PLUMBING LEGEND PLUMBING MATERIALS AND...

11
SHOCK ARRESTOR SIZING TABLE PLUMBING GENERAL NOTES PLUMBING MATERIALS AND NOTES DOMESTIC WATER PIPING: 1. DOMESTIC WATER PIPING AND JOINTS BELOW GRADE : PROVIDE TYPE 'K' SOFT ANNEALED SEAMLESS COPPER TUBING (ASTM B 88) WITH NO JOINTS FOR PIPING 2 1/2" AND SMALLER. PROVIDE DUCTILE IRON PIPE AND FITTINGS (AWWA C151, AWWA C110) WITH RUBBER GASKET JOINTS AND RODS (AWWA C111) PIPING 3" AND LARGER. 2. DOMESTIC WATER PIPING AND JOINTS ABOVE GRADE : PROVIDE TYPE 'L' HARD DRAWN SEAMLESS COPPER TUBING (ASTM B 88) AND CAST COPPER ALLOY FITTINGS (ASME B16.18). JOINTS 1" AND SMALLER SHALL BE LEAD FREE 95-5 TIN/SILVER SOLDER JOINTS (ASTM B 32), JOINTS 1 1/4" AND LARGER SHALL BE BCUP SILVER/PHOSPHORUS/COPPER BRAZED JOINTS (AWS A5.8) OR PROVIDE COPPER PIPE AND FITTINGS AS SPECIFIED ABOVE EXCEPT WITH GROOVED ENDS (ASTM B 88, ASME B16.18) AND JOINTS UTILIZING GROOVED MECHANICAL COUPLINGS MEETING (ASTM F1476). 3. STERILIZE THE DOMESTIC WATER SYSTEM IN ACCORDANCE WITH THE AMERICAN WATER WORKS ASSOCIATION'S SPECIFICATIONS AND LOCAL HEALTH DEPARTMENT REGULATIONS. 4. INSULATE DOMESTIC WATER PIPING ABOVE GRADE (EXCEPT EXPOSED CONNECTIONS TO PLUMBING FIXTURES) WITH GLASS FIBER INSULATION HAVING A VAPOR BARRIER AND JACKET. PIPE INSULATION SHALL HAVE A CONDUCTIVITY NOT EXCEEDING 0.27 BTUH x SQ. FT. FOLLOW SCHEDULE BELOW: SERVICE TYPE PIPE SIZES INSULATION THICKNESS DOMESTIC HOT WATER & CIRCULATION 1/2" - 1 1/4" 1" DOMESTIC HOT WATER & CIRCULATION 1 1/2" - 4" 1 1/2" DOMESTIC COLD WATER 1/2" - 1 1/4" 1/2" DOMESTIC COLD WATER 1 1/2" - 4" 1" 5. DOMESTIC WATER PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES ARE REQUIRED TO MEET A FLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS, AS TESTED BY ASTM E84 (NFPA 255) METHOD AND SHALL BE PLENUM RATED. 6. PROVIDE FULL PORT, BALL TYPE SHUT-OFF VALVES AND INSTALL IN A LOCATION THAT PERMITS ACCESS FOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS. 7. PROTECT COPPER PIPING AGAINST CONTACT WITH DISSIMILAR METALS. ALL HANGERS, SUPPORTS, ANCHORS AND CLIPS SHALL BE COPPER OR COPPER PLATED. WHERE COPPER PIPING IS CARRIED ON TRAPEZE HANGERS WITH OTHER PIPING, PROVIDE A PERMANENT ELECTROLYTIC ISOLATION MATERIAL TO PREVENT CONTACT WITH DISSIMILAR OTHER METALS. 8. PROTECT COPPER PIPING AGAINST CONTACT WITH ALL MASONRY. WHERE COPPER IS SLEEVED THROUGH MASONRY, PROVIDE COPPER OR RED BRASS SLEEVES. WHERE COPPER MUST BE CONCEALED IN OR AGAINST MASONRY PARTITIONS, PROVIDE A HEAVY COATING OF ASPHALTIC ENAMEL ON THE COPPER PIPING AND 15# ASPHALT SATURATED FELT BETWEEN THE PIPING AND THE MASONRY PARTITION. 9. DOMESTIC WATER PIPING SHALL BE SLOPED FOR DRAINAGE WITH DRAIN VALVES INSTALLED AT LOW POINTS. SANITARY WASTE / VENT AND STORM PIPING: 1. SANITARY WASTE AND STORM DRAIN PIPING BELOW GRADE: PROVIDE SERVICE WEIGHT CAST IRON HUB AND SPIGOT PIPE (ASTM A 74) WITH COMPRESSION JOINTS (CISPI HSN) AND NEOPRENE GASKETS (ASTM C 564) OR NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET/STAINLESS STEEL CLAMP JOINTS (CISPI 310) OR PROVIDE SCHEDULE 40 PVC PIPE AND SOCKET FITTINGS (ASTM D 2665) WITH SOLVENT WELD JOINTS (ASTM D2855). FOAM CORE PVC PIPE IS NOT APPROVED. 2. SANITARY WASTE/VENT AND STORM DRAIN PIPING ABOVE GRADE: PROVIDE SERVICE WEIGHT CAST IRON NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET AND STAINLESS STEEL CLAMP JOINTS (CISPI 310). DO NOT INSTALL PVC PIPING IN RETURN AIR PLENUMS. 3. SLOPE SANITARY WASTE AND STORM DRAIN PIPING AT 1/4" PER FOOT MINIMUM FOR PIPING 2 1/2" AND SMALLER AND 1/8" PER FOOT MINIMUM FOR PIPING 3" AND LARGER UNLESS NOTED OTHERWISE. SLOPE ALL KITCHEN WASTE PIPING AT 1/4" PER FOOT MINIMUM. 4. PROVIDE CLEAN-OUTS AT THE BASE OF SANITARY WASTE STACKS AND STORM DRAIN RISERS AND AT EVERY TURN IN PIPING IN EXCESS OF 45° AND NO FURTHER THAN 100'-0" APART IN A LOCATION THAT PERMITS ACCESS FOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS. 5. PROVIDE FLOOR CLEANOUTS WITH TOPS DESIGNED TO MATCH SPECIFIC FLOOR FINISHES SUCH AS CARPET, TILE, ETC. YARD CLEANOUTS SHALL BE PROVIDED IN AN 18"x18"x6" CONCRETE PAD. 6. WHERE WASTE PIPING IS EXPOSED IN REST ROOM AREAS, PROVIDE CHROME PLATED BRASS PIPING, REMOVABLE P-TRAPS, MATCHING STOPS AND ESCUTCHEONS FOR ALL LAVATORIES. 7. INSULATE MECHANICAL ROOM FLOOR DRAIN BODIES, P-TRAP AND HORIZONTAL DRAIN PIPING ABOVE GRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET. 8. INSULATE ROOF DRAIN BODIES AND HORIZONTAL PRIMARY AND SECONDARY STORM DRAIN PIPING ABOVE GRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET. 9. PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES ARE REQUIRED TO MEET A FLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS, AS TESTED BY ASTM E84 (NFPA 255) METHOD. 10. SUMP PUMP DISCHARGE PIPING: PROVIDE SCHEDULE 40 GALVANIZED STEEL PIPE (ASTM A53) AND GALVANIZED 150 POUND MALLEABLE IRON FITTINGS (ASME B16.3) WITH THREADED JOINTS. SLOPE SUMP DISCHARGE LINE AT 1% SLOPE TOWARDS SUMP PUMP. NATURAL GAS PIPING: 1. NATURAL GAS PIPING AND FITTINGS ABOVE GRADE: SCHEDULE 40 BLACK STEEL PIPING, TYPE S, SEAMLESS, GRADE B (ASTM A 53) AND 150 PSI MALLEABLE BLACK IRON FITTINGS, GRADE 32510, (ASTM B 16.3) OR FORGED STEEL WELDING TYPE FITTINGS (ASTM A234). PROVIDE THREADED JOINTS FOR PIPE 2" AND SMALLER. PROVIDE WELDED JOINTS (ASME B31.9) FOR PIPE 2 1/2" AND LARGER. 2. NATURAL GAS PIPING AND FITTINGS OUTSIDE BELOW GRADE: SCHEDULE 40 BLACK STEEL, TYPE S, SEAMLESS, GRADE B (ASTM A 53) AND FORGED STEEL WELDING TYPE FITTINGS (ASTM A234) WITH (AWWA C105) POLYETHYLENE JACKET OR DOUBLE LAYER, HALF LAPPED 10 MIL POLYETHYLENE TAPE. PROVIDE WELDED JOINTS (ASME B31.9) FOR ALL UNDERGROUND PIPE. 3. SPACE GAS PIPING HANGER RODS 7'-0" ON CENTER MAXIMUM AND SPACE TRANSVERSE BRACING 20'-0" ON CENTER MAXIMUM. TRANSVERSE BRACING FOR ONE SECTION MAY ACT AS LONGITUDINAL BRACING FOR THE PIPE SECTION CONNECTED TO IT IF THE BRACING IS INSTALLED WITHIN 24" OF THE ELBOW OR TEE. COORDINATE HANGER LOCATIONS WITH STRUCTURAL DRAWING DETAILS. 4. PROVIDE A.G.A. CERTIFIED SHUT-OFF VALVES MINIMUM, 125 PSI RATED, NON- LUBRICATED PLUG TYPE WITH BRONZE BODY AND BRONZE PLUG, STRAINERS AND REGULATORS (AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER) FOR ALL EQUIPMENT CONNECTED TO THE NATURAL GAS SYSTEM. 5. GAS PRESSURE REGULATORS SHALL BE CSA CERTIFIED (Z21.80) FOR 2 PSI INLET PRESSURE, OUTLET PRESSURE RANGE OF 7 TO 11 INCHES WATER COLUMN. WHEN USING VENTLESS REGULATORS, MOUNT REGULATOR IN A HORIZONTAL UPRIGHT POSITION. IF VENTED TYPE REGULATORS ARE USED, INSTALL VENT PIPING (FULL SIZE OPENING) FROM GAS PRESSURE REGULATORS TO OUTDOORS AND TERMINATE IN WEATHERPROOF HOOD. 6. PAINT ALL GAS PIPING WITH 2 COATS OF YELLOW ENAMEL PAINT APPLIED WITH A BRUSH (2 MIL THICKNESS MINIMUM). STENCIL "GAS" ON PIPE AT 12'-0" CENTERS FOR ALL LOW PRESSURE PIPING (0.5 PSI). STENCIL "2-PSI GAS" ON PIPE AT 6'-0" CENTERS FOR 2 PSI GAS PIPING. GENERAL REQUIREMENTS: 1. PLUMBING WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE COLORADO STATE PLUMBING CODE AND WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. 2. GENERAL AND SPECIAL CONDITIONS ARE HEREBY MADE AN INTEGRAL PART OF THE PLUMBING SPECIFICATIONS INSOFAR AS THE GENERAL AND SPECIAL CONDITIONS ARE APPLICABLE TO THE PLUMBING WORK, UNLESS OTHERWISE SPECIFIED. 