    MANUAL CODE: SYJS-006 -03 Rev.0 .

    Haier Group

    Auto-Restart function

    Group control(with a group controller)

    Auto-changeover

    The same outdoor unit can match with cassette \convertible\

    duct type indoor unit

    With new environment friendly refrigerant R407C

    Weekly timing(with a weekly timer)

    Features

    Service Manual

    Commercial Air Conditioning

    4HP 5HP UniversalOutdoor Unit air conditioning

    AC36NACBEA+AU36NAIBEA

    AD36NAMBEA+AU36NAIBEA

    AB36NACBEA+AU36NAIBEA

    Remotoe control and Wired remote control(Optional)

    AC42NACBEA+AU42NAIBEA

    AD42NAMBEA+AU42NAIBEA

    AB42NACBEA+AU42NAIBEA

    AP42NACBEA+AU42NAIBEA

    AD36NAHBEA+AU36NAIBEA

    AD42NAHBEA+AU42NAIBEA

  • 8/11/2019 Op Manual AU42NAIBEA

    2/149

    CONTENTS

    1. Description of Products & Features....2

    2. Specifications. ...6

    3. Safety precaution...14

    4. Net dimensions of indoor and outdoor unit...17

    5. Installation instructions . ..20

    6. Parts and functions .....48

    7. Remote controller functions.50

    8. Refrigerant diagram......71

    9. Electrical control functions72

    10. Diagnostic information(trouble shooting).78

    11. Electrical data..........................................85

    12. Exploded views and parts lists................ 88

    13. Perdormance curves...............................96

    14. Noise level charts....................................104

    15.Air velocity distribution ...............................106

    CONTENTS

    Contents.....................................................1

    - 1 -

  • 8/11/2019 Op Manual AU42NAIBEA

    3/149

    1. Description of product code and brief introduction of the series

    a) Description of the coding rule of the models

    A U 36 N A I B D A

    Climate type:T1

    Design serial number

    Air conditioner

    Product series:one-tag-one

    Outdoor unit

    Product specification:valid digit above kilobi

    Adaptive voltage:38

    0-400

    V/50Hz

    Appearance features

    Product type: heat pump R407C

    A B 36 N A C B D A

    Climate type:T1

    Design serial number

    Air conditioner

    Product series:one-tag-one

    Product specification:valid digit above kilobi

    Adaptive voltage:380-400V/50Hz

    Appearance features

    Product type: heat pump R407C

    Product type:indoor unit

    P:Cabinet typeC:Convertible typeB:Cassette type D:Duct type

    b). Standard working condition

    Operating ModeIndoor Operating Mode Outdoor Operating Mode

    Nominal Cooling

    Temp. Temp.Humidity

    DB:27 WB:19 DB:35

    DB:7 WB:6

    WB:24

    Humidity

    DB:20 WB:15Nominal Heating

    No.

    1

    2

    Temp.Humidity

    DB:27 WB:19 DB:35

    DB:7 WB:6

    WB:24

    Humidity

    DB:20 WB:15Nominal Heating

    No.

    1

    2

    2

  • 8/11/2019 Op Manual AU42NAIBEA

    4/149

    c)Brif introduction of the series:

    Convertible type:

    AC36NACBEA+AU36NAIBEA AC42 NACBDA+AU42NAIBEA

    (1).Ceiling convertible,flexible installation,convenient

    maintenance,saving the users' expenditures(2).Adopting three-phase power supply,applicable for household

    and commercial usage

    (3).Dual air outlet design,floor air blowing,accelerating the indoor aircirculation, quick temperature adjustment

    (4).Long-distance air blowing,large power,large cooling/heating

    ratio

    (5).Intelligent remote control,convenient and flexible control

    (6).Super-slim indoor unit design,luxury and nice-looking,saving

    space,harmonious and unitive with the indoor environment

    (7).Adopting screw-fastening for the air inlet grill,firmly

    fixed;adopting slipwayinsert-lock fastening method for the

    filter screen,convenient cleaning or replacing the filter screen

    without opening the air inlet grill.

