Transcript of PPT on Generator
![Page 1: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/1.jpg)
Main Turbine Generator & Exciter
Including:
Hydrogen, Stator Cooling Water, Generator Seal Oil, and Iso-Phase Bus & Duct
Systems
![Page 2: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/2.jpg)
Enabling Objectives• STATE the function of
the Main Generator.
• LIST the three requirements for an electrical generator.
• STATE the purpose of the four major components of the Main Generator.
![Page 3: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/3.jpg)
Enabling Objectives (cont..)
• LIST four main generator auxiliary systems and STATE the function of each.
• STATE why Hydrogen gas is used for generator cooling and STATE a special precaution associated with its use.
![Page 4: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/4.jpg)
Function of Generator
• Converts the mechanical energy of the turbine into usable electrical energy
![Page 5: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/5.jpg)
Picture of Generator
![Page 6: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/6.jpg)
Generator
• Three phase, 4 pole AC generator
• Frame pressurized with hydrogen gas for cooling and low windage losses
• Stator windings cooled with circulating demineralized water
• Full load rating of 1504.8 MVA (1354 MW at .9 pf, 1203.84 MW at .8 pf)
![Page 7: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/7.jpg)
Basic Generator Theory
• Requires three elements: conductor, magnetic field, and relative motion
• Power output is proportional to the number of conductors, strength of the magnetic field, and speed of rotation (motion or shaft torque)
![Page 8: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/8.jpg)
Basic Generator Theory
![Page 9: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/9.jpg)
Basic Generator Theory (cont.)
• Number of conductors in the generator is fixed
• Speed (or shaft torque when paralleled) is controlled by the attached steam turbine – provides for power control - MWatts
• Magnetic field strength is controlled by the rotor field current fed by the voltage regulator– provides for voltage control - MVars
![Page 10: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/10.jpg)
Basic Generator Theory (cont.)
• MWatts - megawatts- is actual power (dollar$)
• MVAR - reactive power - represents the total current and voltage losses inherent with AC generation, transmission, and use.
![Page 11: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/11.jpg)
Basic Generator Theory (cont.)
• When the generator is paralleled to the grid:
– power output (MW) is proportional to the torque (or push) of the turbine
– reactive power output (MVAR) is proportional to the rotor field current
![Page 12: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/12.jpg)
Main Generator
![Page 13: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/13.jpg)
Generator Details
• Enclosure Housing: Contains within its boundary the Rotor, Stator, and Hydrogen Cooler.
• The Enclosure Housing is pressurized with hydrogen gas which is used as the cooling medium for the rotor and stator windings.
![Page 14: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/14.jpg)
Generator Details
• Stator : stationary winding through which electric current is induced by the rotating field windings
• Function - collect the induced current and provide a circuit path to the output of the generator (output bushings)
• Stator is cooled by Stator Cooling Water
![Page 15: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/15.jpg)
Stator Bar
![Page 16: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/16.jpg)
Generator Details (cont.)
• Rotor : directly couple to the shaft of the Main Turbine and rotates at 1800 rpm synchronous speed (or 60hz)
• Function - supply a regulated, rotating DC field to induce voltage, and resultant current flow in the generator stator windings
• Rotor is cooled by the hydrogen gas
![Page 17: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/17.jpg)
Picture of Rotor
![Page 18: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/18.jpg)
Generator Details
• Stator Core - securely holds stator windings
• Stator End-Turns - provides winding connections for a continuous circuit
• Hydrogen Blower - circulates cooling hydrogen
• Hydrogen Cooler - heat exchanger for hydrogen gas supplied by OLACW
![Page 19: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/19.jpg)
Generator Details
• Bearings : supports shaft and bears load of the generator weight and torque
• Bushings : provides gas-tight electrical terminal for connection of output power to isolated-phase bus
![Page 20: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/20.jpg)
Function of Exciter
• Controls generator output voltage by varying the current to the generator rotating field windings
![Page 21: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/21.jpg)
Exciter
• Permanent Magnet Generator (PMG) supplies AC power to the Voltage Regulator
• Voltage Regulator supplies DC field current to the Exciter
• Exciter output is rectified and sent to the Rotor through leads in the shaft
![Page 22: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/22.jpg)
Picture of Exciter
![Page 23: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/23.jpg)
Exciter Diagram
![Page 24: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/24.jpg)
Exciter Details
• Self powered from attached Permanent Magnet Generator (PMG)
• PMG consists of 24 permanent magnets located on the end of the exciter shaft. Produces : 120vac at 420hz – PMG also supplies power to the EH Governor
Cab. and Turbine Supervisory Panels
![Page 25: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/25.jpg)
Exciter Details
• Power from PMG is rectified to DC, regulated by the voltage regulator, and applied to the exciter stationary field.