3. SCOPE: PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED FOR THE COMPLETION AND OPERATION OF ALL PLUMBING SYSTEMS IN ACCORDANCE WITH ALL APPLICABLE CODES. 4. PERMITS: APPLY AND PAY FOR ALL NECESSARY PERMITS, FEES AND INSPECTIONS REQUIRED BY ANY PUBLIC AUTHORITY HAVING JURISDICTION. ACREAGE CHARGES, FACILITIES CHARGES AND BOND PROPERTY ASSESSMENTS ARE NOT TO BE CONSTRUED TO BE A PART OF THIS CONTRACT. 5. WARRANTY: PROVIDE A ONE YEAR WARRANTY, FROM THE DATE OF ACCEPTANCE OF WORK BY THE OWNER, FOR ALL PLUMBING MATERIALS AND EQUIPMENT. 6. COORDINATE ALL PLUMBING PIPING LOCATIONS, ROUGH-IN LOCATIONS AND EQUIPMENT LOCATIONS WITH OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. FINAL PIPING AND EQUIPMENT LOCATIONS SHALL BE A CODE COMPLIANT INSTALLATION FOR ALL TRADES. 7. FIELD VERIFY PROPER OPERATION OF EXISTING SYSTEMS BEFORE STARTING CONSTRUCTION. NOTIFY THE ARCHITECT / ENGINEER OF RECORD OF ANY PROBLEMS OR DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS AND/OR ANY POTENTIAL PROBLEMS OBSERVED BEFORE CONTINUING WORK IN THE EFFECTED AREAS. 8. CUT WALLS, FLOORS AND CEILINGS AS REQUIRED FOR INSTALLATION OF PLUMBING WORK. ALL CUTTING SHALL BE HELD TO A MINIMUM. PATCH AND FINISH SURFACES TO MATCH ADJOINING SURFACES. 9. PLUMBING PLANS SHALL NOT BE SCALED. REFERENCE THE ARCHITECTURAL PLANS FOR ALL LOCATIONS OF PLUMBING FIXTURES, WALLS, DOORS, WINDOWS, ETC. 10. PLUMBING PIPING SHALL BE LOCATED CONCEALED IN WALLS, PARTITIONS OR ABOVE CEILINGS UNLESS NOTED OTHERWISE. PLUMBING PIPING IN EXPOSED AREAS SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE. 11. PLUMBING PIPING, VENTS, ETC. EXTENDING THROUGH EXTERIOR WALLS AND/OR THE ROOF SHALL BE FLASHED AND COUNTER FLASHED IN A WATERPROOF MANNER. COORDINATE FLASHING WITH THE GENERAL CONTRACTOR. 12. DO NOT INSTALL PLUMBING PIPING IN AREAS SUBJECT TO FREEZING TEMPERATURES. INSTALL PLUMBING PIPING SHOWN IN EXTERIOR WALLS ON THE CONDITIONED SIDE OF THE WALL INSULATION. 13. PROVIDE NON-CONDUCTING DIELECTRIC UNIONS WHENEVER CONNECTING DISSIMILAR METALS. 14. ATTACH HANGERS TO STRUCTURE, HANGERS SHALL NOT ATTACH TO THE DECK. 15. PROVIDE ACCESS DOORS FOR VALVES, WATER HAMMER ARRESTORS, TRAP PRIMERS, ETC. CONCEALED IN MASONRY WALLS, GYPBOARD WALLS AND/OR CEILINGS THAT WILL REQUIRE MAINTENANCE ACCESS. ACCESS DOORS SHALL BE LOCATED IN CEILILNG ONLY . 16. PLUMBING SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO: PLUMBING FIXTURES AND EQUIPMENT, FIRE STOPPING, SEISMIC BRACING, PIPE IDENTIFICATION, DOMESTIC WATER SYSTEM, SANITARY WASTE AND VENT SYSTEM, STORM DRAIN SYSTEM, NATURAL GAS SYSTEM PLUMBING FIXTURES AND EQUIPMENT: 1. PROVIDE COMPLETE PLUMBING FIXTURES AND EQUIPMENT. INCLUDE SUPPLIES, STOPS, VALVES, FAUCETS, DRAINS, TRAPS, TAIL PIECES, ESCUTCHEONS, ETC. 2. PLUMBING FIXTURES AND EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'S RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS. 3. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH SUBSTITUTIONS TO SPECIFIED PLUMBING FIXTURES AND EQUIPMENT INCLUDING BUT NOT LIMITED TO; PROVIDING MAINTENANCE ACCESS CLEARANCE, PIPING, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM COMPONENTS, BUILDING ALTERATIONS, ETC. AND ANY MODIFICATIONS TO ASSOCIATED MECHANICAL, ELECTRICAL OR PLUMBING SYSTEMS REQUIRED BY THE EQUIPMENTS INSTALLATION INSTRUCTIONS. ALL COSTS ASSOCIATED WITH SUBSTITUTIONS SHALL BE INCLUDED IN THE ORIGINAL BASE BID. FIRE STOPPING: 1. FIRE STOP ALL PENETRATIONS, BY PIPING OR CONDUITS, OF FIRE RATED WALLS, FLOORS AND PARTITIONS. PROVIDE A DEVICE(S) OR SYSTEM(S) WHICH HAS BEEN TESTED AND LISTED AS COMPLYING WITH ASTM E-814 AND INSTALL IN ACCORDANCE WITH THE CONDITIONS OF THEIR LISTING. PROVIDE A DEVICE(S) OR SYSTEM(S) WITH AN 'F' RATING EQUAL TO THE RATING OF THE ASSEMBLY BEING PENETRATED. REFER TO ARCHITECTURAL PLANS FOR WALL AND FLOOR TYPES. SEISMIC BRACING: 1. PROPERLY SUPPORT AND BRACE VERTICALLY AND HORIZONTALLY ALL PIPING, APPARATUS, EQUIPMENT, ETC. IN ACCORDANCE WITH APPLICABLE CODES TO PREVENT EXCESSIVE MOVEMENT DURING SEISMIC CONDITIONS. PIPE IDENTIFICATION: 1. PIPE IDENTIFICATION SHALL MATCH THE FACILITY'S EXISTING STANDARD. IF NO STANDARD EXISTS, THEN THE PIPE IDENTIFICATION SHALL BE IN ACCORDANCE WITH ANSI A13.1. 2. PROVIDE PIPING LABELS FOR ALL PLUMBING PIPING. PIPING LABELS SHALL BE ACRYLIC FACED, WRAP-AROUND TYPE. EACH LABEL SHALL INDICATE THE PIPING CONTENTS, DIRECTION OF FLOW AND SHALL BEAR THE MANUFACTURER'S STANDARD COLOR FOR THE SERVICE INDICATED. 61-113 33-60 12-32 1-11 D C B A 155-330 F E 114-154 1" 1 1/4" 1/2" 3/4" 2" 1 1/2" SA-D SA-C SA-B SA-A SA-F SA-E DRAWING SYMBOL FIXTURE UNITS PDI WH201 STANDARD DESIGNATION ARRESTOR SIZE - SIOUX CHIEF - WATTS - PPP INC. INSTALL SHOCK ARRESTORS PER PDI WH201 GUIDELINES REMARKS APPROVED MANUFACTURERS ESD G SD SD SA-# HOSE BIBB/WALL HYDRANT PRESSURE REDUCING/REGULATING VALVE BALANCING VALVE / CIRCUIT SETTER GAS COCK END OF LINE CLEAN OUT ROOF DRAIN STORM DRAIN PIPING - ABV. CEILING WALL CLEAN OUT YARD CLEAN OUT FLOOR CLEAN OUT NATURAL GAS PIPING CHECK VALVE HOT WATER RETURN PIPING STORM DRAIN PIPING - BEL. GRADE DESCRIPTION NEW PIPING SANITARY WASTE PIPING HOT WATER PIPING SANITARY VENT PIPING COLD WATER PIPING PIPE CONTINUES BALL VALVE FLOOR DRAIN ELBOW UP ELBOW DOWN PIPE REDUCER EMERGENCY STORM DRAIN PIPING SHOCK ARRESTOR - SUFFIX INDICATES PDI SIZE THERMOMETER PLUMBING LEGEND ABBR. CW HW HWR W V SD SD ESD G CV - - - - BV - PRV - FCO WCO CO YCO FD RD HB SA - PIPE CAP - ADDITIONAL ABBREVIATIONS PRESSURE GAUGE - IN-LINE PUMP - DIRECTION OF FLOW - ABV ABOVE AFF ABOVE FINISHED FLOOR AVTR ACID VENT THRU ROOF BAS BUILDING AUTOMATION SYSTEM BEL BELOW BF BARRIER FREE BFF BELOW FINISHED FLOOR BTUH BRITISH THERMAL UNIT / HOUR CFH CUBIC FEET PER HOUR CLG CEILING CONT CONTINUATION DFU DRAINAGE FIXTURE UNIT (WASTE) DN DOWN EX EXISTING FFE FINISHED FLOOR ELEVATION FIN FINISH FL FLOOR FR FROM FU FIXTURE UNITS GPM GALLONS PER MINUTE HP HORSE POWER INV INVERT ELEVATION IW INDIRECT WASTE KW KILOWATT LAV LAVATORY MBH 1,000 BTUH MH MOUNTING HEIGHT PH PHASE PSI POUNDS PER SQUARE INCH SF SQUARE FEET T&P TEMPERATURE AND PRESSURE TW TEMPERED WATER TYP TYPICAL UR URINAL VB VACUUM BREAKER VLV VALVE VTR VENT THRU ROOF WC WATER COLUMN EC ELECTRICAL CONTRACTOR FSEC FOOD SERVICE EQUIP. CONTRACTOR GC GENERAL CONTRACTOR MC MECHANICAL CONTRACTOR PC PLUMBING CONTRACTOR 1 A B C D E 3 4 5 6 2 Description Date Rev # Copyright 2014. All rights reserved. Printed or electronic drawings and documentation may not be reproduced in any form without written permission from ai Design Group, Inc. PROJECT NO: Revision Schedule DRAWN BY: CHECKED BY: SONIC DEVELOPMENT, LLC Charlotte, North Carolina E N G I N E E R I N G I N C Eng. of Record: License No.: M VEIGH MANGUM C & 1610 East Morehead Street, Suite 100 Charlotte, North Carolina 28207 Ph: (704) 547-9035 Fax: (704) 547-9036 email: [email protected] 2/6/2015 11:56:11 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt 2/6/2015 11:56:11 AM 2015-02-06 13554 ISSUED FOR PERMIT MERCEDES-BENZ OF DENVER Street: Corner of E. Kentucky Ave. and South Colorado Boulevard Glendale, CO 80246 P-001 Author Checker PLUMBING NOTES & LEGENDS 48552 Larry P. McWilliams

