Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

download Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

of 10

Transcript of Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    1/10

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    2/10

    Websjournal of Science and Engineering ApplicationISSN: 1974-1400-X, Vol 2, No 2, 2013, 103-112

    A.A. Adedeji, V. S. Kamara and D. P. Katale

    104Websjournal of Science and Engineering Application//Lyon _ AIGEN

    cement plastered and unplastered strawbale as well as the unsprayed termitarium plastered strawbale.

    The methodology of this project includes production of strawbale specimens of plastered and

    unplastered sprayed blocks and prisms. The termitarium plastered strawbale were initially tested and itssimulation carried out at the Department of Civil Engineering, Namibia University of Science and

    Technology (Kamara et al, 2012). The result of the present work is hereby compared with that of the

    termitarium plastered wall. A typical thermal conductivity of natural (coconut) fibre, due to changes in

    temperature, is shown in Table 1.

    Table 1. Experimentally determined ()for coconut fibre

    Density (kg/m ) Thermal Conductivity (W/mK)

    15.6C mean temp. 21.8C mean temp.

    40 0.05624 0.0575850 0.05099 0.05184

    60 0.05051 0.04970

    70 0.04891 0.0488480 0.04800 0.04886

    90 0.04869 0.05009

    Source: Aridome et al (1998)

    2. SPRAYED FIBRE REINFOCED PLASTICS REVIEW

    Closed-cell spray polyurethane foam (ccSPF) insulation is a self-adhering, two-component productthat is spray applied on site. The material tenaciously bonds to most construction material substrates(i.e. metal, wood, plastic, masonry) and provides a rigid insulation system that adds structural strength

    to buildings. It has the highest level of thermal performance per mm, for commonly used thermalinsulation products. Typically, this performance shows a design R-value of 6.2 for 0.91 kg at 23.89oC

    for ccSPF wall insulation, and a design R-value of 6.7 for 1.36 at 23.89oC(ccSPF) roof insulation at a

    mean temperature of23.89oC(ASTM C 518 04).Closed-cell spray polyurethane foam also has nearly

    zero air permeability and acts as an integral vapor barrier. Because the product is sprayed onto thesubstrate and expands to nearly 30 times its original volume when applied, it conforms too many

    irregular spaces and fills voids that other insulation materials leave open. It requires no fasteners and istypically installed in a single application (CES, 2007). The Open-cell spray polyurethane foam (ocSPF)

    utilizes carbon dioxide as the sole blowing agent. In ocSPF, the cells burst open and are suspended in

    the finished foam in an open form.

    In walls, ccSPF insulation can be used throughout the interior or exterior of a structure and may beapplied to nearly any construction surface (i.e. masonry, gypsum board products, wood, metal),including exposed or new construction wall framing. Closed-cell spray polyurethane foam wall-

    insulation systems provide a continuous air barrier, improved building strength and significant thermal

    performance. The system addresses all key issues associated with insulation and air-barrier systems incommercial insulation performance, because of: Superior effective R-value in a complete assembly. A

    monolithic, integral vapor and air barrier that requires no additional products to reduce air andmoisture infiltration and exfiltration, thereby exceeding building codes and standards and meeting

    ASTM C1029/SPFA guidelines. Low water vapor permeability, low liquid water absorption and highthermal performance, which combine to minimize condensation and water intrusion into the building

    (Banthia, 2002). Complete coverage of the building envelope (i.e. roof, walls, foundation and slab),which minimizes thermal bridging caused by fasteners, joints, cracks, penetrations and framing.Finally, ccSPF insulation and waterproofing systems employed in the building envelope (i.e. roof,

    walls, foundation and slab) can substantially improve the structural integrity of the building. In fact,

    studies show that using ccSPF insulation in walls increases racking strength two to three timescompared to assemblies using traditional insulation products. Using ccSPF as a wall-insulation system

    provides significant energy-related benefits. In addition to significantly higher R-value than other

    insulation materials, ccSPF eliminates moisture and air infiltration and exfiltration. Thermal testing

    standard of R-13 of SPF cells and other polystyrenes are shown in Table 2.

