POWER SYSTEMS LAB EE-328-F

26
1 LABORATORY MANUAL POWER SYSTEMS LAB EE-328-F (VI th Semester) Prepared By: Rajiv Kumar B. Tech. (EEE), M. Tech. (EEE) Department of Electrical & Electronics Engineering BRCM College of Engineering & Technology Bahal-127028 (Bhiwani) Modified on 14 November 2014

Transcript of POWER SYSTEMS LAB EE-328-F

Page 1: POWER SYSTEMS LAB EE-328-F

1

LABORATORY MANUAL

POWER SYSTEMS LAB

EE-328-F

(VIth Semester)

Prepared By:

Rajiv Kumar B. Tech. (EEE), M. Tech. (EEE)

Department of Electrical & Electronics Engineering BRCM College of Engineering & Technology

Bahal-127028 (Bhiwani)

Modified on 14 November 2014

Page 2: POWER SYSTEMS LAB EE-328-F

2

SYLLABUS

EE-328-F POWER SYSTEMS LAB L T P Practical: 25 marks

- - 2 Class work: 25 marks

Total: 50 marks

Sr. No List of Experiments:- Page No

1. To draw the operating characteristics of IDMT relay.

2. To study the performance of Earth fault relay.

3. To study the performance of an over voltage relay.

4. To study the performance of under voltage relay.

5. Testing of breakdown strength of transformer oil.

6. To study flash point test of transformer oil.

7. To find ABCD, Hybrid & Image parameters of a model of transmission line.

8. To study performance of a transmission line under no load condition & under

load at different power factors.

9. To observe the Ferranti effect in a model of transmission line.

10. To study performance characteristics of typical DC distribution system

in radial & ring main configuration.

11. To study characteristics of MCB & HRC Fuse.

12. To study radial feeder performance when a) fed at one end b) fed at both ends.

Page 3: POWER SYSTEMS LAB EE-328-F

3

Index

S.No. Name of Experiment Page No. Date Signature

1 To draw the operating characteristics of IDMT relay

2 To study the performance of Earth fault relay

3 To study the performance of an over voltage relay

4 To measure the dielectric (Breakdown) strength

of transformer oil

5 To find ABCD, Hybrid & Image parameters of a

model of transmission line

6 To observe the Ferranti effect in a model of transmission line

7 To study radial feeder performance when a) fed at one end b) fed at both ends.

8 To study characteristics of MCB & HRC Fuse

9 To study the performance of adifferential over

current relay

10 To study the operation of static definite time

reverse power relay

Page 4: POWER SYSTEMS LAB EE-328-F

4

Experiment – 1

Aim: To draw the operating characteristics of IDMT relay

Objective: The aim of the experiment to investigate the operation, inverse characteristics and to

determine the purpose of time and plug settings for over current relay in electrical supply system.

By configuring these settings correctly, and by coordinately the operations of the relays, it is possible

to isolate the smallest section of the system in the shortest time possible, thereby minimizing

unnecessary disruption to other consumers whilst preventing damage the equipment within the fault

section.

In the radial feeder configuration, supply from one end only, discrimination of faults can be achieved

by incorporating time delays at each relay point. This enables the relay closest to the fault to trip,

isolating the fault circuit without affecting the other non-faulty circuits. A disadvantage of this system

is that for faults near the source, the fault current can be much greater than at the opposite end of the

feeder due to the impedance. For a fault at point F in figure (1), the circuit breaker at point C opens

before those at point A and B, leaving most of the feeder operational. The relays have a time grading

of 0.5s (to allow for relay and circuit breaker operation plus error allowance), illustrating

discrimination by time grading only.

The disadvantage can be overcome by employing relays with an inverse current / time characteristic –

i.e. the time delays are reduced for higher currents. These relays are known as IDMT relays (Inverse

Definite Minimum Time). A minimum time of operation is incorporated to ensure co-ordination

between the relays when the fault level does not vary along the feeder.