Transcript of PLUMBING LEGEND PLUMBING MATERIALS AND...

Page 1: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

SHOCK ARRESTOR SIZING TABLE

PLUMBING GENERAL NOTESPLUMBING MATERIALS AND NOTESDOMESTIC WATER PIPING:

1. DOMESTIC WATER PIPING AND JOINTS BELOW GRADE : PROVIDE TYPE 'K' SOFT ANNEALED SEAMLESS COPPERTUBING (ASTM B 88) WITH NO JOINTS FOR PIPING 2 1/2" AND SMALLER. PROVIDE DUCTILE IRON PIPE ANDFITTINGS (AWWA C151, AWWA C110) WITH RUBBER GASKET JOINTS AND RODS (AWWA C111) PIPING 3"AND LARGER.

2. DOMESTIC WATER PIPING AND JOINTS ABOVE GRADE : PROVIDE TYPE 'L' HARD DRAWN SEAMLESS COPPERTUBING (ASTM B 88) AND CAST COPPER ALLOY FITTINGS (ASME B16.18). JOINTS 1" AND SMALLER SHALL BELEAD FREE 95-5 TIN/SILVER SOLDER JOINTS (ASTM B 32), JOINTS 1 1/4" AND LARGER SHALL BE BCUPSILVER/PHOSPHORUS/COPPER BRAZED JOINTS (AWS A5.8) OR PROVIDE COPPER PIPE AND FITTINGS ASSPECIFIED ABOVE EXCEPT WITH GROOVED ENDS (ASTM B 88, ASME B16.18) AND JOINTS UTILIZINGGROOVED MECHANICAL COUPLINGS MEETING (ASTM F1476).

3. STERILIZE THE DOMESTIC WATER SYSTEM IN ACCORDANCE WITH THE AMERICAN WATER WORKSASSOCIATION'S SPECIFICATIONS AND LOCAL HEALTH DEPARTMENT REGULATIONS.

4. INSULATE DOMESTIC WATER PIPING ABOVE GRADE (EXCEPT EXPOSED CONNECTIONS TO PLUMBINGFIXTURES) WITH GLASS FIBER INSULATION HAVING A VAPOR BARRIER AND JACKET. PIPE INSULATIONSHALL HAVE A CONDUCTIVITY NOT EXCEEDING 0.27 BTUH x SQ. FT. FOLLOW SCHEDULE BELOW:SERVICE TYPE PIPE SIZES INSULATION THICKNESSDOMESTIC HOT WATER & CIRCULATION 1/2" - 1 1/4" 1"DOMESTIC HOT WATER & CIRCULATION 1 1/2" - 4" 1 1/2"DOMESTIC COLD WATER 1/2" - 1 1/4" 1/2"DOMESTIC COLD WATER 1 1/2" - 4" 1"

5. DOMESTIC WATER PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES AREREQUIRED TO MEET A FLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS,AS TESTED BY ASTM E84 (NFPA 255) METHOD AND SHALL BE PLENUM RATED.

6. PROVIDE FULL PORT, BALL TYPE SHUT-OFF VALVES AND INSTALL IN A LOCATION THAT PERMITS ACCESSFOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS.

7. PROTECT COPPER PIPING AGAINST CONTACT WITH DISSIMILAR METALS. ALL HANGERS, SUPPORTS,ANCHORS AND CLIPS SHALL BE COPPER OR COPPER PLATED. WHERE COPPER PIPING IS CARRIED ONTRAPEZE HANGERS WITH OTHER PIPING, PROVIDE A PERMANENT ELECTROLYTIC ISOLATION MATERIAL TOPREVENT CONTACT WITH DISSIMILAR OTHER METALS.

8. PROTECT COPPER PIPING AGAINST CONTACT WITH ALL MASONRY. WHERE COPPER IS SLEEVED THROUGHMASONRY, PROVIDE COPPER OR RED BRASS SLEEVES. WHERE COPPER MUST BE CONCEALED IN ORAGAINST MASONRY PARTITIONS, PROVIDE A HEAVY COATING OF ASPHALTIC ENAMEL ON THE COPPERPIPING AND 15# ASPHALT SATURATED FELT BETWEEN THE PIPING AND THE MASONRY PARTITION.

9. DOMESTIC WATER PIPING SHALL BE SLOPED FOR DRAINAGE WITH DRAIN VALVES INSTALLED AT LOW POINTS.

SANITARY WASTE / VENT AND STORM PIPING:

1. SANITARY WASTE AND STORM DRAIN PIPING BELOW GRADE: PROVIDE SERVICE WEIGHT CAST IRON HUBAND SPIGOT PIPE (ASTM A 74) WITH COMPRESSION JOINTS (CISPI HSN) AND NEOPRENE GASKETS (ASTM C564) OR NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET/STAINLESS STEEL CLAMP JOINTS(CISPI 310) OR PROVIDE SCHEDULE 40 PVC PIPE AND SOCKET FITTINGS (ASTM D 2665) WITH SOLVENT WELDJOINTS (ASTM D2855). FOAM CORE PVC PIPE IS NOT APPROVED.

2. SANITARY WASTE/VENT AND STORM DRAIN PIPING ABOVE GRADE: PROVIDE SERVICE WEIGHT CASTIRON NO-HUB PIPE AND FITTINGS (CISPI 301) WITH NEOPRENE GASKET AND STAINLESS STEEL CLAMP JOINTS(CISPI 310). DO NOT INSTALL PVC PIPING IN RETURN AIR PLENUMS.

3. SLOPE SANITARY WASTE AND STORM DRAIN PIPING AT 1/4" PER FOOT MINIMUM FOR PIPING 2 1/2" AND SMALLERAND 1/8" PER FOOT MINIMUM FOR PIPING 3" AND LARGER UNLESS NOTED OTHERWISE. SLOPE ALL KITCHENWASTE PIPING AT 1/4" PER FOOT MINIMUM.

4. PROVIDE CLEAN-OUTS AT THE BASE OF SANITARY WASTE STACKS AND STORM DRAIN RISERS AND AT EVERYTURN IN PIPING IN EXCESS OF 45° AND NO FURTHER THAN 100'-0" APART IN A LOCATION THAT PERMITS ACCESSFOR SERVICE WITHOUT DAMAGE TO THE BUILDING OR FINISHED MATERIALS.

5. PROVIDE FLOOR CLEANOUTS WITH TOPS DESIGNED TO MATCH SPECIFIC FLOOR FINISHES SUCH ASCARPET, TILE, ETC. YARD CLEANOUTS SHALL BE PROVIDED IN AN 18"x18"x6" CONCRETE PAD.

6. WHERE WASTE PIPING IS EXPOSED IN REST ROOM AREAS, PROVIDE CHROME PLATED BRASS PIPING,REMOVABLE P-TRAPS, MATCHING STOPS AND ESCUTCHEONS FOR ALL LAVATORIES.

7. INSULATE MECHANICAL ROOM FLOOR DRAIN BODIES, P-TRAP AND HORIZONTAL DRAIN PIPING ABOVEGRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET.

8. INSULATE ROOF DRAIN BODIES AND HORIZONTAL PRIMARY AND SECONDARY STORM DRAIN PIPING ABOVEGRADE WITH 1" THICK GLASS FIBER INSULATION WITH VAPOR BARRIER AND JACKET.

9. PIPING INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND ADHESIVES ARE REQUIRED TO MEET AFLAME-SPREAD RATING OF 25 OR LESS AND A SMOKE-DEVELOPED RATING OF 50 OR LESS, AS TESTED BYASTM E84 (NFPA 255) METHOD.

10. SUMP PUMP DISCHARGE PIPING: PROVIDE SCHEDULE 40 GALVANIZED STEEL PIPE (ASTM A53) ANDGALVANIZED 150 POUND MALLEABLE IRON FITTINGS (ASME B16.3) WITH THREADED JOINTS. SLOPE SUMPDISCHARGE LINE AT 1% SLOPE TOWARDS SUMP PUMP.

NATURAL GAS PIPING:

1. NATURAL GAS PIPING AND FITTINGS ABOVE GRADE: SCHEDULE 40 BLACK STEEL PIPING, TYPE S, SEAMLESS,GRADE B (ASTM A 53) AND 150 PSI MALLEABLE BLACK IRON FITTINGS, GRADE 32510, (ASTM B 16.3) OR FORGEDSTEEL WELDING TYPE FITTINGS (ASTM A234). PROVIDE THREADED JOINTS FOR PIPE 2" AND SMALLER. PROVIDEWELDED JOINTS (ASME B31.9) FOR PIPE 2 1/2" AND LARGER.