    (8).Group control,units up to 128 sets can be controlled .

    Duct type :

    AD36NAMBEA+AU36NAIBEA AD42NAMBEA+AU42 NAIBEA

    Totally concealed machine body

    All the machine body is to be installed inside the ceiling, having no effect on thebeauty of the room and without taking any room space.

    Air intake via the rear air intake ductThis new design has changed the former unique pattern of air intake, and a largerdistance between air intake and air return cycles as well as better air quality can beachieved.

    Flexible and easier installation

    The machine body is to be installed in a totally concealed way,its fan system hasa longer distance coverage so as to supply its airflow to several rooms, and theindoor unit may be installed inside the ceiling of a room or corridor. Theinstallation is simple and flexible, and there is no need to have specified personnel

    for management, thus cutting down the expenses; the machine is lighter andsmaller, and convenient for installation, it takes an extremely small building space,thus lower the construction cost; the indoor unit is to be concealed inside theceiling, and hence the usable space can be saved and the room decoration willnot be affected.

    3

  • 8/11/2019 Op Manual AU42NAIBEA

    5/149

    AB36NACBEA+AU36NAIBEA AB42NACBEA+AU42NAIBE A

    Products characteristic:

    Completely invisible machine body:The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither

    breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of airconditioner allows it to blend right into ceiling.

    Superbly efficient healthy filter:

    Superbly efficient antibiotic materials are utilized and can prevent germs from

    breeding efficiently .

    Flexible and easy installationSlim design with machine body, completely ceiling concealing and portable shape, all make it greatly

    easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional

    cost prices. It also features a specific drainage system with up to 600mm lift , which allows reducing

    installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill,the ceiling can be protected from pollution effectively and allow the airflow to fit people's

    comfortable need much more.

    Compensation function of power failure:When meeting a power failure during running, no matter how long it will be, once the power isrestored, air conditioner will automatic restart with the previous status.

    Safety and reliable control due to various signal controls1 Inputting with press buttons on the panel2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipetemperature sensors,

    3 Piping pressure signals4 Compressor current signals5 Testing signals6 System time-shorten signal

    7 Water overflowing signal

    8 Communication signals between indoor unit and front plate or between indoor unit and outdoorunit .

    Silent designThe use of radial outward flow turbine fan produces larger cyde airflow volume and acts tosignificantly decrease operating noise.

    When using remote-controlling mode, it is comfortable and convenient to operate.

    Cassette type:

    4

    Advanced wire-controllerand convenient remote-controllerThe new wired controller can connect with 16 indoor units without any device such as detectors.

    The new remote controller can be used for single unit or muti-free unit, or H-MRV,very convenient.

    In addition, it can be compatible with the old remote controllers.

    Low ambient temperature cooling function (optional)Equipped with high/low pressure protection switch

    NEW

    NEW

  • 8/11/2019 Op Manual AU42NAIBEA

    6/149

    Climate type

    Type of Air Conditioner T1 T2 T3

    Cool only 18 43 0 35 21 52

    Heat pump -7 43 -7 35 -7 52

    Electricity heating 43 35 52

    d). Brief Introduction for T1\ T2\ T3 working condition

    Climate type

    Type of Air Conditioner T1 T2 T3

    Cool only 18 43 10 35 21 52

    Heat pump -7 43 -7 35 -7 52

    Electricity heating 43 35 52

    5

  • 8/11/2019 Op Manual AU42NAIBEA

    7/149

    Function Cooling Heating

    Capacity BTU/h 36000 41000

    W 4000 3800W 5500 5500

    EER or COP BTU/W 9 10.8

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHzA / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    k / kUnit model (color)

    Compressor Model / Manufacture

    Type

    Fan Type Number Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total area mTemp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator L

