Pre-Cool and Free-Cool Fan Control - Arctic Chiller...
Transcript of Pre-Cool and Free-Cool Fan Control - Arctic Chiller...
5/26/2014
Pre-Cool and Free-Cool Fan Control
ArcticCool Chillers
ArcticCool Chillers Limited
Authored by: Casey Smith
ArcticCool Chillers Limited
ii
Pre-Cool and Free-Cool Fan Control Sequence of Operations Document
Casey Smith
ArcticCool Chillers Limited
iii
Table of Contents
Introduction ........................................................................................................................ 1 How this document is organized … .............................................................................................1 Who should read this document ................................................................................................... 2 Terms and definitions ................................................................................................................... 2 References and Revisions ............................................................................................................. 2
Hardware Configuration .................................................................................................... 3 Direct – IO ...................................................................................................................................4 Inter-Controller Communications – T3C ....................................................................................6 Modbus Communications - MB ...................................................................................................7 Program Parameters .....................................................................................................................7
Control Strategy .................................................................................................................. 9 Full Mechanical Mode..................................................................................................................9 Mechanical Mode .........................................................................................................................9 Pre-Cool Mode .............................................................................................................................9 Free-Cool Mode ........................................................................................................................ 10
Implementation ................................................................................................................. 10 System Enable ........................................................................................................................... 10
Parameters ........................................................................................................................................... 10 Inputs ................................................................................................................................................... 10 Outputs ................................................................................................................................................. 11 Sequence ............................................................................................................................................... 11
Mechanical Mode ....................................................................................................................... 12 Idle State ............................................................................................................................................... 12
Parameters ........................................................................................................................................ 13 Inputs................................................................................................................................................ 13 Outputs ............................................................................................................................................. 13 Sequence .......................................................................................................................................... 13
Starting State ........................................................................................................................................ 13 Parameters ........................................................................................................................................ 13 Inputs................................................................................................................................................ 14 Outputs ............................................................................................................................................. 14
Operational State ................................................................................................................................. 14 Parameters ........................................................................................................................................ 15 Inputs................................................................................................................................................ 15 Outputs ............................................................................................................................................. 15 Sequence .......................................................................................................................................... 15
Free-Cool Mode ......................................................................................................................... 17 Free Cool/Mechanical Mode Arbitration ............................................................................................ 19
Parameters ........................................................................................................................................ 19 Inputs................................................................................................................................................ 19
ArcticCool Chillers Limited
iv
Outputs ............................................................................................................................................. 19 Sequence .......................................................................................................................................... 19
Valve/Fan Arbitration .......................................................................................................................... 19 Fan Control ......................................................................................................................................... 20
Parameters ....................................................................................................................................... 20 Inputs................................................................................................................................................ 21 Outputs ............................................................................................................................................. 21 Sequence .......................................................................................................................................... 21
Valve Control ....................................................................................................................................... 21 Parameters ........................................................................................................................................ 21 Inputs................................................................................................................................................ 22 Outputs ............................................................................................................................................. 22 Sequence .......................................................................................................................................... 22
List of Figures Figure 1: Typical Wiring Diagram (using MCX152V) ........................................................................ 4
Figure 2: Free Cool - Fan and Valve Control Zones ....................................................................... 18
List of Tables Table 1: Glossary of Terms .............................................................................................................. 2
Table 2: Reference Documentation ................................................................................................ 2
Table 3: I/O Listing ........................................................................................................................... 4
Table 4: Data from T3C Controller................................................................................................... 6
Table 5: Parameter List .................................................................................................................... 7
ArcticCool Chillers Limited
v
Revision History Revision Synopsis 1.0 Design Phase for review 1.1 Update for first build, Pump Control Added 1.2 Pump Control Removed 1.5 First Release with product based on version 1.1 ArcticCool Fan Controller
version 1.1. Graphics and details added.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 1
Introduction
This document describes the design of the control and logic to supplement the capabilities of
the Danfoss Turbocor T3C Standard Chiller Control Software. This Sequence of Operations
design is based on T3C version 1.715.100.
