Power Quality Basics

28
Power Quality Basics Presented by Scott Peele PE

description

calidad de la energia

Transcript of Power Quality Basics

Page 1: Power Quality Basics

Power Quality Basics

Presented by

Scott Peele PE

Page 2: Power Quality Basics

PQ Basics

Terms and DefinitionsSurge, Sag, Swell, Momentary, etc.

MeasurementsCauses of EventsPossible MitigationPQ ToolQuestions

Page 3: Power Quality Basics

Power Quality Measurement

Duration (Time) Cycles (.016 seconds per cycle)

Seconds, Minutes, HoursMagnitude (Voltage level)

Transient level I.e. = 1000 voltsRMS - Voltage level i.e. = 120 voltsWaveforms

Distortions

-150

-100

-50

0

50

100

150

0

Page 4: Power Quality Basics

-200

-150

-100

-50

0

50

100

150

200

0

Magnitude and Duration

60 Hertz/second

DurationTime

Mag

nitu

deV

olta

ge L

evel 169 volts120 Volts RMS

One Cycle .01666 seconds

Page 5: Power Quality Basics

Terms and Definitions

Transient or Surge SagSwellInterruptionOutageHarmonics

Magnitude and DurationMagnitude and Duration Magnitude and DurationMagnitude and DurationDurationSteadystate Condition

Page 6: Power Quality Basics

Duration

Transient or Surge Impulse

Transient or Surge oscillatory

SagSwellMomentary InterruptionInterruptionOutageHarmonicsUnbalance

.00000005 -- .002 seconds

.000005 -- .050 seconds

.008 -- 60 seconds

.008 -- 60 seconds

.008 -- 3 seconds3 seconds to 1 MinuteGreater than 1 Minute Steadystate ConditionSteadystate Condition

Page 7: Power Quality Basics

What is Power Quality & Reliability?

0

100

200

300

400

500

0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100

Time in Seconds

Perc

ent o

f Nom

inal

Vol

tage

Voltage Tolerance EnvelopeApplicable to Single-Phase120-

Volt EquipmentSWELL Region

Outage

Long

Ter

m E

vent

Shor

t Ter

m E

vent

Tran

sien

tSu

rge

Interruptions (<10% of Nominal)

SAG Region

Page 8: Power Quality Basics

What is a Transient or Surge?A Transient can be classified into two categories, impulsive and oscillatoryDuration < 50 ns to 50 ms

.00000005 seconds to .002 seconds

.000005 seconds to .050 seconds

Page 9: Power Quality Basics

Impulsive

This is the category that TVSS (Transient Voltage Surge Suppressor) SPD equipment is designed to mitigate.

Page 10: Power Quality Basics

Sources of Transients

LightningStaticArc Welding

SwitchingcontactorrelaysSCR’s

Page 11: Power Quality Basics

Oscillatory (Low Frequency)

