    Daikin Europe N.V.Consulting Sales SupportSales DivisionHelpdesk: http://marketing.daikineurope.com

    CMSQ and VRV quotation tool

    Manual: version 5

  • 8/10/2019 Phn mm VRV Xpress

    2/73

    2

    License Agreement

    The user acknowledges that the obligations and liabilities of Daikin Europe NV inrespect of the Xpress selection software ("the software") are exhaustively definedin this Agreement.The user is responsible for the consequences of any use of the software andDaikin Europe NV hereby expressly excludes any liability for defects and anywarranty, condition, term, undertaking or representation of any kind, express orimplied, statutory or otherwise, relating to the software provided under thisAgreement including (without limitation) any warranty as to the condition, quality,performance, merchantability or fitness for purpose thereof.Daikin Europe NV will not be liable to the user or any third party for any direct,indirect or consequential loss, damage, cost or expense of any kind whatsoever

    and however caused whether arising under contract, tort (including negligence) orotherwise, including (without limitation) the entire cost of service or repair, loss ofor corruption to data, loss of profits or of contracts, loss of operation time and lossof goodwill or anticipated savings, even if Daikin Europe NV has been advised oftheir possibility.Good data processing procedure dictates that any software programme bethoroughly tested with non-critical data before relying on it. The user mustassume the entire risk of using the software.

  • 8/10/2019 Phn mm VRV Xpress

    3/73

    3

    Contents

    1. Introduction - 5 -1-1. Purpose of Xpress - 5 -1-2. Limitations on Selection - 5 -

    2. Items Required for Selection - 6 -2-1. System Outline - 6 -2-2. Design Condition - 6 -

    3. VRV Selection Procedure - 7 -

    4. Setting of Software and Project - 8 -4-1. Installation of Program - 8 -4-2. Starting up Xpress - 8 -4-3. Tool Bar - 9 -4-4. Input Project Outline - 10 -4-5.Select Refrigerant Type - 10 -4-6. Preferences - 11 -

    5. Indoor Unit Selection - 14 -

    5-1. [Indoor Units] Tab Page - 14 -5-2. Indoor Unit Selection - 15 -5-3. Select Options for Indoor Unit - 18 -5-4. Edit the Existing Indoor Units - 19 -5-5. Edit Multiple Indoor Units Simultaneously - 19 -5-6. Delete Indoor Units - 20 -5-7. Change the Order of Indoor Units - 20 -5-8. Import and export Indoor Units to .csv - 20 -5-9. Add other devices - 25 -

    6. Outdoor Unit Selection - 29 -6-1. [Outdoor Units] Tab Page - 29 -6-2. Add Outdoor Units - 30 -6-3. Edit Outdoor Unit - 31 -6-4. Connect Indoor Units to Outdoor Units - 33 -6-5. Select Options for Outdoor Unit - 36 -6-6. Edit Existing Outdoor Units, Indoor Units, and BS-Boxes - 36 -6-7. Delete Units - 36 -6-8. Change the Order of Outdoor Units - 37 -6-9. Change the Order of Indoor Units - 37 -6-10. Delete units - 39 -

    License Agreement - 2 -

    Contents - 3 -

  • 8/10/2019 Phn mm VRV Xpress

    4/73

    4

    7. Piping Diagram - 40 -7-1. [Piping] Tab Page - 40 -7-2. How to Edit the Piping Diagram - 42 -

    7-3. Edit Piping Diagram : Example - 47 -7-4. Printing large piping diagrams - 52 -

    8. Wiring Diagram - 54 -8-1. [Wiring] Tab Page - 54 -8-2. How to Edit the Wiring Diagram - 55 -

    9. Centralized Controller - 56 -9-1. [Centralized Controller] Tab Page - 56 -9-2. How to select the Centralized Controllers - 57 -

    10. Reports - 58 -10-1. [Reports] Tab Page - 58 -10-2. Set Up the Reports - 59 -

    11. Example - 62 -11-1. Outline of Project - 62 -11-2. Indoor Units Selection - 63 -11-3. Outdoor Units Selection - 64 -11-4. Piping Diagram - 66 -11-5. Wiring Diagram - 71 -11-6. Centralized Control - 72 -11-7. Report - 73 -

  • 8/10/2019 Phn mm VRV Xpress

    5/73

    5

    1. Introduction

    Xpress has some limitations on selection.

    1-1. Purpose of Xpress

    1-2. Limitations on Selection

    Xpress is a selection software for VRV and CMSQ systems.Xpress helps your quick selection for quotation with easy operation.

    1) The capacity correction factors corresponding to height difference betweenoutdoor unit and indoor unit are simplified. They are used depending on therelative position of the outdoor units such as Higher, Same level, orLower.

    2) Though you can input the exact height of the outdoor units, the value is usedonly for checking the limitation of the height difference.

    3) Capacities are not completely equal to Engineering Databook.The Xpress uses an approximation formula made from the capacity table tocalculate capacity. Differences should be less than 1%.

    4) Design temperature can be inputted outside the scope of the capacity tablerange. Data input only has a range check. The actual check of thetemperature to be within the capacity table range is done during the selection.Values outside this capacity table range result in an error message on theoutdoor unit.

    5) The number of the control groups is not considered.The number of control groups are limited by the number of controllers or less.

    6) The sensible capacity is calculated from the actual total capacity, the bypassfactor and the fan airflow at high speed. Therefore, this calculated capacitymay differ slightly from the sensible capacity value of the databook.

    7) The order of indoor units is determined by the piping layout. Therefore, thewiring diagram does not always correspond to the field (actual) diagram.However, they can be set equal by moving indoor units up and down in thetree view.

    8) The order of outdoor units does not affect piping and wiring diagrams.If you change the order of outdoor units, the order will be changed on thereport file.

    9) Some options are not displayed on the [Piping] tab and the [Wiring] tab.

    10) We strongly advise to use the function Enter individual piping lengthsmanually instead of relying on the automated piping length calculation byfilling out the Equivalent piping length and First branch to indoor units.The automated calculation may result in a rough estimation. Therefore, thecorrection of the capacity of the indoor units and the size up of the pipingdiameters may not be accurate. Also, in this case there is no calculation ofthe additional refrigerant charge.

