Operating Instructions Radar sensor for continuous level measurement of bulk solids VEGAPULS 69 4 … 20 mA/HART two-wire Document ID: 47247

Transcript of Operating Instructions - amshladinomery.czmanual_en).pdf · Operating Instructions. Radar sensor...

Operating InstructionsRadar sensor for continuous level measurement of bulk solids

VEGAPULS 694 … 20 mA/HART two-wire

Document ID: 47247

2

Contents

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Contents1 About this document

1.1 Function ........................................................................................................................... 41.2 Target group ..................................................................................................................... 41.3 Symbols used................................................................................................................... 4

2 For your safety2.1 Authorised personnel ....................................................................................................... 52.2 Appropriate use ................................................................................................................ 52.3 Warning about incorrect use ............................................................................................. 52.4 General safety instructions ............................................................................................... 52.5 CE conformity ................................................................................................................... 62.6 NAMUR recommendations .............................................................................................. 62.7 Radio license for Europe .................................................................................................. 62.8 Environmental instructions ............................................................................................... 7

3 Product description3.1 Configuration .................................................................................................................... 83.2 Principle of operation........................................................................................................ 93.3 Packaging, transport and storage ................................................................................... 103.4 Accessories and replacement parts ............................................................................... 10

4 Mounting4.1 General instructions ....................................................................................................... 134.2 Mounting versions, plastic horn antenna ........................................................................ 134.3 Mounting preparations, mounting strap .......................................................................... 164.4 Mounting instructions ..................................................................................................... 16

5 Connecting to power supply5.1 Preparing the connection ............................................................................................... 275.2 Connecting ..................................................................................................................... 275.3 Wiring plan, single chamber housing.............................................................................. 295.4 Wiring plan, double chamber housing ............................................................................ 305.5 Double chamber housing Ex d ....................................................................................... 325.6 Wiring plan, double chamber housing Ex d ia ................................................................ 335.7 Double chamber housing with DIS-ADAPT .................................................................... 345.8 Wiring plan - version IP 66/IP 68, 1 bar ........................................................................... 355.9 Switch-on phase............................................................................................................. 35

6 Set up with the display and adjustment module6.1 Insert display and adjustment module ............................................................................ 366.2 Adjustment system ......................................................................................................... 376.3 Measured value indication - Selection national language ............................................... 386.4 Parameter adjustment - Quick setup .............................................................................. 396.5 Parameter adjustment - Extended adjustment................................................................ 406.6 Saving the parameter adjustment data ........................................................................... 54

7 Setup with PACTware7.1 Connect the PC .............................................................................................................. 567.2 Parameter adjustment .................................................................................................... 577.3 Saving the parameter adjustment data ........................................................................... 58

8 Set up with other systems

3

Contents

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

8.1 DD adjustment programs ............................................................................................... 598.2 Field Communicator 375, 475 ........................................................................................ 59

9 Diagnosis, asset management and service9.1 Maintenance .................................................................................................................. 609.2 Measured value and event memory ............................................................................... 609.3 Asset Management function ........................................................................................... 619.4 Rectify faults ................................................................................................................... 659.5 Exchanging the electronics module ................................................................................ 689.6 Software update ............................................................................................................. 699.7 How to proceed if a repair is needed .............................................................................. 69

10 Dismount10.1 Dismounting steps.......................................................................................................... 7010.2 Disposal ......................................................................................................................... 70

11 Supplement11.1 Technical data ................................................................................................................ 7111.2 Dimensions .................................................................................................................... 79

Safety instructions for Ex areasPleasenotetheEx-specificsafetyinformationforinstallationandop-eration in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.Editing status:2014-05-22

4

1 About this document

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

1 About this document

1.1 FunctionThis operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc-tionsformaintenanceandfaultrectification.Pleasereadthisinforma-tion before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target groupThis operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.

Ex applicationsThis symbol indicates special instructions for Ex applications.

• ListThe dot set in front indicates a list with no implied sequence.

→ ActionThis arrow indicates a single action.

1 Sequence of actionsNumbers set in front indicate successive steps in a procedure.

Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.

5

2 For your safety

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

2 For your safety

2.1 Authorised personnelAll operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.During work on and with the device the required personal protective equipment must always be worn.

2.2 Appropriate useVEGAPULS 69 is a sensor for continuous level measurement.Youcanfinddetailedinformationabouttheareaofapplicationinchapter "Product description".Operational reliability is ensured only if the instrument is properly usedaccordingtothespecificationsintheoperatinginstructionsmanual as well as possible supplementary instructions.

2.3 Warning about incorrect useInappropriate or incorrect use of the instrument can give rise to application-specifichazards,e.g.vesseloverfillordamagetosystemcomponents through incorrect mounting or adjustment.

2.4 General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technicallyflawlessandreliablecondition.Theoperatorisresponsiblefor the trouble-free operation of the instrument.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.The safety approval markings and safety tips on the device must also be observed.Depending on the instrument version, the emitting frequencies are in the C or K band range. The low emitting frequencies are far below the internationally approved limit values. When used correctly, there is no danger to health.

6

2 For your safety

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

2.5 CE conformityThedevicefulfillsthelegalrequirementsoftheapplicableECguide-lines.ByaffixingtheCEmarking,weconfirmsuccessfultestingoftheproduct.YoucanfindtheCECertificateofConformityinthedownloadsectionof our homepage.

Electromagnetic compatibilityInstruments in four-wire or Ex-d-ia version are designed for use in an industrial environment. Nevertheless, electromagnetic interference from electrical conductors and radiated emissions must be taken into account, as is usual with class A instruments according to EN 61326-1.Iftheinstrumentisusedinadifferentenvironment,theelectromag-netic compatibility to other instruments must be ensured by suitable measures.

2.6 NAMUR recommendationsNAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are acceptedasthestandardinfieldinstrumentation.ThedevicefulfillstherequirementsofthefollowingNAMURrecom-mendations:

• NE 21 – Electromagnetic compatibility of equipment• NE 43 – Signal level for malfunction information from measuring

transducers• NE53–Compatibilityoffielddevicesanddisplay/adjustment

components• NE107–Self-monitoringanddiagnosisoffielddevicesFor further information see www.namur.de.

2.7 Radio license for EuropeThe instrument meets the LPR (Level Probing Radar) radio standard EN 302729-1/2.It is approved for unrestricted use inside and outside of closed ves-sels in countries of the EU and EFTA that have implemented this standard.For operation outside of closed vessels, the following conditions must befulfilled:

• Theinstallationmustbecarriedoutbytrainedqualifiedpersonnel• The instrument must be stationary mounted and the antenna

directed vertically downward• The mounting location must be at least 4 km away from the radio

astronomy stations, unless special permission was granted by the responsible national approval authority

• When installed within 4 to 40 km of a radio astronomy station, the instrument must not be mounted higher than 15 m above the ground.

7

2 For your safety

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Youcanfindalistwiththerespectiveradioastronomystationsinchapter "Supplement".

2.8 Environmental instructionsProtection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pro-tection.Theenvironmentmanagementsystemiscertifiedaccordingto DIN EN ISO 14001.Pleasehelpusfulfillthisobligationbyobservingtheenvironmentalinstructions in this manual:

• Chapter "Packaging, transport and storage"• Chapter "Disposal"

8

3 Product description

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

3 Product description

3.1 ConfigurationThetypelabelcontainsthemostimportantdataforidentificationanduse of the instrument:

2

1

14

15

13

12

11

56

43

78910

Fig. 1: Layout of the type label (example)1 Instrument type2 Product code3 Approvals4 Power supply and signal output, electronics5 Protection rating6 Measuring range7 Process and ambient temperature, process pressure8 Material, wetted parts9 Hardware and software version10 Order number11 Serial number of the instrument12 Data-Matrix-Code for Smartphone-App13 Symbol of the device protection class14 ID numbers, instrument documentation15 Reminder to observe the instrument documentation16 NotifiedauthorityforCEmarking17 Approval directive

The type label contains the serial number of the instrument. With it youcanfindthefollowinginstrumentdataonourhomepage:

• Product code (HTML)• Delivery date (HTML)• Order-specificinstrumentfeatures(HTML)• Operating instructions and quick setup guide at the time of ship-

ment (PDF)• Order-specificsensordataforanelectronicsexchange(XML)• Testcertificate(PDF)-optionalGo to www.vega.com, "VEGATools" and "Instrument search". Enter the serial number.Alternatively, you can access the data via your smartphone:

Type label

Serial number - Instru-ment search

9

3 Product description

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

• Download the smartphone app "VEGATools" from the "Apple App Store" or the "GooglePlayStore"

• Scan the Data Matrix code on the type label of the instrument or• Enter the serial number manually in the app

This operating instructions manual applies to the following instrument versions:

• Hardware version from 1.0.0• Software version from 1.0.1

The scope of delivery encompasses:

• Radar sensor• Documentation

– Quick setup guide VEGAPULS 69 – Instructions for optional instrument features – Ex-specific"Safety instructions" (with Ex versions) – ifnecessary,furthercertificates

• DVD "Software & Documents", containing – Operating instructions – Safety instructions – PACTware/DTM-Collection – Driver software

Information:In this operating instructions manual, the optional instrument features are described. The respective scope of delivery results from the order specification.

3.2 Principle of operationThe VEGAPULS 69 is a radar sensor for continuous level measure-mentofbulksolidsevenunderthemostdifficultprocessconditionsand in wide measuring ranges.Itisidealforuseinhigh,slendersilos,withpoorelyreflectionbulksolidssuchasflyash,plasticgranulesorwoodchipsaswellasstrongfalsereflectionsbyinstallations.Thisismadepossiblethankstothefunctional principle, a distance measurement through frequency shift-ing with a particularly small antenna opening angle.Theinstrumentisavailablewithdifferentantennasystemsandequip-ment for virtually all applications and processes:

• Plastic horn antenna or metal jacketed lens antenna• Optional or integrated rinsing air connection• Swivelling holder with seal against the process

The instrument emits a continuous radar signal via its antenna. This signal is frequency modulated with a sawtooth form. The emitted sig-nalisreflectedbythemediumandreceivedbytheantennaasecho.The frequency of the received signal always deviates from the actual emittingfrequency.Thefrequencydifferenceisproportionaltothedistanceandthustothefillingheight.Thisdifferenceiscalculated

Scope of this operating instructions manual

Scope of delivery

Application area

Functional principle

10

3 Product description

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

viaspecialalgorithmsinthesensorelectronics.Thedeterminedfill-ing height is then converted into a corresponding output signal and outputted as the measured value.

3.3 Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.

Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.

The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.

Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:

• Not in the open• Dry and dust free• Not exposed to corrosive media• Protected against solar radiation• Avoiding mechanical shock and vibration

• Storage and transport temperature see chapter "Supplement - Technicaldata-Ambientconditions"

• Relative humidity 20 … 85 %

3.4 Accessories and replacement partsThe display and adjustment module PLICSCOM is used for measured value indication, adjustment and diagnosis. It can be inserted into the sensor or the external display and adjustment unit and removed at any time.Youcanfindfurtherinformationintheoperatinginstructions"Display and adjustment module PLICSCOM" (Document-ID 27835).