2. NATURAL GAS PIPING AND FITTINGS OUTSIDE BELOW GRADE: SCHEDULE 40 BLACK STEEL, TYPE S, SEAMLESS,GRADE B (ASTM A 53) AND FORGED STEEL WELDING TYPE FITTINGS (ASTM A234) WITH (AWWA C105)POLYETHYLENE JACKET OR DOUBLE LAYER, HALF LAPPED 10 MIL POLYETHYLENE TAPE. PROVIDE WELDEDJOINTS (ASME B31.9) FOR ALL UNDERGROUND PIPE.

3. SPACE GAS PIPING HANGER RODS 7'-0" ON CENTER MAXIMUM AND SPACE TRANSVERSE BRACING 20'-0" ONCENTER MAXIMUM. TRANSVERSE BRACING FOR ONE SECTION MAY ACT AS LONGITUDINAL BRACING FOR THEPIPE SECTION CONNECTED TO IT IF THE BRACING IS INSTALLED WITHIN 24" OF THE ELBOW OR TEE. COORDINATEHANGER LOCATIONS WITH STRUCTURAL DRAWING DETAILS.

4. PROVIDE A.G.A. CERTIFIED SHUT-OFF VALVES MINIMUM, 125 PSI RATED, NON- LUBRICATED PLUG TYPE WITHBRONZE BODY AND BRONZE PLUG, STRAINERS AND REGULATORS (AS RECOMMENDED BY THE EQUIPMENTMANUFACTURER) FOR ALL EQUIPMENT CONNECTED TO THE NATURAL GAS SYSTEM.

5. GAS PRESSURE REGULATORS SHALL BE CSA CERTIFIED (Z21.80) FOR 2 PSI INLET PRESSURE, OUTLET PRESSURERANGE OF 7 TO 11 INCHES WATER COLUMN. WHEN USING VENTLESS REGULATORS, MOUNT REGULATOR IN AHORIZONTAL UPRIGHT POSITION. IF VENTED TYPE REGULATORS ARE USED, INSTALL VENT PIPING (FULL SIZEOPENING) FROM GAS PRESSURE REGULATORS TO OUTDOORS AND TERMINATE IN WEATHERPROOF HOOD.

6. PAINT ALL GAS PIPING WITH 2 COATS OF YELLOW ENAMEL PAINT APPLIED WITH A BRUSH (2 MIL THICKNESSMINIMUM). STENCIL "GAS" ON PIPE AT 12'-0" CENTERS FOR ALL LOW PRESSURE PIPING (0.5 PSI). STENCIL"2-PSI GAS" ON PIPE AT 6'-0" CENTERS FOR 2 PSI GAS PIPING.

GENERAL REQUIREMENTS:

1. PLUMBING WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE COLORADO STATE PLUMBINGCODE AND WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.

2. GENERAL AND SPECIAL CONDITIONS ARE HEREBY MADE AN INTEGRAL PART OF THE PLUMBINGSPECIFICATIONS INSOFAR AS THE GENERAL AND SPECIAL CONDITIONS ARE APPLICABLE TO THEPLUMBING WORK, UNLESS OTHERWISE SPECIFIED.

3. SCOPE: PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED FOR THE COMPLETION ANDOPERATION OF ALL PLUMBING SYSTEMS IN ACCORDANCE WITH ALL APPLICABLE CODES.

4. PERMITS: APPLY AND PAY FOR ALL NECESSARY PERMITS, FEES AND INSPECTIONS REQUIRED BY ANYPUBLIC AUTHORITY HAVING JURISDICTION. ACREAGE CHARGES, FACILITIES CHARGES AND BONDPROPERTY ASSESSMENTS ARE NOT TO BE CONSTRUED TO BE A PART OF THIS CONTRACT.

5. WARRANTY: PROVIDE A ONE YEAR WARRANTY, FROM THE DATE OF ACCEPTANCE OF WORK BY THEOWNER, FOR ALL PLUMBING MATERIALS AND EQUIPMENT.

6. COORDINATE ALL PLUMBING PIPING LOCATIONS, ROUGH-IN LOCATIONS AND EQUIPMENT LOCATIONS WITHOTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. FINAL PIPING AND EQUIPMENT LOCATIONSSHALL BE A CODE COMPLIANT INSTALLATION FOR ALL TRADES.

7. FIELD VERIFY PROPER OPERATION OF EXISTING SYSTEMS BEFORE STARTING CONSTRUCTION. NOTIFYTHE ARCHITECT / ENGINEER OF RECORD OF ANY PROBLEMS OR DISCREPANCIES BETWEEN THECONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS AND/OR ANY POTENTIAL PROBLEMS OBSERVEDBEFORE CONTINUING WORK IN THE EFFECTED AREAS.

8. CUT WALLS, FLOORS AND CEILINGS AS REQUIRED FOR INSTALLATION OF PLUMBING WORK. ALL CUTTINGSHALL BE HELD TO A MINIMUM. PATCH AND FINISH SURFACES TO MATCH ADJOINING SURFACES.

9. PLUMBING PLANS SHALL NOT BE SCALED. REFERENCE THE ARCHITECTURAL PLANS FOR ALL LOCATIONSOF PLUMBING FIXTURES, WALLS, DOORS, WINDOWS, ETC.

10. PLUMBING PIPING SHALL BE LOCATED CONCEALED IN WALLS, PARTITIONS OR ABOVE CEILINGS UNLESSNOTED OTHERWISE. PLUMBING PIPING IN EXPOSED AREAS SHALL BE RUN TIGHT TO UNDERSIDE OFSTRUCTURE.

11. PLUMBING PIPING, VENTS, ETC. EXTENDING THROUGH EXTERIOR WALLS AND/OR THE ROOF SHALL BE FLASHEDAND COUNTER FLASHED IN A WATERPROOF MANNER. COORDINATE FLASHING WITH THE GENERALCONTRACTOR.

12. DO NOT INSTALL PLUMBING PIPING IN AREAS SUBJECT TO FREEZING TEMPERATURES. INSTALL PLUMBINGPIPING SHOWN IN EXTERIOR WALLS ON THE CONDITIONED SIDE OF THE WALL INSULATION.

13. PROVIDE NON-CONDUCTING DIELECTRIC UNIONS WHENEVER CONNECTING DISSIMILAR METALS.

14. ATTACH HANGERS TO STRUCTURE, HANGERS SHALL NOT ATTACH TO THE DECK.15. PROVIDE ACCESS DOORS FOR VALVES, WATER HAMMER ARRESTORS, TRAP PRIMERS, ETC. CONCEALED IN

MASONRY WALLS, GYPBOARD WALLS AND/OR CEILINGS THAT WILL REQUIRE MAINTENANCE ACCESS. ACCESSDOORS SHALL BE LOCATED IN CEILILNG ONLY.

16. PLUMBING SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO:PLUMBING FIXTURES AND EQUIPMENT, FIRE STOPPING, SEISMIC BRACING, PIPE IDENTIFICATION, DOMESTIC WATERSYSTEM, SANITARY WASTE AND VENT SYSTEM, STORM DRAIN SYSTEM, NATURAL GAS SYSTEM

PLUMBING FIXTURES AND EQUIPMENT:

1. PROVIDE COMPLETE PLUMBING FIXTURES AND EQUIPMENT. INCLUDE SUPPLIES, STOPS, VALVES,FAUCETS, DRAINS, TRAPS, TAIL PIECES, ESCUTCHEONS, ETC.

2. PLUMBING FIXTURES AND EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'SRECOMMENDATIONS AND INSTALLATION INSTRUCTIONS.

3. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH SUBSTITUTIONS TOSPECIFIED PLUMBING FIXTURES AND EQUIPMENT INCLUDING BUT NOT LIMITED TO; PROVIDING MAINTENANCEACCESS CLEARANCE, PIPING, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM COMPONENTS, BUILDINGALTERATIONS, ETC. AND ANY MODIFICATIONS TO ASSOCIATED MECHANICAL, ELECTRICAL OR PLUMBINGSYSTEMS REQUIRED BY THE EQUIPMENTS INSTALLATION INSTRUCTIONS. ALL COSTS ASSOCIATED WITHSUBSTITUTIONS SHALL BE INCLUDED IN THE ORIGINAL BASE BID.

FIRE STOPPING:

1. FIRE STOP ALL PENETRATIONS, BY PIPING OR CONDUITS, OF FIRE RATED WALLS, FLOORS AND PARTITIONS.PROVIDE A DEVICE(S) OR SYSTEM(S) WHICH HAS BEEN TESTED AND LISTED AS COMPLYING WITH ASTM E-814AND INSTALL IN ACCORDANCE WITH THE CONDITIONS OF THEIR LISTING. PROVIDE A DEVICE(S) OR SYSTEM(S)WITH AN 'F' RATING EQUAL TO THE RATING OF THE ASSEMBLY BEING PENETRATED. REFER TO ARCHITECTURALPLANS FOR WALL AND FLOOR TYPES.

SEISMIC BRACING:

1. PROPERLY SUPPORT AND BRACE VERTICALLY AND HORIZONTALLY ALL PIPING, APPARATUS, EQUIPMENT,ETC. IN ACCORDANCE WITH APPLICABLE CODES TO PREVENT EXCESSIVE MOVEMENT DURING SEISMICCONDITIONS.

PIPE IDENTIFICATION:

1. PIPE IDENTIFICATION SHALL MATCH THE FACILITY'S EXISTING STANDARD. IF NO STANDARD EXISTS, THENTHE PIPE IDENTIFICATION SHALL BE IN ACCORDANCE WITH ANSI A13.1.

2. PROVIDE PIPING LABELS FOR ALL PLUMBING PIPING. PIPING LABELS SHALL BE ACRYLIC FACED,WRAP-AROUND TYPE. EACH LABEL SHALL INDICATE THE PIPING CONTENTS, DIRECTION OF FLOW ANDSHALL BEAR THE MANUFACTURER'S STANDARD COLOR FOR THE SERVICE INDICATED.

61-113

33-60

12-32

1-11

D

C

B

A

155-330 F

E114-154

1"

1 1/4"

1/2"

3/4"

2"

1 1/2"

SA-D

SA-C

SA-B

SA-A

SA-F

SA-E

DRAWINGSYMBOL

FIXTURE UNITSPDI WH201STANDARDDESIGNATION

ARRESTORSIZE

- SIOUX CHIEF- WATTS- PPP INC.