    Noise level dB(A)

    material of reduce noise

    crankcase heater power Wkg / kg

    Refrigerant Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    /

    43/41/39

    /

    /

    //

    /

    /

    /

    /

    Remote

    /

    2-7

    1325920370

    PVC 26/32

    MAX.Piping length 50

    Weight (Net / Shipping) /

    Type of Four way valve /

    /

    Defrosting

    PIPING

    R407C 3800

    65

    Pipe 9.52

    19.05

    Falre

    Between I.D &O.MAX.Drop 30

    Dimension /

    /

    //

    /

    /

    /

    /

    Outdoorunit

    /

    Weight (Net / Shipping) 46/53

    Panel Dimension 134095080

    1400995115Weight (Net / Shipping)

    /

    45

    Dimension 1230840280

    /

    0.06

    1980/-/-

    Centrifugal*1

    590+30/490+40/420+50

    TP2M/7

    item Model AB36NACBEA(SANYO)

    5

    /

    Total power inputMax. power input

    Running /Max.Running

    8.4/12

    3N~ 380V-400V 50HZ

    Indoorunit

    AB36NACBEA(WHITE)

    Noise level (H-M-L)

    Electricity Heater

    cooling7.5/9.5heating6.5/9.5

    2.Specifications

    6

  • 8/11/2019 Op Manual AU42NAIBEA

    8/149

    Function Cooling Heating

    Capacity BTU/h 36000 41000

    W 4000 3800

    W 5500 5500

    EER or COP BTU/W 9 10.8

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    kg / kg

    Unit model (color)

    Compressor Model / Manufacture

    TypeFan Type Number

    Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator LNoise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Refrigerant Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    cooling7.5/9.5heating6.5/9.5

    45

    Dimension

    3pH,380V-400V 50HZ

    item Model AC36NACBEA(SANYO)

    5

    /

    0.06

    1600/1400/1200

    Noise level (H-M-L)

    Electricity Heater

    TP2M/9.52

    Weight (Net / Shipping) 62/77

    2-7

    1980761295PVC 26/32

    /

    48/-/44

    1920715235

    /

    Between I.D &O.MAX.Drop 30

    Outdoorunit

    /

    /

    Dimension /

    /

    /

    Defrosting

    Indoorunit

    AC36NACBEA(WHITE)

    PIPING

    R407C 3800

    65

    Pipe9.52

    19.05

    Flare

    Weight (Net / Shipping) /

    Type of Four way valve /

    /

    /

    /

    /

    Panel Dimension /

    /

    Weight (Net / Shipping)

    MAX.Piping length 50

    Remote

    /

    /

    /

    /

    /

    /

    /

    Total power input

    Max. power input

    Running /Max.Running

    /

    /

    /

    /

    /

    CentrifugalX4

    1350+30/1280+30/1050+30

    7

  • 8/11/2019 Op Manual AU42NAIBEA

    9/149

    Function Cooling Heating

    Capacity BTU/h 36000 41000

    W 4000 3800

    W 5500 5500

    EER or COP BTU/W 9 10.8

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    kg / kg

    Unit model (color)

    Compressor Model / Manufacture

    TypeFan Type Number

    Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator LNoise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Refrigerant Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    /

    MAX.Piping length 50

    Wired

    /

    /

    /

    /

    /

    /

    /

    /

    /

    /

    /

    /

    Panel Dimension

    Weight (Net / Shipping) /

    Type of Four way valve /

    /

    Defrosting

    I

    ndoorunit

    AD36NAMBEA(WHITE)

    PIPING

    R407C 3800

    65

    Pipe9.52

    19.05

    Flare

    Between I.D &O.MAX.Drop 30

    Outdoorunit

    /

    /

    Dimension /

    /

    /

    /

    /

    Weight (Net / Shipping) /

    CentrifugalX3

    1050/ 960/ 870/810

    TP2M/9.52

    Weight (Net / Shipping) 55/75

    2-7

    1557800370PVC 26/32

    /

    43/-/39

    1410645350

    /

    0.06

    2040/1800/1600

    item Model AD36NAMBEA(SANYO)