The interface adapter VEGACONNECT enables the connection of communication-capable instruments to the USB interface of a PC. For parameter adjustment of these instruments, the adjustment software PACTware with VEGA-DTM is required.Youcanfindfurtherinformationintheoperatinginstructions"Interface adapterVEGACONNECT" (Document-ID 32628).

Packaging

Transport

Transport inspection

Storage

Storage and transport temperature

PLICSCOM

VEGACONNECT

11

3 Product description

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

The VEGADIS 81 is an external display and adjustment unit for VEGA plics® sensors.For sensors with double chamber housing the interface adapter "DIS-ADAPT" is also required for VEGADIS 81.Youcanfindfurtherinformationintheoperatinginstructions"VE-GADIS81" (Document-ID 43814).

The adapter "DIS-ADAPT" is an accessory part for sensors with double chamber housings. It enables the connection of VEGADIS 81 to the sensor housing via an M12 x 1 plug.Youcanfindfurtherinformationinthesupplementaryinstructions"AdapterDISADAPT" (Document-ID 45250).

VEGADIS 82 is suitable for measured value indication and adjustment of sensors with HART protocol. It is looped into the 4 … 20 mA/HART signal cable.Youcanfindfurtherinformationintheoperatinginstructions"VE-GADIS82" (Document-ID 45300).

PLICSMOBILE T61 is an external GSM/GPRS radio unit for transmis-sion of measured values and for remote parameter adjustment of plics® sensors. Adjustment is carried out via PACTware/DTM and the integrated USB connection.Youcanfindfurtherinformationinthesupplementaryinstructions"PLICSMOBILET61" (Document-ID 37700).

PLICSMOBILE is an internal GSM/GPRS radio unit for transmission of measured values and for remote parameter adjustment of plics® sensors. Adjustment is carried out via PACTware/DTM and the inte-grated USB connection.Youcanfindfurtherinformationinthesupplementaryinstructions"PLICSMOBILEGSM/GPRSradiomodule" (Document-ID 36849).

The protective cover protects the sensor housing against soiling and intense heat from solar radiation.Youwillfindadditionalinformationinthesupplementaryinstructionsmanual "Protective cover" (Document-ID 34296).

Screwedflangesareavailableindifferentversionsaccordingtothefollowing standards: DIN 2501, EN 1092-1, BS 10, ANSI B 16.5, JIS B 2210-1984, GOST 12821-80.Youcanfindadditionalinformationinthesupplementaryinstructionsmanual "FlangesaccordingtoDIN-EN-ASME-JIS" (Document-ID 31088).

For mounting the instrument with plastic horn antenna to a socket, twoflangeversionsareavailable:thecombicompressionflangeandtheadapterflangeYoucanfindadditionalinformationinchapter"Mounting" of this operating instruction.

VEGADIS 81

DIS-ADAPT

VEGADIS 82

PLICSMOBILE T61

PLICSMOBILE

Protective cap

Flanges

Flanges with plastic horn antenna

12

3 Product description

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

A mounting strap is available for mounting the instrument with plastic horn antenna to the wall or ceiling.Youcanfindadditionalinformationinchapter"Mounting" of this operating instruction.

Electronics module "VEGAPULS series 60" is a replacement part for radarsensorsofVEGAPULSseries60.Adifferentversionisavailablefor each type of signal output.Youcanfindfurtherinformationintheoperatinginstructions"Elec-tronicsmoduleVEGAPULSseries60" (Document-ID 36801).

The supplementary electronics is a replacement part for sensors with double chamber housing and 4 … 20 mA/HART - two-wire.Youcanfindfurtherinformationintheoperatinginstructions"Supple-mentaryelectronicsfor4…20mA/HART-two-wire" (Document-ID 42764).

Mounting strap with plas-tic horn antenna

Electronics module

Supplementary electron-ics for double chamber housing

13

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

4 Mounting

4.1 General instructionsProtect your instrument against moisture ingress through the following measures:

• Use the recommended cable (see chapter "Connecting to power supply")

• Tighten the cable gland• Loop the connection cable downward in front of the cable gland

This applies particularly to:

• Outdoor mounting• Installations in areas where high humidity is expected (e.g. through

cleaning processes)• Installations on cooled or heated vessels

Make sure that all parts of the instrument exposed to the process are suitable for the existing process conditions.These are mainly:

• Active measuring component• Processfitting• Process seal

Process conditions are particularly:

• Process pressure• Process temperature• Chemical properties of the medium• AbrasionandmechanicalinfluencesYoucanfindthespecificationsoftheprocessconditionsinchapter"Technicaldata" as well as on the type label.

4.2 Mounting versions, plastic horn antennaThe optional mounting strap allows simple mounting of the instru-ment on a wall, ceiling or boom. Especially with open vessels, this is a simpleandeffectivewaytoalignthesensortothesurfaceofthebulksolid material.The following versions are available:

• Length 300 mm• Length 170 mm

The instrument is normally mounted with a strap vertically on the ceiling.This allows swivelling the sensor up to 180° for optimal orientation and rotating for optimal connection.

Protection against mois-ture

Suitability for the process conditions

Mounting strap

Mounting strap - Ceiling mounting

14

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Fig. 2: Ceiling mounting via the mounting strap with length 300 mm

Fig. 3: Rotating with ceil mounting

Asanalternativethestrapmountingiscarriedouthorizontallyorobliquely.

> 200 mm(7.87")

Fig. 4: Wall mounting horizontally via the mounting strap with length 170 mm

Mounting strap - Wall mounting

15

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Fig. 5: Wall mounting with inclined wall via the mounting strap with length 300 mm

Two versions are available for mounting the instrument on a socket:

• CombicompressionflangefittingtoDN80(ASME3"andJIS80)• AdapterflangefromDN100(ASME4"orJIS100)In the case of instruments with single chamber housing, the compres-sionflangecanbepasseddirectlyoverthehousing.Withdoublechamber housings, a later mounting this way is not possible, the mountingmethodmustbespecifiedwhenordering.

1

Fig.6:Combicompressionflange1 Combicompressionflange

Flange

16

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

3

1

2

Fig.7:Adapterflange1 Connection screw2 Adapterflange3 Process seal

Youcanfinddrawingsofthesemountingoptionsinchapter"Dimen-sions".

4.3 Mounting preparations, mounting strapThe strap is supplied unassembled and must be screwed to the sensor before setup with three hexagon screws M5 x 10 and spring washers. Max. torque, see chapter "Technicaldata". Required tools: Allenwrenchsize4.There are two ways to screw the strap onto the sensor. Depending on the selected version, the sensors can be swivelled in the strap as follows:

• Single chamber housing – Angleofinclination180°,infinitelyvariable – Angle of inclination in three steps 0°, 90° and 180°

• Double chamber housing – Angleofinclination90°,infinitelyvariable – Angle of inclination in two steps 0° and 90°

4.4 Mounting instructionsRadar sensors for level measurement emit electromagnetic waves. Thepolarizationisthedirectionoftheelectricalcomponentofthesewaves.Thepolarizationdirectionismarkedbyanoseonthehousing,seefollowing drawing:

Polarisation

17

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

1

Fig. 8: Position of the polarisation1 Nose for marking the direction of polarisation

Information:Whenthehousingisrotated,thedirectionofpolarizationchangesandhencetheinfluenceofthefalseechoonthemeasuredvalue.Please keep this in mind when mounting or making changes later.

Mount the sensor at least 200 mm (7.874 in) away from the vessel wall.

200 mm(7.87")

Fig. 9: Mounting the radar sensor on the vessel top

If you cannot maintain this distance, you should carry out a false signal storage during setup. This applies particularly if buildup on the vessel wall is expected. In such cases, we recommend repeating the false signal storage at a later date with existing buildup.

Theinstrumentshouldnotbemountedtooclosetotheinflowingmedium, as the microwave signal could be disrupted.

SilowithfillingfromtopTheoptimalmountingpositionisoppositethefillingaperture.Toavoidheavysoiling,thedistancetoanyfilterordustexhaustershouldbeaslarge as possible.

Installation position

Inflowingmedium

18

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Fig.10:Mountingoftheradarsensorwithinflowingmedium

SilowithlateralfillingInbulksolidssiloswithlateralpneumaticfillingtheinstrumentshouldnotbemountedabovethefillingstream,asthemicrowavesignalwillbedisrupted.Theoptimalmountingpositionisnexttothefillingaper-ture.Toavoidheavysoiling,thedistancetoanyfilterordustexhaustershould be as large as possible.

19

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Fig.11:Mountingoftheradarsensorwithinflowingmedium

Information:The mounting socket should be as short as possible and its end rounded. This reduces false echoes from the vessel mounting socket.

Fig. 12: Recommended socket mounting

fthemediumhasgoodreflectiveproperties,youcanalsomounttheVEGAPULS 69 on longer sockets. Approximate socket heights are shown in the following illustration.

Information:When mounting on longer sockets, we recommend carrying out a false echo storage (see chapter "Parameter adjustment").

Type of socket

20

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

d

h

The below charts specify the max. socket piece h depending on the diameter d.

Socket diameter d Socket length h

80 mm ≤200mm

100 mm ≤300mm

150 mm ≤500mm

Socket diameter d Socket length h

3" ≤7.87in

4" ≤11.8in

6" ≤19.7in

In order to measure as much of the vessel volume as possible, the sensor should be aligned so that the measuring beam reaches the lowest level in the vessel. In a cylindrical silo with conical outlet, the sensor is mounted anywhere from one third to one half of the vessel radius from outside wall (see following drawing).

Orientation

21

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

rrr.../1 3 /1 2

Fig. 14: Mounting position and orientation

With the help of an optional swivelling holder, the sensor can be easily aligned to the vessel centre. The necessary angle of inclination depends on the vessel dimensions. It can be easily checked with a suitable bubble tube or mechanic's level on the sensor.

22

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

d

a

α

Fig.15:ProposalforinstallationafterorientationVEGAPULS69

The following table shows the necessary angle of inclination. It depends on the measuring distance and the distance "a" between vessel centre and installation position.

Distance d (m)

2° 4° 6° 8° 10°

2 0.1 0.1 0.2 0.3 0.4

4 0.1 0.3 0.4 0.6 0.7

6 0.2 0.4 0.6 0.8 1.1

8 0.3 0.6 0.8 1.1 1.4

10 0.3 0.7 1.1 1.4 1.8

15 0.5 1.0 1.6 2.1 2.6

20 0.7 1.4 2.1 2.8 3.5

25 0.9 1.7 2.6 3.5 4.4

30 1 2.1 3.2 4.2 5.3

35 1.2 2.4 3.7 4.9 6.2

40 1.4 2.8 4.2 5.6 7.1

45 1.6 3.1 4.7 6.3 7.9

50 1.7 3.5 5.3 7 8.8

60 2.1 4.2 6.3 8.4 10.5

70 2.4 4.9 7.3 9.7 12.2

23

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Distance d (m)

2° 4° 6° 8° 10°

80 2.8 5.6 8.4 11.1 13.9

90 3.1 6.3 9.4 12.5 15.6

100 3.5 7 10.5 13.9 17.4

110 3.8 7.7 11.5 15.3 19.1

120 4.2 8.4 12.5 16.7 20.8Example:In a vessel 20 m high, the installation position of the sensor is 1.4 m from the vessel centre.The necessary angle of inclination of 4° can be read out from this chart.Proceed as follows to adjust the angle of inclination with the swivelling holder:1. Loosen the six clamping screws on the swivelling holder with a

size5Allenwrench.2. Align the sensor, check angle of inclination

Information:The max. angle of inclination of the swivelling holder is approx. 10°3. Tighten the clamping screws, torque max. 8 Nm.

