PCS 7 APACS OS Symbols and Faceplates V6.1

66
s Preface, Contents Common HMI Elements 1 SINGLE_LOOP_AFB 2 Other Faceplates 3 SIMATIC PCS 7/APACS+ OS Symbols and Faceplates Users Guide for V6.1 Manual Edition 11/2005 A5E00595267-01

description

APACS

Transcript of PCS 7 APACS OS Symbols and Faceplates V6.1

s Preface, Contents Common HMI Elements 1 SINGLE_LOOP_AFB 2 Other Faceplates 3 SIMATIC PCS 7/APACS+ OS Symbols and Faceplates Users Guide for V6.1 Manual Edition 11/2005 A5E00595267-01 Siemens AG Automation and DrivesPostfach 4848 90437 NRNBERG GERMANY Copyright Siemens AG 2005A5E00595267-01 Siemens AG 2005 Technical data subject to change. Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring to property damage only have no safety alert symbol. The notices shown below are graded according to the degree of danger. ! Danger indicates that death or severe personal injury will result if proper precautions are not taken. ! Warning indicates that death or severe personal injury may result if proper precautions are not taken. ! Caution with a safety alert symbol indicates that minor personal injury can result if proper precautions are not taken. Caution without a safety alert symbol indicates that property damage can result if proper precautions are not taken. Notice indicates that an unintended result or situation can occur if the corresponding notice is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notices in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards. Prescribed Usage Note the following: ! Warning This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance. Trademarks All names identified by are registered trademarks of the Siemens AG.The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. PCS 7/APACS+OS Symbols and Faceplates for V6.1 AE00595267-01iii Preface Purpose of the Manual This manual provides information about the PCS 7/APACS+OS Symbols and Faceplates. Required Basic Knowledge Readers are presumed to be knowldedgable in the use of APACS+HMI software. Where is this Manual valid? This manual is valid for the software package PCS 7/APACS+OS Options V6.1. Training Centers Siemens Technical Training Center provides extensive training for all levels of plant personnel to ensure optimal performance from APACS+ and PCS 7 control systems. Classes include extensive hands-on activities using appropriate equipment, making the training directly and immediately applicable. On-line information is available: http://www.sea.siemens.com/sitrain Siemens also offers a number of training courses to familiarize you with the SIMATIC S7 automation system. Please contact your regional training center or our central training center in D 90327 Nuremberg, Germany for details:Telephone:+49 (911) 895-3200.Internet:http://www.sitrain.com Preface PCS 7/APACS+OS Symbols and Faceplates for V6.1 ivAE00595267-01 A&D Technical Support Worldwide, available 24 hours a day: Beijing Nrnberg Johnson City United States: J ohnson City, TNWorldwide: NrnbergAsia / Australia: Beijing Technical Support24 hours a day, 365 days a year Phone:+49 (180) 5050-222 Fax:+49 (180) 5050-223 E-Mail: [email protected] GMT:+1:00 Technical Support and Authorization Local time: Monday to Friday8:00 AM to 5:00 PM Telephone:+1 (423) 262 2522 or +1 (800) 333-7421 (USA only) Fax:+1 (423) 262 2289 Mail to: [email protected] GMT: -5:00 Authorization Local time: Monday to Friday8:00 AM to 5:00 PM Phone: +49 (180) 5050-222 Fax: +49 (180) 5050-223 Mail to: [email protected] GMT: +1:00 Technical Support and Authorization Local time: Monday to Friday8:00 AM to 5:00 PM Phone:+86 10 64 75 75 75 Fax:+86 10 64 74 74 74 Mail to:[email protected] GMT:+8:00 Automation and Drives Service and Support International http://www.siemens.com/automation/service&support The languages of the SIMATIC Hotlines and the authorization hotline are generally German and English. PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01v Contents 1Common HMI Elements1-1 1.1Symbols.......................................................................................................... 1-1 1.2Analog Input Dialog Box................................................................................. 1-3 1.3Discrete Input Dialog Box............................................................................... 1-4 1.4Time Input Dialog Box.................................................................................... 1-4 1.5Confirmation Dialog Box................................................................................. 1-5 1.6Operator Change Confirmation....................................................................... 1-5 1.7Global HMI Elements .PDL Files .................................................................... 1-6 1.8Displayed Decimal Points............................................................................... 1-7 1.9Common Faceplate Elements ........................................................................ 1-8 1.10Redundant Server Architecture ...................................................................... 1-8 1.11APACS Source Address................................................................................. 1-9 1.12Synchronization and Persistence of HMI Tag Values ................................... 1-10 1.13Disabled Alarm List....................................................................................... 1-13 2SINGLE_LOOP_AFB2-1 2.1SINGLE_LOOP_AFB Standard View............................................................. 2-1 2.2SINGLE_LOOP_AFB Tuning View................................................................. 2-3 2.3SINGLE_LOOP_AFB Alarm View................................................................... 2-4 2.4SINGLE_LOOP_AFB Ramp View.................................................................. 2-5 2.5SINGLE_LOOP_AFB Limits View................................................................... 2-6 2.6SINGLE_LOOP_AFB Trend View................................................................... 2-8 2.7SINGLE_LOOP_AFB Faceplate Overview Window........................................ 2-9 2.8SINGLE_LOOP_AFB Faceplate Frame........................................................ 2-10 2.9SINGLE_LOOP_AFB Faceplate View List.................................................... 2-10 2.10SINGLE_LOOP_AFB Loop Display Mode.................................................... 2-11 2.11SINGLE_LOOP_AFB View .PDL Files ......................................................... 2-12 3Other Faceplates3-1 3.1ANALOG_ALM_AFB...................................................................................... 3-1 3.2DISCRETE_ALM_AFB................................................................................... 3-3 3.3MOTOR_1OUT_AFB...................................................................................... 3-5 3.4MOTOR_2OUT_AFB...................................................................................... 3-8 3.5MOTOR_A_AFB............................................................................................. 3-9 3.6MOTOR_A_ALM_AFB.................................................................................. 3-12 3.7BLK_VLV_1OUT_AFB.................................................................................. 3-15 3.8BLK_VLV_2OUT_AFB.................................................................................. 3-17 3.9VALVE_A_AFB............................................................................................. 3-18 3.10VALVE_A_ALM_AFB................................................................................... 3-23 3.11EXT_SET_AFB............................................................................................. 3-25 