    5

    /

    Total power input

    Max. power input

    Running /Max.Running

    /

    Noise level (H-M-L)

    Electricity Heater

    3N 380V-400V 50HZ

    cooling7.5/9.5heating6.5/9.5

    45

    Dimension

    8

  • 8/11/2019 Op Manual AU42NAIBEA

    10/149

    Function cooling heating

    Capacity BTU/h 36000 41000

    Capacity kW 10.55 12.01

    Sensible heat ratio 79% /

    W 4000 3800

    W 5500 5500

    EER or COP W/W 2.64 3.16

    Dehumidifying capacity 10m/hPower cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    Outlet distribution hole dimension mm

    kW

    dB(A)

    kg / kg

    Unit model (color)

    Model / Manufacture

    Type

    Type NumberSpeed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator L

    Noise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    /

    /

    Refrigerant

    /

    Compressor

    Fan

    48/46/44

    /

    /

    /

    /

    wired

    /

    /

    /

    /

    Type of Four way valve /

    /

    Defrosting /

    /

    MAX.Piping length 50

    Weight (Net / Shipping) /

    PIPING

    R407C 3800

    65

    Pipe9.52

    19.05

    flared

    Between I.D &O.MAX.Drop 30

    /

    /

    Heat exchanger

    /

    /

    /

    TP2M/9.52

    Outdoorunit

    /

    Weight (Net / Shipping) 62/77

    Dimension/

    /

    PVC 26/32

    1197828355

    item Model AD36NAHBEA

    5/

    Total power input

    Max. power input

    Running /Max.Running

    centrifugal X2

    Dimension

    /

    2580/2070/1560

    2-7

    1450980530

    Fan

    Heat exchanger

    0.06

    Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DBOutdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB

    1090/1000/930

    3PH 380V-400V 50HZ

    Indoor

    unit

    AD36NAHBEA (grey)

    Noise level (H-M-L)

    Electricity Heater

    Cooling:7.5/9.5, Heating:6.5/9.5

    45

  • 8/11/2019 Op Manual AU42NAIBEA

    11/149

    Function Cooling Heating

    Capacity BTU/h 36000 41000

    W 4000 3800

    W 5500 5500

    EER or COP BTU/W 9 10.8

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package

    LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    kg / kg

    Unit model (color)

    Compressor Model / Manufacture

    Type

    Fan Type Number Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator LNoise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Refrigerant Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    Running /Max.Running

    /

    6000

    MAX.Piping length 50

    /

    /

    /

    64/-/-

    AUTO

    /

    Capiliary

    TP2M/9.52

    43-60

    0.15

    840+30

    Scroll

    C-SBN303H8A(SANYO)

    Panel Dimension /

    /

    Weight (Net / Shipping) 91/111

    Type of Four way valve DHF-12

    XPE

    Defrosting

    Indoorunit

    /

    PIPING

    R407C 3800

    65

    Pipe9.52

    19.05

    Flare

    Between I.D &O.MAX.Drop 30

    Outdoorunit

    AU36NAIBEA(WHITE)

    Axial-flow2

    Dimension 9803401250

    10504401375

    0.92

    Weight (Net / Shipping) /

    Weight (Net / Shipping) /

    /

    //

    /

    /

    /

    /

    /

    item Model AU36NAIBEA(SANYO)

    5

    /

    Total power input

    Max. power input

    Noise level (H-M-L)

    Electricity Heater

    3N380V-400V 50HZ

    cooling7.5/9.5heating6.5/9.5

    45

    Dimension /

    /

    /

    /

    9

  • 8/11/2019 Op Manual AU42NAIBEA

    12/149

    Function Cooling Heating

    Capacity BTU/h 42000 48000

    W 4800 5000W 5700 7200

    EER or COP BTU/W 8.75 9.6

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    kg / kgUnit model (color)