Page 12: Power Quality Basics

Capacitor Bank Switch

Substation Bank Line Bank

Page 13: Power Quality Basics

Voltage Sags

Page 14: Power Quality Basics

Momentary Interruptions

Breaker Tripped

Page 15: Power Quality Basics

Outage

Page 16: Power Quality Basics

Causes of Sag, Interruptions Outages

Page 17: Power Quality Basics

115 kV Substation

23 k

V Fe

eder

Transformer480 V

Customer

Transformer480 V

Transformer480 V

Transformer480 V

Customer Customer

Customer

Fuse Fuse

Fuse Fuse

Fuse

Fuse

FeederBreaker

Simplified Utility SystemTransmission @ 115 kV

Transformer

Distribution @ 23 kVRegulator

23 k

V Fe

eder

23 k

V Fe

eder

Transformer480 V

Customer

Transformer480 V

Transformer480 V

Transformer480 V

CustomerCustomer

Customer

FuseFuse

FuseFuse

Fuse

Fuse

FeederBreaker

23 k

V Fe

eder

Page 18: Power Quality Basics

Example

Page 19: Power Quality Basics

115 kV Substation

23 k

V Fe

eder

Transformer480 V

Customer

Transformer480 V

Transformer480 V

Transformer480 V

Customer Customer

Customer

Fuse Fuse

Fuse Fuse

Fuse

Fuse

FeederBreaker

Simplified Utility SystemTransmission @ 115 kV

Transformer

Distribution @ 23 kVRegulator

23 k

V Fe

eder

23 k

V Fe

eder

Transformer480 V

Customer

Transformer480 V

Transformer480 V

Transformer480 V

CustomerCustomer

Customer

FuseFuse

FuseFuse

Fuse

Fuse

FeederBreaker

23 k

V Fe

eder

Outage

Momentary Interruption

Sag

Page 20: Power Quality Basics

Time

Quick Trip

6-12 cycles

.3 -

2.0 seconds

13 cycles 15 seconds 35 seconds

lockout

Load Current

FaultInitiated

FaultCurrent

13 cycles

13 cycles

6-12 cycles

6-12 cycles

15 seconds

15 seconds

35 seconds

35 seconds

.3 -

2.0 seconds

.3 -

2.0 seconds

Faulted Feeder

Adjacent Feeder

100%

0%

100%

0%

Voltage

Voltage

FeederBreakerOperation

Substation Voltages During a Feeder Fault

68% Cleared on FirstQuick trip

27% Cleared on Secondand Third Relay

5% Goes to Lock Out

Page 21: Power Quality Basics

Steadystate Condition Waveform Distortion

HarmonicsInterharmonicsVoltage BalanceOvervoltageUndervoltage

Page 22: Power Quality Basics

Wave Distortion

Page 23: Power Quality Basics

Harmonics

Page 24: Power Quality Basics

Voltage or Current Unbalance =

Maximum Deviation from Average Voltage

Average voltage

243 Volts RMS241 Volts RMS233 Volts RMS

X 100 (for Percent)

239 Average Volts

6239 2.5% voltage unbalanceX 100 =

EXAMPLE

MeasuredVoltages

Page 25: Power Quality Basics

Customized Solutions

0

100

200

300

400

500

0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100

Time in Seconds

Perc

ent o

f Nom

inal

Vol

tage

Voltage Tolerance EnvelopeApplicable to Single-Phase120-

Volt EquipmentSWELL Region

Outage

Long

Ter

m E

vent

Shor

t Ter

m E

vent

Tran

sien

tSu

rge

Interruptions

SAG Region

TVSS or SPDLine Reactors

Isolation TransformersPower Conditioner

or CVT

UPS

UPS & Genset

Page 26: Power Quality Basics

IEEE 1159-1995Recommended Practice For Monitoring Electric Power Quality

Table 2 Categories and typical characteristics of power systemelectromagnetic phenomena

Categories Typical Spectral Typical Duration Typical VoltageContent Magnitude

1.0 Transient 1.1 Impulsive 1.1.1 Nanosecond 5 ns rise < 50 ns 1.1.2 Microsecond 1 us rise 50 ns - 1 m s 1.1.3 Millisecond 0.1 m s rise >1 m s 1.2 Oscillatory 1.2.1 Low frequency < 5 k Hz 0.3 - 50 m s 0 - 4 pu 1.2.2 Medium frequency 5 - 500 k Hz 20 us 0 - 8 pu 1.2.3 High frequency 0.5 - 5 M Hz 5 us 0 - 4 pu2.0 Short duration variations 2.1 Instantaneous 2.1.1 Sag 0.5 - 30 cycles 0.1 - 0.9 pu 2.1.2 Swell 0.5 - 30 cycles 1.1 - 1.8 pu 2.2 Momentary 2.2.1 Interruption 0.5 cycles - 3 s < 0.1 pu 2.2.2 Sag 30 cycles - 3 s 0.1 - 0.9 pu 2.2.2 Swell 30 cycles - 3 s 1.1 - 1.4 pu 2.3 Temporary 2.3.1 Interruption 3 s - 1 min < 0.1 pu 2.3.2 Sag 3 s - 1 min 0.1 - 0.9 pu 2.3.3 Swell 3 s - 1 min 1.1 - 1.2 pu3.0 Long duration variation 3.1 Interruption, sustained > 1 min 0.0 pu 3.2 Undervoltage > 1 min 0.8 - 0.9 pu 3.3 Overvoltage > 1 min 1.1 - 1.2 pu4.0 Voltage imbalance steady state 0.5 - 2%5.0 Waveform distortion 5.1 DC offset steady state 0 - 0.1% 5.2 Harmonics 0 - 100th H steady state 0 - 20% 5.3 Interharmonics 0 - 6 k Hz steady state 0 - 2% 5.4 Notching steady state 5.5 Noise broad-band steady state 0 - 1%6.0 Voltage fluctuations < 25 Hz intermittent 0.1 - 7%7.0 Power frequency variations < 10 s

Page 27: Power Quality Basics

Power Quality Tool

http://www.progress-energy.com/

http://www.progress-energy.com/custservice/carcig/resourcectr/pq/pqechome.asp

..\WEB\Tool\index.html

Page 28: Power Quality Basics

PQ Events

Questions?