The mounting location of the radar sensor should be a place where no otherequipmentorfixturescrossthepathofthemicrowavesignals.Vessel installations, such as e.g. ladders, limit switches, heating spi-rals, struts, etc., can cause false echoes and impair the useful echo. Make sure when planning your measuring site that the radar sensor has a "clear view" to the measured product.In case of existing vessel installations, a false echo storage should be carried out during setup.If large vessel installations such as struts or supports cause false echoes, these can be attenuated through supplementary measures. Small,inclinedsheetmetalbafflesabovetheinstallationsscattertheradarsignalsandpreventdirectinterferingreflections.

Fig.16:Coverflat,large-areaprofileswithdeflectors

Large material heaps are best measured with several instruments, which can be mounted on e.g. traverse cranes. For this type of ap-plication it is advantageous to orient the sensor perpendicular to the bulk solid surface.

Vessel installations

Material heaps

24

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Thesensorsdonotinfluenceeachother.

Information:Keep in mind that for these applications, the sensors are designed for relatively slow level changes. If the sensor is used on a movable boom, the max. measuring rate must be observed (see chapter "Technicaldata").

Fig. 17: Radar sensors on traverse crane

Instruments for a temperature range up to 200° C have a spacer betweenprocessfittingandelectronicshousing.Thisspacerisusedto thermally decouple the electronics from the high process tempera-tures.

Information:The spacer may only be incorporated up to a maximum of 50 mm into the vessel insulation. Only then is a reliable temperature decoupling guaranteed.

max

. 50

mm

(1

.97"

)

1

2

3

Fig. 18: Mounting the instrument on insulated vessels.1 Electronicshousing2 Spacer3 Vessel insulation

Mounting in the vessel insulation

25

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Thewallsofmultiple-chambersilosareoftenmadeofprofilematerial,e.g.profilesheeting,toensuretherequiredstability.Iftheradarsen-sor is mounted very close to a heavily structured vessel wall, substan-tialinterferingreflectionscanbegenerated.Thusthesensorshouldbe mounted at the largest possible distance from the separating wall.The best mounting location is on the outer wall of the silo, with the sensor pointing towards the discharge opening in the silo centre. This can be accomplished, for example, with the mounting strap.

Fig. 19: Installation and orientation in multiple chamber silos

Fig. 20: Installation and orientation in multiple chamber silos

To avoid heavy buildup and dust on the antenna, the sensor should not be mounted close to the dust exhauster inside the vessel.

Mounting in multiple chamber silo

Dust deposits

26

4 Mounting

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

To avoid buildup, especially with strong condensation, air rinsing is recommended.The VEGAPULS 69 with plastic horn antenna is optionally available withrinsingairconnection.Themechanicalconfigurationdiffersac-cordingtotheflangeversion.

Fig.21:Rinsingairconnectionwithcompressionflange

Fig.22:Rinsingairconnectionwithadapterflange

The VEGAPULS 69 with metal jacketed lens antenna is equipped with a rinsing air connection as a standard feature.

27

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

5 Connecting to power supply

5.1 Preparing the connectionAlways keep in mind the following safety instructions:

• Connect only in the complete absence of line voltage• If overvoltage surges are expected, overvoltage arresters should

be installed

Power supply and current signal are carried on the same two-wire cable.Theoperatingvoltagecandifferdependingontheinstrumentversion.Thedataforpowersupplyarespecifiedinchapter"Technicaldata".Provide a reliable separation between the supply circuit and the mains circuits according to DIN EN 61140 VDE 0140-1.Keepinmindthefollowingadditionalfactorsthatinfluencetheoperat-ing voltage:

• Lower output voltage of the power supply unit under nominal load (e.g. with a sensor current of 20.5 mA or 22 mA in case of fault)

• Influenceofadditionalinstrumentsinthecircuit(seeloadvaluesinchapter "Technicaldata")

The instrument is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326-1 for industrial areas, screened cable should be used.Use cable with round cross section for instruments with housing and cablegland.Toensurethesealeffectofthecablegland(IPprotectionrating),findoutwhichcableouterdiameterthecableglandissuitablefor.Useacableglandfittingthecablediameter.We generally recommend the use of screened cable for HART multi-drop mode.

With plastic housing, the NPT cable gland or the Conduit steel tube must be screwed without grease into the threaded insert.Max. torque for all housings see chapter "Technicaldata".

If screened cable is required, we recommend connecting the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the ground potential (low impedance).With Ex systems, the grounding is carried out according to the instal-lation regulations.

5.2 ConnectingThe voltage supply and signal output are connected via the spring-loaded terminals in the housing.

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and grounding

Connection technology

28

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Connection to the display and adjustment module or to the interface adapter is carried out via contact pins in the housing.

Information:The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When reinserting the terminal block, you should hear it snap in.

Proceed as follows:1. Unscrew the housing cover2. If a display and adjustment module is installed, remove it by turn-

ing it slightly to the left.3. Loosen compression nut of the cable entry gland4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires5. Insert the cable into the sensor through the cable entry

Fig. 23: Connection steps 5 and 6 - Single chamber housing

Connection procedure

29

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Fig. 24: Connection steps 5 and 6 - Double chamber housing

6. Insert the wire ends into the terminals according to the wiring plan

Information:Solidcoresaswellasflexiblecoreswithwireendsleevesareinsert-eddirectlyintotheterminalopenings.Incaseofflexiblecoreswithoutend sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again.Youcanfindfurtherinformationonthemax.wirecross-sectionunder"Technicaldata/Electromechanicaldata"7. Check the hold of the wires in the terminals by lightly pulling on

them8. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation9. Tighten the compression nut of the cable entry gland. The seal

ring must completely encircle the cable10. Reinsert the display and adjustment module, if one was installed11. Screw the housing cover back onTheelectricalconnectionisfinished.

5.3 Wiring plan, single chamber housingThe following illustration applies to the non-Ex as well as to the Ex-ia version.

30

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

51 2+( ) (-) 6 7 8

4...20mA

2

3

41

Fig.25:Electronicsandterminalcompartment,singlechamberhousing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Groundterminalforconnectionofthecablescreen

5.4 Wiring plan, double chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-ia version.

5 6 7 8

4...20mA

1 2+( ) (-)

2

11

Fig.26:Electronicscompartment,doublechamberhousing1 Internal connection to the connection compartment2 For display and adjustment module or interface adapter

Information:Connection of an external display and adjustment unit through the electronics compartment is not possible with this double chamber housing.

Electronics and terminal compartment

Electronics compartment

31

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

51 2+( ) (-) 6 7 8

4...20mA Display

2

3

41

Fig.27:Terminalcompartment,doublechamberhousing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Groundterminalforconnectionofthecablescreen

Information:Parallel use of an external display and adjustment unit and a display and adjustment module in the terminal compartment is not supported.

1

USB

Status

TestSIM-Card

1 2+( ) (-)

Fig.28:Terminalcompartment,radiomodulePLICSMOBILE1 Voltage supply

Youcanfinddetailedinformationonconnectioninthesupplementaryinstructions "PLICSMOBILEGSM/GPRSradiomodule".

Terminal compartment

Terminal compartment - Radio module PLICS-MOBILE

32

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

5.5 Double chamber housing Ex d

5 6 7 8

4...20mA

2

1 2+( ) (-)

11

Fig.29:Electronicscompartment,doublechamberhousingExd1 Internal connection to the terminal compartment2 For display and adjustment module or interface adapter

51 2+( ) (-) 6 7 8

4...20mA

2

3

41

Fig.30:Terminalcompartment,doublechamberhousing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Groundterminalforconnectionofthecablescreen

Information:The use of an external display and adjustment unit and a display and adjustment module in parallel in the connection compartment is not supported.

Electronics compartment

Terminal compartment

33

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

5.6 Wiring plan, double chamber housing Ex d ia

31

2

5 6 7 81 2( ) (-)+

4...20mA

Fig.31:Electronicscompartment,doublechamberhousingExdia1 Internal connection to the connection compartment2 For display and adjustment module or interface adapter3 Internal connection to the plug connector for external display and adjust-

ment unit (optional)

Note:HART multidrop mode is not possible when using an Ex-d-ia instru-ment.

4...20mA

1 2+( ) (-) 2

1

Fig.32:Terminalcompartment,doublechamberhousingExdia1 Voltage supply, signal output2 Groundterminalforconnectionofthecablescreen

34

1 2

Fig.33:Topviewoftheplugconnector1 Pin 12 Pin 23 Pin 34 Pin 4

Electronics compartment

Terminal compartment

Plug M12 x 1 for external display and adjustment unit

34

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Contact pin Colour connection ca-ble in the sensor

Terminal, electronics module

Pin 1 Brown 5

Pin 2 White 6

Pin 3 Blue 7

Pin 4 Black 8

5.7 Double chamber housing with DIS-ADAPT

3

1

2

Fig.34:ViewtotheelectronicscompartmentwithDISADAPTforconnectionofthe external display and adjustment unit1 DIS-ADAPT2 Internal plug connection3 Plug connector M12 x 1

34

1 2

Fig. 35: View to the plug connector M12 x 11 Pin 12 Pin 23 Pin 34 Pin 4

Contact pin Colour connection ca-ble in the sensor

Terminal, electronics module

Pin 1 Brown 5

Pin 2 White 6

Pin 3 Blue 7

Pin 4 Black 8

Electronics compartment

Assignment of the plug connector

35

5 Connecting to power supply

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

5.8 Wiring plan - version IP 66/IP 68, 1 bar

1

2

Fig. 36: Wire assignment in permanently connected connection cable1 brown (+) and blue (-) to power supply or to the processing system2 Shielding

5.9 Switch-on phaseAfter connecting the instrument to power supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 s:

• Internal check of the electronics• Indication of the instrument type, hardware and software version,

measurement loop name on the display or PC• Indication of the status message "F 105 Determine measured

value" on the display or PC• The output signal jumps to the set fault current

As soon as a plausible measured value is found, the corresponding current is outputted to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting.

Wire assignment, con-nection cable

36

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

6 Set up with the display and adjustment module

6.1 Insert display and adjustment moduleThe display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchooseanyoneoffourdiffer-ent positions - each displaced by 90°. It is not necessary to interrupt the power supply.Proceed as follows:1. Unscrew the housing cover2. Place the display and adjustment module in the requested posi-

tion onto the electronics and turn to the right until it snaps in3. Screw housing cover with inspection window tightly back onDisassembly is carried out in reverse order.The display and adjustment module is powered by the sensor, an ad-ditional connection is not necessary.

Fig. 37: Installing the display and adjustment module in the electronics compart-ment of the single chamber housing

37

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

1 2

Fig. 38: Insertion of the display and adjustment module into the double chamber housing1 In the electronics compartment2 Intheterminalcompartment(withEx-d-iaversionnotpossible)

Note:Ifyouintendtoretrofittheinstrumentwithadisplayandadjustmentmodule for continuous measured value indication, a higher cover with an inspection glass is required.