Apparatus Required: 1) Timer 2) IDMT relay (MODEL NO.ICM-21NP)) 3) Auxiliary D.C. supplies = 110V 4) 1 phase Dimmer stat = 230V, 10A 5) Ammeter AC (0-15A) 6) Rheostat (38 ohm, 8.5 Amp) 7) Experiment Kit 8) Connecting wires

Circuit Diagram:

Page 5: POWER SYSTEMS LAB EE-328-F

5

Procedure: 1. Make the connection as shown in the circuit diagram.

2. Select current setting (set phase trip) less than 100%, keeping phase TMS at maximum position.

3. Select any time setting.

4. Switch on variac and check power ON indication provided on relay front panel.

5. Vary dimmer stat and observe current value till Pick-Up will show ‘Red’ indication when current

value exceeds set phase trip position.

6. Switch OFF dimmer stat without disturbing its position with the help of DPT switch. Also reset

time.

7. Measure the relay time from timer by switching on DPT switch.

8. Now increase the fault current and note down timer time after switching ‘OFF’ and ‘DPT’ switch

every time with same time setting.

9. Repeat same procedure for different time setting keeping current setting same.

Observation Table:

Sr. No. Fault Current

(A)

PSM Timer time for

TSM=

Timer time for

TSM=

Timer time for

TSM=

Result:For lower values of current the “time current ” characteristics are inverse and for higher value for

current observed times are constant

Page 6: POWER SYSTEMS LAB EE-328-F

6

Experiment No. 2

Aim: To study the performance of Earth fault relay

Objective: To study the protection of equipment and system by relays in conjunction with switchgear.

Theory: The function of a relay is to detect abnormal conditions in the system and to initiate through

appropriate circuit breakers the disconnection of faulty circuits so that Interference with the general

supply is minimized.

Earth fault protection can be provided with normal over current relays, if the minimum earth fault

current is sufficient in magnitude. The design of a comprehensive protection scheme in a power system

requires the detailed study of time-current characteristics of the various relays used in the scheme.

Thus it is necessary to obtain the timecurrentcharacteristics of these relays. The over current relay

works on the induction principle. The moving system consistsof an aluminum disc fixed on a vertical

shaft and rotating on two jeweled bearings between the poles of an electromagnet and a damping

magnet. The winding of the electromagnet is provided with seven taps (generally0, which are brought

on thefront panel, and the required tap is selected by a push-in -type plug. The pick-up current setting

can thus be varied by the use of such plug multiplier setting. The pick-up current values of earth fault

relays are normally quite low.

Equipment Required: 1) Timer

2) IDMT relay (Model APR-11 P)

3) Auxiliary D.C. supplies = 110V

4) 1 phase Dimmer stat = 230V, 10A

6) Ammeter AC (0-15A)

7) Rheostat (38 ohm, 8.5 Amp)

8) Experiment Kit

9) Connecting wires

Circuit Diagram:

Procedure:

1. Make the connection as shown in fig.

2. Set current and time setting of relays as per requirement

3. Set phase trip to 50% and set phase time at X1 with phase TMS at maximum position.

4. Switch on variac and check power ON indication provided on relay front panel.

5. Very dimmer state with fault current of 1A, relay will trip after certain time delay.

Page 7: POWER SYSTEMS LAB EE-328-F

7

6. Switch OFF dimmer state without disrobing its position and change the position of DPT switch.

Also reset time.

7. Switch ON dimmer state changes the position of switch and measure the relay time from timer.

8. Reap eat same procedure for varying a different fault current.

9. Repeat this procedure consider different set phase time (TMS)

Operation:

With supply on load are continuously monitored Electronic comparator checks this value with set

value (N) of phase & earth fault trip, which can be adjusted on front plate. Pick up response is (1.1 N)

IDMT timing is applicable to over current above 2N as per chosen curve. Time setting multiplier for

actual tripping time delay. TMS is adjusted by 11-position switch & with variable preset pot. These

pots adjusted time for intermediate values indicated on TMS switch. Tripping cause is indicated by

LED lamp (OC/EF). When over current trips the circuit relay ‘ NO’ contact changes to ‘NC’ when

relay trips indicating LED to ‘NC’ when relay trip indicating LED to ‘NC’ when relay trips indicating

LED to ‘NC’ when relay trip indicating LED flag will remain ON till manually reset.