  • 8/10/2019 Phn mm VRV Xpress

    6/73

    6

    2. Items Required for Selection2-1. System Outline

    1) Specified Indoor Model Family (Type)2) Room Load (Required Capacity)

    [Cooling] Total Heat Capacity for each Indoor Unit[Cooling] Sensible Heat Capacity for each Indoor Unit[Heating] Capacity for each Indoor Unit (for H/P or H/R)- Indoor unit will be selected to satisfy all loads chosen

    2-2. Design Condition2-2-1. Common

    2-2-2. for Automatic Selection

    2-2-3. for Manual Selection1) Specified Model Name for each Indoor Unit

    1) Refrigerant TypeR410A (depends on models included in Xpress)

    2) Series (depends on models included in Xpress)VRV III P Compact, VRV III P High Cop, VRV III P R410AVRV III RXYSQ-PA7V1, VRV III RXYSQ-PA7Y1VAM-FA7VE, VKM-GAV1

    3) Family (depends on models included in Xpress)Heat pump, Heat Recovery, Cooling Only

    4) Project InformationProject Name, Reference Number, Client name

    1) Design Temperaturefor Cooling [Outdoor]: Dry Bulb Temperaturefor Cooling [Indoor]: 2 conditions in Dry Bulb Temperature

    - Wet Bulb Temperature- Relative Humidity

    for Heating [Outdoor]: Dry Bulb Temperaturefor Heating [Indoor]: Dry Bulb Temperature

    2) Piping Length-Individual piping length

    OR-Equivalent piping length between outdoor unit and the farthest indoor unit and a

    piping length from first branch to indoor unit.

    3) Combination RatioTarget of combination ratio

    (total index of outdoor units divided by index of outdoor unit.)

  • 8/10/2019 Phn mm VRV Xpress

    7/73

    7

    3. VRV Selection Procedure

    SelectIndoor Units

    DefinePiping Diagram

    InputProject Outline

    Connect IndoorUnits and BS-

    boxes to OutdoorUnit(s)

    SelectCentralized Controller

    Output Report

    Start

    Finish

    - Project Outline- Refrigerant Type

    (1) Automatic Selection- Indoor Type (Family)

    - Required Capacity- Indoor Design Condition

    (2) Manual Selection- Indoor Unit (Model)- Indoor Design Condition

    Define the Combination- Outdoor Type (Series, Family)- Combination %- Outdoor Design Condition- Piping Length (Equivalent)- Height Difference (Relative Position)

    - RTF format- CSV format- DXF format

    -for REFNET Selection- for Piping Diameter(- define individual piping length)

    Define

    Wiring Diagram

    - for Control Grouping

    The selection procedure of Xpress is the same as described in the EngineeringDatabook.The flow of the selection in Xpress is shown below.

    See Chapter 4

    See Chapter 5

    See Chapter 6

    See Chapter 7

    See Chapter 8

    See Chapter 9

    See Chapter 10

    - for Centralized Controller Selection

  • 8/10/2019 Phn mm VRV Xpress

    8/73

    8

    4-2. Starting up Xpress

    Double-click Xpress.exe or shortcut to start Xpress .Then, the main window and [Indoor Units] tab page appears.

    Note:The first time Xpress is executed, a license window will pop-up.

    Read the [License Agreement] and click the [OK] button to close the window.

    4-1. Installation of Program

    Xpress is an independent executable file (.exe) that you dont need to install.Place the Xpress.exe file anywhere you want on your personal computer.

    4. Setting of Software and Project

  • 8/10/2019 Phn mm VRV Xpress

    9/73

    9

    4-3. Tool Bar

    (1) (2) (3) (4) (5) (6) (7)

    Use tool bar to handle files and to set up program in the same way as standardWindows software.

    Add / Edit / Delete indoor units or ventilation devicesCommand Buttons(8)

    Import or export the list of indoor units to .csv formatImport/Export to .csv(9)

    Click ( ) to display the meaning of abbreviations.Help(7)

    Select the type of outdoor unit groupOutdoor unit group(5)

    You can go to the different tabs by clicking on it.: accessible: inaccessible (some data still missing in previous tabs)

    Tabs(2)

    Command buttons to handle files and to set up programs.Tool Bar(1)

    Enter information of project.Project Outline(3)

    Displays description of the indoor units.Indoor Units ListWindow(6)

    (4) Select the type of refrigerant.Refrigerant

    Import a project. There are 2 possibilities:1) When importing an Xpress project file, the project that is

    currently open will merge with the imported project.2) When importing a VRV Water-Cooled Xpress project file,

    the program will automatically convert each water-cooledoutdoor unit into an air-cooled outdoor unit.

    Import Project(3)

    (7)

    (6)

    (5)

    (4)

    (2)

    (1)

    Displays expiry date, software & database version number andlicense of software.About

    Define the units (display only), combination of design conditionand other settings.Preferences

    Exit Xpress.Exit

    Save the project.After [Save as] window pops up, input filename and save theproject file.

    Save Project

    Open a saved project.[Open file] window pops-up, then select the project file (*.vrv)Open Project

    Create a new projectNew Project

  • 8/10/2019 Phn mm VRV Xpress

    10/73

    10

    Select the refrigerant type fromdrop-down list.

    You cannot select the refrigeranttype when the software includesonly one refrigerant.

    4-5. Select Refrigerant Type

    4-4. Input Project Outline

    Input project outline in the text boxes.

    In order to save a project and to create a report, you need to fill in all text boxes

    except for (4) (*Optional).

    Revision

    Client name

    Reference

    Project name

    Input revision information. *Optional

    Input clients name.

    Input project number or reference number to facilitate job history.

    Input project name.

    (4)

    (3)

    (2)

    (1)

    (1)

    (2)

    (3)

    (4)

  • 8/10/2019 Phn mm VRV Xpress

    11/73

    11

    [Data Input] Tab PageYou can define the prefixesfor the name of the devicesat the [Naming] tab page.

    4-6. Preferences

    [Units] Tab Page

    You can select which unit isused for the display oftemperature, capacity, airflow,weight, length, dimensionsand piping.(e.g. m or ft for Length)

    You can also select the indoorconditions: DBT/RH,DBT/WBT or WBT/RH.

    When you click on [Preferences] ( ), the [Preference] window opens.

    [Diagrams] Tab Page

    You can define line styles fordiagrams at the [Diagrams]tab page.

  • 8/10/2019 Phn mm VRV Xpress

    12/73

    12

    [Advanced] Tab Page

    On this tab, you can setthe tolerance. The

    tolerance is thepercentage that theavailable capacity of anindoor unit is allowed todiffer from the requiredcapacity.

    You can also indicatethat indoor units can beused for technicalcooling.

    [Outdoor Models] TabPage

    On this tab, you canselect outdoor units thatare not allowed to beselected in Xpress.

    Click the outdoor unitmodel name and clickthe arrow to move theunit from the groupAllowed to the groupNot allowed.

