Procera Plus GE Consumer & Industrial Power Protection Design, Drawing and calculation software for industrial low voltage installations including distribution circuits

Transcript of Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit,...

Page 1: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

Procera Plus

GE Consumer & IndustrialPower Protection

Design, Drawing and calculation software forindustrial low voltage installations including distribution circuits

Page 2: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

2GE Consumer & Industrial

Industrial Components Team

ProceraPlus

The new HD384 and R064-03 standards require that the design of a low voltage distribution system includes the determination of all perspective short-circuit and fault current levels.

Page 3: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

3GE Consumer & Industrial

Industrial Components Team

ProceraPlus

• Cross section of conductors

• Fault levels

• Switchgear selection

• Draw single line diagram

ProceraPlus is a software to design & calculate

Page 4: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

4GE Consumer & Industrial

Industrial Components Team

ProceraPlus

In Procera Plus a project is entered starting at the Upstream device (source supply ) moving to Downstream (end-user circuits)

This method is used to determine the protective devices and cable cross-sections

First the source must be defined, then the distribution circuits and finish by end-user's circuits.

In Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time.

From transformer to end-user circuits

Page 5: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

5GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Network tree

Single line diagram

Results window

Report

Menu

Software Interface

Page 6: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

6GE Consumer & Industrial

Industrial Components Team

ProceraPlus Pull Down Menus

Page 7: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

7GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Easy data entry on a single line network diagram

Select the circuit style

Select the distribution Board

Software Interface

Page 8: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

8GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Easy control of data entry, parameters and results

Consumption

Length

Calculate

Protection

Software Interface

Page 9: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

9GE Consumer & Industrial

Industrial Components Team

ProceraPlus

A software which automaticaly prints a complete file

Software Interface

Page 10: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

10GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Starting Procera Plusyou will get this window .

To start a project press “New”…

Getting Started

Page 11: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

11GE Consumer & Industrial

Industrial Components Team

ProceraPlus

There are three possiblechoices : • Transformer HV-LV • Genset • Direct supply from utility board (LV direct

Project Started – Type of Source

Page 12: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

12GE Consumer & Industrial

Industrial Components Team

ProceraPlus

TransformerThey can be entered:

a) from a file giving sources impedances and standard Powers or,

b) from Ukr, short circuit voltagein % for transformers, equivalentto impedance

Project Started – Source Characteristics

Page 13: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

13GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Genset:They can be entered :

a) from a file giving sources impedances and standard powers or,

b) steady state and transient reactance, given in % to definegenerating sets.

Project Started – Source Characteristics

Page 14: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

14GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Standarised power of the sourcecharacteristics are given froma file . Power value can be entered as "not normalized" if Ukr was chosen

Project Started – Source Power

Page 15: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

15GE Consumer & Industrial

Industrial Components Team

ProceraPlus

In ProceraPlus, all sourcesare considered as identical. This data is used to determine Ikmax, which makes it possible to proposedownstream protective device incase of paralleling of several transformers. Ik mini are calculatedtaking into account the minimumnumber of sources in parallel.

Project Started – Number of Sources

Page 16: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

16GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•Earthing system: TN, TT, IT•LV opearting voltage•Frequency•3 phase , single phase•HV protection time•HV system power

Project Started – Network Parameters

Page 17: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

17GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•Length•Installation method•Copper , aluminum•Cable type

Project Started – Link Parameters

Page 18: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

18GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•Length •Installation method•Copper , aluminum•Cable type

Project Started – Link Parameters

Page 19: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

19GE Consumer & Industrial

Industrial Components Team

ProceraPlus

To check installation methodpress:

.

Project Started – Link Parameters

Page 20: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

20GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Getting results:

Press Calculate to get results•cable cross section•Fault levels

.

Project Started – Getting First Results

Page 21: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

21GE Consumer & Industrial

Industrial Components Team

ProceraPlus

+

Result Window

Press OK to go further

Project Started – Getting First ResultsResult window

Page 22: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

22GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Criterion

Theoretic Cross Section

Max Short Circuit Current

Min Short Circuit Current

Design Circuit current

Voltage Drop

Max 1Ph SC Current

Ph-E Fault Current (needed for humanprotection)

Cable Cross-section

Calculated for minimum number of sources

Calculated for minimum number of sources

Results window

Project Started – Getting First Results

Page 23: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

23GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Getting first results

Diagram with results for first part of circuit is available

Colours of diagramGreen- OKRed- must be calculatedPurple- NOK

Project Started – Getting First ResultsDiagram

Page 24: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

24GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Project Tree

Project single line diagram

Calculation report

Active SourceDistribution

Active boardConsumption

Available current

Results

Creating Project– Reading Information

Page 25: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

25GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Using Tabs

Defining Source the “ Source” Tab was used.What other Tabs can we use?

.

Creating Project – Using Tabs

Page 26: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

26GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Loop impedances upstream MSB and related to one single transformer. These values are the sum of impedances.

.

