALL MODELS.
MECHANICAL SEAL Type 21 2 Piece Standard – 250°F (121°C) Operating Temperatureor Optional High Temperature – 300°F (149°C) Operating Temperature
WORKING PRESSURE 175 PSI (1207 kpa). In accordance with ANSI Standard B16.1.
SPECIFICATIONS
1600 SERIES STOCK UNIT QUICK SELECTION CURVES (1750 RPM)
Item Standard Optional
Casing Cast Iron Bronze
Impeller Cast Bronze N/A
Shaft Hardened Alloy Steel Stainless Steel 416
Shaft Sleeve Cupro-Nickel N/A
Bracket Cast Iron Cast Iron with StainlessSteel Face Plate
MATERIALS OF CONSTRUCTION
N/A - Not Available
1600 SERIES CUSTOM UNIT QUICK SELECTION CURVES (1750 RPM)
Do it Once. Do it Right.®TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436.
Visit our web site at: http://www.taco-hvac.com
Printed in USA
Copyright 2013
TACO, Inc.
![Page 24: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/24.jpg)
P-3 & P-4 PUMPS
![Page 25: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/25.jpg)
SUBMITTALB-880.4A
JOB: Flynn Elementary HVAC Upgrade REPRESENTATIVE: McNevin Co
UNIT TAG: P-3&4 ORDER NO. DATE: 11/13/2015ENGINEER: SUBMITTED BY: DATE: CONTRACTOR: APPROVED BY: DATE:
2AD-esSeries e-1510Centrifugal Pumps - Base Mounted
SPECIFICATIONSFLOW 90 (GPM) HEAD 40 (FT)
HP 2 RPM 1800
VOLTS 208-230/460
CYCLE 60 PHASE 3
ENCLOSURE ODP Nema Premium Efficient
APPROX. WEIGHT 200
SPECIALS
Note: Equipped with NEOPRENE coupling
MATERIALS OF CONSTRUCTION Stainless Steel Fitted
FEATURESi-ALERT™ Condition MonitorANSI/OSHA Coupling GuardCenter Drop Out Spacer CouplingFabricated Heavy Duty Baseplate
MAXIMUM WORKING PRESSURE175 psi (12 bar) W.P. w/ 125# ANSI flange drilling
TYPE OF SEALStandard Seal(Buna-Carbon/Silicon Carbide)-F Standard Seal w/ Flush Line(Buna-Carbon/Silicon Carbide)
![Page 26: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/26.jpg)
FLANGES ARE 125# ANSI - STANDARD
Series e-1510 2AD-es Centrifugal Pump Submittal B-880.4A
FLANGE DIMENSIONS IN INCHES (MM)SIZE THICKNESS O.D.
Discharge 2" 5/8" (16) 6" (152)Suction 2-1/2" 11/16" (17) 7-1/8" (181)
DIMENSIONS − Inches (mm) STANDARD SEALMOTOR FRAME
HA HB HC MAX HD 2HE HF1 HF2 HH HL HM MAX HO HP Y Z "es" FRAME
56 12(305)
28-3/4(730)
28-7/8(733)
9-3/4(248)
10-1/4(260)
22-1/2(572) − 3/4
(19)3-9/16(90)
13-3/8(340)
16-1/4(413)
3(76)
3-1/2(89)
4-3/4(121)
143T 12(305)
28-3/4(730)
29(737)
9-3/4(248)
10-1/4(260)
22-1/2(572) − 3/4
(19)3-9/16(90)
13-1/2(343)
16-1/4(413)
3(76)
3-1/2(89)
4-3/4(121)
145T12
(305)28-3/4(730)
30(762)
9-3/4(248)
10-1/4(260)
22-1/2(572) − 3/4
(19)3-9/16(90)
13-1/2(343)
16-1/4(413)
3(76)
3-1/2(89)
4-3/4(121)
182T 14-5/8(371)
31(787)
32-5/8(829)
9-3/4(248)
12-7/8(327)
25(635) − 3/4
(19)2-3/16(56)
15(381)
16-1/4(413)
3(76)
3-1/2(89)
4-3/4(121)
184T 14-5/8(371)
31(787)
33-3/8(848)
9-3/4(248)
12-7/8(327)
25(635) − 3/4
(19)2-3/16(56)
15(381)
16-1/4(413)
3(76)
3-1/2(89)
4-3/4(121)
213T 14-5/8(371)
34-5/8(879)
36(914)
9-3/4(248)
12-7/8(327)
28-5/8(727) − 3/4
(19)2-3/16(56)
15-5/8(397)
16-1/4(413)
3(76)
3-1/2(89)
4-3/4(121)
215T 14-5/8(371)
34-5/8(879)
37-1/2(953)
9-3/4(248)
12-7/8(327)
28-5/8(727) − 3/4
(19)2-3/16(56)
15-5/8(397)
16-1/4(413)
3(76)
3-1/2(89)
4-3/4(121)
Dimensions are subject to change. Not to be used for construction purposes unless certified.
