Oregon Joint Use Violation Examples
description
Transcript of Oregon Joint Use Violation Examples
Oregon Joint Use Oregon Joint Use Violation ExamplesViolation ExamplesOregon Joint Use Oregon Joint Use Violation ExamplesViolation Examples
Stump The PanelStump The PanelStump The PanelStump The Panel
Question 1Question 1
Question 2Question 2
Question 3Question 3
Question 4Question 4
Question 5Question 5
Question 6Question 6
Question 7Question 7
Question 8Question 8
Question 9Question 9
Question 10Question 10
Question 1 Answer
Question 1 Answer
Obstruction on pole creates climbing hazard.
217A4
Obstruction on pole creates climbing hazard.
217A4
Question 2 Answer
Question 2 Answer
“Boxed” pole creates climbing hazard.
213, 236, 237, 238
“Boxed” pole creates climbing hazard.
213, 236, 237, 238
Question 3 Answer
Question 3 Answer
Inadequate vertical clearance between Power Company
primary riser and communication cable.
239G
Inadequate vertical clearance between Power Company
primary riser and communication cable.
239G
Question 4 Answer
Question 4 Answer
Inadequate vertical clearance between power supply conductor and
communication cable. Deteriorated pole hardware, standoff bracket rusted and
broken..
235C1, 214A
Inadequate vertical clearance between power supply conductor and
communication cable. Deteriorated pole hardware, standoff bracket rusted and
broken..
235C1, 214A
Question 5 Answer
Question 5 Answer
Inadequate vertical clearance between power
supply conductor and deck.
234C3d
Inadequate vertical clearance between power
supply conductor and deck.
234C3d
Question 6 Answer
Question 6 Answer
Inadequate vertical clearance between communication cable
and roadway.
232, Table 232-1
Inadequate vertical clearance between communication cable
and roadway.
232, Table 232-1
Question 7 Answer
Question 7 Answer
Inadequate mid-span clearance between power supply conductor
and communication cable.
235C2b(1)a
Inadequate mid-span clearance between power supply conductor
and communication cable.
235C2b(1)a
Question 8 Answer
Question 8 Answer
Fire hydrant has inadequate horizontal clearance from anchor
guy. Down guy in pedestrian area does not have substantial
and conspicuous marker.
231A, 217C
Fire hydrant has inadequate horizontal clearance from anchor
guy. Down guy in pedestrian area does not have substantial
and conspicuous marker.
231A, 217C
Question 9 Answer
Question 9 Answer Service conductor has inadequate
vertical clearance over roof.
234C3d
Service conductor has inadequate vertical clearance over roof.
234C3d
Question 10 Answer
Question 10 Answer
Sign has inadequate horizontal clearance from communications
cables at mid-span.
234C, Figure 234-1(b), Table 234-1
Sign has inadequate horizontal clearance from communications
cables at mid-span.
234C, Figure 234-1(b), Table 234-1