  • 8/10/2019 Phn mm VRV Xpress

    13/73

    13

    [Prices] Tab Page

    You can import a price file.A price file can be createdwith the Price Editor.To learn more about thisprogram, please contactus through the helpdesk:http//marketing.daikineurope.com.

    [Reports] Tab Page

    Possible options:

    Show diversifiedcapacity results

    Show required capacity

    Show COP and EER

    Show the dischargetemperature

    Report headers andfooters: you can add yourcompany logo or contactinformation to the

    headers and footers ofthe report

    Paths:

    You can choose wherethe project and its reportwill be saved. Thesepaths are suggestedwhen you want to savesomething, but can be

    changed to another path.

  • 8/10/2019 Phn mm VRV Xpress

    14/73

    14

    5. Indoor Unit Selection5-1. [Indoor Units] Tab Page

    Use these buttons to import the list of indoor units froma .csv file, or to export the list of indoor units to a .csv file

    Import/Exportindoor unitsto .csv

    (5)

    *Common to all pages and windows.Instruction about current tab page is displayed.Instruction(2)

    Click ( ) to display the meaning of abbreviations.Help(3)

    InformationDisplay

    CommandButtons

    Indoor UnitsList

    * Common to all pages and windows.Information and caution on the selected item is displayed.The background color changes to red when a caution isdisplayed.

    Add indoor units or ventilation devices. Edit / Delete theselected units.

    All indoor units are listed. Click to select a unit. You canalso use the [Ctrl] and [Shift] keys to select multiple units.

    (6)

    (4)

    (1)

  • 8/10/2019 Phn mm VRV Xpress

    15/73

    15

    5-2. Indoor Unit Selection

    [Add indoor units] button

    If you need to know the meaning of the abbreviations, click on the ( ).

    [Abbreviations] window

    [Edit Indoor Unit Selection] window

  • 8/10/2019 Phn mm VRV Xpress

    16/73

    16

    5-2-1. Automatic Selection

    The combination of indoor designconditions will depend on yourpreference settings (see 4-6).The temperatures should be choseninside the scope of the capacity table.

    Xpress automatically selects the indoor unit that satisfies the required cooling /heating capacity.

    (1)

    (2)

    (3)

    (4)

    (7)

    (5) (6)

    If sensible heat capacity or heating capacity is not required, put zero.Xpress selects the indoor unit that satisfies all required capacities.

    [Edit Indoor Unit Selection] window

    1) Uncheck the [Manual Selection]check box

    2) A name and/or room (optional) canbe assigned to the indoor unit.When multiple indoor units areassigned to the same room,Xpress will select the indoor unitsin a way that the sum of the indoorunits covers the required

    capacities.3) Select the family (type) of the

    indoor unit from the drop-down list.

    4) Input design criteria (condition) andrequired capacities (loads).

    5) Click the [Add] button after all conditions have been filled in.A new indoor unit is added to the indoor unit list on the [Indoor Units] tab.Repeat the procedures (1) through (5) until all indoor units are added.

    6) Click the [Close] button to finish the indoor unit selection.The [Edit Indoor Unit Selection] window is closed, and the [Indoor unit] tab

    page appears again.

    Note:

    [Select Options] button (7) is unavailable because an indoor unit has notbeen determined yet. After connecting to the outdoor unit, the indoor unit isdetermined and the button will be available.

    Note:Technical cooling is only available for the Heat Recovery Range.

    When the "technical cooling" function is activated, the system can cool a roomwith an operation range starting at -20 C (instead of the default -5 C). Atypical application is the cooling of a server room. The only slightlydisadvantageous consequence is that the noise of the BS-box is a bit louderwhen technical cooling is activated.

  • 8/10/2019 Phn mm VRV Xpress

    17/73

    17

    5-2-2. Manual Selection

    (6)

    (1)

    (2)

    (3)

    (4)

    (5)

    You select the indoor units manually. Xpress will check the capacity, the pipingrules and the connection with the outdoor unit and will select the refnet headers

    and joints.

    The combination of indoor design conditions will depend on your preferencesetting (see 4-6.).The temperatures should be chosen inside the scope of the capacity table.

    [Edit Indoor Unit Selection] window

    (7) (8)

    1) Check the [Manual Selection]check box.

    2) A name and/or room (optional)can be assigned to the indoorunit.

    3) Select the family (type) of theindoor unit from the drop-downlist.

    4) Select the model of the indoorunit (FCU) from the drop-downlist.

    5) Click [Select Options] to selectoptions for the indoor unit. Seesection 5-3 for details.

    6) Input design criteria.

    7) Click the [Add] button after all conditions have been submitted.A new indoor unit is added to the indoor unit list on the [Indoor Units] tab.Repeat the procedure (1) through (6) until all indoor units are added.

    8) Click the [Close] button to finish the indoor unit selection.The [Edit Indoor Unit Selection] window is closed, and the [Indoor unit] tabpage appears again.

    Note :Indoor unit icons in the Indoor

    unit list depend on selectionmethod.

    : Automatic Selection: Manual Selection

    The items displayed on the list

    window also depend onselection method.

  • 8/10/2019 Phn mm VRV Xpress

    18/73

    18

    5-3. Select Options for Indoor Unit

    (1)

    After clicking the [Select Options] buttonon the [Edit Indoor Unit Selection] screen,the [Used Options] screen pops up.

    The [Allowed options] window showsoptions that can be selected for the indoorunit.The [Selected options] window showsoptions that are selected.

    Normally, remote controller and optionswith extension (STD) are listed by default.

    (2)Standard Option

    1) Add an OptionWhen the option on the [Allowed options] windows is selected, the [Select] buttonbecomes available.Click the [Select] button and the option is moved to [Selected options].

    2) Remove an OptionWhen the option on the [Selectedoptions] window is selected, then the[Remove] button becomes available.Click the [Remove] button and theoption is moved to the [Allowed options]window.

    Note:Options with extension (STD) cannot be

    removed because they are standard options;necessary for that indoor unit (e.g.decoration panel for FXCQ)

  • 8/10/2019 Phn mm VRV Xpress

    19/73

    19

    5-4. Edit the Existing Indoor Units

    When an indoor unit is selected, the [Edit the selected device] button ( )becomes available. And if the button is clicked, the [Edit Indoor Unit

    Selection] window pops up. (This window also appears by double-clickingthe unit in the list.)You can now edit the conditions as described in section 5-2.

    5-5. Edit Multiple Indoor Units Simultaneously

    In order to edit multiple indoor unitssimultaneously, select multiple indoorunits in the indoor unit list with the [Ctrl] or[Shift] key and click the [Edit the selecteddevice] button ( ).Then the [Edit Indoor Unit Selection]

    window pops up.