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    3/10

    Websjournal of Science and Engineering ApplicationISSN: 1974-1400-X, Vol 2, No 2, 2013, 103-112

    A.A. Adedeji, V. S. Kamara and D. P. Katale

    105Websjournal of Science and Engineering Application//Lyon _ AIGEN

    Table 2. Current thermal testing standardsInsulation ASTM Standard Mean Test Temperature

    Differential, F (oC)

    Temperature, F (oC)

    R-13 Fiberglass with

    paper facing

    ASTM C 653 75 (23.89) 40 (4.44)or 50 (10)

    Extruded polystyrene ASTM C 578 25 (-6.67), 75 (23.89) 110 (43.33) Min 40 (4.44)

    Polyisocyanurate ASTM C 1289 40 (4.44), 75 (23.89) 110 (43.33) Min 40 (4.44)

    Closed-cell sprayfoam insulation

    C 1029 40 (4.44), 75 (23.89) 110 (43.33)Min 40 (4.44)

    Open-cell spray foaminsulation

    None 75 (23.89) Min 40 (4.44)

    Source : (CES, 2007)

    3. MATERIALS PROPERTIES AND CONSTRUCTION OF SB MASONRY

    3.1 Strawbale wall as energy efficient

    The use of straw as insulation means that the standard insulation materials are removed from the home

    standard fiberglass insulation has formaldehyde in it, a known carcinogen bale walls also eliminate theuse of plywood in the walls. Plywood contains unhealthy glue that off-gas into the house overtime

    (Downton 2003, Lancinski and Bergeron 2000), which can endanger the occupants. A house envelopedwith a strawbale wall can save up to 75% on heating and cooling costs intact in most climates, we do

    not even install air conditioning unit into strawbale building as the natural cooling cycle of the planet

    are enough to keep the house cool all summer long(Downton, 2003). Likewise, Adedeji and Aweda(2013) and Adedeji (2007) postulated that all new buildings must be energy efficient with straw walls,

    the insulation (straw) is also the building block. Also Lee (2001) indicated straw compacted into balesoffers much better insulation with its high thermal resistance.

    3.2 Materials used for specimen construction

    DataBase used for this research work was based on experimental tests on strawbale wall - also reportedherewith - were conducted by Samuel (2012). The following materials were used: Mature straw of

    guinea corn stalk (cut to size of three strings), ordinary Portland cement (OPC), fine aggregate, steel

    wire/twine. The fine aggregate used was clean, soft, well graded, freed from salt and organic

    contaminant of 100% passing through sieve no 5mm was employed in the mix. Two different specimensamples were prepared, one in which strawbale was unplastered and other specimen plastered withSFRP.

    3.3 Particle size distribution tests and results

    500g of dry fine aggregate sample, which passes through sieve no. 5mm, weighted and complied with

    BS 882:1201. This was employed in the mix. The natural sand used was well graded in conformity

    with the limit given in the Table 1 of BS 882:1201. The result of the sieve analysis carried out is shownin Table 1 and in Figure1, for the number of different sized particle available, BS410: 1976 was

    employed for the production of the block specimens.