    Compressor Model / Manufacture

    TypeFan Type Number

    Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mmTotal area mTemp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator LNoise level dB(A)

    material of reduce noise

    crankcase heater power Wkg / kg

    Refrigerant Type / Charge gRechar e uantit /mLiquid mm

    Gas mm

    Connecting Method

    m

    m

    /

    /

    /

    /

    /

    /

    /

    PVC 26/32

    1400995115

    Running /Max.Running

    current

    /

    43/41/39

    MAX.Piping length 50

    Weight (Net / Shipping) /

    Type of Four way valve /

    /

    Defrosting

    PIPING

    R407C 4000

    65

    Pipe 9.52

    19.05

    Flare

    Between I.D &O.MAX.Drop 30

    Dimension /

    /

    /

    /

    /

    0.06

    /

    /

    /

    /

    Remote control

    /

    2-7

    1325920370

    8.4/12Weight (Net / Shipping)

    /

    /

    3N~ 380V-400V 50HZ

    Indoorunit

    AB42NACBEA(WHITE)

    Outdoorunit

    /

    Weight (Net / Shipping) 46/53

    Panel Dimension 134095080

    item model AB42NACBEA

    5

    /

    Total power inputMax. power input

    Noise level (H-M-L)

    Electricity Heater

    Cooling8.3/10.2Heating9.5/12.6

    59.5

    1980/-/-

    Centrifugal

    590+30/490+40/420+50

    TP2M/7

    Dimension 1230840280

    10

  • 8/11/2019 Op Manual AU42NAIBEA

    13/149

    Function Cooling Heating

    Capacity BTU/h 42000 48000

    W 4800 5000

    W 5700 7200

    EER or COP BTU/W 8.75 9.6

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    kg / kg

    Unit model (color)

    Compressor Model / Manufacture

    TypeFan Type Number

    Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator L

    Noise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Refrigerant Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    mm

    Cooling8.3/10.2Heating9.5/12.6

    49.5

    Dimension

    3N380V-400V 50HZ

    Item model AC42NACBEA(SANYO)

    5

    /

    0.06

    1600/1400/1200

    Noise level (H-M-L)

    Electricity Heater

    TP2M/9.52

    Weight (Net / Shipping) 62/77

    2-7

    1980761295PVC 26/32

    /

    48/-/44

    1920715235

    /

    Between I.D &O.MAX.Drop 30

    Outdoorunit

    /

    /

    Dimension /

    /

    /

    Defrosting

    Indoorunit

    AC42NACBEA(WHITE)

    PIPING

    R407C 4000

    65

    Pipe9.52

    19.05

    Flare

    Weight (Net / Shipping) /

    Type of Four way valve /

    /

    /

    /

    /

    Panel Dimension /

    /

    Weight (Net / Shipping)

    MAX.Piping length 50

    Remote

    /

    /

    /

    //

    /

    /

    /

    Total power input

    Max. power input

    Running /Max.Running

    /

    /

    /

    /

    CentrifugalX2

    1350+30/1280+30/1050+30

    11

  • 8/11/2019 Op Manual AU42NAIBEA

    14/149

    Function Cooling Heating

    Capacity BTU/h 42000 48000

    W 4800 5000

    W 5700 7200

    EER or COP BTU/W 8.75 9.6

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    kg / kg

    Unit model (color)

    Compressor Model / Manufacture

    TypeFan Type Number

    Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator L

    Noise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Refrigerant Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    mm

    /

    MAX.Piping length 50

    Wired

    /

    /

    /

    //

    /

    /

    /

    /

    /

    /

    /

    Panel Dimension

    Weight (Net / Shipping) /

    Type of Four way valve /

    /

    Defrosting

    Indoorunit

    AD42NAMBEA(WHITE)