• Larger AC power is produced in the exciter rotating windings and is rectified to DC by diodes mounted on the shaft
• The DC is sent down the internal of the shaft to the attached rotor field
![Page 26: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/26.jpg)
Exciter Details
• Exciter Housing cooled by internal air circulation which includes a heat exchanger cooled by CLACW
• Contains automatic rotor ground detection system, which provides for manual or automatic (once per 24hr) operation
• Exciter bearing ungrounded to prevent circulating currents in the shaft which will attack the bearing seating surfaces
![Page 27: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/27.jpg)
Picture of Exciter
![Page 28: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/28.jpg)
Exciter Details
• The output of the exciter is controlled by the Voltage Regulator– This controls the field current which controls
the output voltage of the generator
• While in parallel, the Voltage Regulator controls MVAR loading.
![Page 29: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/29.jpg)
Voltage Regulator Diagram
![Page 30: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/30.jpg)
Voltage Regulator Details
• Two modes of operation:– Manual - regulator output set by rheostat, non-
regulated or compensated. Sets base voltage output of generator
– Automatic - regulator monitors output and regulates to a desired setting. Sets the MVAR loading of the generator
![Page 31: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/31.jpg)
Voltage Regulator Cabinet
![Page 32: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/32.jpg)
Generator Protection
• Generator trips protect the Generator and Main Turbine in the event of a fault condition within the 25KV system
• Protection is provided by coordination of:– Voltage Regulator Trips / Protective Actions– Field Breaker Trips– Generator Output Breaker Trips
![Page 33: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/33.jpg)
Generator Support Systems
• Generator Hydrogen Gas System
• Generator Stator Cooling Water System
• Generator Seal Oil System
• Isolated-Phase Bus and Duct Cooling System
• Closed Loop Auxiliary Cooling Water System
![Page 34: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/34.jpg)
Hydrogen Gas System
![Page 35: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/35.jpg)
Hydrogen Gas System
• Provides filtered, pressurized (75 psig) hydrogen cooling medium for generator internals to aid in heat removal
• Vital to obtaining full rated output of generator
• Also provides for safe purging of hydrogen gas with carbon dioxide
![Page 36: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/36.jpg)
Hydrogen Gas System
• Besides cooling, the hydrogen gas system functions include– ability to purge to air using carbon dioxide– indication for pressure, temperature, moisture,
and purity– ability to dry and remove impurities– pressurizes Stator Cooling Water system tank
![Page 37: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/37.jpg)
Main Generator
![Page 38: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/38.jpg)
Hydrogen Gas System
• Disadvantages of using Hydrogen– Explosive over wide range of concentration
– Not detectable to senses
• Advantages of using Hydrogen– High thermal conductivity– High specific heat capacity– Low density - low windage losses– Readily available - inexpensive– Does not contribute to corrosion
![Page 39: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/39.jpg)
Stator Cooling Water System
![Page 40: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/40.jpg)
Stator Cooling Water System
• Uses filtered, demineralized water to remove heat from the stator coils.