INSTALL SHOCK ARRESTORSPER PDI WH201 GUIDELINES

REMARKS

APPROVEDMANUFACTURERS

ESD

G

SD

SD

SA-#HOSE BIBB/WALL HYDRANT

PRESSURE REDUCING/REGULATING VALVE

BALANCING VALVE / CIRCUIT SETTER

GAS COCK

END OF LINE CLEAN OUT

ROOF DRAIN

STORM DRAIN PIPING - ABV. CEILING

WALL CLEAN OUT

YARD CLEAN OUT

FLOOR CLEAN OUT

NATURAL GAS PIPING

CHECK VALVE

HOT WATER RETURN PIPING

STORM DRAIN PIPING - BEL. GRADE

DESCRIPTIONNEW PIPING

SANITARY WASTE PIPING

HOT WATER PIPING

SANITARY VENT PIPING

COLD WATER PIPING

PIPE CONTINUES

BALL VALVE

FLOOR DRAIN

ELBOW UP

ELBOW DOWN

PIPE REDUCER

EMERGENCY STORM DRAIN PIPING

SHOCK ARRESTOR - SUFFIX INDICATES PDI SIZE

THERMOMETER

PLUMBING LEGENDABBR.

CW

HW

HWR

W

V

SD

SD

ESD

G

CV

-

-

-

-

BV

-

PRV

-

FCO

WCO

CO

YCO

FD

RD

HB

SA

-

PIPE CAP-

ADDITIONAL ABBREVIATIONS

PRESSURE GAUGE-

IN-LINE PUMP-

DIRECTION OF FLOW-

ABV ABOVEAFF ABOVE FINISHED FLOORAVTR ACID VENT THRU ROOFBAS BUILDING AUTOMATION SYSTEMBEL BELOWBF BARRIER FREEBFF BELOW FINISHED FLOORBTUH BRITISH THERMAL UNIT / HOURCFH CUBIC FEET PER HOURCLG CEILINGCONTCONTINUATIONDFU DRAINAGE FIXTURE UNIT (WASTE)DN DOWNEX EXISTINGFFE FINISHED FLOOR ELEVATIONFIN FINISHFL FLOORFR FROMFU FIXTURE UNITSGPM GALLONS PER MINUTEHP HORSE POWERINV INVERT ELEVATIONIW INDIRECT WASTE

KW KILOWATTLAV LAVATORYMBH 1,000 BTUHMH MOUNTING HEIGHTPH PHASEPSI POUNDS PER SQUARE INCHSF SQUARE FEETT&P TEMPERATURE AND PRESSURETW TEMPERED WATERTYP TYPICALUR URINALVB VACUUM BREAKERVLV VALVEVTR VENT THRU ROOFWC WATER COLUMN

EC ELECTRICAL CONTRACTORFSEC FOOD SERVICE EQUIP. CONTRACTORGC GENERAL CONTRACTORMC MECHANICAL CONTRACTORPC PLUMBING CONTRACTOR

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:56:11 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:56:11 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-001Author Checker

PLUMBING NOTES & LEGENDS

48552Larry P. McWilliams

Page 2: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

EXTERIORDETAILBAYS

104

SERVICEDRIVE

103

CAFE130

BREAKROOM

117

WOMENS134

MENS132

CASHIER /LOANERRENTAL

131

KIDS128

WARRANTY124

SERVICEADMIN

126 MENS122

LOCKERROOM

123

WOMENS121

JANITOR133

P-6

P-4

P-1A P-2A P-3 P-3 P-3 P-3 P-1AP-1

3/4" HW

2" CW

3/4" HW2" CW

2" CW

1 1/2" CW

1 1/2" CW

1/2" CW

1" CW

1/2" HW

3/4"CW UPTO HB4

HB1HB1

2 1/2" CW

2 1/2"CW UP ALONGWALL TO 48"AFF.

PROVIDE RPZ BACKFLOWDEVICE EQUAL TO WILKINS375A. PROVIDE FUNNEL DRAINAND INDIRECT WASTE PIPINGTO SPILL @ 12"AFG

2 1/2"CW UPTO STRUCTURE

2"CW RISER

12

1" CW

2" CW

2" CW

2 1/2" CW

2 1/2" CW

2 1/2" CW

3/4" CW1/2" CW

2" CW

3/4" CW

EXTEND 2 1/2"CW TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.

P-2A

P-3A

P-1P-1A

P-10

EWH-1

STORAGE130A

2 1/2"GAS RISER

1 1/4"GAS DNTO BOILER(500 CFH)

G

GGGGGG

GG

GG

G

G

1 1/4" G

2" G

1 1/4" G

2" G

2" G

2" G

2 1/2" G

2 1/2" G

1 1/4" G

1 1/4" G

1 1/4" G

GAS MAIN TO METERBELOW GRADE BY GAS CO.

GAS METER (BY GAS CO)(3,014 CFH @ 2 PSIG)

2 1/2"GAS THROUGH WALL TOSTRUCTURE.

GAS SIZING BASED ON TABLE 402.4(3)(500 FEET) OF THE 2012 EDITION OFTHE IPC FUEL GAS CODE. TOTAL CFH 4014

3/4" CW3/4" CW

3/4"CW TO HOSE REEL(PROVIDED BY OTHERS)TYPICAL 13 LOCATIONS

HOSE REEL

3/4" CW

HOSE REEL

1/2" CW

1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.

1/2"CW RISER

P-1A P-3A

P-111A2

INSTALL BACKFLOW DEVICE PERCITY OF GLENDALE STANDARDS.

LOCATION OF FIRE RISER

12

P-6

P-4

P-1A P-2A P-3 P-3

P-3 P-3 P-1AP-1

P-2AP-3A

P-1P-1A

P-10

EWH-1

P-1A P-3A

1/2" HW

1/2" CW3/4" CW

3/4" HW

3/4" HW

2" CW 1 1/2" CW 1 1/2" CW

1/2" HW

1/2" CW

1 1/4" CW

1 1/4" CW1" CW P-3A

2" CW

2" CW

1 1/2" CW

2" CW

1 1/4" CW

2" CW 2" CW 1" CW

1/2" CW

1 1/4" CW

1 1/2" CW

1/2" HW2" CW

1/2" HW 1/2" CW

3/4" HW

3/4" CW

3/4" CW

1/2" HW

1 1/4" CW

1/2" HW3/4" CW

2" CW

2" CW

1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.

SA-A

SA-A

SA-A

SA-A

SA-A

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:56:22 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:56:22 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-111AAuthor Checker

DOMESTIC WATER PLAN - LOWERLEVEL - AREA A

48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111A

1

DOMESTIC WATER PLAN - LOWER LEVEL -AREA A

SCALE: 1/4" = 1'-0"P-111A

2 ENLARGED LOWER LEVEL PLUMBING PLAN

Page 3: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

EXTERIORDETAILBAYS

104

SERVICEDRIVE

103

BREAKROOM

117

CAFE130

CASHIER /LOANERRENTAL

131

MENS132

WOMENS134

KIDS128

SERVICEADMIN

126 MENS122

LOCKERROOM

123

WARRANTY124

WOMENS121

JANITOR133

A

B

B.5

C

D

E

F

F.9G

5.1

5

4

3.23

21.1

1

INTERIORDETAIL BAY

105

JAN.118

ELEVATOR1

E101

LANE MGR102

SERVICEMGR

106QUICKLUBE

107

FUTUREALIGNMENT

BAY136

SERVICEWRITERS

101

SERVICEDRIVE

CANOPY100

FCO

FCO

FCO

3"V UP

YCO

12

FCO

FCO

FCO

YCO

4"SD UPTO AD1

4"SD UPTO AD1

4"SD UPTO AD1

4"SD UPTO AD1

4"SD UPTO AD1

6"SD RISER

6"SD DN

SDSDSD

SDSDSD

SDSD

SDSD

SD

SDSDSDSD

10"SD RISER

EXTEND 4"S TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.

EXTEND 4"S TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.

4"S STACK

4" S

4" S 4" S4" S3" S

4" S

4" S

4" S

3" S

4" S

3" S

3"FD2

3"FD2

3"FD23"FD2 3"FD2

2"V RISER

2" V

4" S

4" S

4" S 2" V

4" S

4" S

4" S

4" S

4" S

3" S

4" S

4" S

4" S 4" S

3" S

4" SD4" SD4" SD

2" V

2" V

1 1/2" V 4" S4" S4" S

4" S

4" SD

4" S

4" S3" V

4" S

3" V

4" S

3" V

4" S

4" S

4" S

4" S

3" V4" S

2" V 2" V4" S FCO4" S

1 1/2" V 2" S

2"FD1

SD

10" SD

4" S

PROVIDE 24"X24"X72"DEEPSUMP BASIN WITH 4"FD1 W/DOME STRAINER IN BOTTOMOF PIT. PROVIDE HEAVY DUTYGRATE OVER PIT.

4"S TO SPILL INDIRECTLYINTO SUMP PIT.

2"V UP

3"FD2 3"FD2

3" S 3" S 3" S

4" SD

4" SD

6" SD

6" SD 6" SD 6" SD

6" SD

6" SD

6" SD

6" SD

6" SD2" S

2"S UP

2"S DN IN WALL TO BELOWSLAB.

2"FD12" V

2"FD1

2" S 2" V

2"FD1

3"FD2

3" S

SEE CIVIL DRAWINGS FOR OIL WATER SEPARATOR.PC TO PROVIDE PROCEPTOR OMC-1500, REINFORCEDFIBERGLASS PLASTIC, 819 GALLONS OF OIL STORAGECAPACITY, MANHOLE EXTENSIONS, OR EQUAL.COORDINATE LOCATION WITH UTILITY CONTRACTOR.PROVIDE 2" CONNECTED TO BUILDING VENT SYSTEM.

2" V

2"V TO OIL/WATERSEPARATOR

NOTE:PROVIDE CLEANOUT ATTHE BASE OF ALL RISERSAND STACKS.