Xylem Inc.8200 N. Austin AvenueMorton Grove, IL 60053Phone: (847)966-3700 Fax: (847)965-8379www.bellgossett.comBell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.ESP-REP v2015.03 © 2013 Xylem Inc.
![Page 27: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/27.jpg)
P-5 PUMP
![Page 28: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/28.jpg)
SUBMITTALA-126F
JOB: Flynn Elementary HVAC Upgrade REPRESENTATIVE: McNevin Co
UNIT TAG: ORDER NO. DATE: 11/13/2015ENGINEER: SUBMITTED BY: DATE: CONTRACTOR: APPROVED BY: DATE:
System LubricatedIron Body Circulators
DESCRIPTIONA flanged in-line system lubricated circulating pump designed specifically for quiet operation in a closed hydronic heating system.
OPERATING DATAMaximum Working Pressure: 150 psi (10.3Bar)Minimum Operating Temperature: 40°F (5°C)Maximum Operating Temperature NRF-22 & NRF-9F/LW: 240°F (115°C)
NRF-25, NRF-33, NRF-36 & NRF-45: 225°F (107°C)
CONSTRUCTION MATERIALSPump Body: Cast IronImpeller: NorylShaft: CeramicBearings: Carbon
SCHEDULE
MODELNUMBER
PARTNUMBER
STANDARD 60 CYCLE SINGLE PHASEMOTOR CHARACTERISTICS
TAGGING INFORMATION QUANTITYWATTS VOLTAGEF.L.
AMPS RPMNRF-9F/LW 103267 41 115 .40 2800
NRF-22 103251 92 115 .80 2940 P-5 1
NRF-25* 103417 125 115 1.1 2950NRF-33 103350 125 115 1.1 2950NRF-36* 103400 270 115 2.1 3300
NRF-45* 103404 270 115 2.1 3300*Three-speed pump
![Page 29: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/29.jpg)
INHIBITED PROPYLENE GLYCOL
![Page 30: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/30.jpg)
Technical Bulletin
JEFFCOOL® P-150 INDUSTRIAL COOLANT AND HEAT TRANSFER FLUID
GENERIC NAMES Inhibited propylene glycol
DESCRIPTION An inhibited propylene glycol based industrial coolant and heat transfer fluid.
APPLICATIONS Since JEFFCOOL P-150 coolant is formulated with propylene glycol, it is especially suitable for applications in which toxicological and environmental considerations are critical. JEFFCOOL P-150 is a heat transfer fluid for line heaters, for snow melting systems on loading ramps, highways, and runways; a coolant for ice rinks and air conditioning (HVAC) systems.
SALES SPECIFICATIONS
Specifications Slightly hazy and free of suspended matter
Property Appearance Freezing point,
Test Method* ST-61 ASTM D-3321
50 vol % solution, °C -32 max. 50 vol % solution, °F -25 max. pH, solution, 33% 9.5 min. – 10.5 max. ASTM D-1287 Reserve Alkalinity, mL 10.5 min. – 14.0 max. ASTM D-1121 Specific Gravity, 60/60°F 1.05 min. – 1.06 max. ASTM D-1122 Water, wt% 4.0 max. ASTM D-1123
*Methods of Test are available from Huntsman Corporation upon request.
ADDITIONAL INFORMATION
Regulatory Information DOT/TDG Classification Not regulated
HMIS Code 0-1-0 WHMIS Classification Not regulated
Chemical Control Laws Australia, AICS Listed Canada, DSL Listed Europe, EINECS/ELINCS Listed Japan, METI Not determined United States, TSCA Listed
Typical Physical Properties Boiling point, °C (°F) 187 (368)Density, lb/gal, 60°F 8.8 Flash point, PMCC, °C (°F) 100 (212) Melting/Freezing point, °C (°F) < -60 (< -76) Specific gravity 1 Odor Slight odorpH 9.9Vapor pressure, mmHg, 20°C (68°F) <1Viscosity, cSt, 40°C (104°F) < 20Water solubility (%) > 10
![Page 31: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/31.jpg)
PRODUCT SAFETY POLICY It is the product safety policy of Huntsman Corporation to provide our customers with information on the safe handling and use of our products. The Material Safety Data Sheet (MSDS) should always be read and understood thoroughly before handling the product, and adequate safety procedures should be followed. Information on the toxicity, environmental and industrial hygiene aspects of our products may be found in the MSDS.