3.12RATIO_SET_AFB......................................................................................... 3-26 3.13PRIMARY_AFB............................................................................................ 3-26 3.14SECONDARY_AFB...................................................................................... 3-27 3.15CASCADE_AFB........................................................................................... 3-27 3.16RESOURCE_STATUS_AFB........................................................................ 3-28 3.17SINGLE_LP_SS_AFB.................................................................................. 3-33 Contents viPCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-011-1 1Common HMI Elements 1.1Symbols Each tag structure and faceplate has an associated symbol. You can place these symbols on your process graphics to represent a control object. At runtime, when you click on the symbol, the associated faceplate is displayed and tied to the corresponding instance of the APACS+object. The PCS 7/APACS+Option symbols are shown in the picture below: Common HMI Elements 1-2PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 The APACS+symbols are provided on the picture "@@APACSTypicals.pdl".PCS 7/APACS+DBA uses these symbols as shown to create instances associated with the type found in the APACS+controller. The symbols on this picture can be considered "master" symbols. These symbols use a naming convention of @BlockName/1. When DBA creates an instance of this symbol on a picture, the symbol name is set equal to the tagname of the APACS+tag. DBA manages these symbol names and they should not be edited. Most blocks have several symbols, each with differing sizes and amount of information. The default symbol selected by DBA is the one named @BlockName/1. Alternate symbols can be selected by DBA by modifying the "Symbol Name property for the block in DBA (for example, @BlockName/2). When a symbol is copied or cut and then pasted onto the same picture or another picture, the Graphics Designer changes the name of the symbol. For example, @LOOP_A becomes LOOP_A1; if another instance is pasted, the name becomes LOOP_A2. It is important that the symbol names of symbol instances created by DBA not be changed. DBA manages the creation and deletion of the symbol instances that it creates. If you cut and paste a symbol instance onto the same picture created by DBA, the next time DBA runs it adds another instance of this symbol. Instead, if you need to move a symbol, drag and drop it to ensure that the name does not change. Common HMI Elements PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-011-3 1.2Analog Input Dialog Box This dialog box appears if you click a field that has a floating point value that can be changed. Clicking the OK button logs the change in the PCS 7 operator's log. Key Description 1Step controls 2Minimum permissible value 3Maximum permissible value 4Analog value5Slider control of analog value 6Keypad for entering values 7Confirmation button, logs change in operator's log File: @Common_AnalogInput.PDL Common HMI Elements 1-4PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 1.3Discrete Input Dialog Box A discrete input dialog box appears if you click a field with a discrete value. The box includes an OK button for confirmation. Clicking it confirms the selection and records a change in the PCS 7 operators Log. The following discrete input dialog box, used in loop controls, selects Manual or Auto. File: @Common_DiscreteInput.PDL 1.4Time Input Dialog Box If you click a field with time values, a time input dialog box appears. Clicking the OK button records changes in the PCS 7 operators Log. File: @Common_TimeInput.PDLCommon HMI Elements PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-011-5 1.5Confirmation Dialog Box If you initiate a change that requires confirmation, such as clicking the Open button on a valve faceplate, a confirmation dialog box appears. Clicking on the OK button records changes in the PCS 7 operators Log. File: @Common_ConfirmationBox.PDL 1.6Operator Change Confirmation DBA adds a ConfirmChange extended attribute for each APACS+function block instance (See the DBA help file for details). This controls whether operator actions require a confirmation step or not. If ConfirmChange is FALSE (its default value) then any type of discrete operator change (for example, Auto/Manual, Start Motor, Open Valve, etc.) is immediately made without further confirmation requirements. If ConfirmChange is TRUE, then any type of discrete operator change displays either the Discrete Input Dialog box or a Confirmation box, and requires the operator to select and/or confirm the request. Similarly, any floating-point operator change can only be made via the Analog Input Dialog, and confirmed with its OK button.In either case, an entry in the operators log is always made for any operation that involves a write to the controller. In addition, if ConfirmChange is FALSE, any faceplate bargraph that is editable by the user also includes a set of four quick-change buttons to make immediate step changes to the bargraph value. These make step changes of either -5%, -1%, 1%, or 5% of configured span. The quick change buttons are not displayed if ConfirmChange is TRUE. Common HMI Elements 1-6PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 1.7Global HMI Elements .PDL Files The following table lists the PCS 7 OS graphic files (.PDLs) that create the global HMI elements. These files can be opened and examined with the WinCC Graphics Designer program: Start > Simatic > WinCC > Windows Control Center 6.0 > (open project) > Graphics Designer (right click) > Open (select .PDL file) > Open. ViewFile Analog Input Dialog Box@Common_AnalogInput.PDL Discrete Input Dialog Box@Common_DiscreteInput.PDL Time Input Dialog Box@Common_TimeInput.PDL Confirmation Dialog Box@Common_ConfirmationBox.PDL Common HMI Elements PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-011-7 1.8Displayed Decimal Points The number of decimal points displayed on symbols and faceplates is configurable on a tag by tag basis in DBA. The following table shows which decimal point tags affect which HMI tags. BlockDecimal Places TagAffected Tags .DecimalPlacesPV.PV, .SP, All Alarm Limits, All Alarm Deadbands, Setpoint Limits, Ramp Target, Ramp Rate SINGLE_LOOP .DecimalPlacesOUT.OUT, Output Limits ANALOG_ALARM.DecimalPlacesPV.PV, All Alarm Limits, All Alarm Deadbands DISCRETE_ALARMN/AN/A BLK_VALVE_1OUTN/AN/A BLK_VALVE_2OUTN/AN/A VALVE_AN/AN/A VALVE_A_ALMN/AN/A MOTOR_1OUTN/AN/A MOTOR_2OUTN/AN/A MOTOR_AN/AN/A MOTOR_A_ALMN/AN/A .DecimalPlacesPV.PV, .SP, All Alarm Limits, All Alarm Deadbands, Setpoint Limits, Ramp Target, Ramp Rate SINGLE_LOOP_SS .DecimalPlacesOUT.OUT, Output Limits .DecimalPlacesPV.PV, .SP, .ESP, All Alarm Limits, All Alarm Deadbands, Setpoint Limits, Ramp Target, Ramp Rate EXT_SET .DecimalPlacesOUT.OUT, Output Limits .DecimalPlacesPV.PV, .SP, .ESP, .RAT_INP, All Alarm Limits, All Alarm Deadbands, Setpoint Limits, Ramp Target, Ramp Rate .DecimalPlacesOUT.OUT, Output Limits RATIO_SET .DecimalPlacesRATIO.RAT_ACT, .RAT_DES .DecimalPlacesPV.PV, .SP, All Alarm Limits, All Alarm Deadbands, Setpoint Limits, Ramp Target, Ramp Rate PRIMARY .DecimalPlacesOUT.OUT, Output Limits .DecimalPlacesPV.PV, .SP, .ESP, All Alarm Limits, All Alarm Deadbands, Setpoint Limits, Ramp Target, Ramp Rate SECONDARY .DecimalPlacesOUT.OUT, Output Limits Common HMI Elements 1-8PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 BlockDecimal Places TagAffected Tags .DecimalPlacesP_PV.P_PV, .P_SP, All Primary Alarm Limits, All Primary Alarm Deadbands, Primary Setpoint Limits, Primary Ramp Target, Primary Ramp