P-6

P-4

P-1A P-2A P-3 P-3 P-3 P-3 P-1AP-1

P-2A

P-3A

P-1P-1A

P-10

2" S

2" S

2" V

2" V

6"SD TO SPILL @ 22"AFG.PROVIDE ZURN Z-199DCOR EQUAL

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:56:33 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:56:33 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-111BAuthor Checker

SANITARY & VENT PLAN - LOWERLEVEL - AREA A

48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111B

1

SANITARY & VENT PLAN - LOWER LEVEL -AREA A

Page 4: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

SERVICEBAYS

116

UNITREPAIRS

TOOLEQUIPMENT

113STAIR 102

S102

3/4"CW UPTO HB2

12

1" CW1" CW

1" CW1" CW

3/4"CW RISER

1 1/4"GAS DNTO BOILER(500 CFH)

GG

GG

1 1/4" G

1 1/4" G1 1/4" G

3/4" CW

HOSE REEL

HOSE REEL HOSE REELHOSE REEL

HOSE REEL HOSE REEL

HOSE REEL

HOSE REEL

HOSE REEL

3/4" CW

3/4" CW

3/4" CW

3/4" CW3/4" CW

3/4" CW

3/4" CW

3/4" CW

3/4" CW

3/4" CW

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:56:40 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:56:40 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-111CAuthor Checker

DOMESTIC WATER PLAN - LOWERLEVEL - AREA B

48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111C

1

DOMESTIC WATER PLAN - LOWER LEVEL -AREA B

Page 5: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

SERVICEBAYS

116

UNITREPAIRS

TOOLEQUIPMENT

113

STAIR 102S102

A

B

B.5

C

D

E

F

F.9G

11109

8

76.9

SPECIALTOOLS

109

EQUIPMENT112

SHOPFOREMEN

108

ALIGNMENTBAY115

PARTS LIFTE102

TECHPARTS

111

FASTMOVINGPARTS

110

ELECTRICAL114

12

FCO

FCO

6"SD RISER

4"SD UPTO AD1

8"SD RISER DN

EXTEND 8"SD TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.

SDSD

SDSD

SDSDSD

SDSD

EXTEND 10"SD TO 5'-0"OUTSIDE BUILDING. SEECIVIL UTILITY PLAN FORCONTINUATION.

3"FD2 3"FD2

3"FD2 3"FD2

3"FD2 3"FD2

3"FD2

4" S 4" S

3" S

4" S

3" S

4" S

4" S

3" S 3" S 3" S

4" S

4" S

3" S3" S 3" S

3" S

8" SD

8" SD

8" SD

6" SD

6" SD

4" SD4" SD

FCO

3"S STACK

SD

3"FD2

3" S 3" S

NOTE:PROVIDE CLEANOUT ATTHE BASE OF ALL RISERSAND STACKS.

SEE DETAIL #10/P202FOR CONDENSATE DRAINBOX.

2" S

2" V

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:56:50 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:56:50 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-111DAuthor Checker

SANITARY & VENT PLAN - LOWERLEVEL - AREA B

48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-111D

1

SANITARY & VENT PLAN - LOWER LEVEL -AREA B

Page 6: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

BDC206

TELE /DATA

208

LOCKER207

TRAINING209

BREAKROOM

211

CORRIDOR210

OFFICE212

OFFICEMGR

214

OFFICE213

PARTS MGR234

STAIR 202S202

AIRCOMPRESSOR

/ OILSTORAGE

235

SHIPPINGAND

RECEIVING238

PARTSSTORAGE

233

SALESMGRS

227COPY / KEY

226

RETAILPARTS

225

SHOWROOM204

STAIR 201S201

GENERALMANAGER

228F&I229

F&I230

LOUNGE231

VEHICLEDISPLAY

205

MENS222

STORAGE216

COPY / FAX/ STORAGE

215CONFERENCE

217

SALES219

WOMENS220

JAN.221

3/4"CW RISER

HB2

3/4"CW RISER

HB2

3/4"CW UPTO HB4

12

PARTS LIFTE202

3/4" CW

3/4" CW

3/4" CW

3/4"CW UP TOMECHANICAL CONNECTIONON ROOF. COORDINATEWITH M.C.

3/4"CW UP TOMECHANICAL CONNECTIONON ROOF. COORDINATEWITH M.C.

3"GAS RISER

1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.

P-112A2 3/4" CW

MENS222

SALES219

WOMENS220

JAN.221

2"CW RISER

3/4"CW UPTO HB3

P-1A

P-1

P-1

P-3

P-3

P-9

P-3

P-3

P-1

P-1A

P-2A

P-4

P-6

1 1/4" CW

1 1/2" CW

1 1/2" CW

2" CW1/2" HW

1/2" HW1/2" CW

1" CW

1/2" CW

1 1/2" CW

3/4" HW

1 1/2" CW

1 1/2" CW

3/4" CW

3/4" CW

1/2"CW DN IN WALL TOCOFFEE MACHINE. PROVIDEVACUUM BREAKER.

EWH-1

1/2" HW

1/2" HW

3/4" CW

1/2" CW

SA-B

SA-B

SA-A

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:57:02 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:57:02 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-112AAuthor Checker

DOMESTIC WATER PLAN - UPPERLEVEL

48552Larry P. McWilliams

SCALE: 1/8" = 1'-0"P-112A

1 DOMESTIC WATER PLAN - UPPER LEVEL

SCALE: 1/4" = 1'-0"P-112A

2 ENLARGED UPPER LEVEL PLUMBING PLAN

Page 7: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

BDC206

VEHICLEDISPLAY

205

TELE /DATA

208

LOCKER207

TRAINING209

BREAKROOM

211

CORRIDOR210

OFFICE212

OFFICE213

OFFICEMGR

214

COPY / FAX/ STORAGE

215

CONFERENCE217

SALES219

STORAGE216

WOMENS220

JAN.221

MENS222

STAIR 201S201

RETAILPARTS

225

COPY / KEY226

SALESMGRS

227

PARTSSTORAGE

233

GENERALMANAGER

228F&I229

F&I230

LOUNGE231

SHIPPINGAND

RECEIVING238

AIRCOMPRESSOR

/ OILSTORAGE

235STAIR 202S202

PARTS MGR234

SHOWROOM204

A

B

B.5

C

D

E

F

F.9G

9

8

76.9

5.1

5

4

3.23

21.1

1

2"V UPTO 2"VTR

PARTS LIFTE202

PARTSVESTIBULE

236

PARTSCLERKS

237

KIDS239

DOCUMENTCONTROL

ROOM218

LOUNGE223

DISPLAY224

OUTDOORSHOWROOM

200

NEW CARDELIVERY

232

SHOWROOM204

3"V UPTO 3"VTR

12

SDSDSDSDSDSDSDSDSD SD

2"V RISER

6"SD UPTO 6"SD1

6"SD UPTO 6"SD1

6"SD UPTO 6"SD1

6"SD UPTO 6"SD1

6"SD UPTO 6"SD1

10"SD RISERDOWN

6" SD8" SD10" SD8" SD8" SD6" SD

6" SD

SD SD

SD

4" SD 4" SD

4" SD

4" SD6"SD RISERDOWN

AD1 AD1 AD1

AD1 AD1 AD1

AD1

SD SD SD6" SD 6" SD

6"SD RISERDOWN

WCO

2" V

2" V

2" V

2" V

2" V 1 1/2" V

1 1/2" V

FCOP-1A

P-1

P-1

P-3

P-3

P-9

P-3

P-3

P-1

P-1A

P-2A

P-4

4"S DOWN

4" S

4" S

4" S

4" S

4" S

4" S

2" S

P-6

2"V RISER

3" S 3"FD1

2"V UPTO 2"VTR SEE DETAIL #10/P202

FOR CONDENSATE DRAINBOX.

2"FD1

2"FD1

2" V

2" S

2"FD1

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:57:13 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:57:13 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-112BAuthor Checker

SANITARY & VENT PLAN - UPPERLEVEL

48552Larry P. McWilliamsSCALE: 1/8" = 1'-0"P-112B

1 SANITARY & VENT PLAN - UPPER LEVEL

Page 8: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

6"SD1(5220 SQFT)

6"SD1(5375 SQFT)

6"SD1(5350 SQFT)

6"SD1(4782 SQFT)

6"SD1(5003 SQFT)

5"SD2(2534SQFT)

B

B.5

C

D

E

F

F.9G

9

8

76.9

5.1

5

4

3.23

21.1

1

4"SD2(1427 SQFT)

5"SD2(2534SQFT)5"SD2

(2534SQFT)

12

3"VTR

2"VTR

HB3

RTU-1

RTU-2

RTU-5

RTU-3

RTU-4

1"GASTO RTU-3(130 CFH)

1"GASTO RTU-5(200 CFH)

1"GASTO RTU-3(284 CFH)

2"GASTO OARTU-2(1000 CFH)

2"GASTO OARTU-1(1400 CFH)

1"GASTO RTU-4(284 CFH)

1"GASTO RTU-1(284 CFH)

G

GGGGGGGG

G

GG

GG

G

G

G

G G G G

2" G

2" G2 1/2" G2 1/2" G2 1/2" G2 1/2" G2 1/2" G

1" G

2 1/2" G

2 1/2" G 2 1/2" G 1" G

1" G

1" G

2 1/2" GAS RISER.PROVIDE PITCH POCKETFOR ROOF PENETRATION.

NOTE:COORDINATE LOCATION OFGAS PIPING CONNECTIONS TOROOFTOP EQUIPMENT WITHMC PRIOR TO COMMENCING WORK.

6"SD1(2534 SQFT)

6"SD1(2534 SQFT)

PROVIDE 6"SD1 WITHINTERNAL 3"WATER DAMPIPE TO UNDERSIDE OFCANOPY. TERMINATE WITHPERFORATED STAINLESSSTEEL COVER TO MATCHCANOPY FINISH.

6"SD1(1427 SQFT)

PROVIDE 6"SD1 WITHINTERNAL 3"WATER DAMPIPE TO UNDERSIDE OFCANOPY. TERMINATE WITHPERFORATED STAINLESSSTEEL COVER TO MATCHCANOPY FINISH.

