Oregon Joint Use Violation Examples Standards Subcommittee.

37
Oregon Joint Use Oregon Joint Use Violation Examples Violation Examples Standards Subcommittee Standards Subcommittee

Transcript of Oregon Joint Use Violation Examples Standards Subcommittee.

Page 1: Oregon Joint Use Violation Examples Standards Subcommittee.

Oregon Joint Use Oregon Joint Use Violation ExamplesViolation ExamplesOregon Joint Use Oregon Joint Use Violation ExamplesViolation Examples

Standards SubcommitteeStandards SubcommitteeStandards SubcommitteeStandards Subcommittee

Page 2: Oregon Joint Use Violation Examples Standards Subcommittee.

6

Utility OperatorBasics

Utility OperatorBasics

Secondary/Primary NeutralSecondary/Primary Neutral

PowerSpacePowerSpace

Worker SafetyClearance ZoneWorker Safety

Clearance Zone40”40”

CommunicationSpace

CommunicationSpace

Climbing Space Grounding/Bonding Permitting Clearances Structural Strength: Guying,

holes, loading calculations Tree Trimming

Climbing Space Grounding/Bonding Permitting Clearances Structural Strength: Guying,

holes, loading calculations Tree Trimming

Public Safety Clearance Zone

Public Safety Clearance Zone

Climbable 8’ Clear Zone

Climbable 8’ Clear Zone

Page 3: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceC000 MV COML COML P4321 Raise CATV B 235H2

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

C000 MV COML COML P4321 Raise CATV B 235H2

Violations

Communication Mainline (COML)Communication Mainline (COML)

Communication Mainline (COML)Communication Mainline (COML)

Page 4: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceX000 PC WEO Relocate/Move B 236

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

X000 PC WEO Relocate/Move B 236

Violations

Wireless Equipment (WEO)Wireless Equipment (WEO)

Page 5: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceX000 PV ANT PDLP Lower B 235

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

X000 PV ANT PDLP Lower B 235

Violations

Antenna (ANT)Antenna (ANT)

Power Drip-loop (PDLP)Power Drip-loop (PDLP)

Page 6: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 PG GRND PEDS Lower B 94B2c

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 PG GRND PEDS Lower B 94B2c

Violations

Ground Rod (GRND)Ground Rod (GRND)

Ground Wire (GRWR)Ground Wire (GRWR)

Page 7: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PV STEP PEDS Remove B 217A2bP000 DB CON Repair B 360A

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 PV STEP PEDS Remove B 217A2bP000 DB CON Repair B 360A

Violations

Conduit-PVC (CON)Conduit-PVC (CON)

Pole Step (STEP)Pole Step (STEP)

Page 8: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 PV SOB PEDS Raise B 217A2c

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 PV SOB PEDS Raise B 217A2c

Violations

Stand Off Bracket (SOB)Stand Off Bracket (SOB)

Pedestrian Surface (PEDS)Pedestrian Surface (PEDS)

Page 9: Oregon Joint Use Violation Examples Standards Subcommittee.

Curb (CURB)Curb (CURB)

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 PS ANC CURB Relocate/Move B 231B1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 PS ANC CURB Relocate/Move B 231B1

Violations

Anchor (ANC)Anchor (ANC)

Page 10: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceC000 PS GUY ANC Trim B 012C

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

C000 PS GUY ANC Trim B 012C

Violations

Anchor (ANC)Anchor (ANC)

Down Guy (GUY)Down Guy (GUY)

Page 11: Oregon Joint Use Violation Examples Standards Subcommittee.