Rate .DecimalPlacesS_PV.S_PV, .S_SP, .ESP, All Secondary Alarm Limits, All Secondary Alarm Deadbands, Secondary Setpoint Limits, Secondary Ramp Target, Secondary Ramp Rate CASCADE .DecimalPlacesOUT.OUT, Output Limits RESOURCE_STATUSN/AN/A 1.9Common Faceplate Elements The @CommonElements.pdl file contains a generic discrete I/O button and a generic analog I/O edit field. These objects can be manually copied to any user graphic. If the tag to be edited is part of a tag structure, then standard PCS 7 user authorization will be enforced. If the tag to be edited is a single tag (not part of a tag structure), no PCS 7 user authorization will be enforced since a single tag can not be assigned to a process area for user authorization enforcement. At runtime, the discrete I/O button provides the ability to edit any existing BOOL type tag. All changes to the BOOL tag are recorded in the WinCC operators log. The tag, along with On and Off messages, and On and Off button text are configured from the object properties dialog in Graphics Designer. At runtime, the analog I/O field provides the ability to edit any existing analog tag. All changes to the analog tag are recorded in the WinCC operators log. The tag, along with range limits and display format are configured from the object properties dialog in Graphics Designer. The @CommonElements.pdl file also contains an example of a button that allows a trend group created with the PCS 7 Online Trend Configuration Utility to be opened up directly by name instead of selecting it from a list. The trend group name and the monitor to display the trend group on are configurable. Use the properties dialog box to configure the Mouse Action for the object. 1.10Redundant Server Architecture In a redundant server architecture, client nodes connect to the appropriate server based on the health of each server and the health of the network connection between the client and each server. The health of any APACS+controller, and the health of the servers connection to any APACS+controller are not factors in determining which server a given client will connect to. Information about the health of APACS+controllers is displayed on the Lifebeat monitoring page. Common HMI Elements PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-011-9 1.11APACS+ Source Address The APACS+source address is displayed in the lower right hand corner of the standard view for each block type (in this case HMI_TEST2_CSIM.INC1.SL). Common HMI Elements 1-10PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 1.12Synchronization and Persistence of HMI Tag Values A feature of the PCS 7 HMI is the ability to synchronize and persist arbitrary internal WinCC tag values. The synchronization feature will guarantee that internal tag values remain consistent between redundant server partners in a redundant OS server architecture. The persistence feature will preserve tag values through a restart of the WinCC runtime, or a reboot of the OS server.Without this feature, internal tag values are always initialized to their configured start value. This feature can be used on single station nodes, single OS server nodes, or redundant OS server nodes. The synchronization and persistence features are not required for external tag values since those tag values are already persisted in the controller. The synchronization and persistence configuration is stored in a CSV file (SyncPersistTags.csv) in the RuntimeFramework directory in the WinCC project directory. CSV File Format The CSV file format allows blank lines and comment lines which are designated by a leading semicolon (;). The CSV file must have a header with a leading ":TAG" (case does not matter) and at least another column with PERSIST or SYNC (case does not matter).If the option column is missing, then none of the tags will be processed for that option. For example, if the PERSIST column exists, but the SYNC column does NOT, then the tags will only be processed for PERSIST. The TAG column should contain the full WinCC tagname. The option columns should have the value of "0", "f", or "false" (case does not matter) to NOT ENABLE this option for that tag. Any other value including a blank will ENABLE the option for that tag.Common HMI Elements PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-011-11 Here is an example:; This is a comment : Tag , EXTRA, PERSIST, SYNC, EXTRA, EXTRA Tag1_PS Tag2_PS , , 1, 10 Tag3_PS , , yes, -1 Tag4_P , , True, 0 Tag5_P,,attr1=55:attr2=100,F Tag6_P,,t,FALSE,, Tag7_P , , , False Tag8_S,,f,,,, Tag9_S,,f,+Tag10_S,,f,aaaaa=bbb,,, Tag11_S , , f ; another comment ; Define columns in different order in same file : Tag , SYNC, EXTRA, EXTRA Tag20_S Tag21_S,+,sss,wwww Tag22_S , 1 In this example, all the tags with a suffix of _P will only be added to the PERSIST list, _S will only be added to the SYNC list, and _PS will be added to both. This file shows the defaulted TRUE for blank or missing option columns.An option column can also contain a name/value series which will be further processed to add additional attributes to the output XML Node. The format should be as follows:attrname1=attrvalue1:attrname2=attrvalue2 Notice that an option column value can contain one or more name/value pairs separated by a colon (:).Common HMI Elements 1-12PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 The previous example generates the following XML file, assuming the PERSIST and SYNC configurations were empty to start with:

The 'ASONa' attribute is '??', which allows for later enhancements that may need to track which object created the item.It is not currently used. Common HMI Elements PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-011-13 1.13Disabled Alarm List A disabled alarm list is available that displays all disabled and locked APACS+alarms in the system. It is displayed by clicking the disabled alarm list button on the PCS 7 alarm logging status bar. PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-012-1 2SINGLE_LOOP_AFB 2.1SINGLE_LOOP_AFB Standard View SINGLE_LOOP_AFB 2-2PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 KeyNameTypeDescriptionTag 1IOFieldPVCustomized ObjectProcess VariablePV; PV_EUMAX; PV_EUMIN 2IOFieldSPCustomized ObjectSetpointSP;SPH; SPL; 3IOFieldOUTCustomized ObjectOutputVL;VLH; VLL 4PVUnitsI/O FieldPV unitsPV#unit 5SPUnitsI/O FieldSP unitsPV#unit 6OUTUnitsI/O FieldOutput unitsVL#unit 7ModeControlCustomized ObjectModeAUTO 8DescriptionStaticTextFunction Block Comment#comment 9BarLimitsCustomized ObjectAlarm limits displayPV_EUMAX; PV_EUMIN; HH_LIM; H_LIM; L_LIM; LL_LIM 10PVSPBargraphCustomized ObjectPV and SPPV; PV_EUMAX; PV_EUMIN; SP; 11OutputBargraph Customized ObjectOutput displayVL; VL_EUMAX; VL_EUMIN; The mode control Auto selects process automation, while Manual permits operator control of the output. In Auto mode, clicking the SP (set point) box displays an analog input edit box. Clicking is not allowed when the mode is set to Manual and PVTracking is enabled. Range limits are enforced by the SPH and SPL tags. File: @PG_SINGLE_LOOP_AFB_STANDARD.PDL SINGLE_LOOP_AFB PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-012-3 2.2SINGLE_LOOP_AFB Tuning View 1324567891011 KeyNameTypeDescriptionTag 1CheckBoxPVTrackCustomized ObjectPV Tracking EnabledPV_TRACK 2IOFieldSPHI/O FieldSP High LimitSPH 3IOFieldSPLI/O FieldSP Low LimitSPL 4ActionDirectStatic TextDirect ActingDIR 4ActionReverseStatic TextReverse Acting 5SPHUnits1Static TextSP UnitsPV#unit 5SPHUnits2Static TextSP UnitsPV#unit 6IOFieldVLHI/O FieldVL High LimitVLH 7IOFieldVLLI/O FieldVL Low LimitVLL 8IOFieldPGI/O FieldProportional GainPG, DIR 9IOFieldTII/O FieldIntegral TimeTI 10IOFieldTDI/O FieldDerivative TimeTD 11IOFieldDGI/O FieldDerivative