Observations:

Current setting =……, Phase TMS

Sr. No. Fault Current

(A)

PSM Timer time for

TSM=

Timer time for

TSM=

Timer time for

TSM=

Result:For lower values of current the “time current “characteristics are inverse and for higher value of

current, time observed is constant.

Viva Question

1 Application of IDMT relay.

2 Drawback of IDMT relay

3 Importance of DC supply

4 Detail of other Inverse type of relays

5 Importance of static relays

6 Why IDMT relay suitable for protection of long length of LV/MV TL.

Page 8: POWER SYSTEMS LAB EE-328-F

8

Experiment – 3

Aim: To study the performance of an over voltage relay.

Apparatus Required:-

1) Static over voltage relay (Model No.: -ASOV)

2) Auxiliary D.C. supplies 110V

3) Time interval meter

4) Single pole variac 230V, 4A

5) Voltmeter (0-300V) AC

6) Rheostat (400 ohm, 1.7 Amp)

7) Connecting wires

8) Experiment Kit

Circuit Diagram:

Procedure:

1. Connect the ckt as shown in fig procedure is done & time is noted.

2. Set current and time setting of relays as per requirement.

3. Connect Auxiliary D.C. Supply (110) to pin 11 & 12 of relay and pin no. 3&4 to the time

interval meter.

Page 9: POWER SYSTEMS LAB EE-328-F

9

4. Switch on the D.C. supply & make sure that relay is on Glowing of LED on the front panel of

the relay.

5. Switch on power supply from dimmer as well as to time interval meter.

6. Adjust the voltage setting of the relay.

7. Adjust the time setting of relay.

8. Now by making DPDT switch on, increase the value of voltage by dimmer stat up to the point

at which the relay trip. Trip can be observed by glowing of trip LED on front panel of relay.

9. Switch is made off and relay is reset.

10. Now Switch is made on & time interval meter reading is noted.

11. For the same voltage setting , time setting is changed & same procedure is repeated until all the

time setting are covered.

12. Again voltage setting is changed & same procedure is repeated.

Result: The static over-voltage relay is studied

Page 10: POWER SYSTEMS LAB EE-328-F

10

Experiment –4

Aim: To measure the dielectric (Breakdown) strength of transformer oil.

Equipment Required:

1. Portable oil testing set-220/250 V

2. HV transformer-50 kV/250 V

3. Gap setting gauges -0.15711 width

Theory

The two unit portable testing set is designed for the periodical testing of samples of insulating oils

drawn from plant on site and for checking the dielectric strength of new samples of oil. The equipment

is designed to operate from 200/250V, 50Hz, Single phase AC supply. Test gap voltage up to 50kV, it

consists of two units, one is containing the testing transformer and other is control and metering

equipments. These equipments are kept in a metal box to provide full protection to the apparatus

during transport and storage. The gap is adjusted between electrodes in accordance with British

Standard Specification (BSS) no. 148

Connection Diagram:

Observation Table:

S. No. Break down Voltage (Volts)

1

2

3

4

5

Page 11: POWER SYSTEMS LAB EE-328-F

11

Procedure:

1. Place the High Voltage transformer unit about 7 away from the control unit.

2. The control unit is connected to supply voltage taking care that the earth connections are

effective.

3. The multiple point control switch is set at its lowest tapping.

4. The push button on control unit is pressed firmly for at least 5 seconds. Note that no

Breakdown to occurs, in which case button should be released at once without delay. Break

down is indicated by a continuous discharge across the gap, bubbling of oil in the cell and

meter indicating a sudden voltage drop.