TOXICITY AND SAFETY For additional information on the toxicity and safe handling of this product, consult the Material Safety Data Sheet (Safety Data Sheet in Europe) prior to use of this product.
HANDLING AND STORAGE JEFFCOOL® P-150 coolant may be stored in unlined carbon steel tanks and drums. If storage of concentrated JEFFCOOL P-150 coolant for periods over 12 months is desired, it is recommended that the storage vessels be constructed from aluminum, stainless steel, or lined carbon steel. Vinyl, epoxy, and phenolic linings are suitable.
The normal precautions associated with any chemical should be observed in handling JEFFCOOL P-150 coolant. This product is neither explosive nor flammable under normal storage conditions. The propylene glycol in this product is considered practically nontoxic. Splashes onto eyes or skin, however, must be washed away quickly and medical treatment is advised for eye exposure. Breathing of the vapors or mists should be avoided.
AVAILABILITY JEFFCOOL P-150 coolant is available in tank wagons and 55-gallon, non-returnable steel drums. Bulk and drum inventory is available at select locations throughout the United States. Contact your local Huntsman Sales Representative for details. Samples are available by contacting our sample department at 1-800-662-0924.
Huntsman Corporation Business Offices 10003 Woodloch Forest Dr. The Woodlands, TX 77380 (281) 719-6000
Huntsman Advanced Technology Center Technical Service 8600 Gosling Rd. The Woodlands, TX 77381 (281) 719-7780
Samples 1-800-662-0924
www.huntsman.com
5112-0112
Copyright © 2007, 2012 Huntsman Corporation or an affiliate thereof. All rights reserved. JEFFCOOL® is a registered trademark of Huntsman Corporation or an affiliate thereof in one or more, but not all countries.
Huntsman Corporation warrants only that its products meet the specifications stated herein. Typical properties, where stated, are to be consideredas representative of current production and should not be treated as specifications. While all the information presented in this document is believed to be reliable and to represent the best available data on these products, HUNTSMAN MAKES NO WARRANTY OR GUARANTEE OFANY KIND, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, NON-INFRINGEMENT OF ANY INTELLECTUAL PROPERTY RIGHT OF ANY THIRD PARTY, OR WARRANTIESAS TO QUALITY OR CORRESPONDENCE WITH PRIOR DESCRIPTION OR SAMPLE, AND ANY USER OF PRODUCTS DESCRIBEDHEREIN SHOULD CONDUCT A SUFFICIENT INVESTIGATION TO ESTABLISH THE SUITABILITY OF ANY PRODUCT FOR ITS INTENDED USE AND ASSUMES ALL RISK AND LIABILITY WHATSOEVER RESULTING FROM THE USE OF SUCH PRODUCT, WHETHER USEDSINGLY OR IN COMBINATION WITH OTHER SUBSTANCES. Product(s) described in this publication may be hazardous and/or toxic and require special precautions in handling. For all product(s) described herein, the user should obtain from Huntsman detailed information on hazardsand/or toxicity, together with proper shipping, handling, and storage procedures, and should comply with all applicable safety and environmental standards. The behavior, hazards and/or toxicity of the product(s) referred to in this publication in manufacturing processes and their suitability inany given end-use environment are dependent upon various conditions such as chemical compatibility, temperature, and other variables, whichmay not be known to Huntsman. It is the sole responsibility of the user of such product(s) to evaluate the manufacturing circumstances and thefinal product(s) under actual end-use requirements and to adequately advise and warn future purchasers and users thereof.
![Page 32: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/32.jpg)
GF-1 GLYCOL FEEDER
![Page 33: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/33.jpg)
Data $fteef
ApplicationOur g lycol feeders mainta in a consis tentpressure in closed loop systems automaticallyal lowing for expansion and contraction ofglycol at rcA%.