6.2 Adjustment system

1

2

Fig. 39: Display and adjustment elements1 LC display2 Adjustment keys

• [OK] key: – Move to the menu overview

Key functions

38

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

– Confirmselectedmenu – Edit parameter – Save value

• [->] key: – Presentation, change measured value – Select list entry – Select editing position

• [+] key: – Change value of the parameter

• [ESC] key: – Interrupt input – Jump to next higher menu

The instrument is adjusted via the four keys of the display and adjust-ment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 60 minutes after the last pressing of a key, an automatic reset tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmedwith [OK] will not be saved.

6.3 Measured value indication - Selection national language

With the [->]keyyoumovebetweenthreedifferentindicationmodes.Inthefirstview,theselectedmeasuredvalueisdisplayedinlargedigits.In the second view, the selected measured value and a correspond-ing bar graph presentation are displayed.In the third view, the selected measured value as well as a second se-lectable value, e.g. the temperature of the electronics, are displayed.

During the initial setup of an instrument shipped Ex works,use the "OK" key to get to the menu "National language".

This menu item is used to select the national language for further pa-rameter adjustment. You can change the selection via the menu item "Setup - Display, Menu language".

With the "OK" key you move to the main menu.

Adjustment system

Measured value indica-tion

Selection of national language

39

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

6.4 Parameter adjustment - Quick setupTo quickly and easily adapt the sensor to the application, select the menu item "Quick setup" in the start graphic on the display and adjustment module.

Carry out the following steps in the below sequence.Youcanfind"Extendedadjustment" in the next sub-chapter.

1. Measurement loop nameInthefirstmenuitemyouassignasuitablemeasurementloopname.Permitted are names with max. 19 characters.

2. MediumIn this menu item you select the type of bulk solid. The selection com-prisesdifferentgranulatesizes.

3. Application/Vessel bottomIn this menu item you specify the application and the form of the ves-sel bottom.

4. Vessel height/Measuring rangeIn this menu item you enter the height of the vessel and hence the active measuring range.

5. Max. adjustmentIn this menu item you carry out the max. adjustment.Enterthemeasuringdistancefor100%filling.

40

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

6. Min. adjustmentIn this menu item you carry out the max. adjustment.Enterthemeasuringdistancefor100%filling.

Thequicksetupisfinished.

6.5 Parameter adjustment - Extended adjustmentThemainmenuisdividedintofivesectionswiththefollowingfunc-tions:

Setup: Settings, e.g., for measurement loop name, units, application, adjustment, signal outputDisplay: Settings, e.g., for language, measured value display, lightingDiagnosis: Information, for example, of device status, peak value, simulation, echo curveAdditional adjustments: Date/Time, reset, copy function, scaling, currentoutput,falsesignalsuppression,linearization,HARTmode,special parametersInfo: Instrument name, hardware and software version, calibration date, instrument featuresIn the main menu point "Setup", the individual submenu points should be selected one after the other and provided with the correct parameters to ensure optimum adjustment of the measurement. The procedure is described in the following.

Here you can assign a suitable measurement loop name. Push the "OK" key to start the processing. With the "+" key you change the sign and with the "->" key you jump to the next position.You can enter names with max. 19 characters. The character set comprises:

• Capital letters from A … Z• Numbers from 0 … 9• Special characters + - / _ blanks

In this menu item you select the distance unit and the temperature unit.

Main menu

Setup - Measurement loop name

Setup - Units

41

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

For the distance units you can choose between m, in and ft and for the temperature units °C, °F and K.

With this menu item, the sensor can be optimally adapted to the ap-plication, the installation location or the measurement conditions. It includes selection options for medium, application as well as vessel height/measuring range.

Medium:Everymediumhasadifferentreflectivebehaviour.Withthisselection,the sensor can be perfectly adapted to the medium and measurement reliability,particularlywithmediawithpoorreflectiveproperties,isconsiderably increased.

Application:Depending on the type of bulk solids application, material cones and additional echoes from the vessel wall or bottom can become further interfering factors. Through this selection, the sensor is adapted perfectly to the application.

Vessel height/Measuring range:The VEGAPULS 69 is a radar sensor for bulk solids in high, slender vessels. For this reason, it covers a measuring range of up to 120 m. This menu item allows a limitation of the active measuring range in which the sensor searches for level echoes.

Setup - Application

42

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Information:The min. adjustment must be carried out independently of this.The following features form the basis of the applications:

Silo (slender and high):• Vessel of metal: weld joints• Process/measurement conditions:

– Filling aperture too close to the sensor – System noise in completely empty silo increased

• Properties, sensor: – Stable measured values through higher averaging – False signal suppression during setup recommended, required

for automatic false signal suppression – Automaticfalsesignalsuppressionwithpartlyfilledvessel1)

Bunker (large-volume):• Vessel of concrete or metal:

– Structured vessel walls – Installations present

• Process/measurement conditions: – Large distance to the medium – Large angles of repose

• Properties, sensor: – Mean averaging – High measured value jumps are accepted

Bunkerwithfastfilling:• Vessel of concrete or metal, also multiple chamber silo:

– Structured vessel walls – Installations present

• Process/measurement conditions: – Measured value jumps, e.g. through truck loading – Large distance to the medium – Large angles of repose

• Properties, sensor: – Lower averaging – Very high measured value jumps are accepted

Heap:• Sensor mounting on movable conveyor belts• Detectionoftheheapprofile• Heightdetectionduringfilling• Process/measurement conditions:

– Measuredvaluejumps,e.g.bytheprofileoftheheaportrav-erses

– Large angles of repose – Measurementnearthefillingstream

• Properties, sensor:

1) Theinstrumentrecognizesifamanualfalsesignalsuppressionwascarriedout with empty vessel and high system noise. An automatic false signal sup-pression is then carried out if a product echo was detected at the beginning of the filling process.

43

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

– Mean averaging – High measured value jumps are accepted

Crusher:• Vessel: installations, wear and protective facilities available• Process/measurement conditions:

– Measured value jumps, e.g. by truck loading – Fast reaction time – Large distance to the medium

• Properties, sensor: – Little averaging – Max. reaction speed, very high measured value jumps are

accepted

Demonstration:• Adjustment for all applications which are not typically level meas-

urement – Instrument demonstration – Object recognition/monitoring (additional settings required)

• Properties, sensor: – Sensor accepts all measured value changes within the measur-

ing range immediately – High sensitivity against interferences, because virtually no

averaging

Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

Since the radar sensor is a distance measuring instrument, the distance from the sensor to the product surface is measured. For indication of the real level, an allocation of the measured distance to the percentage height must be carried out.To perform the adjustment, enter the distance with full and empty ves-sel, see the following example:

Setup - Adjustment

44

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

2

1

3

100%

0%

1 m

(39.

37")

35 m

(137

8 ")

Fig.40:Parameteradjustmentexamplemin./max.adjustment1 Min. level = max. meas. distance2 Max. level = min. meas. distance3 Reference plane

If these values are not known, an adjustment with the distances of for example 10 % and 90 % is possible. Starting point for these distance specificationsisalwaysthesealsurfaceofthethreadorflange.Youcanfindspecificationsofthereferenceplaneinchapter"Technicaldata". By means of these settings, the real level will be calculated.The real product level during this adjustment is not important, be-cause the min./max. adjustment is always carried out without chang-ing the product level. These settings can be made ahead of time without the instrument having to be installed.

Proceed as follows:1. Select with [->]themenuitem"Max.adjustment"andconfirm

with [OK].

2. Prepare the percentage value for editing with [OK] and set the cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.

Setup - Max. adjustment

45

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

4. For the full vessel, enter the distance value in m matching the percentage value.

5. Save settings with [OK] and move with [ESC] and [->] to the min. adjustment.

Proceed as follows:1. Select with [->] the menu item "Min. adjustment"andconfirmwith

[OK].

2. Edit the percentage value with [OK] and set the cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.

4. Enter the suitable distance value in m for the empty vessel (e.g. distance from the sensor to the vessel bottom) corresponding to the percentage value.

Todampprocess-dependentmeasuredvaluefluctuations,setanintegration time of 0 … 999 s in this menu item.

The default setting is a damping of 0 s.

In the menu item "Current output mode" you determine the output characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode < 3.6 mA.

Setup - Min. adjustment

Setup - Damping

Setup - Current output mode

46

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

In the menu item "CurrentoutputMin./Max.", you determine the reac-tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

In the menu item "Lock/unlockadjustment", you can protect the sensorparametersagainstunauthorizedmodification.ThePINisactivated/deactivated permanently.The following adjustment functions are possible without entering the PIN:

• Select menu items and show data• Read data from the sensor into the display and adjustment mod-

ule.

Caution:With active PIN, adjustment via PACTware/DTM as well as other systems is also blocked.

This menu item enables the setting of the requested national lan-guage.

The following languages are available:

• German• English• French• Spanish• Russian• Italian• Dutch• Portuguese• Polish• Czech• Turkish

In the delivery status, the VEGAPULS 69 is set to the ordered national language.

Inthismenuitemyoucandefinetheindicationofthemeasuredvalues on the display.

Setup - Current output Min./Max.

Lock/unlock setup - Ad-justment

Display - Language

Display - Displayed value 1 and 2

47

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

The default setting for the display value is "Percent".

The display and adjustment module has a backlight for the display. Inthismenuitemyoucanswitchonthelighting.Youcanfindtherequired operating voltage in chapter "Technicaldata".

Thelightingisswitchedoffindeliverystatus.

In this menu item, the device status is displayed.

The min. and max. measured value, the measurement reliability as well as the min. and max. electronics temperature are stored in the sensor. The values are displayed in the menu item "Peak value".

A reset menu is opened with the [OK] key in the respective peak value window:

With the [OK] key, the peak values are reset to the actual measured value.

The "Echocurve" shows the signal strength of the echoes over the measuring range in dB. The signal strength enables an evaluation of the quality of the measurement.

Display - Backlight

Diagnostics - Device status

Diagnosis - Peak value

Diagnostics - Echo curve

48

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Theselectedcurveiscontinuouslyupdated.Asubmenuwithzoomfunctions is opened with the [OK] key:

• "X-Zoom":Zoomfunctionforthemeas.distance• "Y-Zoom":1,2,5and10xsignalmagnificationin"dB"• "Unzoom":Resetthepresentationtothenominalmeasuringrange

withoutmagnification

In this menu item you can simulate measured values via the current output. This allows the signal path to be tested, e.g. through down-stream indicating instruments or the input card of the control system.

Selecttherequestedsimulationsizeandadjusttherequestedvalue.

Caution:During simulation, the simulated value is outputted as 4 … 20 mA cur-rent value and as digital HART signal. The status message within the context of the asset management function is "Maintenance".Push the [ESC] key to deactivate the simulation.

Information:The simulation is terminated automatically 60 minutes after the last key has been pressed.

The function "Setup" allows the echo curve to be saved at the time of setup.