Page 12: POWER SYSTEMS LAB EE-328-F

12

Experiment – 5

Aim: To find ABCD, Hybrid & Image parameters of a model of transmission line

Apparatus Required: - Transmission Line model is consisting of four sections of transmission Kit

Voltmeter-1, Ammeter-1, Power Supply-220V, Connected Wire (As per Requirement)

Theory: - ABCD Parameter are widely used in analysis of power transmission engineering where they

will be turned as “Generalized circuit parameter” ABCD parameters are also called as Transmission

parameter. It is conventional to designate the input port as sending end and the output port as receiving

end while representing ABCD parameter

Vs = AVr + B Ir

Is = CVr + Dir

[Vs/Is] = [A B/C D] [Vr / Ir]

Assuming the receiving end open Circuit i.e.

A =Vs / Vr Where Ir = 0

B = Vs / Ir Where Vr = 0

C = Is / Vr Where Ir = 0

D = Is / Ir Where Vr = 0

Circuit Diagram:-

In transmission line if impedance at the sending end with Z12

at receiving ends be Z11 and simulations

the impedance looking back from receiving end with Z11 at input part is Z12 then Z11 and Z12 termed as

the image impendence of the network

Z11 =√AB

CD and Z12 =

√BD

AC

α = tanh-1 =√BD

AC

Calculation & Observation:-

Open Circuit:-

S. No Vs Is Vr A= V1 / V2 C = I1 / V2

Page 13: POWER SYSTEMS LAB EE-328-F

13

Short Circuit:-

S. No Vs Is Ir B= Vs / Ir D = Is / Ir

Procedure:-

1. To find out A and C parameters connect voltage supply of 220V to sending end and open circuit

receiving end.

2. Observe the voltage of Vs, Is and Vr with the help of voltmeter and ammeters in the

experimental kit.

3. To find out B and D receiving end is short circuited and supply of 220V is given to sending

end.

4. Observe the voltage of Vs , Is and Ir

Result: - The Calculated A, B, C, D Parameters are

A=

B=

C=

D=

Page 14: POWER SYSTEMS LAB EE-328-F

14

Experiment – 6

Aim: To observe the Ferranti effect in a model of transmission line.

Equipment Required:

1. Three phase alternator rating: 400V, 5kVA, 1500 rpm.

2. Ammeter

3. Voltmeter

4. Rheostat

Theory:Ferranti Effect

A long transmission line/cables draws a substantial quantity of charging current. If such a

line/cable is open circuited or very lightly loaded at the receiving end, the voltage at receiving end may

become greater than voltage at sending end due to capacitive reactance. This is known as Ferranti

Effect. Both capacitance and inductance is responsible to produce this effect. The capacitance (which

is responsible for charging current) is negligible in short line but significant in medium line and

appreciable in long line. Hence, this phenomenon occurs in medium and long lines. The figure shown

below is representing a transmission line by an equivalent pi (π)-model. The voltage rise is

proportional to the square of the line length.

The Line capacitance is assumed to be concentrated at the receiving end.

In the phasor diagram shown above -

OM = receiving end voltage Vr

OC = Charging current drawn by capacitance = Ic

MN = Resistive drop

NP = Inductive reactance drop

Therefore; OP = Sending end voltage at no load and is less than receiving end voltage (Vr)

Since, resistance is small compared to reactance; resistance can be neglected in calculating Fer

ranti effect. From π-model, Vs=Vr-Impedance drop under open circuit condition Ir=0 and hence,

Vs=Vr-IcR-jwL*Ic i.e. receiving end voltage is greater than sending end voltage and this effect is

called Ferranti Effect. It is valid for open circuit condition of long line.