    Table 1 Sieve analysis result or grading of sand for blockSieveSize (mm)

    Sieveweight

    (g)

    Sieve weight +retained

    (g)

    Retainedweight (g)

    Percentageretained %

    Cumulativepercentage

    retained

    Cumulativepercentage

    passing5 100

    4 554 558 4 0.8 0.8 99.2

    2.36 478 493 15 3 3.8 96.22 520 565 45 9 12.2 87.20.5 496 641 145 29 41.8 58.20.25 472 582 114 22.8 70.8 29.20.063 455 552 97 19.4 90.2 9.5Recording pan 254 303 49 9.8 1 00 0

    Percentage retained = (weight retained/total weight of sample) x100%

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    4/10

    Websjournal of Science and Engineering ApplicationISSN: 1974-1400-X, Vol 2, No 2, 2013, 103-112

    A.A. Adedeji, V. S. Kamara and D. P. Katale

    106ebsjournal of Science and Engineering Application//Lyon _ AIGEN

    Figure 1 Particle size distribution curve

    3.4 Spraying of strawbale

    The spray was applied to the strawbale by a compressed pump machine. The polymers were mixed andpoured into the compressed pump machine gun after which the polymer fibre reinforced cement mortar

    was sprayed out of the guns nozzle toward the surface of the strawbale. Contained in the mix waspaint DALUX 01202092 with a base, hardener and reducer in ratio 2:1:02 (that is, 2 part base, 1

    hardener and 0.2 reducer). The surface of the strawbale was cleaned and free of dirt, grease, oil, wateror other contaminants. A total of sixty coupon specimens of each sprayed FRP were prepared as Type

    A test pieces. Thirty specimens were made with carbon fiber (CF), and the other thirty specimens for

    glass fiber (GF). The installing procedure of the sprayed FRP strengthening is as follows:i) Base arrangement; other extra fin leaves on surface of strawbale (SB) prism were trimmed using

    scissors.ii) Primer resin coating; Primer resin was applied to the surface in order to make highly adhesive

    between SB and putty/resin.

    iii) Putty arrangement; Dent areas and steps on SB surface are filled with putty and made the surfaceflat in order to prevent partial stresses of FRP and air voids on SB. After putty got dried, the

    surface was thoroughly sanded.

    iv) Resin coat; In order to make fibers more adhesive, resin was coated first by a spray gun. Maximum

    lengths of the carbon and glass fibers are 0.5mm and 0.2mm respectively.

    0

    20

    40

    60

    80

    100

    0.001 0.01 0.1 1 10

    PERCENTAGEFINER(%)

    PARTICLE SIZE (mm)

    Figure 2 SFRP plasteredStrawbale prism before loading

    Figure 3 Failure mode in ruptureand splitting

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    5/10

    Websjournal of Science and Engineering ApplicationISSN: 1974-1400-X, Vol 2, No 2, 2013, 103-112

    A.A. Adedeji, V. S. Kamara and D. P. Katale

    107ebsjournal of Science and Engineering Application//Lyon _ AIGEN

    In this study however, it was a goal to obtain sufficient behaviours as applicable to the wall element

    by factoring the results of the prism (Adedeji, 2007). Figure 2 shows typical FRP sprayed strawbaleprism, while Figures 3, 4 and 5 show typical failure modes of the prisms subjected to compressive

    strength test.

    3.5 DataBase

    Mechanical properties of carbon and glass fibres are shown in Table 2 and database for specimensare also indicated in Table 3.

    Table 2. Mechanical properties of FRP and plastered strawbale and TSB

    Identification Tensile Strength(MPa) Elastic Modulus(GPa) Ultimate strain (%)

    CF-A1** 4451* 254.1* 1.76

    GF-A2** 2378* 127.1* 1.87CF-A3** 117.1 15.24 0.78

    GF-A4** 112.9 8.00 1.48

    T-SB*** - 6.00 -* For sectional area of only fiber (not included resin)

    **(Toshiyuki, c_kanakubo_final_pdf)*** Kamara et al (2012)

    T-SB = Termitarium Strawbale composition, thermal conductivity =0.020 0.035

    Table 3. Prism specimensSpecimen Section FRP FRP (Specified values)

    (mm) Length (mm) Arrangement pFRP(%) Elastic modulus (GPa) Thickness (mm)