Information:This is generally recommended, however, for use of the Asset Management functions it is absolutely necessary. Saving should be carried out with a very low level.The function "Echocurvememory" allows up to ten individual echo curves to be stored, for example to detect the measurement behav-iourofthesensorindifferentoperatingconditions.With the adjustment software PACTware and the PC, the stored echo curvescanbedisplayedwithhighresolutionandusedtorecognizesignal changes over time. In addition, the echo curve saved during setup can also be displayed in the echo curve window and compared with the actual echo curve.

Diagnosis - Simulation

Diagnostics - Echo curve memory

49

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

In this menu item, the internal clock of the sensor is set to the request-ed time and time format. At the time of shipment from factory, the instrument is set to CET (Central European Time).

During a reset, the parameter settings carried out by the user are reset to the default values (see below table).Proceed as follows:1. Select with [->] under "Additional adjustment" the menu item

"Reset"andconfirmwith[OK].

2. Confirmwith[OK] and select the requested reset function with [->]

3. Confirmwith[OK], for approx. 5 s the message "Resetting" is displayed, then the selection window appears.

Caution:For the duration of the reset, the set trouble signal is outputted via the current output. Within the context of the asset management function, the message "Maintenance" is outputted.The following reset functions are available:Delivery status: Restores the parameter settings at the time of ship-mentfromthefactory,incl.theorder-specificsettings.Anycreatedfalsesignalsuppression,user-programmablelinearizationcurveaswell as measured value and echo curve memory is deleted. The event andparametermodificationmemoriesremainunaffected.Basic settings: Resets the parameter settings, incl. special param-eters, to the default values of the respective instrument. Any stored false signal suppression or user programmable linearisation curve, as well as the measured value memory, is deleted. Order-related settings are not taken over into the current parameters after this reset.The following table shows the scope of the reset function and the default values of the instrument:

Additional adjustments - Date Time

Additional adjustments - Reset

50

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Menu Menu item Default value

Setup Measurement loop name

Sensor

Units Distance in mTemperature in °C

Application Medium: Crushed stones/gravelApplication: SiloVessel bottom: FlatVessel height/Measuring range: 120 m

Min. adjustment 120 m

Max. adjustment 0,000 m(d)

Damping 0.0 s

Current output mode

Output characteristics: 4 … 20 mAFailure mode: < 3.6 mA ▼

Current output Min./Max.

Min. current: 3.8 mA ▼Max. current: 20.5 mA

Display Displayed value 1 Filling height

Displayed value 2 Temperature

Backlight Switchedoff

Additional adjust-ments

Date/Time Time format: 24 h

Scalingsize Volumel

Scaling format 100.00 lin %, 100 l0.00 lin %, 0 l

Current output 1 and2size

Lin %

Current output 1 and 2 adjustment

100.00 %, 100 l0.00 %, 0 l

Linearization Linear

HART mode HART address: 0Loop current mode: Analogue cur-rent output

The instrument settings are copied with this function. The following functions are available:Read from sensor: Read data from sensor and store into the display and adjustment moduleWrite into sensor: Store data from the display and adjustment mod-ule back to the sensorThe following data or settings for adjustment of the display and ad-justment module are saved:

• All data of the menu "Setup" and "Display"

Additional adjustments - Copy instrument settings

51

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

• The menu items "Reset,Date/Time" in the menu "Additional set-tings"

• Theuser-programmablelinearizationcurve

The copied data are permanently saved in an EEPROM memory in the display and adjustment module and remain there even in case of power failure. From there, they can be written into one or more sen-sors or kept as backup for a possible electronics exchange.

Note:Before saving the data in the sensor, a safety check is made if the data match with the sensor. For this purpose the sensor type of the source data as well as the target sensor are displayed. If the data do not match, a failure message is outputted or the function is blocked. The data are only saved after release.

In the menu item "Scaling"youdefinethescalingvariableandthescaling format for the indication of the level measured value for 0 % and 100 % on the display, for example as volume in l.

In menu item "Current output, variable" you specify which measured variable the current output refers to.

In menu item "Current output, adjustment" you can assign a respec-tive measured value to the current output.

Thefollowingcircumstancescauseinterferingreflectionsandcaninfluencethemeasurement:

• High sockets• Vessel installations such as struts• Agitators

Additional settings - Scal-ing

Additional settings - Cur-rent output 1 and 2 (size)

Additional settings - Current output 1 and 2 (adjustment)

Additional adjustments - False signal suppression

52

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

• Buildup or welded joints on vessel walls

Note:A false signal suppression detects, marks and saves these false signals so that they are no longer taken into account in the level measurement.This should be done with a low level so that all potential interfering reflectionscanbedetected.Proceed as follows:1. Select with [->] the menu item "False signal suppression" and

confirmwith[OK].

2. Confirmagainwith[OK].

3. Confirmagainwith[OK].

4. Confirmagainwith[OK] and enter the actual distance from the sensor to the product surface.

5. All interfering signals in this section are detected by the sensor andstoredafterconfirmingwith[OK].

Note:Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as a false echo.Thefillinglevelwouldthennolongerbedetectableinthisarea.If a false signal suppression has already been created in the sensor, the following menu window appears when selecting "False signal suppression":

Delete: An already created false signal suppression will be com-pletely deleted. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel.

53

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Extend: is used to extend an already created false signal suppres-sion. This is useful if a false signal suppression was carried out with a too high level and not all false signals could be detected. When selecting "Extend", the distance to the product surface of the created false signal suppression is displayed. This value can now be changed and the false signal suppression can be extended to this range.

Alinearizationisnecessaryforallvesselsinwhichthevesselvolumedoesnotincreaselinearlywiththelevel.Correspondinglinearizationcurves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. The linearizationappliestothemeasuredvalueindicationandthecurrentoutput.

In this menu item you determine the HART mode and enter the ad-dress for multidrop mode.In the mode "Fixed current output" up to 63 sensors can be operated on one two-wire cable (Multidrop operation). An address between 0 and 63 must be assigned to each sensor.When chosing the function "Analogue current output", then a 4 … 20 mA signal is outputted in multidrop mode.With the mode "Fixed current (4 mA)"afixed4mAsignalisoutputtedindependently of the actual level.

The default setting is "Analogue current output" and the address "00".

In this menu item you gain access to the protected area where you can enter special parameters. In exceptional cases, individual parameterscanbemodifiedinordertoadaptthesensortospecialrequirements.Change the settings of the special parameters only after having con-tactedourservicestaff.

Setup - Linearization

Additional adjustments - HART mode

Additional adjustments - Special parameters

54

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

In this menu item, you can read out the instrument name and the instrument serial number:

In this menu item, the hardware and software version of the sensor is displayed.

In this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module or via the PC.

In this menu item, the features of the sensor such as approval, pro-cessfitting,seal,measuringrange,electronics,housingandothersare displayed.

6.6 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operating instructions manual, and archiving them afterwards. They are thus available for multiple use or service purposes.If the instrument is equipped with a display and adjustment module, the data in the sensor can be saved in the display and adjustment module. The procedure is described in the operating instructions manual "Display and adjustment module" in the menu item "Copy sensor data". The data remain there permanently even if the sensor power supply fails.The following data or settings for adjustment of the display and ad-justment module are saved:

• All data of the menu "Setup" and "Display"• In the menu "Additional adjustments" the items "Sensor-specific

units, temperature unit and linearization"• ThevaluesoftheuserprogrammablelinearizationcurveThe function can also be used to transfer settings from one instru-ment to another instrument of the same type. If it is necessary to exchange a sensor, the display and adjustment module is inserted

Info - Instrument name

Info - Instrument version

Info - Factory calibration date

Info - Sensor character-istics

55

6 Set up with the display and adjustment module

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy sensor data".

56

7 Setup with PACTware

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

7 Setup with PACTware

7.1 Connect the PC

3

1

2

Fig. 41: Connection of the PC directly to the sensor via the interface adapter1 USBcabletothePC2 InterfaceadapterVEGACONNECT3 Sensor

1

5

2 4

3 OPEN

TWIS

T

USB

LOCK

Fig.42:ConnectingthePCviaHARTtothesignalcable1 Sensor2 HARTresistance250Ω(optionaldependingonprocessing)3 Connection cable with 2 mm pins and terminals4 Processingsystem/PLC/Voltagesupply5 Interfaceadapter,forexampleVEGACONNECT4

Note:With power supply units with integrated HART resistance (internal resistanceapprox.250Ω),anadditionalexternalresistanceisnotnecessary. This applies, e.g. to the VEGA instruments VEGATRENN 149A, VEGAMET 381, VEGAMET 391. Common Ex separators are alsousuallyequippedwithasufficientcurrentlimitationresistance.In

Via the interface adapter directly on the sensor

Via the interface adapter and HART

57

7 Setup with PACTware

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

such cases, the interface converter can be connected parallel to the 4 … 20 mA cable (dashed line in the previous illustration).

7.2 Parameter adjustmentFor parameter adjustment of the instrument via a Windows PC, the configurationsoftwarePACTwareandasuitableinstrumentdriver(DTM) according to FDT standard are required. The latest PACTware version as well as all available DTMs are compiled in a DTM Collec-tion. The DTMs can also be integrated into other frame applications according to FDT standard.

Note:To ensure that all instrument functions are supported, you should always use the latest DTM Collection. Furthermore, not all described functionsareincludedinolderfirmwareversions.Youcandownloadthe latest instrument software from our homepage. A description of the update procedure is also available in the Internet.Further setup steps are described in the operating instructions manu-al "DTMCollection/PACTware" attached to each DTM Collection and which can also be downloaded from the Internet. Detailed descrip-tions are available in the online help of PACTware and the DTMs.

Fig.43:ExampleofaDTMview

All device DTMs are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assistant for simpleprojectconfigurationsimplifiestheadjustmentconsiderably.Saving/printing the project as well as import/export functions are also part of the standard version.In the full version there is also an extended print function for complete project documentation as well as a save function for measured value

Prerequisites

Standard/Full version

58

7 Setup with PACTware

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

and echo curves. In addition, there is a tank calculation program as well as a multiviewer for display and analysis of the saved measured value and echo curves.The standard version is available as a download under www.vega.com/downloads and "Software". The full version is avail-able on CD from the agency serving you.

7.3 Saving the parameter adjustment dataWe recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or service purposes.

59

8 Set up with other systems

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

8 Set up with other systems

8.1 DD adjustment programsDevice descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AMS™ and PDM.Thefilescanbedownloadedatwww.vega.com/downloads under "Software".

8.2 Field Communicator 375, 475Device descriptions for the instrument are available as EDD for pa-rameter adjustment with the Field Communicator 375 or 475.For the integration of the EDD in the Field Communicator 375 or 475, the software "Easy Upgrade Utility" is required which is available from the manufacturer. This software is updated via the Internet and new EDDs are automatically taken over into the device catalogue of this software after they are released by the manufacturer. They can then be transferred to a Field Communicator.

60

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

9 Diagnosis, asset management and service

9.1 MaintenanceIf the device is used correctly, no maintenance is required in normal operation.Insomeapplications,buildupontheantennasystemcaninfluencethe measuring result. Depending on the sensor and application, make arrangements to avoid strong pollution of the antenna system. If nec-essary, clean the antenna system in certain intervals.

9.2 Measured value and event memoryThe instrument has several memories which are available for diagno-sis purposes. The data remain even with voltage interruption.