When load current is increased of R-L loads the resultant current is not remains leading, because of the

inductive drop. Hence, receiving end voltage (Vr) is lesser than sending end voltage (Vs) under full

load conditions

Observation Table:

S. No. Length of

the line(km)

Sending end

voltage Vi(volts)

Receiving end

voltage Vo(volts)

Sending end

current Ii(amp)

Receiving end

current Io(amp)

1

2

3

4

5

Procedure:

Page 15: POWER SYSTEMS LAB EE-328-F

15

1. Select initial length of line(say 30kms).

2. Start the motor-generator set.

3. Note down the sending end voltage Vi, sending end current Ii and receiving end voltage Vo.

4. Disconnect the supply of motor-generator set.

5. Increase the length of line.

6. Repeat the steps 2-5.

Page 16: POWER SYSTEMS LAB EE-328-F

16

Experiment – 7

Aim: To study radial feeder performance when a) fed at one end b) fed at both ends.

Theoretical Background: Whole of the power system can be subdivided in to number of radial feeders fed from one end.

Generally such radial feeders are protected by over current and earth fault relays used as primary relays

for 11 kV and 66 kV lines. For lines of voltage rating beyond 66 kV, distance protection is applied as a

primary protection whereas over current and earth fault relays are used as back up relays.

A simplified radial feeder network without transformers (in actual practice transformers do exist at

substations) is shown in single line diagram of fig. 1.1 below.

If the fault occurs in distribution network, fuse should isolate the faulty section. Should the fuse fail,

relay R3 shall give back-up protection. Relays R1, R2, and R3 act as primary relays for faults in section

I, section I, and section III respectively. If fault in section III is not cleared by relaying scheme at

relaying point R3, relay R2 will act as a back-up. Similarly back-up protection is provided by relay R1

for faults in section II. A,B, C and D are substations in fig. 1.1.

Generally Inverse time over current relays with Definite Minimum Time feature (IDMT relays) are

used in practice. There are many types of such relays available in relay market, viz. normal inverse

relays, very inverse relays and extremely inverse relays. The characteristics of these relays are shown

in fig. 1.2. The other types of o/c relays are 3 second relay and 1.3 second relay. This means the time

of operation of the relay is either 3 or 1.3 second at Plug Setting Multiplier (PSM) equal to 10. Long

time inverse relays are used for o/c cum overload application. Voltage restrains o/c relays have their

own application.

Very inverse relays are less prone to the ratio ZS/ZL. Extremely inverse relays are yet better. Very

inverse relays are faster in operation for close-in faults yet maintaining the discrimination with fuse

and other relays. Extremely inverse relays are more meritorious in this aspect too. Instantaneous o/c

relays are not immune to ZS/ZL ratio. Definite time o/c relays are 100 % immune to this ratio. Very

inverse relays can be used with an additional advantage while protecting a machine or a transformer as

they match with the heating characteristic of equipment better than their normal inverse equivalent.

Page 17: POWER SYSTEMS LAB EE-328-F

17

Extremely inverse relays can best co-ordinate with the fuse characteristic. The aim of this experiment

is to reveal these facts experimentally.

Fig. 1.2 Normal, Very and Extremely Inverse Characteristics

Laboratory Simulations: Referring to a.c.circuit of fig. 1.3. A live model of a radial feeder fed from one end can be self-

understood.

This is only a single phase version of a radial feeder. Faults in different sections can be created by

switches S1, S2 and S3. Fault limiting resistance of 18 ohms is used for practical purposes only. Here

C.T. secondary rating is 5 Amp and relay rating is 1 Amp. This is contradicting the practice for for

practical purpose.