6"SD1(2534 SQFT)

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:57:22 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:57:22 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-131Author Checker

PLUMBING ROOF PLAN

48552Larry P. McWilliams

SCALE: 1/8" = 1'-0"P-131

1 T.O.W. - HIGH

Page 9: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

PLUMBING FIXTURE SCHEDULEDESIGNATION MANUFACTURER MODEL # FIXTURE DESCRIPTION

CONNECTION SCHEDULE

WASTE VENT CW HW

P-1 AMERICAN STANDARD "MADERA" 2234.000114" HIGH VITREOUS CHINA WATER CLOSET W/ ELONGATED BOWL

FLUSH VALVE - SLOAN NO. 8111-1.28

SEAT (NO LID) - CHURCH MODEL 9500-SSC 1.6 GPF)

3" 2" 1" --

P-1A AMERICAN STANDARD "MADERA" 3043.001

17" HIGH VITREOUS CHINA WATER CLOSET W/ ELONGATED BOWL (HANDICAP)

FLUSH VALVE - 8111-1.28

SEAT - (NO LID) - CHURCH MODEL 9500-SSC

LOW WATER CONSUMPTION (1.6 GALLONS PER FLUSH)

LOCATE FLUSH CONTROL ON WIDE SIDE OF STALL

3" 2" 1" --

P-2 AMERICAN STANDARD"WASHBROOK"

6541.132

WALL- HUNG, VITREOUS CHINA, FLUSH VALVE URINAL

FLUSH VALVE - SLOAN OPTIMA 8186-0.125

LOW WATER CONSUMPTION (0.125 GALLON PER FLUSH)

MOUNT TOP OF FRONT RIM AT 17" A.F.F. TO MEET A.D.A.

PROVIDE SUITABLE FIXTURE CARRIER

2" 2" 3/4" --

P-2A AMERICAN STANDARD"WASHBROOK"

6541.132

WALL- HUNG, VITREOUS CHINA, FLUSH VALVE URINAL (HANDICAP)

FLUSH VALVE - SLOAN OPTIMA 8186-0.125

LOW WATER CONSUMPTION (0.125 GALLON PER FLUSH)

MOUNT TOP OF FRONT RIM AT 17" A.F.F. TO MEET A.D.A.

PROVIDE SUITABLE FIXTURE CARRIER

2" 2" 3/4" --

P-3 AMERICAN STANDARD "OVALYN 2" 0496.211

VITREOUS CHINA COUNTER-MOUNT LAVATORY

FAUCET - SLOAN OPTIMA ETF-80

PROVIDE BELOW DECK THERMOSTATIC MIXING VALVE

PROVIDE PLUG-IN TRANSFORMER

TRAP - 1 1/4" CAST BRASS WITH C.O. PLUG

SUPPLY - 3/8" ANGLE-TYPE WITH STOPS

INSULATE TRAP OUTLET & HW SUPPLY TO MEET A.D.A.

2" 1 1/4" 1/2" 1/2"

P-3A AMERICAN STANDARD "LUCERNE" 0355.012

VITREOUS CHINA WALL-HUNG LAVATORY (HANDICAP)

FAUCET - SLOAN OPTIMA ETF-80

PROVIDE BELOW DECK THERMOSTATIC MIXING VALVE

PROVIDE PLUG-IN TRANSFORMER

TRAP - 1 1/4" CAST BRASS WITH C.O. PLUG

SUPPLY - 3/8" ANGLE-TYPE WITH STOPS

INSULATE TRAP OUTLET & HW SUPPLY TO MEET A.D.A.

2" 1 1/4" 1/2" 1/2"

P-4 ELKAY LZSTLG8WSLKELECTRIC WATER COOLER W/DUAL SPLIT LEVEL BASINS AND BOTTLE FILLING STATION

(BARRIER FREE)

8.0 GPH CAPACITY, 4.5 F.L.A., 120-1-60.

2" 1 1/4" 1/2" --

P-6 ELKAY ELUHAD311845PD

DOUBLE-COMPARTMENT, STAINLESS STEEL SINK (HANDICAP)

FAUCET - AMERICAN STANDARD 6114.380

CUP STRAINERS - (2) ELKAY LK-35

SUPPLY - 3/8" ANGLE-TYPE WITH STOPS

TRAP - 1 1/2" CAST BRASS WITH C.O. PLUG

INSULATE TRAP OUTLET & HW SUPPLY TO MEET A.D.A.

2" 1 1/2" 1/2" 1/2"

P-7 SIOUX CHIEF 696-1010MF ICE MAKER BOX W/ WATER HAMMER ARRESTERS. -- -- 1/2" --

P-9 FIAT MSB 2424

FLOOR-MOUNTED MOLDED STONE MOP BASIN

FAUCET- FIAT 830-AA

FURNISH WALL- MOUNTED MOP HANGER

3" 2" 1/2" 1/2"

P-10 BRADLEYSN2023-IR-STD

TMA-LSD-BS

36" SEMI-CIRCULAR SHALLOW BOWL WASH FOUNTAIN

PROVIDE INFRARED SENSOR ACTIVATION

PROVIDE THERMOSTATIC MIXING VALVE

PROVIDE BACKSPLASH AND LIQUID SOAP DISPENSER

2" 2" 3/4" --

FD1 ZURNZ-415 W/ TYPE "B"

STRAINER

FLOOR DRAIN W/ 5" NICKALOY STRAINER TOP

PROVIDE PROSET TRAP GUARD3" 2" -- --

FD2 ZURN Z-610-AR-TS-SS-DG

HEAVY DUTY FLOOR DRAIN W/ 16" DUCTILE IRON STRAINER TOP

PROVIDE HEEL PROOF GRATES IN SERVICE RECEPTION ONLY.

PROVIDE PROSET TRAP GUARD

-- -- -- --

EWH1 A.O. SMITH DEL-30-4.5

30-GALLON ELECTRIC WATER HEATER

4.5 KW,208-3-60

SET WATER TEMP. CONTROL TO 120° F

-- -- 3/4" 3/4"

HB1 WOODFORD MODEL-24 HOSE BIBB (BRASS) - MANUFACTURED BY WOODFORD OR EQUAL

1/2" I.P.S. INLET; 1/2" HOSE CONNECTION OUTLET-- -- 1/2" --

HB2 ZURN Z-1300

FREEZE-PROOF, ENCASED, ANTI-

SIPHON, RECESSED WALL HYDRANT W/ LOCKABLE COVER

PROVIDE OPTIONAL WALL CLAMP AND PLAIN BRONZE BOX

-- -- 3/4" --

HB3 WOODFORD SRH-MS FREEZELESS ROOF HYDRANT W/ MOUNTING SYSTEM -- -- 3/4" --

HB4 WOODFORD Y95 FREEZELESS YARD HYDRANT, INSTALL FLUSH WITH FINISHED FLOOR -- -- 3/4" --

SA ZURN Z-1700 SERIESWATER HAMMER ARRESTOR. SIZE PER P.D.I. WH-201

VERIFY THAT COMPONENT IS ACCESIBLE.-- -- -- --

WCO ZURN Z-1446 WALL CLEANOUT - PROVIDE SCREW COVER MATCH SIZE OF PIPE. -- -- -- --

FCO ZURN Z-1400FLOOR CLEANOUT - PROVIDE SCREW COVER MATCH

SIZE OF PIPE.-- -- -- --

AD1 ZURN Z-627--C-DG-FISOLATION DECK DRAIN W/ 9" NICKALOY STRAINER TOP

COORDINATE EXTENSION LENGTH WITH STRUCTURAL DRAWINGS3" 2" -- --

SD1 ZURN Z-100MAIN ROOF DRAIN WITH CAST IRON BODY

LOW SILHOUETTE DOME & DOUBLE TOP-SET DECK PLATE; MATCH SIZE OF PIPE-- -- -- --

SD2 ZURN Z-187-BSSCUPPER DRAIN WITH CAST IRON BODY

NICKEL BRONZE GRATE; MATCH SIZE OF PIPE-- -- -- --

APPROVED MANUFACTURERS: ACCEPTED SUBSTITUTION:SPECIFIED MANUFACTURER/PRODUCT:

PROVIDE ONLY PRODUCTS MADE BY THECLOSELY MATCHES THE SPECIFIED PRODUCT.PROVIDING THE MODEL WHICH MOSTTHE CONTRACTOR IS RESPONSIBLE FOR

MANUFACTURER'S LISTED.

T&S BRASS, DELTA, AMERICAN STANDARD

BRASSCRAFT, E.B.C.

CENTOCO, BENEKE, BEMIS

BRADFORD-WHITE, STATE, RHEEM

KOHLER, SLOAN

OASIS, HAWS, MURDOCHELKAY (WATER COOLERS)AO SMITH (WATER HEATERS)

MCGUIRE (SUPPLY STOPS)

CHURCH (TOILET SEATS)AMERICAN STANDARD (A.S.)

SLOAN COMMERCIAL (FAUCETS)ELKAY (S.S. SINKS) JUST

ZURN (FLOOR DRAINS, CLEANOUTS) JR SMITH, WADE, JOSAMSCHIER, ROCKFORD

ZURN, JR SMITH, MIFABACORN, WILLOUGHBYBRADLEY (MULTI STATION WASH SINKS)

WOODFORD (HYDRANTS)

PROCEPTOR (OIL/WATER SEPARATOR)

FLORESTONEFIAT (MOP SINK)

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:57:37 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:57:37 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-201Author Checker

PLUMBING SCHEDULES

48552Larry P. McWilliams

Page 10: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

GAS PIPING

ROOF

DIELECTRICUNION

DIRTLEG

GAS COCKPITCH BACK TO SOURCE

ROOFTOPUNIT

GAS PRESSUREREGULATOR(2 PSI TO 7" W.G.)

DIELECTRICUNION

10 PIPE DIAMETERS (MIN.)

DIELECTRICUNION

CAPPEDPRESSURETEST PORT

ROOFTOP PIPING SUPPORTSEE DETAIL #11/P0.3

BY M.C.BY P.C.

NOTE:GAS PIPING AND SHUT-OFF VALVE SHALL BE BY PLBG. CONTR., DIRT LEG, REGULATOR,AND FINAL CONNECTION TO UNIT SHALL BE BY MECH. CONTR.