This specification includes:
1. Fan Control:
a. Condenser Fan
b. Free-Cooling Fan
2. Cooling Coil By-pass Valve Control.
How this document is organized …
This Sequence of Operations Document has the following sections:
Introduction – this section. o Document organization o Who this document is designed for. o Glossary of terms o Document history and sources
Hardware Setup o Wiring Considerations and options o Communications to other devices
Control Strategy o Full Mechanical mode o Mechanical mode o Pre-Cool Mode o Free-Cool Mode o Pump Control
Implementation o System Enable o Mechanical mode o Pre-Cool Mode o Free-Cool Mode o Pump Control
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 2
Who should read this document
The sequence of operations design document is meant for all personnel associated with the
chiller design and any programmers building controls for the chiller.
This document can then be part of the larger IOM document as part of the delivery package of
the chiller.
Terms and definitions
Table 1: Glossary of Terms
Term What it means UI or HMI The User Interface – a display is provided with the controller. Glyph A small graphical display with a specific function. Fan Bank 1-6 fans comprise a fan bank and the fan bank is dedicated to 1
refrigeration circuit. A fan bank operates as a unit and is controlled to the same speed.
References and Revisions
Table 2: Reference Documentation
Document Description Revision T3C chiller standard software
MCX Turbocor Compound Capacity Controller user manual, Filename: AC_T3C_DKRCC.PS.RI0.B5.02_520H7630
May 2013
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 3
Hardware Configuration
The design calls for either the MCX61V or MCX152V. Project size will dictate. The specifications
for this revision are:
1. Chiller with 2 refrigeration circuits expandable to 4 (4 circuits requires MCX152V).
2. Includes Free Cool Fluid Cooler.
This control has the following data sources:
1. Direct connect IO
2. Data from the main controller (T3C) via CAN bus.
3. Data from fans/pumps via Modbus (MB).
4. BMS Control via Modbus from HMI.
This control allows for some selectability for sources of input information; i.e., raw IO or
communicated IO.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 4
Figure 1: Typical Wiring Diagram (using MCX152V)
Direct – IO
Table 3: I/O Listing
INDEX DESCRIPTION TYPE OR POLARITY
ANALOG INPUTS 1 Ambient Temperature NTC-10K 2 Chilled Leaving Water Temperature NTC-10K
DIGITAL INPUTS
1 On/Off N.C.
8 General Alarm N.O.
ANALOG OUTPUTS
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 5
1 Cooling Valve Position 0-10 V 2 Fan Bank 1 Speed Reference 0-10 V 3 Fan Bank 2 Speed Reference 0-10 V
DIGITAL OUTPUTS
1 Alarm N.O.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 6
Inter-Controller Communications – T3C to ArcticCool Fan Controller
This set of data leverages the functional capabilities of the T3C Chiller software to which this
controller is designed to be companion controller.
Table 4: Data from T3C Controller
Name Type Notes
a07 Cooling enable Parallels with Digital input for auto enable.
t01 Compressor Max Power Used with Calculated Total Power to provide current capacity
t17 Bypass Solenoid Delay Used to delay fan Start up to Operation State Change
a10 Control Setpoint For Free Cooling Control
a41 Compressor 1 actual state Fan State is controlled to match
c08 Discharge Pressure DTC1 Used to derive SDT, Process Value for condenser control
c14 Calculated Total Power DTC1 Used in capacity Calculation
a44 Compressor 2 actual state Fan State is controlled to match
d08 Discharge Pressure DTC2 Used to derive SDT, Process Value for condenser control
d14 Calculated Total Power DTC2 Used in capacity Calculation
a47 Compressor 3 actual state Fan State is controlled to match
e08 Discharge Pressure DTC3 Used to derive SDT, Process Value for condenser control
e14 Calculated Total Power DTC3 Used in capacity Calculation
A50 Compressor 4 actual state Fan State is controlled to match
f08 Discharge Pressure DTC4 Used to derive SDT, Process Value for condenser control
f14 Calculated Total Power DTC4 Used in capacity Calculation
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 7
Modbus Communications - MB
Modbus has 2 prime functions:
1. Communicate bi-directionally with the HMI so that the HMI can:
a. Display information from the controller.
b. Set parameters in the controller.