    Edit the inputted conditions for all selectedunits simultaneously as described insection 5-2.

    Note:When the value is indicated in brown,

    the values are not same for all selectedunits. Change the value carefully.

  • 8/10/2019 Phn mm VRV Xpress

    20/73

    20

    5-6. Delete Indoor Units

    When indoor units on the indoor unit list are selected, the [Delete theselected device] button ( ) becomes available. Click the button to delete

    the selected units.

    To change the order of the indoor units, drag and drop units on theindoor units list window. For example, to insert Unit 1 before Unit 2,drop Unit 1 on Unit 2.The change of the indoor units order on the [Indoor Units] tab doesntchange the indoor units order on the other tab pages.

    5-7. Change the Order of the Indoor Units

    Note:You cannot move the unit to the last

    position directly.To move the unit 1 to the last position,first drop the unit 1 on the last unit.

    Then move up the last unit on the unit 1.

    Unit 1

    Unit 1

    Unit 1

    5-8. Import and Export Indoor Units to .csv

    Using the import ( ) and export ( ) button at the bottom right of the

    Indoor Units tab, you can import Indoor Units from a .csv file, and exportIndoor Units to a .csv file.

    5-8-1. Export Indoor Units to a .csv filePlease proceed as follows to export the Indoor Units:- Select all the indoor units that you want to export in the Indoor Units tabwith the Edit Indoor Unit Selection screen, as explained in chapter 5-2.- When you have finished adding indoor units, go to the next tab andconnect them to an outdoor unit. Now all indoor units have a model selected.- To export the units, go back to the Indoor Units tab and click the ExportIndoor Units button and save the .csv-file.

  • 8/10/2019 Phn mm VRV Xpress

    21/73

  • 8/10/2019 Phn mm VRV Xpress

    22/73

  • 8/10/2019 Phn mm VRV Xpress

    23/73

    23

    Column E Cooling DBT: Enter the design temperature for cooling in CDBTRestriction: the design temperature should be within the operation range ofthe unit

    Column F Cooling WBT: Enter the design temperature for cooling in C

    WBTRestriction: the design temperature should be within the operation range ofthe unit

    Column G Heating T: Enter the design temperature for heating in C DBTRestriction: the design temperature should be within the operation range ofthe unit

    Column H Tot Cool Cap: Enter the required total cooling capacity for theindoor unit in kW

    Column I Sens Cool Cap: Enter the required sensible cooling capacity forthe indoor unit in kW

    Column J Heat Cap: Enter the required heating capacity for the indoor unitin kW

    M Manual selection Column D Family or Model: enter the model name of the unit

    E.g.: FXSQ50P7VEB Column E Cooling DBT: Enter the design temperature for cooling in C

    DBTRestriction: the design temperature should be within the operation range ofthe unit

    Column F Cooling WBT: Enter the design temperature for cooling in CWBTRestriction: the design temperature should be within the operation range ofthe unit

    Column G Heating T: Enter the design temperature for heating in C DBTRestriction: the design temperature should be within the operation range ofthe unit

    - If all indoor units are entered, save the .csv-file again and close Excel. It is veryimportant to close the file before you start importing the indoor units, if not

    there will be errors.

  • 8/10/2019 Phn mm VRV Xpress

    24/73

  • 8/10/2019 Phn mm VRV Xpress

    25/73

    25

    5-9. Add other devices

    [Add other devices] button

    If you need to know the meaning of the abbreviations, click on the ( ).

    [Abbreviations] window

  • 8/10/2019 Phn mm VRV Xpress

    26/73

    26

    5-9-1. Add VAM

    (1)

    (2)

    (3)

    (4) (5)

    5-9-2. Add Fresh air treatment unit

    1) A name can be assigned to theVAM unit

    2) Select the Model (type) of theVAM unit from the drop-down list

    3) Click [Select Options] to selectoptions for the VAM unit.See section 5-3 for details.

    4) Click the [Add] button.A new VAM is added to the liston the [Indoor Units] tab.Repeat the procedures (1)through (4) until all VAM unitsare added.

    5) Click the [Close] button to finishthe VAM unit selection.

    1) A name and/or room (optional)can be assigned to the fresh airunit.

    2) Select the Model (type) of freshair unit from the drop-down list.

    3) Click [Select Options] to selectoptions for the fresh air unit.See section 5-3 for details.

    4) Select the model of indoor unit(FCU) from the drop-down list.

    5) Click the [Add] button.A new fresh air unit is added tothe list on the [Indoor Units]tab.Repeat the procedures (1) to(5) until all fresh air units areadded.

    6) Click on the [Close] button tofinish the fresh air unitselection.

    (5) (6)

    (1)

    (3)

    (2)(4)

  • 8/10/2019 Phn mm VRV Xpress

    27/73

    27

    5-9-3. Add VKM

    (6) (7)

    (1)

    (2)

    (3)

    (4)

    (5)

    1) A name and/or room (optional) canbe assigned to the VKM unit

    2) Select the family (type) of the VKMunit from drop-down list.

    3) Select the model of the indoor unit(FCU) from the drop-down list.

    4) Click [Select Options] to selectoptions for the VKM unit.See section 5-3 for details.

    5) Input design criteria. Thecombination of indoor designconditions will depend on yourpreference setting (see 4-6.).The temperatures should bechosen inside the scope of thecapacity table.

    6) Click [Add] button after allconditions have been filled in.A new VKM is added to the list onthe [Indoor Units] tab.Repeat the procedures (1) through(6) until all indoor units are added.

    7) Click the [Close] button to finish the VKM unit selection

    5-9-4. Add Air handling unit connection box

    1) A name and/or room (optional)can be assigned to the AHUconnection box

    2) Select the family (type) of theAHU connection box from drop-down list.

    3) Select the model of the AHUconnection box from the drop-down list.

    4) Click [Select Options] to selectoptions for the AHU Connection

    Box. See section 5-3 for details.

  • 8/10/2019 Phn mm VRV Xpress

    28/73

    28

    5-9-5. Add Biddle air curtain

    1) A name and/or room (optional)can be assigned to the Biddle air

    curtain2) Select the family (type) of the

    Biddle air curtain from the drop-down list.

    3) Select the door width of the doorwhere you want to install theBiddle air curtain

    4) Select the door height

    5) Select the color of the Biddle aircurtain

    6) The model is then selectedautomatically

    7) Click [Select Options] to selectoptions for the Biddle air curtain.See section 5-3 for details.