Up to 100,000 measured values can be stored in the sensor in a ring memory. Each entry contains date/time as well as the respective measured value. Storable values are for example:

• Distance• Filling height• Percentage value• Lin. percent• Scaled• Current value• Meas. reliability• Electronics temperature

When the instrument is shipped, the measured value memory is active and stores distance, measurement reliability and electronics temperature every 3 minutes.The requested values and recording conditions are set via a PC with PACTware/DTM or the control system with EDD. Data are thus read out and also reset.

Up to 500 events are automatically stored with a time stamp in the sensor (non-deletable). Each entry contains date/time, event type, event description and value. Event types are for example:

• Modificationofaparameter• Switch-onandswitch-offtimes• Status messages (according to NE 107)• Error messages (according to NE 107)

The data are read out via a PC with PACTware/DTM or the control system with EDD.

The echo curves are stored with date and time and the corresponding echo data. The memory is divided into two sections:Echo curve of the setup: This is used as reference echo curve for the measurement conditions during setup. Changes in the measure-ment conditions during operation or buildup on the sensor can thus berecognized.Theechocurveofthesetupisstoredvia:

Measured value memory

Event memory

Echo curve memory

61

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

• PC with PACTware/DTM • Control system with EDD • Display and adjustment module

Further echo curves: Up to 10 echo curves can be stored in a ring bufferinthismemorysection.Furtherechocurvesarestoredvia:

• PC with PACTware/DTM • Control system with EDD

9.3 Asset Management functionThe instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables there are more detailed error messages available under the menu item "Diagnostics" via the display and adjustment module, PACTware/DTM and EDD.

The status messages are divided into the following categories:

• Failure• Function check• Outofspecification• Maintenance requirement

and explained by pictographs:

41 2 3Fig. 44: Pictographs of the status messages1 Failure - red2 Outofspecification-yellow3 Function check - orange4 Maintenance - blue

Failure: Due to a malfunction in the instrument, a failure message is outputted.This status message is always active. It cannot be deactivated by the user.Function check: The instrument is in operation, the measured value is temporarily invalid (for example during simulation).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.Outofspecification: The measured value is unstable because the instrumentspecificationisexceeded(e.g.electronicstemperature).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.

Status messages

62

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Maintenance:Duetoexternalinfluences,theinstrumentfunctionislimited.Themeasurementisaffected,butthemeasuredvalueisstill valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.

The following table shows the error codes in the status message "Failure"andgivesinformationonthereasonandrectification.Keepin mind that some information is only valid with four-wire instruments.

CodeText mes-sage

Cause Rectification

F013no measured value avail-able

– Sensor does not detect an echo during operation

– Antenna system dirty or defective

– Check or correct installation and/or parameter adjust-ment

– Clean or exchange process component or antenna

F017Adjustment span too small

– Adjustment not within specification

– Change adjustment accord-ing to the limit values (dif-ference between min. and max.≥10mm)

F025Error in the linearizationtable

– Index markers are not con-tinuously rising, for example illogical value pairs

– Checklinearizationtable – Delete table/Create new

F036No operable software

– Failed or interrupted soft-ware update

– Repeat software update – Check electronics version – Exchanging the electronics – Send instrument for repair

F040Error in the electronics

– Hardware defect – Exchanging the electronics – Send instrument for repair

F080General soft-ware error

– General software error – Disconnect operating volt-agebriefly

F105Determine measured value

– The instrument is still in the start phase, the measured value could not yet be determined

– Wait for the end of the switch-on phase

– Duration depending on the version and parameter adjustment up to approxi-mately 3 min.

F113Communica-tion error

– EMC interference – Transmission error with the

external communication with 4-wire power supply unit

– RemoveEMCinfluences – Exchange 4-wire power

supply unit or electronics

Failure

63

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

CodeText mes-sage

Cause Rectification

F125Impermissi-ble electronics temperature

– Temperature of the elec-tronicsinthenon-specifiedsection

– Check ambient temperature – Isolate electronics – Use instrument with higher

temperature range

F260Error in the calibration

– Error in the calibration car-ried out in the factory

– Error in the EEPROM

– Exchanging the electronics – Send instrument for repair

F261Error in the instrument settings

– Error during setup – False signal suppression

faulty – Error when carrying out a

reset

– Repeat setup – Carry out a reset

F264Installation/Setup error

– Adjustment not within the vessel height/measuring range

– Max. measuring range of theinstrumentnotsufficient

– Check or correct installation and/or parameter adjust-ment

– Use an instrument with big-ger measuring range

F265Measurement function dis-turbed

– Sensor no longer carries out a measurement

– Operating voltage too low

– Check operating voltage – Carry out a reset – Disconnect operating volt-agebriefly

The following table shows the error codes and text messages in the status message "Function check" and provides information on causes as well as corrective measures.

CodeText mes-sage

Cause Rectification

C700Simulation ac-tive

– A simulation is active – Finish simulation – Wait for the automatic end

after 60 mins.

The following table shows the error codes and text messages in the status message "Outofspecification" and provides information on causes as well as corrective measures.

CodeText mes-sage

Cause Rectification

S600Impermissi-ble electronics temperature

– Temperature of the elec-tronicsinthenon-specifiedsection

– Check ambient temperature – Isolate electronics – Use instrument with higher

temperature range

Function check

Outofspecification

64

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

CodeText mes-sage

Cause Rectification

S603Impermissi-ble operating voltage

– Operating voltage below specifiedrange

– Check electrical connection – if necessary, increase

operating voltage

The following table shows the error codes and text messages in the status message "Maintenance" and provides information on causes as well as corrective measures.

CodeText mes-sage

Cause Rectification

M500Error with the reset delivery status

– With the reset to delivery status, the data could not be restored

– Repeat reset – LoadXMLfilewithsensor

data into the sensor

M501Error in the non-active linearizationtable

– Hardware error EEPROM – Exchanging the electronics – Send instrument for repair

M502Error in the event memory

– Hardware error EEPROM – Exchanging the electronics – Send instrument for repair

M503Meas. reliabil-ity too low

– The echo/noise ratio is too small for reliable measure-ment

– Antenna dirty or defective

– Check installation and process conditions

– Change polarisation direc-tion

– Use instrument with higher sensitivity

– Clean the antenna

M504Error on an device inter-face

– Hardware defect – Check connections – Exchanging the electronics – Send instrument for repair

M505No echo avail-able

– Sensor does not detect an echo during operation

– Antenna dirty or defective

– Clean the antenna – Use a more suitable

antenna/sensor – Remove possible false

echoes – Optimizesensorposition

and orientation

M506Installation/Setup error

– Error during setup – Check or correct installation and/or parameter adjust-ment

Maintenance

65

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

CodeText mes-sage

Cause Rectification

M507Error in the instrument settings

– Error during setup – Error when carrying out a

reset – False signal suppression

faulty

– Carry out reset and repeat setup

9.4 Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.

Thefirstmeasuresare:

• Evaluation of fault messages, for example via the display and adjustment module

• Checking the output signal• Treatment of measurement errors

Further comprehensive diagnostics options are available with a PC with PACTware and the suitable DTM. In many cases, the reasons can bedeterminedinthiswayandfaultsrectified.

Connect a multimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to remove them:

Error Cause Rectification

4 … 20 mA signal not stable

– Fluctuations of the measured variable

– Set damping according to the instrument via the display and adjustment module or PACTware/DTM

4 … 20 mA signal missing

– Electrical con-nection faulty

– Check connection according to chapter "Connection steps" and if necessary, correct according to chapter "Wiring plan"

– Voltage supply missing

– Check cables for breaks; repair if necessary

– Operating volt-age too low or load resistance too high

– Check, adapt if necessary

Current sig-nal greater than 22 mA or less than 3.6 mA

– Electronics module in the sensor defec-tive

– Exchange the instrument or send it in for repair

The below tables show typical examples for application-relevant measurement errors with bulk solids. A distinction is made between measurement errors during:

• Constant level

Reaction when malfunc-tions occur

Procedure for fault recti-fication

Check the 4 … 20 mA signal

Treatment of measure-ment errors with bulk solids

66

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

• Filling• Emptying

The images in column "Errorpattern" show the real level with a bro-ken line and the level displayed by the sensor as a continuous line.

12

Leve

l

time0

1 Real level2 Level displayed by the sensor

Notes:

• Wherever the sensor displays a constant value, the reason could also be the fault setting of the current output to "Hold value"

• If the level indication is too low, the reason could be a line resist-ance that is too high

Measurement error with constant level

Fault description Error pattern Cause Rectification

1. Measured value shows a too low or too high level

Leve

l

time0

– Min./max. adjustment not correct

– Adapt min./max. adjustment

– Incorrectlinearizationcurve – Adaptlinearizationcurve

2. Measured value jumps towards 100 % Le

vel

time0

– Due to the process, the amplitude of the product echo decreases

– A false signal suppression was not carried out

– Carry out a false signal sup-pression

– Amplitude or position of a false echo has changed (e.g. con-densation, buildup); false signal suppression no longer matches actual conditions

– Determine the reason for the changed false echoes, carry out false signal suppression, e.g. with condensation

67

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Measurementerrorduringfilling

Fault description Error pattern Cause Rectification

3. Measured value jumps towards 0 % duringfilling

Leve

l

time0

– Amplitude of a multiple echo (vessel top - product surface) is larger than the level echo

– Check parameter "Application", especially vessel top, type of medium, dished bottom, high dielectric constant, and adapt if necessary

– The level echo cannot be distin-guished from the false echo at a false echo position (jumps to multiple echo)

– Remove/reduce false echo: minimizeinterferinginstalla-tionsbychangingthepolariza-tion direction

– Chose a more suitable installa-tion position

– Transversereflectionfromanextraction funnel, amplitude of thetransversereflectionlargerthan the level echo

– Direct sensor to the opposite funnel wall, avoid crossing with thefillingstream

4. Measured val-uefluctuatesaround10 … 20 %

Leve

l

time0

– Various echoes from an uneven product surface, e.g. a material cone

– Check parameter "Type of medium" and adapt, if neces-sary

– Optimizeinstallationpositionand sensor orientation

– Reflectionsfromtheproductsurface via the vessel wall (deflection)

– Select a more suitable installa-tionposition,optimizesensororientation, e.g. with a swivel-ling holder

5. Measured value jumps sporadically to 100%duringfilling

Level

time0

– Changing condensation or con-tamination on the antenna

– Carry out a false signal sup-pression or increase false signal suppression with con-densation/contamination in the close range by editing

– With bulk solids use radar sen-sor with purging air connection orflexibleantennacover

Measurement error during emptying

Fault description Error pattern Cause Rectification

6. Measured value re-mains unchanged in the close range during emptying

Leve

l

time0

– False echo larger than the level echo

– Level echo too small

– Remove false echoes in the close range. Check: Antenna must protrude out of the socket

– Remove contamination on the antenna

– Minimizeinterferinginstal-lations in the close range by changingthepolarizationdirection

– After removing the false ech-oes, the false signal suppres-sion must be deleted. Carry out a new false signal suppression

68

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Fault description Error pattern Cause Rectification

7. Measured value jumps sporadically to-wards 100 % during emptying

Leve

l

time0

– Changing condensation or con-tamination on the antenna

– Carry out false signal suppres-sion or increase false signal suppression in the close range by editing

– With bulk solids use radar sen-sor with purging air connection orflexibleantennacover

8. Measured val-uefluctuatesaround10 … 20 %

Leve

l

time0

– Various echoes from an uneven product surface, e.g. an extrac-tion funnel

– Check parameter "Type of medium" and adapt, if neces-sary

– Optimizeinstallationpositionand sensor orientation

– Reflectionsfromtheproductsurface via the vessel wall (deflection)

Depending on the reason for the fault and the measures taken, the steps described in chapter "Setup" must be carried out again or must be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550.The hotline is also available outside normal working hours, seven days a week around the clock.Sinceweofferthisserviceworldwide,thesupportisprovidedinEnglish. The service itself is free of charge, the only costs involved are the normal call charges.