    CF- A1 254.1 0.5GF- A2 250 *450 1000 Mixed 0.13 127.1 0.16CF-A3 15.2 0.2GF-A4 8.0 0.13

    pFRP= Percentage of FRP

    3.6 Compressive strength test results

    The characteristic values of axial compressive strength of the SFRP masonry prisms are obtained

    from the compression test results on full height prism subjected to eccentric loading. In general, it isconservative to assume pinned-pinned condition and it may be noted that for design purposes, the

    characteristic values should be divided by partial safety factor 1.7 and maximum of 3.3 (Adedeji, 2000)

    Compressive strength applied in this study involved the capacity of the masonry to withstand axialload only. When the limit of compressive strength is reached, materials are crushed. Tables 4 to 7

    Figure 4 Sprayed plastered strawbale

    prism splitting under loading

    Figure 5 Sprayed plastered strawbale prism

    crushing under loading

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    6/10

    Websjournal of Science and Engineering ApplicationISSN: 1974-1400-X, Vol 2, No 2, 2013, 103-112

    A.A. Adedeji, V. S. Kamara and D. P. Katale

    108Websjournal of Science and Engineering Application//Lyon _ AIGEN

    shows the average compressive strength test results on sprayed and unsprayed plastered strawbale

    prisms with their standard deviation.

    Table 4. Average compressive strength for sprayed cement plastered strawbale prism

    Analysis Plan Area

    (mm2)

    Crushing load

    (N)

    Compressive strength (N/mm )

    Prism Actual wall

    Mean Value 85.6 x140.6 7838.77 0.65 6.5

    Standard deviation 1192.75 0.092

    Table 5. Average compressive strength for unsprayed cement plastered strawbale prism

    .

    Table 6.average compressive strength for sprayed cement unplastered strawbale prism

    Analysis Plan Area

    (mm2)

    Crushing load

    (N)

    Compressive strength (N/mm )

    Prism Actual wall

    Mean Value 85.6 x140.6 7838.77 0.65 6.5Standard deviation 1192.75 0.092

    Table 7.average compressive strength for unplastered strawbale prism without spray

    Prism model is factored by 0.1 of the actual wall dimensions

    For the height of the strawbale prism, HP = 1m and thickness BP = 0.45m, the maximum stressesallowable and calculated using SAP2000 are also shown in the Tables 8 and 9for both cement

    (Adedeji, 2011) and termitarium plaster composition (Kamara et al, 2012).

    Table 8.Minimum and maximum stresses (N/mm2) between each of the plaster compositions

    and the strawbale material.

    Outside plaster Inside plaster

    Plaster composition Minimum stressMaximum

    stressMinimum stress Maximum stress

    *Cement -9.8 9.6 -19.3 18.3

    Termitarium -6.0 6.2 -6.3 6.5

    *Adedeji (2011), Kamara et al (2012)

    Table 9Differences between the allowable and calculated stresses for both plaster compositions.

    Wall composition Maximum allowable stressMaximum calculated stress using

    SAP2000*Cement plastered strawbalewall

    70.14kN/m2 38.836kN/m

    2

    Termitarium plasteredstrawbale wall

    73.14kN/m2 67.452kN/m

    2

    *Adedeji (2011), Kamara et al (2012)

    Analysis Plan Area(mm

    2)

    Crushing load(N)

    Compressive strength (N/mm )Prism Actual wall

    Mean Value 85.7x140.6 7305.7 0.61 6.1

    Standard deviation 865.28 0.076

    Analysis Plan Area(mm

    2)

    Crushing load(N)

    Compressive strength(N/mm )Prism Actual wall

    Mean Value 85.8 x 140.5 5297.4 0.44 4.4Standard Deviation 727.14 0.061

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    7/10

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    8/10

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    9/10

    Websjournal of Science and Engineering ApplicationISSN: 1974-1400-X, Vol 2, No 2, 2013, 103-112