Observation Table:

Page 18: POWER SYSTEMS LAB EE-328-F

18

Table:1.1 Measured fault currents for extreme

faults in each section

Fault Location Fault current (A)

Table:1.2 Calculated relay settings

Relay P.S. TMS

R1

R2

R3

Table:1.3 Normal Inverse Relays Fault

Location

Relay R1 Relay R2 Relay R3

PSM Obs time

of op

(sec)

Measured

time of op

(sec)

%

Error

PSM Obs time

of op

(sec)

Measured

time of op

(sec)

%

Error

PSM Obs

time of

op (sec)

Measured

time of

op (sec)

%

Erro

r

F1

F1’

F2

F2’

F3

F3’

Table 1.4

Relays Difference in time of operation of relay for extreme faults

Section Observed Calculated

R1 I

R2 II

R3 III

Procedure:

1. Measure the fault currents for corresponding rheostat in minimum (zero resistance) and

maximum (full resistance) positions and using the corresponding fault-switch S1, S2, or S3 (refer

fig. 1.3). Maximum fault currents in sections I, II and III are denoted by F1, F2, F3 respectively

and the minimum fault currents by F1’, F2’, F3’ respectively. Deactivate the relays for this

purpose. Record the readings in table 1

2. Calculate the plug –settings (or Tap Value) of relays R1, R2 and R3. (Plug settings will be same

irrespective of type of relays). For this purpose, assume the number of distributors each of 0.5

Amp rating from the following possibilities (The experiment is a simulation and hence the

distributor current is 0.5 Amp. In actual practice it may be 500 Amp or more or less):

Number of distributors: 1, 2, 3 or 4.

(Calculations of the plug setting shall be done w.r.t. following considerations)

(I) The plug setting shall be more than or equal to the maximum full-load current passing

through the relay.

(II) The pickup of the relay varies from 1.05 to 1.3 times the plug setting of the relay

(III) For back up, relay R1 shall reach for the fault F’2 and R2 for the fault F’3.

3. Time Settings. (Normal Inverse Relays)

For deciding time-settings, co-ordinate the characteristics of relay R3 with that of an MCB.Use

discriminating time-interval of 1.0 sec. b/w two characteristics. This will decide TMS of R3.

Why discrimination time of 1.0 second? (Try answer to this question.)

For coordinating R2 & R3 use the worst possible current to decide TMS of R2 (F3 in table:1.1).

Similarly decide TMS of R1 by using F2 and setting of R2. Use discriminating time interval

between two successive relays as 0.4 seconds (why 0.4 seconds?) for these calculations.

Tabulate the results as in table (2).

Page 19: POWER SYSTEMS LAB EE-328-F

19

4. Time-settings (Very Inverse Relays) can be carried out for very inverse relays also. The results

are to be tabulated as in the case of normal inverse relays as per calculated settings.

5. Set the normal inverse relays as per the settings in table 1.2

6. Calculate the time of operation of the main and back-up relay for extreme fault in each section

using the relay settings in table:1.2 and the fault current readingsrecorded in table:1.1. Enter

these in table:1.3 as “Calculated Time of Operation”

7. Vary the 550 ohms load resistance such that the current in the radial feeder varies from 0.5

Amp to about 4 Amp. See that MCB trips and relay R3 does not trip.

8. Now create extreme faults (one by one) in each section starting from section III. For each fault,

measure the time of operation of the main and the back-up relay (to measure time of operation

of back-up relay, the main relay has to be deactivated using switches T2 or T3 (as the case may

be) in fig. 1.4). Record these in table 1.3 as “Measured Time of Operation”. Calculate the error

between the calculated and the measured time of operation for each fault and record it in table:

1.3.

9. Derive the table 1.4 from table 1.3.

10. Replace the normal inverse relays by very inverse relays.

11. Repeat steps at Sr. No. 5 to 9 for very inverse relays.

12. Draw your own conclusion.

Page 20: POWER SYSTEMS LAB EE-328-F

20

Experiment – 8

Aim: To study characteristics of MCB & HRC Fuse

Apparatus Required: 1) Fuse wire

2) Ammeter AC (0-10 A)

3) Stop watch 4) 1 ph Dimmerstat – 230V, 10 A

5) Loading Rheostat

6) Rheostat (38 Ohm, 8.5 A) 7) Experimental Kit

8) Connecting Wires Circuit Diagram:

Observation Table

S.No. Current (Amp.) Time (Sec.)