9.5 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications, only instruments and electronics modules with ap-propriate Ex approval may be used.If there is no electronics module available on site, the electronics module can be ordered through the agency serving you. The electron-icsmodulesareadaptedtotherespectivesensoranddifferinsignaloutput or voltage supply.The new electronics module must be loaded with the default settings of the sensor. These are the options:

• In the factory• Or on site by the user

In both cases, the serial number of the sensor is needed. The serial numbers are stated on the type label of the instrument, on the inside of the housing as well as on the delivery note.Whenloadingonsite,firstofalltheorderdatamustbedownloadedfrom the Internet (see operating instructions manual "Electronicsmodule").

Caution:Alluser-specificsettingsmustbeenteredagain.Hence,youhavetocarry out a new setup after the electronics exchange.

Reaction after fault recti-fication

24 hour service hotline

69

9 Diagnosis, asset management and service

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

If you have stored the data of the parameter adjustment during the firstsetupofthesensor,youcantransferthesetothereplacementelectronics module. A new setup is no more necessary.

9.6 Software updateThe following components are required to update the instrument software:

• Instrument• Voltage supply• Interface adapter VEGACONNECT• PC with PACTware• CurrentinstrumentsoftwareasfileYoucanfindthecurrentinstrumentsoftwareaswellasdetailedinformation on the procedure under "www.vega.com/downloads" and "Software".

Caution:Instruments with approvals can be bound to certain software versions. Thereforemakesurethattheapprovalisstilleffectiveafterasoftwareupdate is carried out.Youcanfinddetailedinformationatwww.vega.com/downloads and "Approvals".

9.7 How to proceed if a repair is neededYoucanfindarepairformaswellasdetailedinformationonhowtoproceed at www.vega.com/downloads and "Formsandcertificates".By doing this you help us carry out the repair quickly and without hav-ing to call back for needed information.If a repair is necessary, please proceed as follows:

• Printandfilloutoneformperinstrument• Clean the instrument and pack it damage-proof• Attach the completed form and, if need be, also a safety data

sheet outside on the packaging• Please contact the agency serving you to get the address for

thereturnshipment.Youcanfindtheagencyonourhomepagewww.vega.com.

70

10 Dismount

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

10 Dismount

10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel or pipeline, high temperatures, cor-rosive or toxic products etc.Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.

10.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the parts to be easily separable.Correctdisposalavoidsnegativeeffectsonhumansandtheenviron-ment and ensures recycling of useful raw materials.Materials: see chapter "Technicaldata"If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal.

WEEE directive 2002/96/EGThis instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a spe-cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.

71

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

11 Supplement

11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts

Ʋ Processfitting 316L, Alloy C22, Alloy 400 Ʋ Process seal On site Ʋ Antenna 316L, PP, PEEK Ʋ seal, antenna system FKM (SHS FPM 70C3 GLT), EPDM (COG AP310)

Materials, non-wetted parts Ʋ Plastic housing plastic PBT (Polyester) Ʋ Aluminium die-casting housing Aluminium die-casting AlSi10Mg, powder-coated - basis:

Polyester Ʋ Stainless steel housing 316L Ʋ Seal between housing and housing cover

NBR (stainless steel housing, precision casting), silicone (aluminium/plastic housing; stainless steel housing, electropolished)

Ʋ Inspection window in housing cover (optional)

Polycarbonate

Ʋ Ground terminal 316LProcessfitting

Ʋ Flanges DIN from DN 80, ASME from 3"Weights

Ʋ Instrument (depending on housing, processfittingandantenna)

approx. 2 … 17.2 kg (4.409 … 37.92 lbs)

Torque for NPT cable glands and Conduit tubes Ʋ Plastic housing max. 10 Nm (7.376 lbf ft) Ʋ Aluminium/Stainless steel housing max. 50 Nm (36.88 lbf ft)

Input variableMeasured variable The measured variable is the distance between the pro-

cessfittingofthesensorandtheproductsurface.Thereferenceplaneisthesealsurfaceoftheflange.

72

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

24

13

Fig. 54: Data of the input variable1 Reference plane2 Measured variable, max. measuring range3 Antenna length4 Usefulmeasuringrange

Max. measuring range 120 m (393,7 ft)

Output variableOutput signal 4 … 20 mA/HARTRange of the output signal 3.8 … 20.5 mA/HART (default setting)Signal resolution 0.3 µAResolution, digital < 1 mm (0.039 in)Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mAMax. output current 22 mAStarting current ≤3.6mA;≤10mAfor5msafterswitchingonLoad see load diagram under Power supplyDamping (63 % of the input variable), adjustable

0 … 999 s

HART output values according to HART 7.02)

Ʋ PV (Primary Value) Lin. percent Ʋ SV (Secondary Value) Distance Ʋ TV (Third Value) Meas. reliability Ʋ QV (Fourth Value) Electronics temperature

FulfilledHARTspecification 7.0Further information on Manufacturer ID, Device ID, Device Revision

See website of HART Communication Foundation

2) Default values, can be assigned individually

73

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Accuracy (according to DIN EN 60770-1)Process reference conditions according to DIN EN 61298-1

Ʋ Temperature +18 … +30 °C (+64 … +86 °F) Ʋ Relative humidity 45 … 75 % Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions Ʋ Min. distance to internal installations > 200 mm (7.874 in) Ʋ Reflector Flatplatereflector Ʋ Falsereflections Biggest false signal, 20 dB smaller than the useful signal

Deviation See following diagrams

0,5 m (1.6 ft)

20 mm (0.787 in)

- 20 mm (- 0.787 in)

0

10 mm (0.394 in)

- 10 mm (- 0.394 in)

1 2

Fig. 55: Deviation under reference conditions1 Reference plane2 Antenna edge3 Recommended measuring range

Repeatability ≤±1mmDeviation with bulk solids The values depend to a great extent on the application.

Bindingspecificationsarethusnotpossible.DeviationunderEMCinfluence ≤±50mm

VariablesinfluencingmeasurementaccuracySpecificationsapplytothedigitalmeasuredvalueTemperature drift - Digital output ±3mm/10Krelatingtothemax.measuringrangeor

max. 10 mmAdditional deviation through electromag-netic interference acc. to EN 61326

<±50mm

SpecificationsapplyalsotothecurrentoutputTemperature drift - Current output ±0.03%/10Krelatingtothe16mAspanmax.±0.3%Deviation on the current output through analogue/digital conversion

<±15µA

Deviation on the current output due to strong, high frequency electromagnetic fieldsacc.toEN61326

<±150µA

74

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Characteristics and performance dataMeasuring frequency W-band(79GHztechnology)Measuring cycle time approx. 700 msStep response time3) ≤3sBeam angle4)

Ʋ Plastic horn antenna 3.5° Ʋ Metal jacketed lens antenna 4°

Emitted HF power (depending on the parameter adjustment)5)

Ʋ Average spectral transmission power density

-3dBm/MHzEIRP

Ʋ Max. spectral transmission power density

+34dBm/50MHzEIRP

Ʋ Max. power density at a distance of 1 m

< 3 µW/cm²

Ambient conditionsAmbient, storage and transport tempera-ture

-40 … +80 °C (-40 … +176 °F)

Process conditionsFortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.Thelowestvaluealways applies.Process temperature

Seal Antenna lens Process temperature (measured on the process fitting)

FKM (SHS FPM 70C3 GLT)

PEEK -40 … +130 °C (-40 … +266 °F)

PEEK -40 … +200 °C (-40 … +392 °F)

FKM (SHS FPM 70C3 GLT)

PP -40 … +80 °C (-40 … +176 °F)

EPDM (COG AP310) PP -40 … +80 °C (-40 … +176 °F)

Ambient temperature - Process temperature

3) Time span (after a sudden measuring distance change of max. 2 m in bulk solids applications) until the output signal has taken on 90 % of the final value for the first time (IEC 61298-2).

4) Outsidethespecifiedbeamangle,theenergyoftheradarsignalisreducedby50%(-3dB)5) EIRP: Equivalent Isotropic Radiated Power

75

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

1

20 °C

(32 °F)

-40 °C(-104 °F)

50 °C(122 °F)

80 °C(176 °F)

200 °C(392 °F)

80 °C(176 °F)-40 °C

(-104 °F)

Fig. 56: Ambient temperature - Process temperature, metal jacketed lens antenna up to +200 °C (392 °F)1 Ambient temperature2 Process temperature

1

20 °C

(32 °F)

-40 °C(-104 °F)

50 °C(122 °F)

80 °C(176 °F)

130 °C(266 °F)

80 °C(176 °F)-40 °C

(-104 °F)

Fig. 57: Ambient temperature - Process temperature, metal jacketed lens antenna up to +130 °C (266 °F)1 Ambient temperature2 Process temperature

1

20 °C

(32 °F)

-40 °C(-104 °F)

80 °C(176 °F)

80 °C(176 °F)-40 °C

(-104 °F)

Fig. 58: Ambient temperature - Process temperature, plastic horn antenna1 Ambient temperature2 Process temperature

76

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Vessel pressureVessel pressure

Ʋ Metal jacketed lens antenna -1 … 3 bar (-100 … 300 kPa/-14.5 … 43.5 psig) Ʋ Plastic horn antenna -1 … 2 bar (-100 … 200 kPa/-14.5 … 29.1 psig) Ʋ Plastic horn antenna - Version with adapterflangefromDN100PPorPP-GF 30

-1 … 1 bar (-100 … 100 kPa/-14.5 … 14.5 psig)

Vesselpressurerelatingtotheflangenominal pressure stage

see supplementary instructions manual "Flanges ac-cordingtoDIN-EN-ASME-JIS"

Mechanial stressesVibration resistance - Metal jacketed lens antenna

4gat5…200HzaccordingtoEN60068-2-6(vibrationwith resonance)

Vibration resistance - Plastic horn antenna Ʋ Withadapterflange 2gat5…200HzaccordingtoEN60068-2-6(vibration

with resonance) Ʋ with mounting strap 1gat5…200HzaccordingtoEN60068-2-6(vibration

with resonance)Shock resistance 100 g, 6 ms according to EN 60068-2-27 (mechanical

shock)

Data rinsing air connection - Metal jacketed lens antennaMax. permissible pressure 6 bar (87.02 psig)Air volume, depending on pressure (recommended area)