Creating Project – Using TabsImpedance Tab

Page 27: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

27GE Consumer & Industrial

Industrial Components Team

ProceraPlus

R0 Phase-Phase - Loop resistance Phase to Phase (equals to 2 times one phase resistance), calculated at 20°C conductors temperature. This value is used to determine the maximum short circuit currents (Ik Max). R1 Phase-Phase Loop resistance Phase to Phase (equals to 2 times one phase resistance), calculated at operating temperature. This value is used to determine among others the minimum short circuit currents (Ik Min). X Phase-Phase Loop reactance Phase to Phase. This value is used to determine minimum short circuit currents (Ik Min). X Phase Phase reactance. This value is used to determine maximum short circuit currents. R0 Phase-Neutral Loop resistance Phase to Neutral, calculated at 20°C conductors temperature. This value is used to determine the maximum short circuit current (Ik Max SIngle). R1 Phase-Neutral Loop resistance Phase to Netral, calculated at operating temperature. This value is used to determine among others the minimum short circuit current (Ik Min Single). X Phase-Neutral Loop reactance Phase to Neutral. This value is used to determine minimum short circuit current (Ik Min

Creating Project – Using TabsImpedance Tab

Page 28: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

28GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•Ref mark Board Downstream Ref mark –Editable•Designation Board name (data recommended for ease of identification). –Editable•Coincidence factor (K.Simultaneity) Simultaneity factor for circuits fed by the considered board. -EditableExample : a distribution feeds 10 circuits of 10 Amps each. A Simultaneity factor of 0.8 means that the total real consumption is 10 x 10 x 0,8, to say 80 Amps. •Earthing system Board Earthing system : TT, TN, IT •Voltage ,No load voltage No load voltage in V, used to calculate Ik3 Max. •Upstream circuit ref mark Circuit Upstream ref mark. In case of an installation with a standby, the board can be fed by two different circuits. An upstream circuit supplied from the normal supply and another one from the standby source supply.

•Breaking device Board breaking device (generally a switching device in distribution boards). -Editable

Creating Project – Using TabsBoard Tab

Page 29: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

29GE Consumer & Industrial

Industrial Components Team

ProceraPlus

This tab appears if the Breaking device on Board Tab differs from “NIL”

•File Protection manufactuers file. •Protection Protective device commercial name. •Rating Circuit breakers rating. •Irth Circuit breaker thermal relay setting or fuses rating value. •IrMg Circuit breaker magnetic setting or fuses rating value. •Magnetic Type of magnetic used Standard or C curve for modular CrBrk Low or B curve Electronic or D/K curve •Delay Circuit breakers short circuit delay •RCD setting Circuit breakers residual current (differential) delay setting. RCD Delay Circuit breakers residual current differential) delay.

Creating Project – Using TabsProtection Tab

Page 30: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

30GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•A UPS can be connected either on a Normal or Standby distribution. •A comparison between Ik is done to keep the least favorable one (Ik max on the network, Ikmin on the UPS). The process is inverted when Normal source Ik Min become less than UPS ones. UPS are considered as current generators. Due to that, Ik are unchanged along the network tree. The UPS is always considered as connected in "By-Pass"mode.

.

Creating Project – Using TabsUPS Tab

Page 31: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

31GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•Normal and standby short circuit currents at board level. •IK2/3 Max Maximum three-phase short circuit current. Maximum value between Normal and standby if it exists. IK1 Max Maximum single-phase short circuit current if neutral is present. Maximum value between Normal and standby if it exists. •Ik1/2Min Minimum single-phase short circuit current if neutral is present. biphase (phase to phase) if neutral is absent. •If Phase-PE default short circuit current at line end. Minimum value between Normal and standby if it exists. •dU Cumulated voltage drop (in %) at board level from source of

.

Creating Project – Using TabsIk/dU Tab

Page 32: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

32GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•I Allowed -allowed current downstream board. This value is equal to the current of the circuit feeding the board. •I available -available current downstream board : available design current for new circuits which can still be fed from the board. •S Intensities -design current IB sum of all circuits issued from the board multiplied by the board simultaneity factor. •Mean cos phi -mean power factor phi at board level, taking into account downstream circuits and eventual capacitors. •R=S IZ cables / Irth board -ratio between: sum of currents of downstream circuits (current calculated without taking into account group factor) and upstream thermal relay setting.

Creating Project – Using TabsCurrents Tab

Page 33: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

33GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Board TabYou can display the Board window by:

•In the Source Window by clicking on the Downstream Board Tab.

•Double-clicking board on diagram

• Going to Pull down menu- Distributions Information

.

Creating Project – Using TabsBoard Tab

Page 34: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

34GE Consumer & Industrial

Industrial Components Team

ProceraPlus Creating Project – Source Has Been Defined

Page 35: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

35GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Mains (N) & Stand-by (S) source have been defined

Creating Project – Types of Source(Mains and Stand-by)

Page 36: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

36GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Next step: Adding next subboards

Besides choosing standard parameters it must be specified if the load ( board) will be fed from Stand- By Supply.

Since Stand by Supply usually has much less SC current – The crtiterion that Imag< ISC_min must checked as well. The max setting of Imag is given.