    PIPING

    R407C 4000

    65

    Pipe9.52

    19.05

    Flare

    Between I.D &O.MAX.Drop 30

    Outdoorunit

    /

    /

    Dimension /

    /

    /

    /

    /

    Weight (Net / Shipping) /

    Weight (Net / Shipping) 55/75

    2-7

    14509800530PVC 26/32

    /

    42/36/30

    cooling8.3/10.2heating9.5/12.6

    49.5

    Dimension 1410645350

    /

    0.06

    2040/1800/1600

    CentrifugalX3

    1050/960/ 870/810

    TP2M/9.52

    3N380V-400V 50HZ

    Item model AD42NAMBEA(SANYO)

    5

    5X2.5mm2

    Total power input

    Max. power input

    Running /Max.Running

    Noise level (H-M-L)

    Electricity Heater

    12

  • 8/11/2019 Op Manual AU42NAIBEA

    15/149

    Function cooling heating

    Capacity BTU/h 42000 48000

    Capacity kW 12.31 14.06

    Sensible heat ratio 79% /

    W 4800 5000

    W 5700 7200

    EER or COP W/W 2.56 2.81

    Dehumidifying capacity 10m/hPower cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    Outlet distribution hole dimension mm

    kW

    dB(A)

    kg / kg

    Unit model (color)

    Model / Manufacture

    Type

    Type NumberSpeed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator L

    Noise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    /

    /

    Refrigerant

    /

    Compressor

    Fan

    48/-/44

    /

    /

    /

    /

    wired

    /

    /

    /

    /

    Type of Four way valve /

    /

    Defrosting /

    /

    MAX.Piping length 50

    Weight (Net / Shipping) /

    PIPING

    R407C 4000

    65

    Pipe9.52

    19.05

    flared

    Between I.D &O.MAX.Drop 30

    /

    /

    Heat exchanger

    /

    /

    /

    TP2M/9.52

    Outdoorunit

    /

    Weight (Net / Shipping) 62/77

    Dimension/

    /

    PVC 26/32

    1197828355

    item Model AD42NAHBEA

    5/

    Total power input

    Max. power input

    Running /Max.Running

    centrifugal X2

    Dimension

    /

    2580/-/1560

    2-7

    1450980530

    Fan

    Heat exchanger

    0.06

    Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DBOutdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB

    1090+30/-/930+50

    3PH 380V-400V 50HZ

    Indoor

    unit

    AD42NAHBEA (grey)

    Noise level (H-M-L)

    Electricity Heater

    Cooling: 8.3/10.2, Heating: 9.5/12.6

    49.5

  • 8/11/2019 Op Manual AU42NAIBEA

    16/149

    Function coolin heatin

    Capacity BTU/h 42000 50000

    Capacity kW 12.31 14.65

    W 5000 6000

    W 6000 7200

    EER or COP W/W 2.46 2.44

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH

    mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    dB(A)

    kg / kg

    Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    0.06

    Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DBOutdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB

    590/400/350

    1PH 380V-400V 50HZ

    Indoorunit

    AP42NACBEA (white)

    Noise level (H-M-L)

    Cooling:8.5/10.2 Heating:10.0/12.0

    49.5

    Dimension

    0.338

    1560/-/-

    2-7

    1952660455

    PVC 26/32

    1820530310

    item Model AP42NACBEA

    5

    /

    Total power input

    Max. power input

    Running /Max.Running

    centrifugalX1

    TP2M/9.52

    Weight (Net / Shipping) 62/77

    PIPING

    R407C 4000

    /

    Pipe9.52

    19.05

    flared

    Between I.D &O.MAX.Drop 30

    MAX.Piping length 50

    wired control

    Refrigerant

    Fan

    Heat exchanger

    48/-/44

  • 8/11/2019 Op Manual AU42NAIBEA

    17/149

    Function Cooling Heating

    Capacity BTU/h 42000 48000

    W 4800 5000

    W 5700 7200

    EER or COP BTU/W 8.75 9.6

    Dehumidifying capacity 10m/h

    Power cable

    Power source NVHz

    A / A

    Start Current A

    Unit model (color)