2. Communicate with the Fan Array (Future – current incompatibilities exist between fan controller
and MCX controller. At this time all fan communications are via Analog output):
a. Collect Status and Alarm data from each fan.
b. Send Speed Commands to each fan.
Program Parameters
The following table shows the parameters used by the program. All values are modifiable with
the appropriate access code.
Table 5: Parameter List
LABEL DESCRIPTION MIN MAX VALUE UNIT ADU StU General > Setup HOA Hand/Off/Auto 0 2 1 - Hand 3001 UOM Unit of Measure Select 0 1 0 - US 3002
y07 Restore default parameters 0 1 0 - NO 3003 ALA General > Configuration BUZ Buzzer activation time 0 15 1 min 3004 AdL Alarm relay activation delay 0 999 0 s 3005 AOF Alarm relay active if unit in OFF 0 1 1 - YES 3006 SEr General > Serial settings
SEr Serial address (Modbus and CAN) 1 100 30 3007 bAU Serial baudrate (Modbus) 0 8 6 - 192 3008 COM Serial settings (Modbus) 0 2 1 - 8E1 3009 PAS General > Password L01 Password level 1 0 999 100 3010 L02 Password level 2 0 999 200 3011 L03 Password level 3 0 999 300 3012 TEM Unit config > Temperature control SEt Setpoint -20.0 90.0 45.0 deg 3013 dIF Differential 0.0 20.0 0.5 deg 3014 XOT Fan - Valve Crossover Timer 0 500 20 s 3015 FCL Unit config > Free Cooling
Configuration
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 8
LABEL DESCRIPTION MIN MAX VALUE UNIT ADU FCE Free Cooling Enable 0 1 1 - Enable 3016 FMN Fan Minimum Speed 0.0 100.0 5.0 % 3017 FMx Fan Maximum Speed 0.0 100.0 100.0 % 3018 FPG Free Cool Fan PID Loop Proportional
Gain 0.0 100.0 10.0 3019
FPI Free Cooling Fan PID Integral Factor 0 500 200 s 3020 LTH Free Cool Enable Threshold -40.0 100.0 35.0 deg 3021 UTH Free Cooling Disable Threshold -40.0 100.0 45.0 deg 3022 FCV Unit config > Free Cooling Valve
Configuration
VLP Bypass Valve PID Loop Proportional Factor
0.0 100.0 10.0 3023
VLI Bypass Valve PID Loop Integral Factor
0 100 250 s 3024
VMx Bypass Valve Maximum Open Position
0.0 100.0 100.0 % 3025
VMn Bypass Valve Minimum Open Position
0.0 100.0 0.0 % 3026
CND Unit config > Condenser Cooling Configuration
CLA Condenser Minimum Approach 0.0 100.0 5.0 deg 3027 CHA Condenser Maximum Approach 0.0 100.0 25.0 deg 3028 CSN Condenser Minimum Setpont 0.0 100.0 75.0 deg 3029 CSX Condenser Max Setpoint 0.0 150.0 115.0 deg 3030 CPC Condenser Power Compensation
Enable 0 1 1 - Enable 3031
FST Fan Start Speed 0.0 100.0 50.0 % 3032 CMN Condenser Fan Speed Minimum 0.0 100.0 0.0 % 3033 CMX Condenser Fan Speed Maximum 0.0 100.0 100.0 % 3034 CPG Condenser Fan PID Loop
Proportional Gain 0.0 300.0 25.0 3035
CPI Condenser Fan PID Loop Integral 0 500 250 s 3036 FFL Sensor Failure Default Fan Speed 0.0 100.0 100.0 % 3037 CTL Parameters > Fan Unit Control VHA Free Cooling Bypass Valve
Hand/Off/Auto 0 2 0 - Off 3038
VSP Bypass Valve Manual PositionSetting 0.0 100.0 0.0 % 3039 F1C Fan Bank 1 Hand/Off/Auto Control 0 2 2 - Auto 3040 F2C Fan Bank 2 Hand/Off/Auto Control 0 2 2 - Auto 3041
F3C Fan Bank 3 Hand/Off/Auto Control 0 2 2 - Auto 3042 F4C Fan Bank 4 Hand/Off/Auto Control 0 2 2 - Auto 3043 F1S Fan Bank 1 Manual Speed Setting 0.0 100.0 0.0 % 3044 F2S Fan Bank 2 Manual Speed Setting 0.0 100.0 0.0 % 3045 F3S Fan Bank 3 Manual Speed Setting 0.0 100.0 0.0 % 3046
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 9
LABEL DESCRIPTION MIN MAX VALUE UNIT ADU F4S Fan Bank 4 Manual Speed Setting 0.0 100.0 0.0 % 3047
Control Strategy
This section details the functional components of the controller:
1. Chiller Mode – Full Mechanical.
2. Chiller Mode – Pre-Cool.
3. Fan Mode – Mechanical.
4. Fan Mode – Free Cool.
Full Mechanical Mode
Full Mechanical mode is enabled when the ambient temperature is above the mechanical mode
threshold. In this mode the modulating bypass valve is in the full bypass position and no fluid is
flowing through the fluid cooler coils. All compressors, refrigeration circuits and fans are set to
provide mechanical cooling
Mechanical Mode
Mechanical mode, at a circuit level, indicates that all cooling capacity is provided by the
compressor. The fans in the associated fan bank provide condenser cooling only.
Pre-Cool Mode
In pre-cool mode, the ambient temperature is such that surroundings provide some of the
cooling capacity which is then topped up by the compressors. The fans in this case provide some
fluid cooling and some condenser cooling. The 3-way valve is set to full flow through the fluid
cooler. This a combination mode, the fans only really function in either Mechanical mode or
Free Cool mode. Pre-cool mode allows the fan banks to operate independently such that some
of the fan banks provide free cooling and others provide mechanical cooling.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 10
Free-Cool Mode
Free Cool mode indicates that the ambient air provides enough cooling capacity without the
need to engage the compressors at all. In this mode, the fans and 3-way valve modulate to
control the LWT temperature at setpoint.
Implementation
This section details the sequence of operations for fan control in the 2 modes of the chiller:
1. Mechanical Mode
2. Free-Cooling Mode
Note: From the fan control perspective there are only the 2 modes and the pre-cool mode is a
combination including both Mechanical and Free Cool modes working in concert.
All modes are dependent on the System Enable.
System Enable
The Fan Control program has a System Enable function that is a global control. See the following
sections for details.
Parameters
The System Enable function has the following parameters:
1. Hand/Off/Auto control – settable by display
2. Free-Cool Temperature Threshold.
3. Mechanical Temperature Threshold.
Inputs
The System Enable function has the following inputs:
Remote Enable – IO or T3C (Cooling Enable).
Ambient Temperature – IO or T3C.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 11
Outputs
The System Enable function has the following outputs:
When system is disabled then all outputs are set to safe state.
Sequence
The following describes the System Enable Function:
1. Hand/Off/Auto set to Off – System is disabled.
2. Hand/Off/Auto set to Hand – System is enabled.
3. Hand/Off/Auto set to Auto:
a. Remote Enable or Cooling Enable on– System is enabled.
b. Remote Enable and Cooling Enable off – System is disabled.
The following describes the sequence while the system is enabled:
1. Mode Setting is determined by Ambient Temperature
2. Ambient Temperature greater than Mechanical Threshold:
a. 3-way Valve set to full fluid cooler by-pass.
b. Chiller set to Mechanical Mode – Cooling capacity is provided by compressors under the
control of the T3C software.
c. Fan banks are controlled according to Mechanical Mode below.
3. Ambient Temperature less than Free-Cool Threshold:
a. 3-way Valve set to engage fluid cooler and is under the control of LWT and its setpoint.
b. Controller is set to Free-cool mode – cooling capacity is provide by both fluid coolers and
mechanical cooling where fluid coolers are allowed to provide as much capacity as they
are capable of. The mechanical cooling then provides the balance required to meet
setpoint. Fan banks are controlled in the following manner:
i. Idle circuit fan banks are controlled by the LWT setpoint providing free cooling
capacity.
ii. Fan banks on circuits providing mechanical cooling are controlled according to
mechanical mode below.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 12
Mechanical Mode
In Mechanical Mode, the fans work in banks where a bank is
assigned to each refrigeration circuit. Each circuit has 1
Turbocor compressor and the fan bank for each circuit is
controlled to provide the most efficient combination of fan
power and compressor power. All banks and circuits work
independently but controlled by the same algorithm.