The feeder is construcled on a rugged paintedsteel frame with a polyethylene tank, highflow feed purnp, prewired controller, low levelcut-off alarm and preplumbed piping assemblywith pressure gauge, pressure sensor, backcheck and relief valve,
Dig i ta l models d ig i ta l ly d isp lay the actualpressure of the loop and have a user settablecontrol pointfor pump activation and pressurerelief makrng start-up and operation easy.
wc-370302wc-370392-DwcD-3703A2wcD-370302-DGlycol Feeder
For ClosedLoop Sysferns
Key Features. Digital Displayed Pressure
' Simple $et Point Control
. lndustrial Steel Frame
, Audible Alarm
' Prewired Controls
. Low Level Pump Cut off
' Dual Systems
. Copper Pip ing
wcD-370302
#tu
![Page 34: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/34.jpg)
Models$tanciari unrt: Copgi*r Pli:, 'nbing. analog cnntrol,55 gai lank, sie*i frame, 1d-i6 psi swiich, 1.3 *pnrpump, lov!/ level cut-aif anci audible alarm withsiience switch, dry contaci alarrn, pr*ssure relielvaive and PVC plumbing assembiy with presnuregauge.
Dig i ta l models have a contro i uni t tha i d ig i ia l lydispiays the actual ioop pressure and allow for usersettable contrsl pcints. The plumbing asseinblycomes compiete with a presslire sensof rated for5-100 psi {0.3-6.9 bar} applications.An exampie msdel number WCD-370302
Analog models have a cnntrol unit wtth analogswitches for testing and LED indicaior l ights" Theplumbrng assembly conts$ complete with a 30-60psj (2 04 1 bar) pressur* switclr.
WC-370302 Standard Uni lWC-37030?D Dual Unit, {or iwo separate loopsWCD-370302 Single Digiiai UnilWCD-370302D Digital and Dual, fsr two
separate loopes
Opt ions
30 30 gal (1 '1 3 l i ier ) tark rn p lece of 55 ga '100 100 gal . (378 l i ter ) tank in p lace of 55 gal .Al ternate purnp s ize" 3 3 gpm / 6C psi
Specif icat ionsElectrical
" Inpul. Alarm
. Motor
Plumbing. Standard
'120 VAC, 5C160 i-.t:Dry Cantact5 Amp {resistive), SPST
113 HP Pump: 1.3 GPhl
Copper
LE'EL \>-caxTnoule ,1,//
r;.-;--*.:-=")l c c $ i i ? iia_:_--_:__:-'
Digiial Controller Analog Controller
Fositive Displacement Pump. Pump ra ted a t 1 .3 GPM = 100 psr (s tandard) < -. Pump rated at 3 3 GPM = 6C psi
EnclosureHeavy Duty NEMA 4X style hiEh irnpactthermoplastic wlth padlockable gasketed Lexanviewing door
Pressure Gauge 0-100 psi
G lyco lTankL J d F i d U l t y
Tank and L id
Dimensions
/S lpnoard 55 na l ra rk
stand & single prmpli
Vd:S.5" (74.93 crn)H 5'3' l '160.02 cmJD 29.5 ' {74 .93 cm)
Shipping WeightwcD-370302wcD-370302D
5 5 n a l l n n c
Polyethylene
140 lbs {63 50 kg) approx165lbs i74.84 kg) approx
i . 3 t- * l* * l
t g L ! r
1-.;*M E{ : Bc e l0 i g| l 0
si20 ''10
![Page 35: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/35.jpg)
PRE-STARTUP CLEANER
![Page 36: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/36.jpg)
PreClean-6032
PreClean-6032 Boiler/Cooling System Cleanser
Product Description • PreClean-6032 is a blend of organic surface reduction and dispersal agents for cleaning
applications of industrial water systems.• PreClean-6032 was designed to clean fouled surfaces of heat transfer equipment, to cleanse
the system of dirt, debris, oil, mill scales and general grime.• PreClean-6032 is especially effective in both cleaning and scrubbing these dirt like deposits
and at the same time providing a passivated corrosion inhibitory film on the cleansed metalsurface.
• PreClean-6032 can be used for boiler, closed loop or cooling systems.• PreClean-6032 should be applied as a pre-treatment cleaner and is not intended as an on-line
treatment.• PreClean-6032 functions by penetrating the matrix of organic deposits, chelation of metallic
ion deposits, dispersal of particulate matter and reducing the surface tension of the dirt/oil filmas well as surface scrubbing agent action which clean away the dirt.
• PreClean-6032’s cleansing action allows the surface areas to be free of dirt, oil and millscales, which then allows the temporary corrosion inhibitory films of PreClean-6032 to adhereuntil a longer term treatment regimen is applied.