ADDITIONAL LAYEROF ROOF MEMBRANEAS CUSHION

GAS PIPING

MIRO PIPESTAND

UNION

3-R

3-R

2" 3-R 10'

15'2 1/2"

4" 4-R, 4-RAH 9'

13'3"

1 1/4" 1.5 8'

10'1.51 1/2"

1" 1.5 7'

6'1.53/4"

MAX. SPACINGMODEL NO.PIPE SIZE

3. DO NOT ATTACH PIPE STANDS TO ROOF.

2. PIPE STAND SHALL BE MIRO, IND. OREQUAL "PILLOWBLOCK" MODEL 1.5 (UPTO 1 1/2"), 3-R (UP TO 3"), AND 4-R &4-RAH FOR 4", 6-RAH (5 TO 6").

1. PIPING SHALL BE SUPPORTED AT ALLELBOWS AND TEES AND AT SPACINGSPECIFIED IN THE TABLE BELOW.

GG

(TYPICAL)

BY GAS CO. BY CONTRACTOR

4" CONCRETE PAD

FINISH GRADE

PRESSURE REGULATOR

SHUT-OFF VALVE(TYPICAL)

1 1/2" (1,254 CFH @ 2 PSI)

DIGITAL PLUSE OUTPUTGAS METER, SHUT-OFF VALVE ANDREGULATOR. CONTRACTOR SHALLCOORDINATE WITH LOCAL GAS UTILITY(PRIOR TO UTILITY WORK) FOR TOENSURE THE PROVISION OF A GAS METERWITH DIGITAL PULSE OUTPUT REQUIREDBUILDING AUTOMATION SYSTEM'SMEASUREMENT AND VERIFICATION.

10 PIPE DIAMETERS (MIN.)

CAPPED PRESSURETEST PORT

TO EQUIPMENTGAS TRAIN

GAS PIPING

DIELECTRICUNION (TYP)

GAS COCK GWH

FLOOR

GAS PRESSUREREGULATOR.(2 PSI TO .5 PSI)

DRIP LEG

GRID DRAINCONNECTOR.

36"

48"

18"

WALL

MOP (BY OTHERS)

HOSE BRACKET

FINISHED FLOOR.

MOP BASIN

APPLY SILICONESEALANT AROUNDTOP AND SIDES OFSINK AT ALL WALLS.

MOP HANGER (BY G.C.)

SERVICE FAUCETWITH VACUUMBREAKER.

30" HOSE

SADDLE

FOAM GLASS(AT SADDLE ONLY)

CLEVIS HANGER

INSULATION

PIPE

RUN RESTRAINING CABLES INFOUR DIRECTIONS AND SECURETO STRUCTURE TO PREVENTLATERAL MOVEMENT OF PIPES.(SEE SEISMIC RESTRAINT CODEFOR REQUIREMENT CRITERIA.)

GALVANIZED THREADED ROD,SECURE TO STRUCTURE.

LOCKING NUT

3"=1'-0"TYPICAL VENT THRU ROOF

VENT PIPE THRUROOF BY P.C.

SEALANT BY G.C.

ADHESIVE BY G.C.

ROOF INSUL.BY G.C.

FORMED PIPE FLASHINGBY G.C.

BALLASTED SINGLE PLYMEMBRANE ROOFING

ROOF DECK - SEE PLUMB.& MECH. DWGS. FORLOCATION AND NO. OFPENETRATIONS

4"

8"

FLOW

GRADE

VARI

ES

UNDERGROUND PIPING

CAST IRON PIPING1/8 BEND

CONCRETE

CLEANOUT BOX

CLEANOUT PLUG

COVER

STEEL CHANNEL SUPPORTBASE. SHALL MATCH SIZEOF WTR. HTR. DRAIN PAN

ELECTRIC WATER HEATERSEE EQUIPMENT SCHEDULE

3/8" ALL THREAD RODATTACH TO STRUCTURE

EXTEND PAN DRAIN TOTERMINATE 6" ABOVEAN APPROVED WASTERECEPTOR. (EXIST. MOP SINK)

THERMOMETER (TYP)

3/4"HW SUPPLY3/4"CW SUPPLY THERMAL

EXP.TANKEQUAL TOAMTROL ST-5

VACUUM RELIEF VALVE

T&P RELIEF VALVEPIPE FULL SIZE TODRAIN OVER PAN.

GALVANIZED DRAINPAN 2" HIGH MIN.

CORRUGATED STEELDECKING OR PLATETO MATCH THE SIZEOF DRAIN PAN

EWH-1

D

MECH EQUIPMENT

VENT PIPING(BY PLBG. CONTR.)

FULL SIZECONDENSATEDRAIN DOWN INWALL TO WASHERBOX CONNECTIONBY M.C.

REFRIGERANT PIPINGBY M.C.

FLOORWASTE PIPING(BY PLBG. CONTR.)

MOUNT UNIT @4'-0" A.F.F.

PROVIDE SOUIX CHIEF "OX BOX"696-3 W/696-CF DRAINAGEFUNNEL AND COVER MOUNTEDAT 48"AFF. GUY GREY ANDPLASTIC ODDITIES ARE EQUALS

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:57:49 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:57:49 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-202Author Checker

PLUMBING DETAILS

48552Larry P. McWilliams

SCALE: 1/8" = 1'-0"P-202

1 GAS CONNECTION SCHEMATIC

SCALE: 1/8" = 1'-0"P-202

2 GAS PIPING SUPPORT SCHEMATIC

SCALE: 1/8" = 1'-0"P-202

3 GAS SERVICE ENTRANCE

SCALE: 1/8" = 1'-0"P-202

4 GAS SERVICE PRV PIPING SCHEMATIC

SCALE: 1/8" = 1'-0"P-202

5 MOP BASIN AND ACCESSORIES

SCALE: 1/8" = 1'-0"P-202

6 PIPING HANGER SCHEMATIC

SCALE: 1/8" = 1'-0"P-202

7 VENT THRU ROOF DETAIL

SCALE: 1/8" = 1'-0"P-202

8 YARD CLEANOUT DETAIL

SCALE: 1/8" = 1'-0"P-202

9 WATER HEATER DETAIL EWH-1

SCALE: 1/8" = 1'-0"P-202

10 WALL MTD A/C UNIT CONDENSATE DRAIN

Page 11: PLUMBING LEGEND PLUMBING MATERIALS AND …rives.com/wp-content/uploads/2014/10/ALL-11-Total-Plumbing-2-MB.pdfplumbing materials and notes plumbing general notes ... before continuing

6"SD1

6"SD1

6"SD1

6"SD1

6"SD1

5"SD2

5"SD2

4"SD2

5"SD2

AD1

AD1

AD1

AD1

AD1

AD1

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

3"FD2

FCO

FCO FCO

FCO

FCO

FCO

FCO

FCO

FCO

FCO

WCO 3"FD2

FCO

3"VTR

2"VTR6" SD

8" SD

10" SD

8" SD

6" SD

10" SD

10" SD

4" S

2" V

4" S

4" S

4" S

4" S

2" V

4" S

4" S

3" S

4" S

4" S

4" S

4" S 3" S4" S

3" S

3" S4" S

8" SD

6" SD6" SD

4" S

3" S

3" S

3" S8" SD

4" S

4" S

4" S

4" SD

4" S

2" V

4" S

4" S

1 1/2" V2" V

2" V

2" V3" V3" V

3" V

4" S

6" SD

6" SD

3" S

4" S4" S

6" SD

4" SD

4" SD

4" SD

6" SD

6" SD

6" SD

6" SD

3" V

2" V2" V

2" V 2" V1 1/2" V

2" V

2" S4" S4" S

2" S

4" S

4" S

3" S

4" SD

3" S

4" S4" S

4" S

4" S

4" S

1 1/2" V

2" V

3"FD1

HB2

P-6

P-3A

P-2A

P-1

P-1A

P-4

P-6P-1A

P-10

P-3A

P-1A

P-9

P-1A

P-1

P-3P-9

P-3

P-1AP-1P-1P-3P-3

P-3P-3

P-9

P-2A

P-1P-1A

P-4

2"VTR

2" V

2" S

2" S

3"FD2

3"FD23" S

4" S

3" S

1" CW

1" CW2" CW

2 1/2" CW

2 1/2" CW

2 1/2" CW

2" CW

3/4" CW

2" CW3/4" CW

2" CW

1 1/2" CW

2" CW 1 1/2" CW

3/4" HW

1 1/4" CW3/4" CW

2" CW

2" CW

1 1/2" CW

1 1/2" CW 1/2" CW

3/4" CW

1" CWHB2

HB2

HB4

HB3

2 1/2"RPZ

P-6

P-3A

P-2A

P-1

P-1AP-4

P-6

P-1A

P-10

P-3AP-1A

P-9

P-1A

P-1P-3

P-9

P-3

P-1

P-1A

P-1P-1

P-3P-3

P-3 P-3

P-9

P-2AP-1P-1A

HB1

HB1

1/2" CW1/2" HW1 1/2" CW

1" CW1/2" CW1/2" CW

1 1/4" CW1 1/2" CW

1 1/2" CW

3/4" CWP-4

3/4"CW TOMECHANICALUNITS

3/4"CW TOMECHANICALUNITS

3/4" CW

3/4" CW

1

A

B

C

D

E

3 4 5 62

DescriptionDateRev #

Copyright 2014. All rights reserved. Printed or electronic drawings and documentationmay not be reproduced in any form without written permission from ai Design Group, Inc.

PROJECT NO:

Revision Schedule

DRAWN BY: CHECKED BY:

SONIC DEVELOPMENT, LLC

Charlotte, North Carolina

E N G I N E E R I N G I N C

Eng. of Record: License No.:

M VEIGH MANGUMC &1610 East Morehead Street, Suite 100

Charlotte, North Carolina 28207Ph: (704) 547-9035 Fax: (704) 547-9036

email: [email protected]

2/6/2015 11:58:10 AM C:\Users\dsmith\Documents\14567 MB Denver MP Model 2014_dsmith.rvt

2/6/2015 11:58:10 AM

2015-02-06

13554

ISSUED FOR PERMIT

MERCEDES-BENZ OFDENVER

Street: Corner of E. Kentucky Ave. andSouth Colorado Boulevard

Glendale, CO 80246

P-203Author Checker

PLUMBING RISER DIAGRAMS

48552Larry P. McWilliams

SCALE:P-203

1 Sanitary Sewer Riser Diagram

SCALE:P-203

2 Domestic Water Riser Diagram