Page 21: POWER SYSTEMS LAB EE-328-F

21

Procedure:

1. Make the connections as shown in Fig. 2. Switch on the supply and keep the full load in the on position. Adjust the current to certain value

with the help of dimmerstat.

3. Stop watch is stopped when the fuse element is blown which is indicated by decreasing of current

in ammeter to zero. Note down the time of stop watch.

4. Again after changing the fuse element increase the current to certain value and repeat above

procedure.

Result: The characteristics of fuse wire is studied in this experiment and is found to be inverse type ,and is

plotted on graph paper .

Viva Question

1 Application of fuse wire

2 comparisons of fuse and circuit breaker

3 Types of fuses and their application

4 types of fuse require for protection of transformer, generator and induction motor

Page 22: POWER SYSTEMS LAB EE-328-F

22

Experiment – 9

Aim: To study the performance of adifferential over current relay

Theory:Relays are of many types. SomeDepend on the operation of an armature by some form of

electromagnet. A verylarge numbers of relays operate on the induction principle. When a relay

operates itcloses contacts in the trip circuit which is normally connected across 110 V D.C.supplyfrom

a battery. The passage of current in the coil of the trip circuit actuatesthe plunger, which causes

operation of the circuit breaker, disconnecting the faultysystem. In the laboratory, a 3-phase contactor

simulates the operation of the circuit breaker.The closure of the relay contacts short-circuits the 'no-

volt ' coil of the contactor,which, in turn, disconnects the faulty system.The protective relaying which

responds to a rise in current flowing through theprotected element over a pre-determined value is

called 'overcurrent protection' andthe relays used for this purpose are known as over current relays.

The operating time of all overcurrent relays tends to become asymptotic to a definiteminimum value

with increase in the value of current. This is an inherent property of the electromagnetic relays due to

saturation of the magnetic circuit. By varying thepoint of saturation, different characteristics can be

obtained and these are

1. Definite time

2. Inverse Definite Minimum Time (IDMT)

3. Very Inverse

4. Extremely Inverse

The torque of these relays is proportional to Sin, where and are thetwo fluxes and is the

angle between them. Where both the fluxes are produced bythe same quantity (single quantity relays)

as in the case of current or voltageoperated, the torque T is proportional to I2, or T = K I2, for coil

current belowsaturation. If the core is made to saturate at very early stages such that with increaseof I2,

K decreases so that the time of operation remains the same over the workingrange. The time -current

characteristic obtained is known as definite –timecharacteristic.If the core is made to saturate at a later

stage, the characteristic obtained is known asIDMT. The time-current characteristic is inverseover

some range and then aftersaturation assumes the definite time form. In order to ensure selectivity, it

isessential that the time of operation of the relays should be dependent on the severityof the fault in

such a way that more severe the fault, the less is the time to operate,this being called the inverse-time

characteristic. This will also ensure that a relayshall not operate under normal overload conditions of

short duration.It is essential also that there shall be a definite minimum time of operation, whichcan be

adjusted to suit the requirements of the particular installation. At low valuesof operating current the

shape of the curve is determined by the effect of therestraining force of the control spring, while at

high values the effect of saturationpredominates. Different time settings can be obtained by moving a

knurledclamping screw along a calibrated scale graduated from 0.1 to 1.0 in steps of 0.05.This

arrangement is called Time Multiplier Setting and will vary the travel of thedisc required to close the

contacts. This will shift the time-current characteristic ofthe relay parallel to itself.By delaying the

saturation to a further point, the Very Inverse and Extremely VeryInverse time current characteristics

can be obtained.