Application Rate and Control Parameters • PreClean-6032, the amount used will depend upon the severity of the dirt, grime, oil and mill
scale left in the equipment. For maintenance of clean surfaces in previously cleaned systemswhere PreClean-6032 is being applied occasionally as preventive maintenance.
• PreClean-6032 should be fed at a rate of 120-360 ppm. For systems where a greatercleansing action is required PreClean-6032 should be fed at a rate of 1200-10,000 ppm.
• PreClean-6032 should be pre-mixed in a volume of water and then applied to the system. Forboiler or hot water closed loops increasing the temperature of the re-circulating water willassist PreClean-6032 in its cleansing action.
• PreClean-6032 utilized for cooling or chill loops should be applied at ambient temperature andre-circulate the system for a longer period of time. Generally a 4-12 hour recirculation rate isneeded for any effective cleaning process.
• PreClean-6032 applied to heavily fouled systems may tend to slough large amounts ofdeposited material; therefore, adequate precautions should be taken to prevent plugging ofscreens, small lines and heat exchangers.
Physical Properties: PreClean-6032 System Boiler/Cooling Cleanser Form: Liquid Color: Light AmberOdor: Slight Aromatic pH: 12+/-Density: 9.09#/gallon Specific Gravity: 1.09Freeze Point: Approximately 32F Freeze/Thaw Recovery: Complete Ship Class: Non Regulated Materials HMIS Code 100C Refer to the MSDS for further health, safety and environmental information regarding this product. Information and recommendations in this bulletin are based on information believed to be reliable. However, the use of the product is beyond the control of MCI, and no guarantee, expressed or implied, is made as to the effects of such the results to be obtained if not used in accordance with directions or established safe practice. The buyer must assume all responsibility, including injury or damage, resulting from misuse of the product as such, or in combination with other material
![Page 37: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/37.jpg)
BYPASS CHEMICAL POT FEEDER
![Page 38: PROJECT: DATE: TO: RE: ATTN: JOB: WE ARE SENDING ...pix.ghphipps.com/projects/2015/15.0732/ProjDocs/06 - Submittals... · No. 16D5292-0072 Central Mechanical Inc 3774 Puritan Way](https://reader034.fdocuments.us/reader034/viewer/2022051509/5b00d54e7f8b9a0c028d5a67/html5/thumbnails/38.jpg)
Specification SheetFLAT BOTTOM BYPASS FEEDERS
MANUFACTURING: Mixers, Bypass Feeders, Filter Feeders, Bromine Feeders, Sample Coolers, Sludge Traps, Separators, Separator Systems, Tank Stands, Tank Package Systems, Glycol Feed Systems, Coupon Racks, Control Stations, NEMA Enclosures, Custom Packaged Systems and Specialty Welding
P.O. Box 6207 l Garden Grove, CA 92846-6207 / 11800 Monarch St. l Garden Grove, CA 92841-2113 l Phone (714) 379-5519 l Fax (714) 379-5549Northern California Region l Phone (510) 487-5310 l Southwest Region l Phone (602) 470-1015 l Email: [email protected]
www.jlwingert.com
Note: All dimensions are +/- 1/8". All weights are approximate. All dimensions are subject to change without notice.
SS030001.A 10/12
DIMENSIONS, WEIGHT & CUBE:
KEY 2HD 5HD 12HD 18HD
A 21 1/8" 21 1/8" 41 3/4" 60 5/8"
B 12 1/2" 10 5/8" 31" 44"
C 3 1/4" 4 1/4" 4 1/8" 8 1/2"
D 6" 10" 10" 10"
WEIGHT 19 lbs. (8.6 kgs.) approx. 33 lbs. (15 kgs.) approx. 58 lbs. (26.3 kgs.) approx. 82 lbs.(32.7 kgs.) approx.
CUBE 6" x 6" x 22" 10" x 10" x 22" 10" x 10" x 44" 10" x 10" x 63"
PARTS, MATERIALS AND SPECIFICATIONS
KEY PART SPECIFICATIONS
1 3071 CLOSURE: 3 1/2" cast iron, 1/4 turn closure, (O-ring included)
2 3072 O-RING: Buna-N O-ring 200°F
3 BODY: Carbon steel
4 INLET: 3/4" FNPT
5 OUTLET: 3/4" FNPT
MAX. PRESSURE 200 PSI (13.6 BAR)
MAX. TEMPERATURE 200°F (93°C)
VOLUME (FILL CAPACITY)
MODEL GALLONS LITERS
2HD 2.16 8.17
5HD 5.79 21.92
12HD 12.76 48.30
18HD 19.22 72.75