  • 8/10/2019 Phn mm VRV Xpress

    29/73

    29

    6-1. [Outdoor Units] Tab Page6. Outdoor Unit Selection

    After indoor units are created, you can

    move to the [Outdoor Units] tab page.

    When the [Outdoor Units] tab is clicked,the [Outdoor Units] tab page appears.

    (1)

    (2)

    (3)

    (4)

    Click to Add / Edit / Duplicate / Delete the selected unit (Outdoor,Indoor or BS-Box)Command Buttons(2)

    Click unit (Outdoor, Indoor or BS-Box) to display specificationof that unit.

    Specification ofSelected Unit(3)

    List of indoor units that have not been connected to the outdoorunit yet

    Indoor units not yetattached(4)

    This window lists all selected systems.To expand / shrink the system tree, click + /- icon at the left sideof the unit (same as Windows explorer).

    Systems ListWindow(1)

  • 8/10/2019 Phn mm VRV Xpress

    30/73

    30

    6-2. Add Outdoor Units

    When the [Add an outdoorunit] button ( ) on [OutdoorUnits] tab page is clicked, the[Edit Outdoor Unit Selection]window pops up.Xpress selects the outdoor unitautomatically based on theconditions and the connectedindoor units.

  • 8/10/2019 Phn mm VRV Xpress

    31/73

    31

    6-3. Edit Outdoor Unit

    (1)

    (2)(3)(4)

    (5)

    (8)

    (7)

    1) Input name of the outdoor unitin the text boxex. 2nd floor, East area

    2) Select the VRV series from thedrop-down list. The drop-downlist varies depending on themodels the software includes.

    3) Select the outdoor unit family(type) from the drop-down list.The family (heat pump, heatrecovery or cooling only)

    depends on the models thesoftware includes.

    The icon of the outdoor unit changesdepending on the selected family (type).

    : Heat Pump (Red)

    : Heat Recovery (Blue and Red)

    : Cooling Only (Blue)

    4) Select the combination ratio between indoor units and outdoor unit from thedrop-down list.Xpress selects the outdoor unit so that the combination ratio is equal or lessthan the selected value.

    5) Input the outdoor design temperature (dry bulb) for cooling and heating. Thetemperatures should be chosen inside the scope of the capacity table.

    6) Choose how to define the piping length:If you want to calculate the additional refrigerant to be charged and a thoroughcheck on the pipe rules, click the [Enter individual piping length manually]check box, and then you can input the individual piping lengths manually onthe [Piping] tab.

    (See section 7-2-2)If you dont want to calculate the additional refrigerant to be charged, uncheck

    the box and input the equivalent piping length and the piping length from firstbranch to indoor units.*Equivalent piping length: the piping length between outdoor unit and thefarthest indoor unit. It is used to correct capacities of the indoor units.*First branch to indoor units: the piping length between first branch to thefarthest indoor unit

    (6)

  • 8/10/2019 Phn mm VRV Xpress

    32/73

    32

    7) Select the position of the outdoor units relative to the indoor units.When choosing Higher or Lower, you can enter the difference in heightmanually.

    8) Click [Select Options] to select options for the outdoor units.(See section 6-5 for details)

  • 8/10/2019 Phn mm VRV Xpress

    33/73

    33

    6-4. Connect Indoor Units to Outdoor Units

    (1)

    (2)

    2) Choose connections of header fromdrop-down list, then click the headerbutton ( ) to insert a header.Now connect indoor units to the headeras described in procedure (1).

    1) Drag indoor units from the [Available

    indoor units] window to the outdoor unitof your choice in the [Outdoor unit]window.

    To disconnect an indoor unit with anoutdoor unit; drag the indoor unit fromthe [Outdoor unit] window back to the[Available indoor units] window.

    Repeat the procedure (1) until you haveconnected all relevant indoor units tothe outdoor unit.

    Note:Xpress uses REFNET joints for piping by

    default.

    If you want to use REFNET headers, go toprocedure (2), otherwise go to procedure(3).

    Note:Each REFNET header has a limitednumber of connections. If you try to connectmore indoors units than there areconnections, an error window will pop-up.

    6-4-1. Heat Pump and Cooling Only

  • 8/10/2019 Phn mm VRV Xpress

    34/73

    34

    (3) The model name of selectedoutdoor unit and the combinationratio are displayed on the right sideof the outdoor unit icon.

    (3)

    Note:If a cross icon ( ) is displayed on the

    left side of the outdoor unit icon, thesystem has not been defined properly yet.To find out what the problem is, click onthe unit and an explanation bar will bedisplayed at the bottom of the window.

    After the system is defined and conditionsare determined, click the [OK] button. Ifyou want to cancel, click on the [Cancel]button.

    The [Edit Outdoor Unit Selection] windowwill now close and the [Outdoor Units] tabpage appears.

  • 8/10/2019 Phn mm VRV Xpress

    35/73

    35

    Note:When indoor units are connected directly to the outdoor unit, they can only

    operate in cooling only mode.In this case, the caution icon ( ) will be displayed at the left side of the indoorunit icons and a caution message will be displayed at the bottom of the window.

    Indoor units cannot be connected toheat recovery model outdoor unitsdirectly (except for cooling only mode).For heat recovery operation, a BS-boxis necessary.

    The [Add BS] button ( ) becomesavailable when Heat Recovery familyis selected.Click the [Add BS] button to add a BS-Box to the outdoor unit.

    Next, connect indoor units to the BS-box as described in section 6-4-1.

    6-4-2. Heat Recovery

  • 8/10/2019 Phn mm VRV Xpress

    36/73

    36

    6-5. Select Options for Outdoor Unit

    When the [Select Options] button on the[Edit Indoor Unit Selection] is clicked, the[Used Options] window pops up.

    Add or remove options with the samemethod described in section 5-3 forindoor units.

    6-6. Edit Existing Outdoor Units, Indoor Units and BS-Boxes

    Select a unit (outdoor, indoor or BS-box) in the system list window andclick the [Edit the selected device]button ( ) on the [Outdoor Units]tab page, to edit existing units.

    Then the [Edit Outdoor (Indoor, BS-Box) Unit Selection] window pops up.You can edit the given condition and

    options for each unit.

    To edit each unit, refer to section6-3 (outdoor units)5-2, 5-3 (indoor units)and 6-7 (BS-box)

    6-7. Edit BS-Box Selection

    (1)

    (2)

    1) Change the name of the BS-box (optional)

    2) When the [Select Options]button on the [Edit BS-BoxSelection] is clicked, the [UsedOptions] window pops up.