Apparatus Required:

1) Single pole directional O/C relay ACDR 11 HPD

2) Phase shifting transformer

3) Dimmerstat ( 3 phase , 440 volt, 50 Hz )

Page 23: POWER SYSTEMS LAB EE-328-F

23

4) Ammeter (0-1 Amp)

5) Rheostate ( 300 ohm , 1.7 Amp)

6) Dimmerstat ( 1 phase , 230 volt, 4 Amp)

7) DC Power Supply ( 110 Volt )

Circuit Diagram:

Operation: Load current is continuously monitored and compared to set value and polarized with

voltage for direction sensing. As soon as the current exceeds the set value and it is operating direction

then N value (Time set value) is calculated and then the delay time count is started , two types of

curves 10 times ( N=10 ) current 3.0 sec . Delay and 1.3 sec delay can be provided. At the end of the

time count if the current still exceeds the set value TRIP is exceeded. All the monitored current value

is available at the front D is skeet’s for external recording.

If the direction is reverse then the TRIP execution is (represented) restrained high fault setting is also

provided (2N. 20 N) IF the current value exceeds the HF set value instant trip (i.e. 100 msec.) is

executed, by passing the directional restraint.

Observation Table:

S. No. Phase Angle MTS = MAX torque setting

45 degree 60 degree 9th Line

0 degree

30 degree

60 degree

90 degree

120 degree

150 degree

180 degree

-150 degree

Page 24: POWER SYSTEMS LAB EE-328-F

24

Procedure: 1) Make the connections as shown in the fig.

2) Apply the voltage across the P.T of relay

3) The pick –up current through the relay coil.

4) Set current and time setting of relays as per requirement

5) Switch on the supply.

6) Find out the operating region and non-operating region of relay by changing angle using the phase

shifting transformer.

7) Adjust the current to such a value, which is more than plug setting.

8) Change the shifter angle such that relay operates in that region.

Result: The static directional relay is studied and graph for different maximum________ torque

setting is drawn.

Page 25: POWER SYSTEMS LAB EE-328-F

25

Experiment – 10

Aim: To study the operation of static definite time reverse power relay.

Apparatus Required:

1) Timer

2) Static definite time reverse power relay (Model APDR 21)

3) Auxiliary D.C. supply = 110V

4) 3 phase variac =440V, 50 Hz, 8A

5) 1 phase variac =230V, 4A

6) Ammeter AC (0-1A) AC

7) Rheostat (300 ohm, 1.7Amp)

8) Phase shifting transformer

9) Voltmeter (0-300V) AC

10) Experiment Kit

11) Connecting wires

Circuit Diagram:

Operation: Solid static state voltage and current sensing circuits measure the instantaneous voltage

and current value in scales down format .The algorithmic circuit does the multiplication of the derived

data. The output of this circuit remains positive as the moment when power reversal occurs, output of

the circuit’s changes again. It is noted as pick up point and thus indicated by pick up LED. This also

triggers the internal timer cit. This timer is adjustable by 11 positive switches. It has very high repeat

accuracy. (Better than class 17) After the end of set timing and if power conduction are still reverse.

Procedure:

1) Make the connection as shown in fig.

2) Set current and time setting of relays as per requirement

3) Switch on supply to 3phase dimmerstate and also D.C. supply to relay.

4) By varying 3 phase dimmerstate adjust the value of current.

5) Now keeping current at this value constant change the angle of phase shifting transformer gradually.

6) Observe the tripping zone of reverse power relay.

Page 26: POWER SYSTEMS LAB EE-328-F

26

7) The relay will trip at certain angle of phase shifting transformer note down the angle and reset the

relay.

8) Again increase the angle and observe tripping of relay.

9) Plot the tripping region of reverse power relay on the graph paper.

Observation Table:

Table – 1

S. No Phase angle ф (in Degree) Trip response

0

30

60

90

120

150

180

210

240

270

300

330

360

Table – 2

Result: The operation of definite time reverse power relay is studied and triggering zone is plotted in

the graph paper.

Viva Question

1 Application of Reverse power relay

2 Types of relays used and its setting for protection of ring main feeders

3 Comparison of other directional relays and reverse power relays

S. No. Time setting (in Sec.) Trip Time (in Sec.)

1

2

3

4

5

6

7

8

9

10