Communication Drop (COMD)Communication Drop (COMD)

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceC000 AB COMD Remove B 214B

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

C000 AB COMD Remove B 214B

Violations

Page 12: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 PH POLE HYD Relocate/Move B 231A

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 PH POLE HYD Relocate/Move B 231A

Violations

Pole (POLE)Pole (POLE)Fire Hydrant

(HYD)Fire Hydrant (HYD)

Page 13: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 PV PDLP COML Raise Power B 235C1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 PV PDLP COML Raise Power B 235C1

Violations

Communication Mainline (COML)Communication Mainline (COML)

Power Drip-loop (PDLP)Power Drip-loop (PDLP)

Page 14: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 PV SEC COML Place Split Duct B 235C1P000 PR SEC Attach B 239A1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 PV SEC COML Place Split Duct B 235C1P000 PR SEC Attach B 239A1

Violations

Power Secondary (SEC)Power Secondary (SEC)

Communication Mainline (COML)Communication Mainline (COML)

Page 15: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceX000 PV COFO SLT Lower Fiber B 238D

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

X000 PV COFO SLT Lower Fiber B 238D

Violations

Communication Fiber-optic (COFO)Communication Fiber-optic (COFO)

Power Street Light (SLT)Power Street Light (SLT)

Page 16: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PV COMD PDLP Lower Telco B 235-5

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 PV COMD PDLP Lower Telco B 235-5

Violations

Power Drip-loop (PDLP)Power Drip-loop (PDLP)

Communication Drop (COMD)Communication Drop (COMD)

Page 17: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 U COMD PEDS Bury B 230A2d

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 U COMD PEDS Bury B 230A2d

Violations

Communication Drop (COMD)Communication Drop (COMD)

Pedestal (PED)Pedestal (PED)

Pedestrian Surface (PEDS)Pedestrian Surface (PEDS)

Page 18: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 MV COMD PEDS B1234 Tighten B 232

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 MV COMD PEDS B1234 Tighten B 232

Violations

Communication Drop (COMD)Communication Drop (COMD)

Pedestrian Surface (PEDS)Pedestrian Surface (PEDS)

Unusual Support (JOHN)Unusual Support (JOHN)

Page 19: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PV COML PDLP Lower Telco B 235C1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 PV COML PDLP Lower Telco B 235C1

Violations

Communication Mainline (COML)Communication Mainline (COML)

Power Drip-loop (PDLP)Power Drip-loop (PDLP)

Page 20: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PC COMD Relocate/Move B 236

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PC COMD Relocate/Move B 236

Violations

Communication Drop (COMD)Communication Drop (COMD)

Page 21: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PR COMD Attach B 239D3P000 PV SEC COML Place split Duct B 235C1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 PR COMD Attach B 239D3P000 PV SEC COML Place split Duct B 235C1

Violations

Communication Drop (COMD)Communication Drop (COMD)

Power Secondary (SEC)Power Secondary (SEC)

Communication Mainline (COML)Communication Mainline (COML)

Page 22: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PC TRM Relocate/Move B 236P000 PV SEC COML Place Split Duct B 235C1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 PC TRM Relocate/Move B 236P000 PV SEC COML Place Split Duct B 235C1

Violations

Communication Mainline (COML)Communication Mainline (COML)

Power Secondary (SEC)Power Secondary (SEC)

Communication Terminal (TRM)Communication Terminal (TRM)

Page 23: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceX000 PV COML SEC Lower B 235C1X000 PH COML POLE Attach B 234B1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

X000 PV COML SEC Lower B 235C1X000 PH COML POLE Attach B 234B1

Violations

Power Secondary (SEC)Power Secondary (SEC)Communication Mainline

(COML)Communication Mainline (COML)

Pole (POLE)Pole (POLE)

Page 24: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 MV PDLP COML P4321 Shorten B 235C2b(1)(a)

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 MV PDLP COML P4321 Shorten B 235C2b(1)(a)

Violations

Communication Mainline (COML)Communication Mainline (COML)

Power Drip-loop (PDLP)Power Drip-loop (PDLP)

Page 25: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceC000 MV COMD SEC P4321 Raise Power B 235C2b(1)(a)T000 MV COMD SEC P4321 Raise Power B 235C2b(1)(a)