    Add or remove options withthe same method described in

    section 5-3 for indoor units.

  • 8/10/2019 Phn mm VRV Xpress

    37/73

    37

    6-8. Change the Order of Outdoor Units

    To change the order of outdoor units,drag and drop outdoor units in thesystem list window.

    If you drag the outdoor unit onto anotherunit, it will be inserted before the otherunit.

    To insert the [Out Hall1] before [OutRoom2], drop [Out Hall1] onto [OutRoom2].

    To move to the last position, it takes 2steps.

    First move the outdoor unit that you wantto move to the last position onto the lastoutdoor unit.Then move up the last outdoor unit.

    Note:This change is only applied in the

    [Outdoor Units] tab page.The outdoor units order in other tabpages dont change unless you deleteone.

    6-9. Change the Order of Indoor Units

    The order of indoor units is very important for the piping layout.Define the order in consideration of the actual indoor units grouping and pipinglayout.

    To define the order, recommended basic rules are:

    - Create indoor units groups (e.g. units for each room)- Change the order of groups based on the distance from the outdoor unit

    (from the farthest group to the nearest group)- Organize the indoor units in the group, by number (name)

  • 8/10/2019 Phn mm VRV Xpress

    38/73

    38

    In the case of the next figure, recommended order is :

    See section 7-3 for reference.

    To change the order of the indoorunits, drag and drop indoor units inthe system list window.

    To insert Unit 1 before Unit 2, drop

    Unit 1 onto Unit 2.To move to the last position, dropthe indoor unit onto the outdoor unit.

    Changing the order of indoor unitswill affect the [piping] and [wiring]diagrams.

    Note:Changing the order in the

    [Outdoor Units] tab page has norelation with the order of indoorunits on the [Indoor Units] tab page.The order should be definedaccording to actual layout.

    3-1 3-2 2-1 2-2 2-3 1-1 1-2 1-3

    1-1 1-2 1-3 2-1 2-2 2-3 3-1 3-2

    farthest group nearest group

  • 8/10/2019 Phn mm VRV Xpress

    39/73

    39

    6-10. Delete Units

    Select a unit (outdoor, indoor or BS-box) on the system list window, then clickthe [Delete the selected device] button ( ) on the [Outdoor Units] tab page, todelete the unit.

    - Delete outdoor unit The connected indoor units are moved to [Indoorunits not yet attached]; BS-boxes and headers areremoved.

    - Delete BS-box or header The connected indoor units are moved to[Indoor units not yet attached].

    - Delete indoor units The indoor units are deleted from the indoor units listof the project.

  • 8/10/2019 Phn mm VRV Xpress

    40/73

    40

    7. Piping Diagram

    After systems are determined in the [Outdoor Units] tab page, you can move to the

    [Piping] tab page. When the [Piping] tab is clicked, the [Piping] tab page appears.Edit the piping diagram so Xpress can select the REFNET joints and headers, anddefine the piping diameters.

    7-1. [Piping] Tab Page

    (2)

    (9)

    (4)

    (6)(8)

    (7)

    (10)

    (5)(1)

    (3)

    Click here to hide /open the [SystemsTree] window.

    Note:

    You can hide the [Systems Tree] Window, by clicking on the small arrow next to it.

    (11)

  • 8/10/2019 Phn mm VRV Xpress

    41/73

    41

    Information and caution are displayed about selected item.Information display(10)

    [Piping not yet complete] tabIndicates if the piping diagram contains any error.

    [Calculation details tab]Indicates additional information about the selection of the

    REFNET, BS-boxes, indoor and outdoor units.

    Explanation area(11)

    Check to be able to enter the piping lengths manually.[Manual PipingLength] check box(3)

    Click to show quick instruction of how to edit piping diagram.[Example] button(7)

    Reverse the last action (ctrl+z) and redo the last undo (ctrl+y)[Undo & Redo] button(5)

    Adapts the size of the piping diagram to the window.[Fit window] button(8)

    The piping diagram is drawn in this area for the selectedoutdoor unit. You can edit the diagram by double-clickingindoor units with mouse (or pointing device).

    Piping layout area(9)

    Click to reset (initialize) the piping diagram. The program showsa pop-up to ask if you are sure you want to reset to the originallay-out. Click [Yes] to reset the piping diagram, click [No] toreturn to the piping diagram without resetting it.

    [Reset] button(4)

    Select the outdoor unit to edit the piping diagram.Outdoor units list box(2)

    This window lists all selected systems.To expand / shrink the system tree, click + /- icon at the left sideof the unit (same as Windows explorer).

    Systems TreeWindow(1)

    (6) Check it to change the direction of the diagram.[Vertical] check box

    Note:[Calculation details] tabappears by right-mouse clickingon the device and selectingExplain Selection

  • 8/10/2019 Phn mm VRV Xpress

    42/73

  • 8/10/2019 Phn mm VRV Xpress

    43/73

    43

    Drag

    and

    Drop

  • 8/10/2019 Phn mm VRV Xpress

    44/73

    44

    7-2-2. Edit the Piping Diagram with REFNET header

    You can edit the piping diagram by drag-and-drop.REFNET joints and headers are selected automatically and properly for the current

    piping diagram.

    drag-and-drop

    Note:You can also edit the piping

    diagram by changing the order ofthe indoor units in the extractable[Systems Tree] Window.(as described in section 6-8)

  • 8/10/2019 Phn mm VRV Xpress

    45/73

    45

    Drag

    and

    Drop

  • 8/10/2019 Phn mm VRV Xpress

    46/73

    46

    7-2-2. Edit the Piping Length

    When checking the [Manual Piping Length] check box, you can enter the pipinglengths manually. In case you have checked this box in the Edit Outdoor Unit

    Selection window, this box is already checked.

    All pipes will be red, until a piping length has been entered, after which theyll becomeblue. When all piping lengths have been entered, the Piping not yet complete-message will disappear.

    This can be done in multiple ways:

    - Double click on a pipe - Right-click on a pipe andselect Enter Pipe Length

    After double clicking or right-clicking the pipe, the [EnterPiping Length] screen pops up.

    1) Enter the length of the pipe.

    2) Enter the number of bends

    Result:

  • 8/10/2019 Phn mm VRV Xpress

    47/73

    47

    1-1 1-2 1-3

    2-1 2-2 2-3

    7-3. Edit Piping Diagram : Example

    (1) Clarify an image of the piping diagram for the selection of REFNET.It is not necessarily the same as an actual piping layout.

    It is for the selection of REFNET joint.

    (2) Change the order of indoorunits as described in section 6-8on the [Outdoor Units] tab page.

