Procera Plus
GE Consumer & IndustrialPower Protection
Design, Drawing and calculation software forindustrial low voltage installations including distribution circuits
2GE Consumer & Industrial
Industrial Components Team
ProceraPlus
The new HD384 and R064-03 standards require that the design of a low voltage distribution system includes the determination of all perspective short-circuit and fault current levels.
3GE Consumer & Industrial
Industrial Components Team
ProceraPlus
• Cross section of conductors
• Fault levels
• Switchgear selection
• Draw single line diagram
ProceraPlus is a software to design & calculate
4GE Consumer & Industrial
Industrial Components Team
ProceraPlus
In Procera Plus a project is entered starting at the Upstream device (source supply ) moving to Downstream (end-user circuits)
This method is used to determine the protective devices and cable cross-sections
First the source must be defined, then the distribution circuits and finish by end-user's circuits.
In Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time.
From transformer to end-user circuits
5GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Network tree
Single line diagram
Results window
Report
Menu
Software Interface
6GE Consumer & Industrial
Industrial Components Team
ProceraPlus Pull Down Menus
7GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Easy data entry on a single line network diagram
Select the circuit style
Select the distribution Board
Software Interface
8GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Easy control of data entry, parameters and results
Consumption
Length
Calculate
Protection
Software Interface
9GE Consumer & Industrial
Industrial Components Team
ProceraPlus
A software which automaticaly prints a complete file
Software Interface
10GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Starting Procera Plusyou will get this window .
To start a project press “New”…
Getting Started
11GE Consumer & Industrial
Industrial Components Team
ProceraPlus
There are three possiblechoices : • Transformer HV-LV • Genset • Direct supply from utility board (LV direct
Project Started – Type of Source
12GE Consumer & Industrial
Industrial Components Team
ProceraPlus
TransformerThey can be entered:
a) from a file giving sources impedances and standard Powers or,
b) from Ukr, short circuit voltagein % for transformers, equivalentto impedance
Project Started – Source Characteristics
13GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Genset:They can be entered :
a) from a file giving sources impedances and standard powers or,
b) steady state and transient reactance, given in % to definegenerating sets.
Project Started – Source Characteristics
14GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Standarised power of the sourcecharacteristics are given froma file . Power value can be entered as "not normalized" if Ukr was chosen
Project Started – Source Power
15GE Consumer & Industrial
Industrial Components Team
ProceraPlus
In ProceraPlus, all sourcesare considered as identical. This data is used to determine Ikmax, which makes it possible to proposedownstream protective device incase of paralleling of several transformers. Ik mini are calculatedtaking into account the minimumnumber of sources in parallel.
Project Started – Number of Sources
16GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•Earthing system: TN, TT, IT•LV opearting voltage•Frequency•3 phase , single phase•HV protection time•HV system power
Project Started – Network Parameters
17GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•Length•Installation method•Copper , aluminum•Cable type
Project Started – Link Parameters
18GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•Length •Installation method•Copper , aluminum•Cable type
Project Started – Link Parameters
19GE Consumer & Industrial
Industrial Components Team
ProceraPlus
To check installation methodpress:
.
Project Started – Link Parameters
20GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Getting results:
Press Calculate to get results•cable cross section•Fault levels
.
Project Started – Getting First Results
21GE Consumer & Industrial
Industrial Components Team
ProceraPlus
+
Result Window
Press OK to go further
Project Started – Getting First ResultsResult window
22GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Criterion
Theoretic Cross Section
Max Short Circuit Current
Min Short Circuit Current
Design Circuit current
Voltage Drop
Max 1Ph SC Current
Ph-E Fault Current (needed for humanprotection)
Cable Cross-section
Calculated for minimum number of sources
Calculated for minimum number of sources
Results window
Project Started – Getting First Results
23GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Getting first results
Diagram with results for first part of circuit is available
Colours of diagramGreen- OKRed- must be calculatedPurple- NOK
Project Started – Getting First ResultsDiagram
24GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Project Tree
Project single line diagram
Calculation report
Active SourceDistribution
Active boardConsumption
Available current
Results
Creating Project– Reading Information
25GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Using Tabs
Defining Source the “ Source” Tab was used.What other Tabs can we use?
.
Creating Project – Using Tabs
26GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Loop impedances upstream MSB and related to one single transformer. These values are the sum of impedances.
.