    A.A. Adedeji, V. S. Kamara and D. P. Katale

    111Websjournal of Science and Engineering Application//Lyon _ AIGEN

    5. DISCUSSION OF RESULTS

    Due to the tests carried out on strawbale prisms and simulation, the results are presented as follows:In a sprayed fibre reinforced plastics walls, thepeak values for the state of stress and deformation occur

    in the same minute cycle of temperatures. So, the results of thesimulation of temperature for the stress

    and deformation indicate the rational 'stress and deformation tolerance 'in which the wall situates, The

    section of an SFRP of the strawbale (SB)wall plastered with cement mortar has minimum compressive

    stress (outside wall-surface) of 8.839, 8.034 and 7.001 N/mm2

    at eccentricity, e = 0, e = 6 and e =20mm and the length of 1.0 m respectively, while the compressive stress (inside wall-surface of 0.1

    N/mm2 occurred

    at 20 hrs respectively. The case is different with a two-sideplastered wall, where the

    tensile stress of 1.8N/mm2was recorded at 15 hrs, while the compressive stress of 0.5 N/mm

    2occurred

    at 24 hrs. The maximum (normal) stress at the contact of the wall and the FRPplaster outside the wallis 1.3N/mm2and it occurred at 20hrs. The shear stress along the contact is in compression with a

    maximum value of 0.2N/mm2in the 23hrs. This is not the case with the wall plastered on both sides

    where tensile stress occurs in the 14hrs mid the shear stress (compressive) occurs in the 20hrs .The

    SFRPplastered wall is very sensitive to thermal movement, from 'all indications,when compared with

    both cement plastered and termitarium plastered SB wall and so is the compatibility (bond) between thewall elements and the plasters. The high bond stress is due to the field of stress by the modulus of

    elasticity of SFRP plaster and the strawbale surface area. Though, a modular ratio (ESFRP/ESB) of 1.33gives moderate compatibility between the two materials, the time cycle for this rapid change may affectthebond between the two elements as yearspassby. This maybe more damaging at any slight daily

    swings of temperature. Temperaturepatterns forboth plastered and unplastered wall arethe same.

    6. CONCLUSION

    The performance of sprayed fibre reinforced polymer plasters, on strawbale prism, has beenidentified by this research work. The results obtained were factored 0.95 (Adedeji, 2007) to obtain the

    values for the wall. Strawbale wall has shown adequate resistance against vertical loading. Comparison

    of results was made between plastered and unplastered strawbale with spray, unplastered and plastered

    strawbale without spray. Spray-plastered strawbale have stresses of 8.838N/mm2over 8.387N/mm

    2of

    unsprayed plastered strawbale with the sprayed FRP thermal conductivity ranges between 0.020and0.035.This implies that when higher loading such as the above stresses occur, the response of the

    fibre reinforced cement plastered strawbale is high compared to other unsprayed strawbale wall. From

    this work however, it could be recommended that strawbale sprayed plastic fibre mortar should beemployed for sustainable, strong and ecosystem compatible buildings; as there is a strong indication of

    a moderate bond between the SFRP of both cement and termitarium plaster and the SB surface areaeven, on the west wall, at 700 W/m2solar gain at a temperature of 43.33oC.

    REFERENCES

    Adedeji, A. A. and Aweda, J. O. (2013). Design optimisation and maintenance of strawbale masonryprism by genetic algorithm, Websjournal of Science and Engineering Application, 2(1) pp 77-87

    Adedeji A.A. (2007) Introduction and design of strawbale masonry. Olad Printing Enterprises Ltd,

    Ilorin.Adedeji, A.A. (2000). Strength evaluation of strawbale plastered masonry-prism in construction,

    Reports for Senate Research (grants VCO/PO/96), University of Ilorin, Ilorin, Nigeria.Aridome, Y., Kanakubo, T., Furuta, T. and Matsui, M. (1998). Ductility of T-shape RC beams

    Strengthened by CFRP Sheet, Transactions of the Japan Concrete Institute, 20, pp 117-124

    Banthia N. and Boyd A.J (2000). Sprayed Fibre-reinforced polymer for repairs Canadian journal ofCivil Engineering 27(5), pp 907-915.