    (2)

    1-1 1-2 1-3 2-1 2-2 2-3 3-1 3-2

    A B

    C D E F G

    A B

    C D

    F

    A B G

    C

    D

    E

    F

    - Piping LayoutSchematic

    - GoalPiping Diagram on Xpressfor REFNET selection

    E

    G

    3-23-1

    1-1 1-2 1-3

    2-1 2-2 2-3

    3-1 3-2

    Group 1 Group 2 Group 3

  • 8/10/2019 Phn mm VRV Xpress

    48/73

  • 8/10/2019 Phn mm VRV Xpress

    49/73

    49

    Units below "2-1" are now connected to the main pipe by new first branch.

    Note :

    Unit "2-1" is a top unit of group 2.

  • 8/10/2019 Phn mm VRV Xpress

    50/73

    50

    (4) Connect the 1-1 indoor unit to the main branch by drag-and-drop.

  • 8/10/2019 Phn mm VRV Xpress

    51/73

    51

    Units below "1-1" are now connected to the main pipe by new 1st branch.

    Note :

    Unit "1-1" is a top unit of group 1.

  • 8/10/2019 Phn mm VRV Xpress

    52/73

    52

    7-4. Printing large piping diagrams

    When the piping diagram is printed in the report, it is always printed shrink to fitpage. For VRV systems with many indoor units, this results in a report where

    the names of the units are no longer readable. Therefore, it is possible to cut thediagram into several parts and label each part. Each part is then printed onanother page in the report, with its label in the sub diagram title.

    The cuts need to be defined in the[Piping] tab. You can define a cut byclicking on the intermediate pipe partwhere you want to cut the diagram.Then right click and select EnterSubdiagram label.

    The screen Enter Subdiagram Labelappears, which allows to enter a labelfor the subdiagram. Suppose we enterA.

    After entering the label, click OK.The label A appears on theintermediate pipe that will be cut.

    Enter the other cuts in the same way.It is advisable to create the .rtf-outputto see the result. If you are satisfiedwith the result, save your project. Thelabels are stored within the project.

  • 8/10/2019 Phn mm VRV Xpress

    53/73

  • 8/10/2019 Phn mm VRV Xpress

    54/73

    54

    After systems are determined in the [Outdoor Units] tab page, you can move to the[Wiring] tab page.

    When the [Wiring] tab is clicked, the [Wiring] tab page appears.Edit the wiring diagram for grouping indoor units.

    8-1. [Wiring] Tab Page8. Wiring Diagram

    (1)

    (2)

    (3)

    (3)

    (2)

    (1)

    Information and caution are displayed about the selected item. Thebackground color changes to red when a caution is displayed.

    Informationdisplay

    The wiring diagram is drawn automatically in this area for the systemof the selected outdoor unit.

    - The wired remote controller is indicated by solid line (default).- The wireless remote controller is indicated by dashed line (default).

    Wiring layoutarea

    Select the outdoor unit to edit the wiring diagram of its correspondingsystem.

    Outdoor unit listbox

    Note:You can also edit the wiring diagram by changing the order of the indoor units inthe extractable [Systems Tree] Window. (as described in section 6-8)

  • 8/10/2019 Phn mm VRV Xpress

    55/73

    55

    8-2. How to Edit the Wiring Diagram

    (1)

    (3)

    (2)

    (4)

    1) Right-click on the Office 201-2 unit

    and select [Select Options]. The[Used options] window pops up.

    Next, remove the remote controllerfrom the Office 201-2 unit asdescribed in section 5-3.

    2) The remote controller icon is deleted

    from the wiring diagram.

    3) To connect the Office 201-2 unitwith the Office 201-1 unit; right-click on the Office 201-2 unit andselect [Remote controller previous].

    4) The Office 201-2 unit is nowconnected to the remote controllerOffice 201-1 unit and form onecontrol group.

    Note:

    To remove the Office 201-2 unit fromthe control group; right-click and select [NoInter-wired Remote Controller], and add theremote controller again as an option.

    The wiring layout is just a reference. It isdefined as a sequential layout and cannotbe defined as desired.Also, some options (e.g. wiring adapter,BEV unit) are ignored.

  • 8/10/2019 Phn mm VRV Xpress

    56/73

    56

    After systems are determined, you can move to the [Centralized Controllers]tab page.

    When the [Centralized Controllers] tab is clicked, the [Centralized Controllers]tab page appears.Here you can select the centralized controllers and the management systemsfor the project.

    9-1. [Centralized Controllers] Tab Page9. Centralized Controller

    (1)

    (2)(4)

    (5)

    (3)

    The schematic diagram of the system with centralized controller.CentralizedController Diagram(4)

    - Change the order of outdoor units and create centralizedcontrol groups.- Select centralized controller for each outdoor unit.

    Outdoor Units(3)

    (5)

    (2)

    (1)

    Information and caution are displayed about selected item. Thebackground color is changed into red when caution is displayed.Information display

    Select management systems for the system from the list-box.ManagementSystem

    Select centralized controllers for the system from the listDescriptions of the controllers are displayed at the right side.

    CentralizedControllers

  • 8/10/2019 Phn mm VRV Xpress

    57/73

    57

    Select the centralized controller from the [centralized controller] list.Select "None if no controller is needed.

    9-2. How to Select the Centralized Controllers

    9-2-1. Select 1 Centralized Controllers for all Outdoor Units

    9-2-4. Select the management system

    Select the management system from the list.Select None if no management system is needed.

    9-2-2. Select multiple Centralized Controllers

    To separate outdoor units into 2 ormore groups, select an outdoor unitand click the [separator] icon ( ).

    The clicked unit becomes the top unit

    of the group. The separator ">" isshown on the left side of the outdoorunit.

    To merge the groups, select theoutdoor unit with separator ">", andclick the [separator] icon.

    You can also change the order of theoutdoor units by using the arrow icons

    ( ).

    To assign a centralized controller to asingle outdoor unit, press the ( ) button.The [Choose Centralized Controller]window pops up. Now choose thecontroller and press [OK] to close thewindow.

    9-2-3. Grouping and changingthe order of outdoor units

  • 8/10/2019 Phn mm VRV Xpress

    58/73

    58

    After systems are determined, you can move to the [Reports] tab page.When the [Reports] tab is clicked, the [Reports] tab page appears.After setting up the contents of the report, its possible to create an RTF, CSV orDXF output.

    10-1. [Reports] Tab Page

    10. Reports

    Enter information on the project. (required to create report)Project outline(1)

    When a caution is listed in this window, the report file cannotbe made. (e.g. project outline, indoor units that are notconnected to an outdoor unit, etc.)