GainDG Clicking the PVTrack check box produces a discrete input confirmation box. Clicking any of the eight edit boxes produces an analog input edit box. Range limits (if configured) are enforced by the WinCC Data Manager. The controller action (Direct/Reverse) is a read-only field. File: @PCS7_APACS_TUNING.PDL SINGLE_LOOP_AFB 2-4PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 2.3SINGLE_LOOP_AFB Alarm View The alarm view uses a standard WinCC Active X control. No modifications were made to it for the PCS 7 OS option. File: @PCS7_ALARM.PDL SINGLE_LOOP_AFB PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-012-5 2.4SINGLE_LOOP_AFB Ramp View KeyNameTypeDescriptionTag 1CheckBoxUseRRCustomized ObjectUse Ramp RateUSE_RR 2RampControlCustomized ObjectRamp ControlRAMP 3IOFieldTargetI/O FieldTarget SPTSP 4TargetUnitsStatic TextTarget SP UnitsPV#unit 5IOFieldRateI/O FieldSP Ramp RateR_RATE 6RateUnitsStatic TextSP Ramp Rate UnitsPV#unit 7IOFieldTimeI/O FieldSP Ramp TimeR_TIME Clicking the Use Ramp Rate check box will cause the Rate value below to be used to specify the ramping, and the Time value will be ignored. Otherwise, Time is used and Rate is ignored. A discrete input confirmation dialog will appear if ConfirmChange is TRUE. Clicking the Ramp Status edit box produces a discrete input confirmation box, if ConfirmChange is TRUE. Clicking any of the three edit boxes produces an analog input edit box. Range limits (if configured) are enforced by the WinCC Data Manager. File: @PCS7_APACS_RAMP.PDL SINGLE_LOOP_AFB 2-6PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 2.5SINGLE_LOOP_AFB Limits View KeyNameTypeDescriptionTag 1CheckBoxHHENCustomized ObjectHigh High Alarm EnableHH_EN 1CheckBoxHENCustomized ObjectHigh Alarm EnableH_EN 1CheckBoxLENCustomized ObjectLow Alarm EnableL_EN 1CheckBoxLLENCustomized ObjectLow LowAlarm EnableLL_EN 1CheckBoxHDENCustomized ObjectHigh Deviation Alarm EnableHD_EN 1CheckBoxLDENCustomized ObjectLow Deviation Alarm EnableLD_EN 1CheckBoxADENCustomized ObjectAbsolute Deviation Alarm EnableAD_EN 1CheckBoxIRENCustomized ObjectIncreasing ROC Alarm EnableIR_EN 1CheckBoxDRENCustomized ObjectDecreasing ROC Alarm EnableDR_EN 1CheckBoxARENCustomized ObjectAbsolute ROC Alarm EnableAR_EN 1CheckBoxOORENCustomized ObjectOut Of Range Alarm EnableOOR_EN 1CheckBoxQUALENCustomized ObjectQuality Alarm EnableQUAL_EN 2IOFieldHHLimitI/O FieldHigh High Alarm LimitHH_LIM 2IOFieldHLimitI/O FieldHigh Alarm LimitH_LIM 2IOFieldLLimitI/O FieldLow Alarm LimitL_LIM 2IOFieldLLLimitI/O FieldLow LowAlarm LimitLL_LIM 2IOFieldHDLimitI/O FieldHigh Deviation Alarm LimitHD_LIM 2IOFieldLDLimitI/O FieldLow Deviation Alarm LimitLD_LIM SINGLE_LOOP_AFB PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-012-7 KeyNameTypeDescriptionTag 2IOFieldADLimitI/O FieldAbsolute Deviation Alarm LimitAD_LIM 2IOFieldIRLimitI/O FieldIncreasing ROC Alarm LimitIR_LIM 2IOFieldDRLimitI/O FieldDecreasing ROC Alarm LimitDR_LIM 2IOFieldARLimitI/O FieldAbsolute ROC Alarm LimitAR_LIM 2IOFieldHHDBI/O FieldHigh High Alarm DeadbandHH_DB 2IOFieldHDBI/O FieldHigh Alarm DeadbandH_DB 2IOFieldLDBI/O FieldLow Alarm DeadbandL_DB 3IOFieldLLDBI/O FieldLow LowAlarm DeadbandLL_DB 3IOFieldHDDBI/O FieldHigh Deviation Alarm DeadbandHD_DB 3IOFieldLDDBI/O FieldLow Deviation Alarm DeadbandLD_DB 3IOFieldADDBI/O FieldAbsolute Deviation Alarm DeadbandAD_DB 3IOFieldIRDBI/O FieldIncreasing ROC Alarm DeadbandIR_DB 3IOFieldDRDBI/O FieldDecreasing ROC Alarm DeadbandDR_DB 3IOFieldARDBI/O FieldAbsolute ROC Alarm DeadbandAR_DB 4HHUnitsStatic TextHigh High Alarm Limit UnitsPV#unit 4HUnitsStatic TextHigh Alarm Limit UnitsPV#unit 4LUnitsStatic TextLow Alarm Limit UnitsPV#unit 4LLUnitsStatic TextLow LowAlarm Limit UnitsPV#unit 4HDUnitsStatic TextHigh Deviation Alarm Limit UnitsPV#unit 4LDUnitsStatic TextLow Deviation Alarm Limit UnitsPV#unit 4ADUnitsStatic TextAbsolute Deviation Alarm Limit UnitsPV#unit 4IRUnitsStatic TextIncreasing ROC Alarm Limit UnitsPV#unit 4DRUnitsStatic TextDecreasing ROC Alarm Limit UnitsPV#unit 4ARUnitsStatic TextAbsolute ROC Alarm Limit UnitsPV#unit Clicking any check box produces a discrete input confirmation box, if the ConfirmChange attribute for this block is TRUE. Clicking any of the edit boxes produces an analog input edit box. Range limits (if configured) are enforced by the WinCC Data Manager. In the case of the APACS+ported blocks running in the PCS 7 OS, all of the user editable fields are available and enabled. In the case of the APACS+blocks running in an ACM or CCM, the function block will have at most four of twelve alarm types configured. The fields for each unused alarm type are hidden in the user interface. This will happen automatically because the PCS 7 OS attribute of the field is not mapped to the ACM or CCM. File: @PCS7_APACS_ALARM_CONFIG.PDL SINGLE_LOOP_AFB 2-8PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 2.6SINGLE_LOOP_AFB Trend View The trend view is the standard view for displaying trends for the function block. For the SINGLE_LOOP_AFB function block the trend view displays the process value (PV), setpoint (SP), and output value (VL). Only one trend window is needed for each function block type. A script assigns proper tags to the trend control at runtime. The standard PCS 7 OS trend view is available for use with APACS+function blocks through normal PCS 7 OS procedures and configuration.The illustration below shows the trend view with rulers enabled. 821346711109125SINGLE_LOOP_AFB PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-012-9 Key Description 1Ruler (see key 12) 2Zoom 3Original view (return from zoom) 4Select time range 5Previous trend 6Next trend 7Stop (freeze)/start (continue)8Moveable cursor, shown when ruler, key 1, is enabled 9SP (blue) 10PV (green) 11VL (orange) 12Detachable window displayed when ruler (see key 1) is enabled. Shows process values at cursor position, which can be dragged. Color coded with trend curves. File: @PCS7_APACS_TREND3.PDL 2.7SINGLE_LOOP_AFB Faceplate Overview Window KeyDescription 1Alarm Group Display 2Lock/unlock messages button 3Alarm ACK button 4Go to primary graphic button (display function block's primary graphic) File: @PG_SINGLE_LOOP_AFB_OVERVIEW.PDL SINGLE_LOOP_AFB 2-10PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 2.8SINGLE_LOOP_AFB Faceplate Frame Shown in group display mode: KeyDescription 1Current tagname 2Pulldown view-selector list 3Go to loop display mode (all faceplate views, with the option of selecting a large trend display) File: @PG_SINGLE_LOOP_AFB.PDL 2.9SINGLE_LOOP_AFB Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. File: @PG_SINGLE_LOOP_AFB_VIEWLIST.PDL SINGLE_LOOP_AFB PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-012-11 2.10SINGLE_LOOP_AFB Loop Display Mode The loop display mode provides all six of the available single loop faceplates. It is not the default mode, and must be invoked from the initial (standard) view faceplate by the loop display mode button: From the loop display mode, you can expand the trend display to cover four views by clicking Display Large Trend. With the loop display expanded, you can shrink it to cover a single view by clicking Display Small Trend. SINGLE_LOOP_AFB 2-12PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 2.11SINGLE_LOOP_AFB View .PDL Files The following table lists the PCS 7 OS graphic files (.PDLs) that create the OS HMI for the SINGLE_LOOP_AFB views. These files can be opened and examined with the WinCC Graphics Designer program: Start > Simatic > WinCC > WinCC> (open project) > Graphics Designer (right click) > Open (select .PDL file) > Open. ViewFile Standard@PG_SINGLE_LOOP_AFB_STANDARD.PDL Tuning@PCS7_APACS_TUNING.PDL Alarm @PCS7_ALARM.PDL Ramp@PCS7_APACS_RAMP.PDL Limits @PCS7_APACS_ALARM_CONFIG.PDL Trend @PCS7_APACS_TREND3.PDL Faceplate Overview Window@PG_SINGLE_LOOP_AFB_OVERVIEW.PDL Faceplace Frame @PG_SINGLE_LOOP_AFB.PDL Faceplate View List@PG_SINGLE_LOOP_AFB_VIEWLIST.PDL Faceplate Loop@PL_SINGLE_LOOP_AFB.PDL PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-1 3Other Faceplates 3.1ANALOG_ALM_AFB Standard View The Standard view is the default view when the faceplate is first displayed in Group Display mode. It displays the function block description, process variable, and some alarm limits. The standard view contains a subset of the elements in the PG_SINGLE_LOOP_AFB_STANDARD.PDL file. See the SINGLE_LOOP_AFB section for details on the remaining elements. Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Other Faceplates 3-2PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Faceplate Loop View The loop view of the faceplate, displayed by clicking the loop display mode button on the group faceplate, displays all four faceplate views in one window. Clicking the Display Large Trend button increases the size of the trend view by four times and places it on top of two of four smaller views. Clicking the Display Small Trend button restores the trend view to the original size. View .PDL Files ViewFile Standard@PG_ANALOG_ALM_AFB_STANDARD.PDL Alarm @PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Limits @PCS7_APACS_ALARM_CONFIG.PDL (see the SINGLE_LOOP_AFB) Trend View (one pen)@PCS7_APACS_TREND1.PDL (see the SINGLE_LOOP_AFB) Faceplace Frame @PG_ANALOG_ALM_AFB.PDL (see the SINGLE_LOOP_AFB) Faceplate Overview Window@PG_ANALOG_ALM_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate View List@PG_ANALOG_ALM_AFB_VIEWLIST.PDL Faceplate Loop@PL_ANALOG_ALM_AFB.PDL Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-3 3.2DISCRETE_ALM_AFB Standard View The Standard view is the default view when the faceplate is first displayed in Group Display mode. It displays the function block description, alarm status, and certain alarm configuration values. The following table lists all of the significant objects on the view: KeyNameTypeDescriptionTag 1StaticTextOnStatic TextOn IndicatorDIN, DIN#string_1 StaticTextOffStatic TextOff IndicatorDIN#string_0 2DescriptionStatic TextFB comment#comment 3CheckBoxENCustomized object EnabledEN 4AlarmHighText Static TextAlarm Type HighLIM AlarmLowTextStatic TextAlarm Type Low Clicking the Enabled check box displays a discrete input confirmation box and asks for confirmation of changes, if the ConfirmChange attribute of the block is TRUE. Other Faceplates 3-4PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Faceplate Loop View Clicking the loop display mode button on the group faceplate displays both faceplate views in one window. View .PDL Files Unless otherwise indicated, faceplate views listed in the table below are identical or similar to corresponding views for the SINGLE_LOOP_AFB. See the SINGLE_LOOP_AFB sections for more information. ViewFile Standard@PG_DISCRETE_ALM_AFB_STANDARD.PDL Alarm@PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_DISCRETE_ALM_AFB.PDL (see the SINGLE_LOOP_AFB) Faceplate Overview Window @PG_DISCRETE_ALM_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate View List@PG_DISCRETE_ALM_AFB_VIEWLIST.PDL Faceplate Loop@PL_DISCRETE_ALM_AFB.PDL Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-5 3.3MOTOR_1OUT_AFB Standard View The Standard view is the default view when the faceplate is first displayed in Group Display mode. It displays the function block description, alarm status, and various motor status values and motor configuration values. Operation and Controls The On/Off indicator displays the current state of the MOTOR. The Out indicator displays the output of the function block. The Interlock indicator displays the current interlock status of the function block. The Start and Stop buttons allow operator control of the MOTOR. These buttons are only enabled when the function block is in Manual mode. Clicking the Start or Stop buttons brings up a confirmation box, if the ConfirmChange attribute of the block is TRUE.The Mode indicator displays the current mode of the function block (Auto/Manual). Other Faceplates 3-6PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 The Start Time indicator displays the maximum allowable time between the OUT signal going TRUE and PROOF feedback going TRUE before the FAIL output goes TRUE. A time to start MOTOR in excess of this value fires an alarm. Clicking the Start Time or Stop Time I/O field brings up a time input edit box. The Stop Time indicator displays the maximum allowable time between the OUT signal going FALSE and PROOF feedback going FALSE before the FAIL output goes TRUE. A time to stop MOTOR in excess of this value fires an alarm. Clicking the Start Time or Stop Time I/O field brings up a time input edit box. The Enabled check box controls the discrete alarm of the function block. Objects The following table lists all of the significant objects on the standard view: KeyNameTypeDescriptionTag 1StaticTextOnStatic TextMotor on IndicatorPROOF 2StaticTextOffStatic TextMotor off IndicatorPROOF StaticTextOff1Static TextMotor off Indicator 3StaticTextOutStartStatic TextOutput Start IndicatorOUT StaticTextOutStopStatic TextOutput Stop Indicator 4StaticTextInterlockOKStatic TextIntorlock OK IndicatorINTRLK StaticTextInterlockedStatic TextIntorlocked Indicator 5DescriptionStatic TextFB comment#comment 6ButtonStartCustomized objectStart MOTOR ControlSTART, AUTO 7ButtonStopCustomized objectStop MOTOR ControlSTOP, AUTO 8ModeControlCustomized objectModeAUTO 9IOFieldStartTimeCustomized objectStart time limitSTART_T 10IOFieldStopTimeCustomized objectStop time limitSTOP_T 11CheckBoxENCustomized objectEnabledA1EN Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-7 Faceplate Loop View Clicking the loop display mode button on the group faceplate displays both faceplate views in one window. View .PDL Files ViewFile Standard@PG_MOTOR_1OUT_AFB_STANDARD.PDL Alarm View@PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_MOTOR_1OUT_AFB.PDL (see the SINGLE_LOOP_AFB)Faceplate Overview Window@PG_MOTOR_1OUT_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate View List@PG_MOTOR_1OUT_AFB_VIEWLIST.PDL Faceplate Loop View@PL_MOTOR_1OUT_AFB.PDL Other Faceplates 3-8PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 3.4MOTOR_2OUT_AFB See MOTOR_1OUT_AFB for information about operation and controls. View .PDL Files ViewFile Standard@PG_MOTOR_2OUT_AFB_STANDARD.PDL Alarm View@PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_MOTOR_2OUT_AFB.PDL (see the SINGLE_LOOP_AFB) Faceplate Overview Window @PG_MOTOR_2OUT_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate View List@PG_MOTOR_2OUT_AFB_VIEWLIST.PDL Faceplate Loop View@PL_MOTOR_2OUT_AFB.PDL Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-9 3.5MOTOR_A_AFB Standard View The standard view is the default view when the faceplate is first displayed in Group Display mode. It displays the function block description, alarm status, and various motor status values and motor configuration values. Operation and Controls The On/Off indicators display the current state of the MOTOR. Only one is visible at a time. They are controlled by one tag, PROOF. The Out indicator displays the output of the function block. The Override indicator displays the current override status of the function block. The Permit indicator displays the current permit status of the function block. The Interlock indicator displays the current interlock status of the function block. The Start and Stop buttons allow operator control of the MOTOR. These buttons are only enabled when the function block is in Manual mode. The Mode