Pressure Air volume

Withoutrefluxvalve Withrefluxvalve

0.2 bar (2.9 psig) 1.7 m3/h -

0.4 bar (5.8 psig) 2.5 m3/h -

0.6 bar (8.7 psig) 2.9 m3/h 0.8 m3/h

0.8 bar (11.6 psig) 3.3 m3/h 1.5 m3/h

1 bar (14.5 psig) 3.6 m3/h 2.0 m3/h

1.2 bar (17.4 psig) 3.9 m3/h 2.3 m3/h

1.4 bar (20.3 psig) 4.0 m3/h 2.7 m3/h

1.6 bar (23.2 psig) 4.3 m3/h 3.0 m3/h

1.8 bar (20.3 psig) 4.5 m3/h 3.5 m3/h

2 bar (23.2 psig) 4.6 m3/h 4.0 m3/h

Thread G⅛Closure Threaded plug of 316TiRefluxvalve-unmounted(asoptionwithnon-Exversion,includedinthescopeofdeliverywithExversion)

Ʋ Material 316Ti Ʋ Thread G⅛

77

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Ʋ Seal FKM (SHS FPM 70C3 GLT), EPDM (COG AP310) Ʋ For connection G¼ Ʋ opening pressure 0.5 bar (7.25 psig) Ʋ Nominal pressure stage PN 250

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable gland M20 x 1.5 or ½ NPTWire cross-section (spring-loaded terminals)

Ʋ Massive wire, cord 0.2 … 2.5 mm² (AWG 24 … 14) Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)

Electromechanical data - version IP 66/IP 68 (1 bar)Options of the cable entry

Ʋ Cable gland with integrated connec-tion cable

M20 x 1.5 (cable: ø 5 … 9 mm)

Ʋ Cable entry ½ NPT Ʋ Blind plug M20 x 1.5; ½ NPT

Connection cable Ʋ Wire cross-section 0.5 mm² (AWG 20) Ʋ Wire resistance <0.036Ω/m Ʋ Tensile strength < 1200 N (270 lbf) Ʋ Standard length 5 m (16.4 ft) Ʋ Max. length 180 m (590.6 ft) Ʋ Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F) Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour - Non-Ex version Black Ʋ Colour - Ex-version Blue

Display and adjustment moduleDisplay element Display with backlightMeasured value indication

Ʋ Number of digits 5 Ʋ Sizeofdigits W x H = 7 x 13 mm

Adjustment elements 4 keysProtection rating

Ʋ unassembled IP 20 Ʋ mounted in the housing without cover IP 40

Materials Ʋ Housing ABS Ʋ Inspection window Polyester foil

78

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Interface to the external display and adjustment unitData transmission digital (I²C-Bus)Configuration,connectioncable 4-wire, screenedCable length max. 25 m

Integrated clockDate format Day.Month.YearTime format 12 h/24 hTimezoneExfactory CETRate deviation max. 10.5 min/year

Measurement electronics temeratureResolution 0.1 °C (1.8 °F)Accuracy ±1°C(1.8°F)Permissible temperature range -40 … +85 °C (-40 … +185 °F)

Voltage supplyOperating voltage UB

Ʋ Non-Ex instrument 12 … 35 V DC Ʋ Ex-d instrument 12 … 35 V DC Ʋ Ex-ia instrument 12 … 30 V DC Ʋ Ex-d-ia instrument 17 … 35 V DC

Operating voltage UB - illuminated display and adjustment module Ʋ Non-Ex instrument 18 … 35 V DC Ʋ Ex-d instrument 18 … 35 V DC Ʋ Ex-ia instrument 18 … 30 V DC Ʋ Ex-d-ia instrument Due to the barrier, no lighting possible

Reverse voltage protection IntegratedPermissible residual ripple - Non-Ex, Ex-ia instrument

Ʋ for 9.6 V< UB < 14 V ≤0.7Veff(16…400Hz) Ʋ for 18 V< UB < 36 V ≤1.0Veff(16…400Hz)

Permissible residual ripple - Ex-d-ia instrument Ʋ for 18 V< UB < 36 V ≤1Veff(16…400Hz)

Load resistor Ʋ Calculation (UB - Umin)/0.022 A Ʋ Example - Non-Ex instrument with UB= 24 V DC

(24V-12V)/0.022A=545Ω

Electrical protective measuresProtection rating

79

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Housing material Version IP-protection class NEMA protection

Plastic Single chamber IP 66/IP 67 NEMA4X

Double chamber IP 66/IP 67 NEMA4X

Aluminium Single chamber IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA 6PNEMA 6P

Double chamber IP 66/IP 67IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA4XNEMA 6PNEMA 6P

Stainless steel, electro-polished

Single chamber IP 66/IP 68 (0.2 bar) NEMA 6P

Stainless steel, investment casting

Single chamber IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA 6PNEMA 6P

Double chamber IP 66/IP 67IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA4XNEMA 6PNEMA 6P

Overvoltage category III6)

Protection class III7)

ApprovalsInstrumentswithapprovalscanhavedifferenttechnicalspecificationsdependingontheversion.For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com, "VEGATools" and "Instrument search" as well as under www.vega.com/downloads and "Approvals".

11.2 DimensionsThe following dimensional drawings represent only an extract of all possible versions. Detailed dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".

6) IEC 61010-17) IEC 61010-1

80

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Plastic housing~ 69 mm(2.72")

ø 79 mm(3.11")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 84 mm(3.31")

M16x1,5

112

mm

(4.4

1")

M20x1,5/½ NPT1 2

ø 79 mm(3.11")

Fig.59:HousingversionsinprotectionIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

Aluminium housing

21

ø 86 mm(3.39")

~ 116 mm(4.57")

116

mm

(4.5

7")

M20x1,5M20x1,5/½ NPT

~ 87 mm(3.43")

M16x1,5

ø 86 mm(3.39")

120

mm

(4.7

2")

M20x1,5/½ NPT

Fig.60:HousingversionsinprotectionIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

81

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

Aluminium housing with protection rating IP 66/IP 68 (1 bar)

120

mm

(4.7

2")

~ 105 mm(4.13")

116

mm

(4.5

7")

~ 150 mm(5.91")

ø 86 mm(3.39")

ø 86 mm(3.39")

M20x1,5/½ NPT

M16x1,5

2

M20x1,5M20x1,5

1

Fig.61:HousingversionsinprotectionIP␣66/IP␣68(1␣bar)-withintegrateddisplayandadjustmentmodulethehousingis9␣mm/0.35␣inhigher1 Single chamber version2 Double chamber version

Stainless steel housing~ 69 mm(2.72")

ø 79 mm(3.11")

117

mm

(4.6

1")

M20x1,5/½ NPT

~ 59 mm(2.32")

ø 80 mm(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 87 mm(3.43")

ø 86 mm(3.39")

120

mm

(4.7

2")

M20x1,5/½ NPT

M16x1,5

321

Fig.62:HousingversionsinprotectionIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version, electropolished2 Single chamber version, precision casting3 Double chamber version, precision casting

82

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

Stainless steel housing with protection rating IP 66/IP 68, 1 bar

117

mm

(4.6

1")

~ 103 mm(4.06") ø 79 mm

(3.11")

120

mm

(4.7

2")

~ 105 mm(4.13") ø 86 mm

(3.39")

M20x1,5

M20x1,5/½ NPT

M16x1,5

~ 93 mm(3.66") ø 80 mm

(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

321

Fig.63:HousingversionsinprotectionIP␣66/IP␣68(1␣bar)-withintegrateddisplayandadjustmentmodulethehousingis9␣mm/0.35␣inhigher1 Single chamber version, electropolished2 Single chamber version, precision casting3 Double chamber version, precision casting

VEGAPULS69,plastichornantennawithcompressionflange

126

mm

(4.9

6")

10,5

mm

(0.4

1")

19 m

m(0

.75"

)

ø 75 mm(2.95")

ø 115 mm(4.53")

ø 156 mm(6.14")

ø 200 mm(7.87")

ø 21 mm (0.83")

ø 107 mm (4.21")

1

Fig.64:VEGAPULS69,plastichornantenna,compressionflange1 Compressionflange

83

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

VEGAPULS69,plastichornantennawithadapterflange

2

1144

mm

(5.6

7")

36,5

mm

(1.4

4")

20 m

m(0

.79"

)

17,5

mm

(0.6

9")

ø 75 mm(2.95")

ø 98 mm(3.86")

Fig.65:VEGAPULS69,plastichornantenna,adapterflange1 Adapterflange2 Process seal

84

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

VEGAPULS 69, plastic horn antenna with mounting strap

125 mm(4.92")2,5 mm

(0.10")

ø 75 mm(2.95")

ø 107 mm(4.21")

ø 115 mm(4.53")

300

mm

(11.

81")

19 m

m(0

.75"

)

98 m

m(3

.86"

)6

mm

(0.2

4")

8,5

mm

(0.3

4")

9 mm(0.35")

85 m

m(3

.35"

)

12 m

m(0

.47"

)9

mm

(0.3

5")

12 mm(0.47")

170

mm

(6.6

9")

Fig.66:VEGAPULS69,plastichornantenna,mountingstrapin170or300mmlength

85

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

VEGAPULS 69, metal jacketed lens antenna

21

144

mm

(5

.67"

)63 m

m(2

.48"

)

Fig.67:VEGAPULS69,metaljacketedlensantennainflangeversion

VEGAPULS 69, metal jacketed lens antenna and swivelling holdermax. 10°

144

mm

(5

.67"

)

63 m

m(2

.48"

)

21

Fig.68:VEGAPULS69,metaljacketedlensantennaandswivellingholder

86

11 Supplement

VEGAPULS 69 • 4 … 20 mA/HART two-wire

47247-EN-140526

11.3 Industrial property rightsVEGA product lines are global protected by industrial property rights. Further information see www.vega.com.Only in U.S.A.: Further information see patent label at the sensor housing.VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.Nähere Informationen unter www.vega.com.Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec-tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus-trial. Para mayor información revise la pagina web www.vega.com.Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте www.vega.com.VEGA系列产品在全球享有知识产权保护。进一步信息请参见网站<www.vega.com>。

11.4 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.

87

INDEX

VEGAPULS 69 • 4 … 20 mA/HART two-wire

4724

7-EN

-140

526

INDEX

AAdjustment 44, 45Adjustment system 38Adjust the current output 51Adjust the indication 46

CChange the language 46Check output signal 65Connecting

– Electrically 27 – To the PC 56

Connection – Cable 27 – Steps 28 – Technology 27

Copy sensor settings 50Current output 45Current output Min./Max. 46Curve indication

– Echo curve 47

DDamping 45Date/Time 49Default values 49Deviation 65Display lighting 47

EEcho curve memory 60Echo curve of the setup 48EDD (Enhanced Device Description) 59Electronics and terminal compartment, single chamber housing 30Error codes 63Event memory 60

FFalse signal suppression 51Faultrectification65Functional principle 9

GGrounding 27

HHART address 53HART resistance 56

LLinearization53Lock adjustment 46

MMain menu 40Measured value memory 60Measurement loop name 40Mounting

– Flange 15 – Strap 13

NNAMUR NE 107 62, 64

PPeak value indicator 47Polarisation 16

RRepair 69Reset 49

SSensor status 47Service hotline 68Setup

– Quick setup 39Shielding 27Simulation 48Socket 19Special parameters 53Status messages - NAMUR NE 107 61

TType label 8

UUnits 40

VVessel installations 23Vessel insulation 24