Figure 2: Condenser Cooling Control page
For this control mode there are 4 States:
1. Off – System enable is off, no Fan Function
2. Ready – System is enabled and fans are available
3. Start – proceeds from Ready and normally continues to
operational but can return to idle.
4. Cooling – proceeds from starting and returns to Ready
While chiller is in Full Mechanical mode the fluid cooler is
completely by-passed, no fluid flows through the fluid cooler.
Ready State
The Ready state is the resting state. The fans are in Ready when the compressors are off and the
chiller is in full Mechanical mode. In this state the output to the fan bank is 0%. The Fan Ready
state is active under the following compressor states:
Fan Banks and the
Bypass Valve have Hand
and Off Modes:
Off – No fan or
valve operation.
Fan Bank State
shows “Off”
Hand – fan bank
speed and valve
bypass position
are controlled by
user–entry. Fan
Bank State shows
“Hand”
NOTE
Any fan banks that are
Ready are available to
Free Cool Mode control.
NOTE
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 13
Absent (enumerated Value – 0)
Off-Line (enumerated Value – 1)
Idle (enumerated Value – 2)
Stopping (enumerated Value – 6)
Fault (enumerated Value – 8)
Time-out (enumerated Value – 9)
Parameters
The Ready State has the following parameters:
Hand/Off/Auto control.
Inputs
The Ready State has the following inputs:
Compressor State – T3C.
System Enable – Internal.
Outputs
The Ready State has the following outputs:
Fan Speed % - MB.
Sequence
The following describes the Ready State Function:
1. System is enabled
2. Fan Banks are in Auto Mode
3. Set fan bank output to 0%.
Start State
The Start state is dictated by the T3C software when a requirement for compressor to start
occurs. Start State for fans follows Start state for compressors.
Parameters
The Start State has the following parameters:
Hand/Off/Auto control.
Fan Start Speed Setpoint %
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 14
Inputs
The Start State has the following inputs:
System Enable - Internal.
Compressor State – T3C.
Fan bank Status – MB.
Bypass Solenoid Delay Time – T3C. (Used as Start to Cooling State Change delay)
Outputs
The Start State has the following outputs:
Fan Speed % – MB.
Sequence
In the Start state has the following steps:
1. System is enabled
2. Fan Banks are in Auto Mode
3. Fan Control is in Ready or Free COOL (Condenser Cooling takes precedence over free cooling)
4. Fan Controller monitors T3C Compressor State, when Start detected, the fan control changes to
Start also.
5. Fan bank output is set to Start Speed setpoint.
6. When Compressor changes to Operational, the delay timer starts.
7. When the delay timer completes, state changes to Cooling.
Cooling State
In the Cooling state, the controller modulates the speed of the fans to optimize the performance
of the compressors. The Cooling state for fan control includes the following compressor states:
Operational (enumerated Value – 3)
Hold (enumerated Value – 4)
Retreating (enumerated Value – 7)
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 15
Parameters
The Cooling State has the following parameters:
Hand/Off/Auto control.
Saturated Discharge Temperature Setpoint – Dynamic,
based on the following (see Setpoint Control section for
details):
o Maximum SDT setpoint.
o Minimum SDT Setpoint.
o Maximum Approach.
o Minimum Approach.
Mechanical Cooling PID Loop Gain Factor.
Mechanical Cooling PID Loop Integral Factor.
Maximum and Minimum Speed.
Capacity Compensation Enable/Disable.
Inputs
The Cooling State has the following inputs:
System Enable.
Compressor State – T3C.
Fan bank Status – IO/MB.
Saturated Discharge Temperature (SDT – Calculated from DTC discharge pressure and
refrigerant) – T3C.
Compressor Capacity.
Ambient Temperature.
Outputs
The Cooling State has the following outputs:
Fan Speed % – MB.