indicator displays the current mode of the function block (Auto/Manual). The Failure Reset button lets operator clear the failure output. Other Faceplates 3-10PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 The Start Time indicator displays the maximum allowable time between the OUT signal going TRUE and PROOF feedback going TRUE before the FAIL output goes TRUE. A time to start MOTOR in excess of this value fires an alarm. The Stop Time indicator displays the maximum allowable time between the OUT signal going FALSE and PROOF feedback going FALSE before the FAIL output goes TRUE. A time to stop MOTOR in excess of this value fires an alarm. Clicking the Start, Stop or Reset buttons brings up a confirmation box and asks the user to confirm the change, if the ConfirmChange attribute is TRUE. Start and Stop buttons are only enabled when the function block is in Manual mode. The Failure Reset button is enabled when the tag FAIL is true. Objects The following table lists all of the significant objects on the standard view: KeyNameTypeDescriptionTag 1StaticTextOnStatic TextMotor on IndicatorPROOF 2StaticTextOffStatic TextMotor off IndicatorPROOF 3StaticTextOutStartStatic TextOutput Start IndicatorOUT StaticTextOutStopStatic TextOutput Stop Indicator 4StaticTextOverrideStatic TextOverride IndicatorOVERRD StaticTextPermitOverrideStatic TextPermit IndicatorOVERRD 5StaticTextPermitOKStatic TextPermit IndicatorPERMIT StaticTextNotPermittedStatic TextPermit Indicator 6StaticTextInterlockOKStatic TextIntorlock OK IndicatorINTRLK StaticTextInterlockedStatic TextIntorlocked Indicator 7DescriptionStatic TextFB comment#comment 8ButtonStartCustomized object Start MOTOR ControlSTART, AUTO 9ButtonStopCustomized object Stop MOTOR ControlSTOP, AUTO 10ModeControlCustomized object ModeAUTO 11ButtonResetCustomized object Reset Failure Output ControlFAIL 12IOFieldStartTimeCustomized object Start time limitSTRT_T 13IOFieldStopTimeCustomized object Stop time limitSTOP_T Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-11 Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Interlocks View The interlocks view is the same view used by the VALVE_A_AFB faceplate. See the VALVE_A_AFB section for details. Faceplate Loop View Clicking the loop display mode button on the group faceplate displays three faceplate views in one window. View .PDL Files ViewFile Standard@PG_MOTOR_A_AFB_STANDARD.PDL Alarm @PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_MOTOR_A_AFB.PDL (see the SINGLE_LOOP_AFB) Interlocks @PCS7_APACS_INTERLOCKS.PDL (see VALVE_A_AFB) Faceplate Overview Window@PG_MOTOR_A_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate View List@PG_MOTOR_A_AFB_VIEWLIST.PDL Faceplate Loop@PL_MOTOR_A_AFB.PDL Other Faceplates 3-12PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 3.6MOTOR_A_ALM_AFB See the MOTOR_A_AFB section. Operation and Controls Clicking the Enabled check box invokes a discrete input confirmation box, if the ConfirmChange attribute is TRUE. Limits View The Limits view shows the alarm configuration of the function block. Note that this faceplate view is not specific to the MOTOR_A_ALM function block. Every function block that implements discrete alarms references this .PDL file.The Type indicators display the alarm type. These types are hard coded. For MOTOR_A_ALM, they are displayed in the illustration that follows.Objects The following table lists all of the significant objects on the view: KeyNameTypeDescriptionTag 1CheckBoxA1ENCustomized objectA1 Alarm EnabledA1EN 2CheckBoxA2ENCustomized objectA2 Alarm EnabledA2EN 3CheckBoxA3ENCustomized objectA3 Alarm EnabledA3EN 4CheckBoxA4ENCustomized objectA4 Alarm EnabledA4EN Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-13 Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Interlocks View The interlocks view is the same view used by the VALVE_A_AFB faceplate. See the VALVE_A_AFB section for details. Faceplate Loop View The loop view of the faceplate, displayed by clicking the loop display mode button on the group faceplate, displays all four faceplate views in one window. Other Faceplates 3-14PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 View .PDL Files ViewFile Standard@PG_MOTOR_A_ALM_AFB_STANDARD.PDL (see the SINGLE_LOOP_AFB) Alarm @PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_MOTOR_A_ALM_AFB.PDL (see the SINGLE_LOOP_AFB) Interlocks @PCS7_APACS_INTERLOCKS.PDL (see the VALVE_A_AFB section) Limits@PCS7_APACS_DISCRETE_ALARM_CONFIG.PDL Faceplate View List@PG_MOTOR_A_ALM_AFB_VIEWLIST.PDL Faceplate Overview Window @PG_MOTOR_A_ALM_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate Loop View@PL_MOTOR_A_ALM_AFB.PDL Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-15 3.7BLK_VLV_1OUT_AFB Standard View The Standard view is the default view when the faceplate is first displayed in Group Display mode. It displays the function block description, alarm status, and various valve status values and valve configuration values. 123467891011512 Operation and Controls The Open/Travel/Close indicator displays the current state of the valve. The Out indicator displays the output of the function block. The Interlock indicator displays the current interlock status of the function block. The Open and Close buttons allow operator control of the valve. These buttons are only enabled when the function block is in Manual mode. The Mode indicator displays the current mode of the function block (Auto/Manual), and allows the user to change the mode. The Travel Time indicator displays the configured travel time of the function block. A valve travel time in excess of this value fires an alarm. The Enabled check box controls the 1 discrete alarm of the function block. The Alarm Type indicator displays the alarm type. In the case of the BLK_VLV_1OUT_AFB function block, this is always HIGH. Other Faceplates 3-16PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Clicking the Open or Close buttons brings up a confirmation box, if the ConfirmChange attribute is TRUE. These buttons are only enabled when the function block is in Manual mode. Clicking the ModeControl box displays a discrete input confirmation box, if the ConfirmChange attribute is TRUE and asks the user to select a choice from the radio buttons displayed. Clicking the Enabled check box brings up a discrete input confirmation box, if the ConfirmChange attribute is TRUE. Clicking the Travel Time I/O field brings up a time input edit box. Objects The following table lists all of the significant objects on the view: KeyNameTypeDescriptionTag 1StaticTextOpenStatic TextOpen IndicatorOP_VER 2StaticTextCloseStatic TextTravel IndicatorTRANS 3StaticTextTravelStatic TextClose IndicatorCL_VER 4StaticTextOutOpenStatic TextOutput Open IndicatorOUT StaticTextOutCloseStatic TextOutput Close Indicator 5StaticTextInterlockOKStatic TextIntorlock OK IndicatorINTRLK StaticTextInterlockedStatic TextIntorlocked Indicator 6DescriptionStatic TextFB comment#comment 7ButtonOpenCustomized object Open Valve ControlOPEN, AUTO 8ButtonCloseCustomized object Close Valve ControlCLOSE, AUTO 9ModeControlCustomized object ModeAUTO 10IOFieldTravelTimeCustomized object Travel Time LimitTRAV_T 11CheckBoxENCustomized object EnabledA1EN 12AlarmTypeLabelStatic TextAlarm Type Label Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-17 Faceplate Loop View The loop view of the faceplate, displayed by clicking the loop display mode button on the group faceplate, displays all four faceplate views in one window. View .PDL Files ViewFile Standard@PG_BLK_VLV_1OUT_AFB_STANDARD.PDL Alarm @PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_BLK_VLV_1OUT_AFB.PDL (see the SINGLE_LOOP_AFB) Interlocks @PCS7_APACS_INTERLOCKS.PDL (see the VALVE_A_AFB section) Faceplate View List@PG_BLK_VLV_1OUT_AFB_VIEWLIST.PDL Faceplate Overview Window @PG_BLK_VLV_1OUT_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate Loop View@PL_BLK_VLV_1OUT_AFB.PDL 3.8BLK_VLV_2OUT_AFB The BLK_VLV_2OUT_AFB faceplate is identical in every respect to the BLK_VLV_1OUT_AFB except in the names of the PDL files and any associated attribute values. In addition, the .OPEN_LATCH parameter is exposed as the OUT tag in the mapper template file instead of the .