    Banthia, N, Nanda Kumar N and Boyd A.J (2002) . Sprayed fibre reinforced polymer: from laboratoryto a real bridge ACI Concrete Intentional; Design and Construction, 24(11) pp 41-52.

    Bruce King, P.E. (1996). Buildings of earth and straw. Text on Ecological Design Press 1996, pp 95152.

    Bruce King (2003). Load-bearing strawbale structure, a summary of testing and experience of dateEcological Design Press.

    British Standard Institution, BS 882:1201, Aggregation from Natural Sources for Concrete, British

    Standard House, London, pp 1-35.British Standard Institution, BS 410:1975, Specification for test Sieves, British Standard House,

    London, pp 1-36.

  • 8/11/2019 Performance Indices for a Simulated Strawbale _sb_ Masonry Sprayed With Fibre Reinforced

    10/10

    Websjournal of Science and Engineering ApplicationISSN: 1974-1400-X, Vol 2, No 2, 2013, 103-112

    A.A. Adedeji, V. S. Kamara and D. P. Katale

    112Websjournal of Science and Engineering Application//Lyon _ AIGEN

    CES (2007), Insulation Energy Savings: Key issues and performance factors, CEC, Energy Savings

    from Building Standards, 2007 Integrated Energy Policy Report.

    DIN, 52612. 1980. Waermeschutztechnisch pruefungen bestimung der waermeleitfaehigkeit mit demplatten great,Durchfuehrung und Auswertung.

    Downtown P. (2003) Australia strawbale Australia, Available @www.ausbale.org.

    Ishola S.T. (2010) Effective of contact between strawbaleand plaster composition for the wall optional

    design B. Eng. Project submitted to the Department of Civil Engineering, University of Ilorin,

    Ilorin pp 1-80.Jones Barbara (2002) Building with Strawbale; A practical Guide for UK and Ireland (2011.ed),

    Dartington, Totne, Devon 7Q 96EB: Green Books, pp26.Kamara, V. S., D. P. Katale and A. A. Adedeji. (2012). Modelling the prism of termitarium-strawbale

    composite masonry for its bearing capacity, Journal of Research Information in Civil Engineering,9(2), pp 227-256.

    Lancinski P. and Bergeron M. (2000), Serious strawbale; a home construction, guide for all climate,Chelsea Green Publishing Coy. U.S.A.

    Lee F. (2001), Strawbale construction U.S.A. www.Uheac.org/links.Html.

    Samuel, O. Juwon, (2012), Performance of sprayed fibre reinforced plastic on plastered and unplasterdstrawbale prism. B Eng project, submitted to the Department of Civil Engineering, University of

    Ilorin,Taha H M Ashour. (2003). The use of renewable agricultural by-products as building materials, PhD

    Thesis submitted to Department of Agricultural Engineering, Faculty of agriculture, Moshtohor

    Zagazig University Benha Branch, German Strawbale Association FASBA in June 2006 pp 1-348.Talukdar S. (2008), Strengthen the timber beams polymers, M.A Sc thesis, University of British

    Columbia. Vancouver, Canada.Talukdar S. and Banthia, N. (2010) Performance of sprayed fibre reinforced polymer strengthened

    Timber Beans reinforced polymer strengthened Timber Beams Department of Civil Engineering,University of British Columbia, 6250 applied science lane, Vancouver, Bc, Canada, V6TIZ4.

    Toshiyuki, K., Tomoki, F., Keisuke, T. and Nemoto, T., Sprayed fiber-reinforced polymers for

    strengthening of concrete structures, Technical paper, c_kanakubo_finalpdf @ Institute ofEngineering Mechanics and Systems, University of Tsukuba, Japan.