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

C000 MV COMD SEC P4321 Raise Power B 235C2b(1)(a)T000 MV COMD SEC P4321 Raise Power B 235C2b(1)(a)

Violations

Communication Drop (COMD)Communication Drop (COMD)

Power Secondary (SEC)Power Secondary (SEC)

Page 26: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 MV PDRP COML B1234 Raise Power B 233C1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 MV PDRP COML B1234 Raise Power B 233C1

Violations

Power Service Drop (PDRP)Power Service Drop (PDRP)

Communication Mainline (COML)Communication Mainline (COML)

Page 27: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceX000 MV COMD PDRP B1234 Move 1st attachment B 235C1

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

X000 MV COMD PDRP B1234 Move 1st attachment B 235C1

Violations

Communication Drop (COMD)Communication Drop (COMD)

Power Service Drop (PDRP)Power Service Drop (PDRP)

Page 28: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 MV COMD DRSR B1234 Raise Telco B 232

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 MV COMD DRSR B1234 Raise Telco B 232

Violations

Drivable Surface (DRSR)Drivable Surface (DRSR)

Communication Drop (COMD)Communication Drop (COMD)

Page 29: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 MV SEC ROOF P4321 Raise Power B 234C

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 MV SEC ROOF P4321 Raise Power B 234C

Violations

Roof (ROOF)Roof (ROOF)

Power Secondary (SEC)Power Secondary (SEC)

Page 30: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 BV PDRP PEDS B1234 Raise Power B 234C3d(1)

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 BV PDRP PEDS B1234 Raise Power B 234C3d(1)

Violations

Power Service Drop (PDRP)Power Service Drop (PDRP)

Pedestrian Surface (PEDS)Pedestrian Surface (PEDS)

Page 31: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 BV PDLP ROOF B1234 Shorten B 234C3d(1)

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 BV PDLP ROOF B1234 Shorten B 234C3d(1)

Violations

Power Drip-loop (PDLP)Power Drip-loop (PDLP)

Roof (ROOF)Roof (ROOF)

Page 32: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 AB COMD Remove B 214B

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 AB COMD Remove B 214B

Violations

Communication Drop (COMD)Communication Drop (COMD)

Page 33: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceC000 BV COMD PDLP B1234 Relocate/Move B NEC

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

C000 BV COMD PDLP B1234 Relocate/Move B NEC

Violations

Communication Drop (COMD)Communication Drop (COMD)

Power Drip-loop (PDLP)Power Drip-loop (PDLP)

Page 34: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 BH PDRP WIN B1234 Relocate/Move B 234C3d(2)

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 BH PDRP WIN B1234 Relocate/Move B 234C3d(2)

Violations

Power Service Drop (PDRP)Power Service Drop (PDRP)

Window (WIN)Window (WIN)

Page 35: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 PC TREE Trim B 217A4

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 PC TREE Trim B 217A4

Violations

Trees/Vegetation (TREE)Trees/Vegetation (TREE)

Page 36: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceP000 AB XARM Remove B 214BP000 AB PBRK Remove B 214B

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

P000 AB XARM Remove B 214BP000 AB PBRK Remove B 214B

Violations

Power Bracket (PBRK)Power Bracket (PBRK)

Cross-arm (XARM)Cross-arm (XARM)

Page 37: Oregon Joint Use Violation Examples Standards Subcommittee.

U.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC ReferenceT000 PH Pole Pole Transfer B OPUC Joint Use PolicyC000 PH Pole Pole Transfer B OPUC Joint Use Policy

ViolationsU.C. Dev. Equip. 1 Equip. 2 Toward Suggested Action SEV. NESC Reference

T000 PH Pole Pole Transfer B OPUC Joint Use PolicyC000 PH Pole Pole Transfer B OPUC Joint Use Policy

Violations

Pole (POLE)Pole (POLE)