[OUT] for BLK_VLV_1OUT_AFB See the BLK_VLV_1OUT_AFB section for details. Other Faceplates 3-18PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 3.9VALVE_A_AFB Standard View The Standard view is the default view when the faceplate is first displayed in Group Display mode. It displays the function block description, alarm status, and various valve status values and valve configuration values. Operation and Controls The Open/Travel/Close indicator displays the current state of the valve. The Out indicator displays the output of the function block. The Override indicator displays the current override status of the function block. The Permit indicator displays the current permit status of the function block. The Interlock indicator displays the current interlock status of the function block. The Open and Close buttons allow operator control of the valve. These buttons are only enabled when the function block is in Manual mode. The Mode indicator displays the current mode of the function block (Auto/Manual), and allows the user to change the mode. The Failure Reset button allows the operator to clear the valves FAIL status. This button is only enabled when the function block is in a failed state. Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-19 The Open Time indicator displays the configured travel time of the function block. A valve open time in excess of this value fires an alarm. The Close Time indicator displays the configured travel time of the function block. A valve close time in excess of this value fires an alarm. Clicking the Permit or Interlock indicators switches to the Interlock view. If the faceplate is in loop display mode, this action is ignored since the interlocks view is already being displayed. Clicking the Open or Close buttons brings up a confirmation box, if ConfirmChange is TRUE. These buttons are only enabled when the function block is in Manual mode. Clicking the Reset button brings up a confirmation box, if ConfirmChange is TRUE. This button is only enabled when the function block is in FAIL mode. Clicking the ModeControl box displays a discrete input confirmation box, if ConfirmChange is TRUE and asks the user to select a choice from the radio buttons displayed. Clicking the Open Time or Close Time I/O fields displays a time input edit box. Standard View Objects The following table lists all of the significant objects on the view: KeyNameTypeDescriptionTag 1StaticTextOpenStatic TextOpen IndicatorOP_VER 2StaticTextCloseStatic TextTravel IndicatorOP_VER,CL_VER 3StaticTextTravelStatic TextClose IndicatorCL_VER 4StaticTextOutOpenStatic TextOutput Open IndicatorOUT StaticTextOutCloseStatic TextOutput Close Indicator 5StaticTextOverrideStatic TextOverride IndicatorOVERRD 6StaticTextPermitOKStatic TextPermit OK IndicatorPERMIT StaticTextPermitOverrideOKStatic TextPermit OK IndicatorOVERRD StaticTextNotPermittedStatic TextNot Permitted Indicator 7StaticTextInterlockOKStatic TextIntorlock OK IndicatorINTRLK StaticTextInterlockedStatic TextIntorlocked Indicator 8DescriptionStatic TextFB comment#comment 9ButtonOpenCustomized objectOpen Valve ControlOPEN, AUTO 10ButtonCloseCustomized objectClose Valve ControlCLOSE, AUTO 11ModeControlCustomized objectModeAUTO 12ButtonResetCustomized objectValve Reset controlFAIL 13IOFieldOpenTimeCustomized objectOpen Time LimitOPEN_T 14IOFieldCloseTimeCustomized objectClose Time LimitCLOSE_T Other Faceplates 3-20PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Interlocks View The Interlocks view displays permit status and description, and interlock status and descriptions. It also allows the user to place the block into and out of override mode. Note that this faceplate view is not specific to the VALVE_A_AFB function block. Every function block that implements multiple interlock inputs references this .PDL file.The Interlocks view actually has 11 interlock status indicators. The VALVE_A and VALVE_A_ALM blocks only have 10 interlock inputs, so the 11th indicator is hidden in these cases. The MOTOR_A and MOTOR_A_ALM blocks, which have 11 interlock inputs, will display all 11 indicators. Interlock indicators are displayed for all interlock inputs that have a non-blank interlock description.Unused or unconfigured interlocks should be configured with a blank interlock description in 4-mation. The faceplate will not display indicators for these unused interlocks. Interlocks Operation and Controls The Override button allows the operator to put the block into override. This button is only enabled when the function block is not in override. The Clear Override button allows the operator to take the block out of override. This button is only enabled when the function block is in override. Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-21 Status Indicators (12): In each case, the description is displayed for the appropriate input. If the input is TRUE (1) the text is black on a green background. If the input is FALSE (0) the text is white on a red background. If the description for an interlock is NULL, its Status indicator will be blank (same as gray background) regardless of TRUE or FALSE value. This generally means that this interlock is not in use and has a default value of TRUE. However, there is the possibility that an interlock is in use but has no description configured in the block (by oversight) and in the case, the operator will not be able to see the Status indicator of the interlock that may be preventing valve operation.Clicking the Override button brings up a confirmation box, if ConfirmChange is TRUE. This button is only enabled when the function block is not in override mode. Clicking the Clear Override button brings up a confirmation box, if ConfirmChange is TRUE. This button is only enabled when the function block is in override mode. Interlock Objects The following table lists all of the significant objects on the view: KeyNameTypeDescriptionTag 1StaticTextPermitStatic TextPermit IndicatorPERMIT, PERMIT_DESC 2StaticTextInterlock1Static TextInterlock 1 IndicatorINT01, INT01_DESC2StaticTextInterlock2Static TextInterlock 2 IndicatorINT02, INT02_DESC2StaticTextInterlock3Static TextInterlock 3 IndicatorINT03, INT03_DESC2StaticTextInterlock4Static TextInterlock 4 IndicatorINT04, INT04_DESC2StaticTextInterlock5Static TextInterlock 5 IndicatorINT05, INT05_DESC2StaticTextInterlock6Static TextInterlock 6 IndicatorINT06, INT06_DESC2StaticTextInterlock7Static TextInterlock 7 IndicatorINT07, INT07_DESC2StaticTextInterlock8Static TextInterlock 8 IndicatorINT08, INT08_DESC2StaticTextInterlock9Static TextInterlock 9 IndicatorINT09, INT09_DESC2StaticTextInterlock10Static TextInterlock 10 IndicatorINT10, INT10_DESC2StaticTextInterlock11Static TextInterlock 11 IndicatorINT11, INT11_DESC3ButtonOverrideCustomized object Open Valve ControlOPEN, AUTO 4ButtonClearOverrideCustomized object Close Valve ControlCLOSE, AUTO Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Other Faceplates 3-22PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Faceplate Overview Window The faceplate frame is the same view used by the SINGLE_LOOP_AFB faceplate, but renamed. See the SINGLE_LOOP_AFB section for details. Faceplate Loop View The loop display mode displays all three