Creating Project – Types of Source(Mains and Stand-by)

Page 37: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

37GE Consumer & Industrial

Industrial Components Team

ProceraPlus

NS on crossing indicates that subboard is fed from Mains or Stand ByN- fed only from Mains

Creating Project – Types of Source(Mains and Stand-by)

Page 38: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

38GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Results for Board which can be suplied from NS.Since SC currents are smaller in case when fed from Stand By –the minimum Isc which can appear is 4260A.

The value assumes the tolerance3550 *1,2=4260

Creating Project – Types of Source(Mains and Stand-by)

Page 39: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

39GE Consumer & Industrial

Industrial Components Team

ProceraPlus

When board is fed only from Mains ( there is not possible situation to be fed from Stand by only) the magnetic settings can be much higher.

For the same board and cable in this case the max Imag could be equal even 14272A

Creating Project – Types of Source(Mains and Stand-by)

Page 40: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

40GE Consumer & Industrial

Industrial Components Team

ProceraPlus

.

Enter board tab- choose Breaker or switch

Press Calculate to getdevice

Project Adding– Link Switches and Breakers

Page 41: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

41GE Consumer & Industrial

Industrial Components Team

ProceraPlus Project Adding– Link Switches and Breakers

Page 42: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

42GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Link switches,Breakers are added

Project Adding– Link Switches and Breakers

Page 43: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

43GE Consumer & Industrial

Industrial Components Team

ProceraPlus

3 4

2

1

5- Right mouse button click

Five ways of addingCircuit

“3” adding number Of circuits

Project Adding– New Circuits how to

Page 44: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

44GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Different types of circuits can be added

Project Adding– Different types of circuits, loads

Page 45: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

45GE Consumer & Industrial

Industrial Components Team

ProceraPlus

•Board was added.•It is still in red because it has not been calculated yet

Project Adding New Circuits– Different types of circuits, loads

Page 46: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

46GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Must be specified when added

•Type of breaker protecting circuit•Cable parameters•Coefficients•Consumption (Load)

and “Calculate”

Project Adding New Circuits - values which must be specified

Page 47: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

47GE Consumer & Industrial

Industrial Components Team

ProceraPlus

When “calculate” pressedbreakers are proposed.

Project Adding New Circuits - selection of breakers protection circuit

Page 48: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

48GE Consumer & Industrial

Industrial Components Team

ProceraPlus Project New Circuit is Added

Page 49: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

49GE Consumer & Industrial

Industrial Components Team

ProceraPlus

ResultsThe circuit is “ green”- OKBut:In result window there is written:Discrimination – I<8.33kA

Is the result OK for you?

If NOT “up” or “down” stream breaker must be changed.

Project New Circuit is Added– Is the result OK?

Page 50: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

50GE Consumer & Industrial

Industrial Components Team

ProceraPlus

To choose breakers assuring total discrimination/ selectivitypress button as on drawing or F12

Project New Circuit is AddedProject total discrimination

Page 51: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

51GE Consumer & Industrial

Industrial Components Team

ProceraPlus

Changing upper and lower breakers type change the achieved discrimination results.

Thus the upper breaker should be changed to for instance K frame SMR1e.

Project New Circuit is AddedProject total discrimination

Page 52: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

52GE Consumer & Industrial

Industrial Components Team

ProceraPlus

After changing the upper stream breaker

The lower part of diagram is in red- it must be recalculated

Project New Circuit is AddedProject total discrimination

Page 53: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

53GE Consumer & Industrial

Industrial Components Team

ProceraPlus

The total discrimination is assured

Project New Circuit is AddedProject total discrimination

Page 54: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

54GE Consumer & Industrial

Industrial Components Team

ProceraPlus

In the same way adding next circuits the project is designed

Project - building up project

Page 55: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

55GE Consumer & Industrial

Industrial Components Team

ProceraPlus

For given example despite the fact that the I3max on DB2 is 34kA, the end load circuits are protected with cost effective 25kA MCCBs.This effect is achieved thanks to backup backup protectionprotection.

DB2- 34kA

FD 25kA

Project – back up protection

Page 56: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

56GE Consumer & Industrial

Industrial Components Team

ProceraPlus

To generate a complete report ( printout) choose FolderAll. Otherwise results can be got 1 by one

Project finished – generating report

Page 57: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

57GE Consumer & Industrial

Industrial Components Team

ProceraPlus Project finished – generating reportFolios List

Page 58: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

58GE Consumer & Industrial

Industrial Components Team

ProceraPlus Project finished – generating reportSupply sheet

Page 59: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

59GE Consumer & Industrial

Industrial Components Team

ProceraPlus Project finished – generating reportNetwork single line

Page 60: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

60GE Consumer & Industrial

Industrial Components Team

ProceraPlus Project finished – generating reportProtection settings

Page 61: Procera Plus - pme.supme.su/GE/ppt/SG/ProceraPlus Presentation.pdfIn Procera Plus, any circuit, distribution board or end-user circuit can be changed at any time. ... steady state

61GE Consumer & Industrial

Industrial Components Team

ProceraPlus Project finished – generating reportCircuit specification