ComAp Electronic Engines Support 15 ComAp © 2004-2011, ComAp Electronic Engines Support 04-2011.pdf
Recommended wiring
Note 1:Check that CAN bus terminating resistors or appropriate jumpers are connected.
List of supported values, frames and diagnostic messages (ESF) I-CB/CAT Diesel (p.206) I-CB/CAT Gas (p.207)
ADEM + EMCP3.x
ADEM A4 EMCP3.3
Configuration
Controller IG/IS-NT ID-DCU IL-NT ID-Lite IC-NT ID Mobile ECU Type selection in configuration tool
CaterpillarEMCP3 Not supported
ComAp Electronic Engines Support 16 ComAp © 2004-2011, ComAp Electronic Engines Support 04-2011.pdf
Available commands
Controller Command
IG/IS-NTGenConfig
ID-DCU DriveConfig
IL/IL-NTLiteEdit
IC-NTLiteEdit
Speed request Via PWM input on ADEM only See Note 1
Not supported Via PWM input on ADEM only
Start command
Stop command
N/A in ECU
Start/Stop command can be configured as Remote Start/Stop EMPC input. In this case configure used controller output as ECU PwrRelay.
Note 1:PWM rate in the IGS-NT controller has to be set to Sync/Load ctrl: SpdGovPWM rate = 500Hz. PWM signal should be connected to ADEM J1 connector, pin 66. This feature has to be enabled in ECU. Contact your local distributor for check this issue.
Recommended wiring 70-pin AMP connector
on EMCP3 Service connector Controller
34 F CAN1 (Extension modules/J1939) connector - CAN L 50 G CAN1 (Extension modules/J1939) connector - CAN H 42 C CAN1 (Extension modules/J1939) connector - CAN COM 52 - Power +65 - Power - 66 38 (S-SPD) * SGout (PWM) 68 39 (D-SPD) * SGcom (PWM)
valid for EMCP3.1, 3.2, 3.3
* Caterpillar PWM speed contol terminal Note2:Pin layout of the diagnostic connector:
List of supported values, frames and diagnostic messages (ESF) Caterpillar EMCP3 (p.107)