• Allows for obtaining more power from less copper in the coils
• Also cools Main Lead Bushings, Neutral Bus and Bushings, and Current Transformers (CT’s)
![Page 41: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/41.jpg)
Stator Cooling Water System
![Page 42: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/42.jpg)
Stator Cooling Water System
• Besides providing cooling water to the stator bars, the system also provides:– Cooling to the generator bushings– Cooling to the neutral bus segments– Cooling to current transformers (CTs)
• Heat exchangers cooled by CLACW• Incorporates expansion tank which is maintained
with hydrogen pressure (2 psig) for corrosion control
![Page 43: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/43.jpg)
Stator Cooling Water System
• Stator Cooling Water Skid (located beneath generator on 29’elev. east-side) contains:– 2 full-capacity motor driven pumps (1 run, 1 backup)– 2 heat exchangers– 2 demineralizer beds – 2 filter beds– 2 heater banks– Instrumentation, and alarms
• pressure, flow, core differential pressure• conductivity, oxygen concentration• tank level
![Page 44: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/44.jpg)
Seal Oil System
![Page 45: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/45.jpg)
Generator Seal Oil System
• Provides lubrication to the generator gland seals and acts as a separating medium between internal hydrogen and outside air.
• Two sub-systems– Air-Side Seal Oil – primary sealing oil against
internal hydrogen pressure– Hydrogen Side Seal Oil – secondary sealing oil,
increases efficiency of system to near 100%
![Page 46: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/46.jpg)
Seal Oil System
• Provides for maintaining full rated hydrogen pressure at shaft penetrations to generator frame
• Each side has two seals; air-side and hydrogen-side
• Oil pressure is maintained about 12 psig above generator gas pressure – Differential between oil and gas pressure must be
maintained to prevent leakage
– Pressure at both seals about the same for gas-tight seal
![Page 47: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/47.jpg)
Seal Oil System
• Air-side seal oil system shares oil with main lube oil system
• Hydrogen-side seal oil is a closed loop system with provisions for removing entrained hydrogen gas from the oil
• Each side has its own heat exchanger, supplied by CLACW
![Page 48: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/48.jpg)
Seal Oil System
![Page 49: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/49.jpg)
Seal Oil System
• Seal Oil Skid (located beneath generator on 29’elev. west-side) contains:– 3 seal oil pumps ; hydrogen-side, air-side, and air-
side backup– 2 oil coolers, 2 cuno-type filters – 3 tanks ; hydrogen-side receiver, hydrogen-side drain
regulator, air-side reservoir (includes heater)– 4 regulating valves, 3 pressure relief valves– Instrumentation ; pressures, differential pressures,
temperatures, tank levels, alarm
![Page 50: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/50.jpg)
Isolated Phase Bus and Duct Cooling
![Page 51: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/51.jpg)
Isolated-Phase Bus and Duct Cooling System
• Connects the output of Main Generator (25kV) to the primary (input) windings of the main transformers.
• Provides cooling of the enclosed circuit path bus conductors
![Page 52: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/52.jpg)
Isolated Phase Bus and Duct Cooling
• Consists of– Isolated Phase Bus Conductors
• Tubular, all welded aluminum mounted on porcelain insulators
– Isolated Phase Bus Enclosure Duct• Continuous weather and dust tight aluminum housing suitable
for outside use
– Bus and Duct Expansion Joints• Allows for expansion and contraction of bus and duct due to
loading, temperature changes, and short circuit conditions
– Disconnect Links• Stranded flexible connectors that make connection between
the generator and the isolated phase bus
![Page 53: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/53.jpg)
Isolated Phase Bus and Duct Cooling
• Also:– Isolated Phase Bus Cooling
• The busses between the main generator and the transformer are forced-air cooled
• Consists of two full-capacity fans and heat exchangers
– Surge Protection and Potential Transformer Cubicles
• Contains the components that provide signals to instrumentation and protective relaying
![Page 54: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/54.jpg)
Main Generator Output Breaker
• Connects and disconnects generator output with the AC distribution system for protection of the generator
• 3 breakers poles – one per phase
• Integral part of bus ducting
• Operated by compressed air
![Page 55: PPT on Generator](https://reader034.fdocuments.us/reader034/viewer/2022050618/544dd8dfb1af9faa758b4cf8/html5/thumbnails/55.jpg)
Main Turbine Generator & Exciter
• Questions
• Review