Sequence
In the Cooling state has the following steps:
1. System is enabled
2. Fan Banks are in Auto Mode
3. Fan Control is in Starting and delay timer has expired
4. Fan Controller monitors T3C Compressor State, when Operational, Hold or Retreating state is
detected, the fan control changes to Operational also. This state is maintained until an Idle, Fault,
Absent, Offline, Timeout, Lockout or Stopping state condition is detected. (See Idle State section).
Figure 3: Condenser Control Setup
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 16
5. Fan bank output is controlled by a PID loop to maintain compressor relative speed. Ideally, this
algorithm keeps the compressor speed at minimum but allowing for maximum compressor turn
down. Chiller is at its most efficient when the compressor is running close to the surge speed.
The SDT setpoint is active based on Ambient Temperature and Approach temperature. In turn,
the approach temperature in conditioned by the compressor capacity.
Setpoint Control
The controller recalculates the saturated discharge setpoint
continuously based on ambient temperature and optionally
compressor capacity. Therefore, there are 2 modes of setpoint
control:
1. No Compensation
2. Capacity Compensation
The mode is controlled by the Capacity Compensation
Enable/Disable parameter.
A dynamic setpoint keeps the SDT as low as possible allowing the
compressor to run as efficiently as possible and yet allow the
compressor its highest turn-down capability.
No Compensation
The No Compensation mode Saturated Discharge
Temperature setpoint is very simple:
𝑆𝐷𝑇𝑆𝑃 = 𝐴𝑚𝑏𝑖𝑒𝑛𝑡𝑇𝑒𝑚𝑝 +𝑀𝑎𝑥_𝐴𝑝𝑝𝑟𝑜𝑎𝑐ℎ
The chart to the right tracks the SDT setpoint
versus the Ambient Temperature. For this chart
the Maximum Approach was 25°F. Notice that at
the extremes of the chart, the maximum (125°F)
and minimum (65°F) setpoint parameters are in
force.
0
20
40
60
80
100
120
140
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Tem
per
atu
re
Uncompensated SDT Setpoint
Ambient SDT SP No Comp
Figure 4: Circuit 2 Setpoint Control
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 17
Capacity Compensation
Free-Cool Mode
Free Cool mode uses the ambient air and fluid coolers to provide some or all of the cooling
capacity of the chiller. This chiller is equipped with 2 independent coils, the Fluid Cooler coil and
the Condenser Coil configured such that air flow passes the fluid cooler coil first then the
condenser coil.
The chilled fluid path is directed via modulating valve through the fluid cooler coil then into the
evaporator barrel. If the ambient conditions and load are such that leaving fluid temperature
from the fluid cooler coil is at setpoint then no mechanical cooling is required. This is referred to
0
20
40
60
80
100
120
140
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Tem
per
atu
re
Compensated SDT Setpoint 50% Load
Ambient SDT SP
0
20
40
60
80
100
120
140
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Tem
per
atu
re
Compensated SDT Setpoint With Variable Load
Ambient Load SDT SP
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 18
as full Free Cool operation. If the fluid cooler is not capable of producing enough capacity to
satisfy the setpoint then Mechanical cooling is added to “top-up” the capacity. This state is
called Pre-cool operation.
When controller is in Free Cool mode the fans operate in either Mechanical or Free Cool modes.
If the setpoint cannot be satisfied by free cooling alone then the chiller provides additional
mechanical cooling; in this case, the following is true:
Fan banks are aligned to refrigeration circuits and are controlled as a bank – they are all running
or stopped as required. Fans are controlled to provide the most energy efficient balance
between compressor power and fan power.
Fan banks on circuits in mechanical cooling mode provide condenser cooling.
Fan banks on circuits Idle provide free cooling to achieve LWT setpoint.
The Fluid Cooler bypass valve and fans work in concert to provide constant LWT at setpoint.
The following figure shows the relative contribution of the fans and by-pass valve in Free Cool
mode.
Tem
per
atu
re
Fan Control
Valve Control
LWT Setpoint
LWT
100% 0%
100% 0%
Fan Control Area
Valve Control Area
Figure 5: Free Cool - Fan and Valve Control Zones
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 19
Free Cool/Mechanical Mode Arbitration
The controller uses ambient temperature and 2 threshold settings to arbitrate when to enable
free cooling control of fans and when to return to a full mechanical mode.