faceplates. It is not the default mode, and must be invoked from the initial (standard) view faceplate by the loop display mode button: View .PDL Files ViewFile Standard@PG_VALVE_A_AFB_STANDARD.PDL Interlocks@PCS7_APACS_INTERLOCKS.PDL Alarm @PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_VALVE_A_AFB.PDL (see the SINGLE_LOOP_AFB) Interlocks @PCS7_APACS_INTERLOCKS.PDLFaceplate View List@PG_VALVE_A_AFB_VIEWLIST.PDL Faceplate Overview Window@PG_VALVE_A_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate Loop View@PL_VALVE_A_AFB.PDL Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-23 3.10VALVE_A_ALM_AFB Standard View The standard view is the same view used by the VALVE_A_AFB faceplate, but renamed. See the VALVE_A_AFB section for details. Interlocks View The interlocks view is the same view used by the VALVE_A_AFB faceplate. See the VALVE_A_AFB section for details. Limits View The Limits view is the same view used by the MOTOR_A_ALM_AFB faceplate, but renamed AS follows For VALVE_A_ALM: Failure to close Failure to open Uncommanded close/open or rejected command (due to interlock) Failed limit switch (open and close verify inputs are set) The Enabled check boxes control the enabled status of the alarms. See the MOTOR_A_ALM_AFB section for details. Alarm View The Alarm view is the same view used by the SINGLE_LOOP_AFB faceplate. See the SINGLE_LOOP_AFB section for details. Faceplate Frame The faceplate frame is the same view used by the SINGLE_LOOP_AFB faceplate, but renamed. See the SINGLE_LOOP_AFB section for details. Faceplate View List The drop-down faceplate view list provides the names of the available faceplate views. Clicking a name selects a view. Other Faceplates 3-24PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Faceplate Overview Window The faceplate frame is the same view used by the SINGLE_LOOP_AFB faceplate, but renamed. See the SINGLE_LOOP_AFB section for detail Faceplate Loop View The loop display mode displays all four faceplates. It is not the default mode, and must be invoked from the initial (standard) view faceplate by the loop display mode button: View .PDL Files ViewFile Standard@PG_VALVE_A_ALM_AFB_STANDARD.PDL (See the VALVE_A_AFB) Interlocks@PCS7_APACS_INTERLOCKS.PDL (See the VALVE_A_AFB) Limits@PCS7_APACS_DISCRETE_ALARM_CONFIG.PDL (See the MOTOR_A_ALM_AFB) Alarm @PCS7_ALARM.PDL (see the SINGLE_LOOP_AFB) Faceplate Frame@PG_VALVE_A_ALM_AFB.PDL (see the SINGLE_LOOP_AFB) Faceplate View List@PG_VALVE_A_ALM_AFB_VIEWLIST.PDL Faceplate Overview Window @PG_VALVE_A_ALM_AFB_OVERVIEW.PDL (see the SINGLE_LOOP_AFB) Faceplate Loop View@PL_VALVE_A_ALM_AFB.PDL Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-25 3.11EXT_SET_AFB The EXT_SET_AFB faceplate is identical to the SINGLE_LOOP_AFB faceplate except for the addition of four tags as follows: TagTypeDescriptionACM Source ESPFLOATExternal Setpoint.SETPOINT.[ESP] EXTRNLBITExternal/Internal.SETPOINT.[EXTRNL] EXT#string_0TEXTREFInternal stringHardcoded in HMI file EXT#string_1TEXTREFExternal stringHardcoded in HMI file The Standard view of the faceplate has one additional "ESP" read-only field (1), and one "E/I" field (2) as shown below: All other views are identical to the SINGLE_LOOP_AFB faceplate. See the SINGLE_LOOP_AFB documentation for details on all other features. Other Faceplates 3-26PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 3.12RATIO_SET_AFB The RATIO_SET_AFB faceplate is identical to the EXT_SET_AFB faceplate except for the addition of five tags as follows: KeyTagTypeDescriptionACM Source 1RAT_INPFLOATExternal Input.[EXTINP] 2RAT_ACTFLOATActual Ratio.[ACTRAT] 3RAT_DESFLOATDesired Ratio.RATIO.[CSP] 4RATIO_MAXFLOATRatio Max.RATIO.HILIM 5RATIO_MINFLOATRatio Min.RATIO.LOLIM The Standard view of the faceplate has two additional bargraphs and three additional I/O fields for the ratio settings, as shown below: All other views are identical to the EXT_SET_AFB faceplate. See the EXT_SET_AFB documentation for details on all other features. 3.13PRIMARY_AFB The PRIMARY_AFB faceplate is identical to the SINGLE_LP_SS_AFB faceplate in all respects except filenames. See the SINGLE_LP_SS_AFB documentation for details on all other features. Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-27 3.14SECONDARY_AFB The SECONDARY_AFB faceplate is identical to the EXT_SET_AFB faceplate in all respects except filenames. See the EXT_SET_AFB documentation for details on all other features. 3.15CASCADE_AFB The CASCADE_AFB faceplate is essentially the PRIMARY_AFB and SECONDARY_AFB faceplates combined into one faceplate.The Standard view of the faceplate is shown below: All other group views are identical to the PRIMARY_AFB and SECONDARY_AFB faceplate views. The loop view is different in that there is a button on the title bar to switch between PRIMARY and SECONDARY loop views: Other Faceplates 3-28PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 See the PRIMARY_AFB and SECONDARY_AFB documentation for details on all other features. 3.16RESOURCE_STATUS_AFB The RESOURCE_STATUS_AFB displays controller hardware status. Standard View The standard view displays some controller overview information: Clicking the Scan Rate allows the user to change the controller scan rate.The Reset Statistics button resets the Max % Scan values. Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-29 Embedded Variables View The embedded variables view displays controller embedded variable information: All fields on the view are read-only. Alarm View The Alarm view is the same view used by the SINGLE_LOOP_AFB faceplate. See the SINGLE_LOOP_AFB section for details. Alarm Status View The alarm status view displays alarm status information: Other Faceplates 3-30PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Any alarm that is active is red. Any unACKed alarm blinks.Clicking any button acknowledges (ACK) that alarm. Error Log View The error log view displays error log information: Clicking the Details button brings up a help file containing information about the particular controller error.The Next Error button allows the user to step though each controller error. The Purge Errors button deletes controller errors from the error log. Miscellaneous View The miscellaneous view displays miscellaneous controller information: Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-31 All fields on the view are read-only. Error Status A View The error status A view displays errors about the primary controller in a redundant controller architecture: Clicking the Details button brings up a help file containing information about the particular controller error.The Manual Clear button clears the error from the controller. Error Status B View The error status B view displays errors about the backup controller in a redundant controller architecture. It is not displayed in non-redundant architectures. Other Faceplates 3-32PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-01 Clicking the Details button brings up a help file containing information about the particular controller error. The Manual Clear button clears the error from the controller. Loop View The loop view displays all the views on one window. Clicking the Display Alarm button toggles view three between the Alarm and Alarm Status views. Other Faceplates PCS 7/APACS+OS Symbols and Faceplates for V6.1 A5E00595267-013-33 3.17SINGLE_LP_SS_AFB The SINGLE_LP_SS_AFB faceplate is identical to the SINGLE_LOOP_AFB faceplate except for the addition of one binary input (SS). The tag structure (and HMI file) has one additional tag: TagTypeDescriptionACM Source SSBITStandby Sync.[SS] The standard view of the faceplate has an additional SS annunciator, which is tied to the SS tag. It is not editable.