Creating Project – Using TabsImpedance Tab
27GE Consumer & Industrial
Industrial Components Team
ProceraPlus
R0 Phase-Phase - Loop resistance Phase to Phase (equals to 2 times one phase resistance), calculated at 20°C conductors temperature. This value is used to determine the maximum short circuit currents (Ik Max). R1 Phase-Phase Loop resistance Phase to Phase (equals to 2 times one phase resistance), calculated at operating temperature. This value is used to determine among others the minimum short circuit currents (Ik Min). X Phase-Phase Loop reactance Phase to Phase. This value is used to determine minimum short circuit currents (Ik Min). X Phase Phase reactance. This value is used to determine maximum short circuit currents. R0 Phase-Neutral Loop resistance Phase to Neutral, calculated at 20°C conductors temperature. This value is used to determine the maximum short circuit current (Ik Max SIngle). R1 Phase-Neutral Loop resistance Phase to Netral, calculated at operating temperature. This value is used to determine among others the minimum short circuit current (Ik Min Single). X Phase-Neutral Loop reactance Phase to Neutral. This value is used to determine minimum short circuit current (Ik Min
Creating Project – Using TabsImpedance Tab
28GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•Ref mark Board Downstream Ref mark –Editable•Designation Board name (data recommended for ease of identification). –Editable•Coincidence factor (K.Simultaneity) Simultaneity factor for circuits fed by the considered board. -EditableExample : a distribution feeds 10 circuits of 10 Amps each. A Simultaneity factor of 0.8 means that the total real consumption is 10 x 10 x 0,8, to say 80 Amps. •Earthing system Board Earthing system : TT, TN, IT •Voltage ,No load voltage No load voltage in V, used to calculate Ik3 Max. •Upstream circuit ref mark Circuit Upstream ref mark. In case of an installation with a standby, the board can be fed by two different circuits. An upstream circuit supplied from the normal supply and another one from the standby source supply.
•Breaking device Board breaking device (generally a switching device in distribution boards). -Editable
Creating Project – Using TabsBoard Tab
29GE Consumer & Industrial
Industrial Components Team
ProceraPlus
This tab appears if the Breaking device on Board Tab differs from “NIL”
•File Protection manufactuers file. •Protection Protective device commercial name. •Rating Circuit breakers rating. •Irth Circuit breaker thermal relay setting or fuses rating value. •IrMg Circuit breaker magnetic setting or fuses rating value. •Magnetic Type of magnetic used Standard or C curve for modular CrBrk Low or B curve Electronic or D/K curve •Delay Circuit breakers short circuit delay •RCD setting Circuit breakers residual current (differential) delay setting. RCD Delay Circuit breakers residual current differential) delay.
Creating Project – Using TabsProtection Tab
30GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•A UPS can be connected either on a Normal or Standby distribution. •A comparison between Ik is done to keep the least favorable one (Ik max on the network, Ikmin on the UPS). The process is inverted when Normal source Ik Min become less than UPS ones. UPS are considered as current generators. Due to that, Ik are unchanged along the network tree. The UPS is always considered as connected in "By-Pass"mode.
.
Creating Project – Using TabsUPS Tab
31GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•Normal and standby short circuit currents at board level. •IK2/3 Max Maximum three-phase short circuit current. Maximum value between Normal and standby if it exists. IK1 Max Maximum single-phase short circuit current if neutral is present. Maximum value between Normal and standby if it exists. •Ik1/2Min Minimum single-phase short circuit current if neutral is present. biphase (phase to phase) if neutral is absent. •If Phase-PE default short circuit current at line end. Minimum value between Normal and standby if it exists. •dU Cumulated voltage drop (in %) at board level from source of
.
Creating Project – Using TabsIk/dU Tab
32GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•I Allowed -allowed current downstream board. This value is equal to the current of the circuit feeding the board. •I available -available current downstream board : available design current for new circuits which can still be fed from the board. •S Intensities -design current IB sum of all circuits issued from the board multiplied by the board simultaneity factor. •Mean cos phi -mean power factor phi at board level, taking into account downstream circuits and eventual capacitors. •R=S IZ cables / Irth board -ratio between: sum of currents of downstream circuits (current calculated without taking into account group factor) and upstream thermal relay setting.
Creating Project – Using TabsCurrents Tab
33GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Board TabYou can display the Board window by:
•In the Source Window by clicking on the Downstream Board Tab.
•Double-clicking board on diagram
• Going to Pull down menu- Distributions Information
.
Creating Project – Using TabsBoard Tab
34GE Consumer & Industrial
Industrial Components Team
ProceraPlus Creating Project – Source Has Been Defined
35GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Mains (N) & Stand-by (S) source have been defined
Creating Project – Types of Source(Mains and Stand-by)
36GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Next step: Adding next subboards
Besides choosing standard parameters it must be specified if the load ( board) will be fed from Stand- By Supply.