    Project not yetcomplete(5)

    Information and cautions about the selected item aredisplayed. The background color changes to red when acaution is displayed.

    Information display(6)

    Select the systems to be included in the report.Systems included inreport(3)

    Click to generate the report file: .rtf, .csv or.dxfFile export tool bar(4)

    Indicates the contents to be included in the report file.Report contents(2)

  • 8/10/2019 Phn mm VRV Xpress

    59/73

    59

    (1) Define the contents of the report

    Check the check boxes of contents to be included in the report file.

    10-2. Set Up the Report

    Overall material ListNames, quantities and descriptions of the materials (units and options)- Foresee place for prices: creates additional columns in the report to enter prices- Show outdoor unit modules: the material list shows the names and quantities ofthe outdoor unit modules, instead of the outdoor units

    Indoor unit details: Table of the indoor units specifications

    Outdoor unit details: Table of the outdoor units specifications- Material list per system: Show a separate material list per system- Foresee place for prices: creates additional columns to enter prices- Piping limitations: a list of the applied piping rules is included in the report

    Piping diagrams: Piping diagrams for each system (outdoor unit).- Vertical: change the direction of the diagram

    Wiring diagramsWiring diagrams for each system (outdoor unit).

    Device optionsTable including the options chosen for each unit

  • 8/10/2019 Phn mm VRV Xpress

    60/73

    60

    When [All systems] check box

    is checked, all systems areincluded in the report file.

    To include only certain systemsin the report file, uncheck the [Allsystems] check box.

    Then remove the systems thatyou do not want to include in thereport. Select the system(outdoor unit) in the list-windows,and click arrow button ( ) tomove it to the Not includedwindow.

    (2) Select the Systems to be Included in the Reports.

    Note:In this case, report contents will

    be piping diagrams and wiringdiagrams only. The check boxesof Report contents will changeaccordingly.

  • 8/10/2019 Phn mm VRV Xpress

    61/73

    61

    (3) Create a report

    When the [Create a report] icon ( ) is clicked, the [Make Report] windowpops up. Enter the file name to save the report as RTF file (Rich TextFormat, for word processor).After saving, the text editor will open automatically to show the report thatwas just created.

    When the [Export to spreadsheet] icon ( ) is clicked, the [Export File]window pops up. Enter the file name to save the report as CSV file (CommaSeparated Values, for spreadsheet). The report file is opened in spreadsheet(usually MS-Excel) after being saved.

    (4) Export to spreadsheet

    When the [Export diagrams to DXF] icon ( ) is clicked, the [Export File]window pops up. Two diagrams are exported: the piping diagram and thewiring diagram.Choose the directory to save the report as DXF file (Data Exchange File, forAutoCAD).

    (5) Export piping and wiring diagram to CAD

  • 8/10/2019 Phn mm VRV Xpress

    62/73

    62

    (1) System

    RXYQ-PY1R410A, Heat Pump (selection based on the cooling load)

    (2) Design ConditionOutdoor Temperature 35 CDBIndoor Temperature 25 CDB, 50%RH

    (3) Building Plan and Cooling Loads for each RoomShown in figure below

    11-1. Outline of the Project (see chapter 4)

    11. Example

    10110kW

    1027kW

    1037kW

    1047kW

    1057kW

    1119kW

    10617kW

    1078kW

    1088kW

    1098kW

    11020kW

    1129kW

    1139kW

    1149kW

    11511kW

    Hall150kW

    N

    Outdoor Units

    35m

    2 0 m

    5 m

  • 8/10/2019 Phn mm VRV Xpress

    63/73

    63

    (1) Automatic Selection (based on the total capacity)(2) FXFQ (Round Flow Cassette)(3) Rooms 101-105, Rooms 107-109, Rooms 111-115: 1 unit for each room

    Room 106, Room 110: 2 units for each roomHall: 15 units

    11-2. Indoor Units Selection (see chapter 5)

    101 102 103 104 105

    111

    106

    107

    108

    109

    110112113114115

    Hall

  • 8/10/2019 Phn mm VRV Xpress

    64/73

  • 8/10/2019 Phn mm VRV Xpress

    65/73

    65

    [Out Hall1]

    Refer to section 11-4 for changing order of indoor units

    [Out Room2]

    [Out Hall2]

  • 8/10/2019 Phn mm VRV Xpress

    66/73

    66

    11-4. Piping Diagram (see chapter 7)

    Piping Tree[Out Room1] Room101-Room106-2,Room107-Room108

    [Out Room2] Room109-Room115[Out Hall1] Hall1-Hall7 (with REFNET header)[Out Hall2] Hall8-Hall15 (with REFNET header)

    101 102 103 104 105

    111

    106

    107

    108

    109

    110112113114115

    Hall1

    Hall2

    Hall3

    Hall4

    Hall5

    Hall6

    Hall7

    Hall8

    Hall9

    Hall10

    Hall11

    Hall14

    Hall13

    Hall14

    Hall15

  • 8/10/2019 Phn mm VRV Xpress

    67/73

    67

    101

    102 103 104 105 106-1 106-2 107

    - Piping Layout Schematic (Out Room1)

    108

    101

    102

    103

    104

    105

    106-1 106-2

    107 108

    - Ordering Indoor Units (Out Room1)

    ABCDEF

    GH

    A B C D E F

    G

    H

  • 8/10/2019 Phn mm VRV Xpress

    68/73

    68

    - Piping Diagram (Out Room 1)

  • 8/10/2019 Phn mm VRV Xpress

    69/73

  • 8/10/2019 Phn mm VRV Xpress

    70/73

    70

    - Piping Diagram (Out Hall 1) - Piping Diagram (Out Hall 2)

  • 8/10/2019 Phn mm VRV Xpress

    71/73

    71

    11-5. Wiring Diagram (see chapter 8)

    Control GroupOut Room 1 Room 106-1 and Room 106-2

    Out Room 2 Room 110-1 and Room 110-2Out Hall 1 Hall 1-Hall 7Out Hall 2 Hall 8-Hall 15

    101 102 103 104 105

    111

    106

    107

    108

    109

    110112113114115

    Hall

  • 8/10/2019 Phn mm VRV Xpress

    72/73

    72

    11-6. Centralized Control (see chapter 9)

    (1) Centralized Controller

    DCS302C61 for Out Room1/2, Out Hal1/2(2) The outdoor units grouping.

    Out Room1 and Out Room 2,Hall-1 and Hall-2

    (3) Management SystemDMS502A51 (BACNET)

    (1)

    (2)

    (3)