Parameters
The Free Cool/Mechanical arbitration function has the following parameters:
Free Cool Enable threshold
Free Cool Disable threshold
System Enable
Inputs
The Free Cool/Mechanical arbitration function has the following inputs:
Ambient Temperature – IO or T3C
Outputs
The Free Cool/Mechanical arbitration function has the following outputs:
System internal control – Free Cool Mode / Mechanical Mode
Sequence
The Free Cool/Mechanical arbitration function has the following sequence of operations:
1. Temperature is less than Free Cool Enable threshold – Set Mode Free Cool.
2. Temperature is greater than Free Cool Disable threshold – Set Mode Mechanical.
3. If temperature is between the threshold values mode setting is not changed and Default is
Mechanical mode
Valve/Fan Arbitration
Refer to Figure 5: Free Cool - Fan and Valve Control Zones. The controller monitors the LWT and
provides fan air flow in increasing amounts as the LWT rises above Chiller Setpoint. As the LWT
drops below setpoint, the fans shut off (0% speed) and the valve modulates towards a full
bypass position as the LWT gets farther from setpoint.
The controller provides a hysteresis control using timers. The Valve delay starts when fans are at
0% speed and the LWT temperature is below setpoint. The Fan delay timer starts when the
Valve is in the full fluid cooler flow position and the LWT is above setpoint.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 20
Fan Control
Fans in this controller are controlled as a group called a fan bank. Each fan bank is dedicated to a
refrigeration circuit and is controlled independently. This allows the chiller to function in a
combination mode, or pre-cool, where some fan banks are providing condenser cooling and the
rest are providing free cooling.
Parameters
The Free Cool Fan Control function has the following parameters:
Free Cool Fan PID Gain factor.
Free Cool Fan PID Integral Factor.
Fan/Valve delay timer.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 21
Inputs
The Free Cool Fan Control function has the following inputs:
Remote Enable – internal
System Mode – Free Cool enable.
Chiller Setpoint – T3C.
Outputs
The Free Cool Fan Control function has the following outputs:
Fan Bank Speed – MB or IO.
Sequence
The following describes the Free Cool Fan Control Function:
1. System Enabled
2. Free Cool Mode Enabled.
3. Valve position is 100% bypassed – all chiller flow is through the free cooling coils.
4. LWT is above Chiller Setpoint.
5. Fan Delay is instantiated.
a. Timer continues while above remain true.
6. Fan delay has expired.
7. Fan Bank not required for mechanical cooling – Circuit (Turbocor Compressor) is Idle.
8. Fan bank is started.
9. Control Fan Bank Speed to achieve Chiller Setpoint on leaving water temperature (LWT).
a. All fan banks not in use for mechanical cooling in free cooling mode are controlled to
the same speed.
Valve Control
In extreme conditions, the ambient temperature is low enough that passive flow through the
cooler coils is more than capable of satisfying the load. In this case, the controller uses the
modulating bypass valve to operate and allow some flow to bypass the fluid cooler to maintain
the setpoint and not drop too far below.
Parameters
The Free Cool Valve Control function has the following parameters:
Free Cool Valve PID Gain factor.
Free Cool Valve PID Integral Factor.
Fan/Valve delay timer.
Arctic Cool Chillers Limited
January 2015 Pre-Cool and Free-Cool Controller SOO 1.5 pg. 22
Inputs
The Free Cool Valve Control function has the following inputs:
Remote Enable – internal
System Mode – Free Cool enable.
Chiller Setpoint – T3C.
Outputs
The Free Cool Valve Control function has the following outputs:
Valve Position – IO.
Sequence
The following describes the Free Cool Valve Control Function:
1. System Enabled
2. Free Cool Mode Enabled.
3. Valve is set to free cool position – all flow is directed through the cooling coils prior to flowing
through the evaporator.
4. Free Cool Fan Speed is 0%. (Mechanical Cooling should be disabled at this point – if not, other
settings should be checked).
5. LWT is less than Chiller Setpoint.
6. Valve Delay is instantiated.
a. Timer continues while above remain true.
7. Valve delay has expired.
8. Control Valve bypass position to achieve Chiller Setpoint on leaving water temperature (LWT) by
allowing entering water flow to bypass the cooler coils.