Since Stand by Supply usually has much less SC current – The crtiterion that Imag< ISC_min must checked as well. The max setting of Imag is given.
Creating Project – Types of Source(Mains and Stand-by)
37GE Consumer & Industrial
Industrial Components Team
ProceraPlus
NS on crossing indicates that subboard is fed from Mains or Stand ByN- fed only from Mains
Creating Project – Types of Source(Mains and Stand-by)
38GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Results for Board which can be suplied from NS.Since SC currents are smaller in case when fed from Stand By –the minimum Isc which can appear is 4260A.
The value assumes the tolerance3550 *1,2=4260
Creating Project – Types of Source(Mains and Stand-by)
39GE Consumer & Industrial
Industrial Components Team
ProceraPlus
When board is fed only from Mains ( there is not possible situation to be fed from Stand by only) the magnetic settings can be much higher.
For the same board and cable in this case the max Imag could be equal even 14272A
Creating Project – Types of Source(Mains and Stand-by)
40GE Consumer & Industrial
Industrial Components Team
ProceraPlus
.
Enter board tab- choose Breaker or switch
Press Calculate to getdevice
Project Adding– Link Switches and Breakers
41GE Consumer & Industrial
Industrial Components Team
ProceraPlus Project Adding– Link Switches and Breakers
42GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Link switches,Breakers are added
Project Adding– Link Switches and Breakers
43GE Consumer & Industrial
Industrial Components Team
ProceraPlus
3 4
2
1
5- Right mouse button click
Five ways of addingCircuit
“3” adding number Of circuits
Project Adding– New Circuits how to
44GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Different types of circuits can be added
Project Adding– Different types of circuits, loads
45GE Consumer & Industrial
Industrial Components Team
ProceraPlus
•Board was added.•It is still in red because it has not been calculated yet
Project Adding New Circuits– Different types of circuits, loads
46GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Must be specified when added
•Type of breaker protecting circuit•Cable parameters•Coefficients•Consumption (Load)
and “Calculate”
Project Adding New Circuits - values which must be specified
47GE Consumer & Industrial
Industrial Components Team
ProceraPlus
When “calculate” pressedbreakers are proposed.
Project Adding New Circuits - selection of breakers protection circuit
48GE Consumer & Industrial
Industrial Components Team
ProceraPlus Project New Circuit is Added
49GE Consumer & Industrial
Industrial Components Team
ProceraPlus
ResultsThe circuit is “ green”- OKBut:In result window there is written:Discrimination – I<8.33kA
Is the result OK for you?
If NOT “up” or “down” stream breaker must be changed.
Project New Circuit is Added– Is the result OK?
50GE Consumer & Industrial
Industrial Components Team
ProceraPlus
To choose breakers assuring total discrimination/ selectivitypress button as on drawing or F12
Project New Circuit is AddedProject total discrimination
51GE Consumer & Industrial
Industrial Components Team
ProceraPlus
Changing upper and lower breakers type change the achieved discrimination results.
Thus the upper breaker should be changed to for instance K frame SMR1e.
Project New Circuit is AddedProject total discrimination
52GE Consumer & Industrial
Industrial Components Team
ProceraPlus
After changing the upper stream breaker
The lower part of diagram is in red- it must be recalculated
Project New Circuit is AddedProject total discrimination
53GE Consumer & Industrial
Industrial Components Team
ProceraPlus
The total discrimination is assured
Project New Circuit is AddedProject total discrimination
54GE Consumer & Industrial
Industrial Components Team
ProceraPlus
In the same way adding next circuits the project is designed
Project - building up project
55GE Consumer & Industrial
Industrial Components Team
ProceraPlus
For given example despite the fact that the I3max on DB2 is 34kA, the end load circuits are protected with cost effective 25kA MCCBs.This effect is achieved thanks to backup backup protectionprotection.
DB2- 34kA
FD 25kA
Project – back up protection
56GE Consumer & Industrial
Industrial Components Team
ProceraPlus
To generate a complete report ( printout) choose FolderAll. Otherwise results can be got 1 by one
Project finished – generating report
57GE Consumer & Industrial
Industrial Components Team
ProceraPlus Project finished – generating reportFolios List
58GE Consumer & Industrial
Industrial Components Team
ProceraPlus Project finished – generating reportSupply sheet
59GE Consumer & Industrial
Industrial Components Team
ProceraPlus Project finished – generating reportNetwork single line
60GE Consumer & Industrial
Industrial Components Team
ProceraPlus Project finished – generating reportProtection settings
61GE Consumer & Industrial
Industrial Components Team
ProceraPlus Project finished – generating reportCircuit specification