    Fan Type Number

    Speed(H-M-L) r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total Area m

    Temp. scope

    External LWH mmmmmm

    Package

    LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Control type (Remote /wired)

    Fresh air hole dimension mm

    kW

    dB(A)

    kg / kg

    External LWH mmmmmm

    Package LWH mmmmmm

    kg / kg

    Unit model (color)

    Compressor Model / Manufacture

    Type

    Fan Type Number Speed r/min

    Fan motor output power kW

    Air-flow(H-M-L) m/h

    Heat exchanger Type / Diameter mm

    Total area m

    Temp. scope

    External LWH mmmmmm

    Package LWH mmmmmm

    Drainage pipe (material , I.D./O.D.) mm

    Refrigerant control method mm/mm

    Volume of Accumulator LNoise level dB(A)

    material of reduce noise

    crankcase heater power W

    kg / kg

    Refrigerant Type / Charge g

    Recharge quantity g/m

    Liquid mm

    Gas mm

    Connecting Method

    m

    m

    Cooling8.3/10.2Heating9.5/12.6

    49.5

    Dimension

    PVC 26/32

    3N380V-400V 50HZ

    Item model AU42NAIBEA(SANYO)

    5

    /

    /

    /

    /

    Noise level (H-M-L)

    Electricity Heater

    Weight (Net / Shipping) /

    /

    //

    /

    /

    /

    Between I.D &O.MAX.Drop 30

    Outdoorunit

    AU42NAIBEA(WHITE)

    Axial-flow2

    Dimension 9803401225

    10504401375

    0.92

    Defrosting

    Indoorunit

    /

    PIPING

    R407C 4000

    65

    Pipe9.52

    19.05

    Flare

    Weight (Net / Shipping) 91/116

    Type of Four way valve DHF-12

    XPE

    43-60

    0.15

    1180+30 840+30

    Scroll

    C-SBN373H8A(SANYO)

    Panel Dimension /

    MAX.Piping length 50

    /

    /

    42

    64/-/-

    Auto

    /

    Capiliary

    TP2M/9.52

    Total power input

    Max. power input

    Running /Max.Running

    6000

    /

    Weight (Net / Shipping) /

    /

    /

    /

    13

  • 8/11/2019 Op Manual AU42NAIBEA

    18/149

    WARNING

    CAUTION

    WARNING

    CAUTION

    This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior

    environment such as engineering shop could cause equipment malfunction.

    Please entrust installation to either the company which sold you the equipment or to a professional contractor.

    Defects from improper installations can be the cause of water leakage, electric shocks and fires.

    Execute the installation accurately, based on following the installation manual. Again, improper installations can

    result in water leakage, electric shocks and fires.

    When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned

    countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.

    In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,

    and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold

    concentration does occur,there is the danger of a resultant oxygen deficiency accident.

    For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,

    injury can result from a falling of the unit.

    Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and

    hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.

    For electrical work, please see that a licensed electrician executes the work while following the safety standards

    related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive

    use circuits are used.

    Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and

    fires.

    Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to

    the terminal connection part, through properly securing it. Improper connection or securing can result in heat

    generation or fire.

    Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can

    also result in heat generation or fire.

    WARNING

    In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.

    After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please

    explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's

    manual.

    Moreover, ask the customer to keep this sheet together with the owner's manual.

    Please read these "Safety Precautions" first then accurately execute the installation work.

    Though the precautionary points indicated herein are divided under two headings, and

    those points which are related to the strong possibility of an installation done in error

    resulting in death or serious injury are listed in the section. However, there is also a

    possibility of serious consequences in relationship to the points listed in the section as well.

    - 14-

    SAFETY PRECAUTIONS

    3 SAFETY PRECAUTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    19/149

    When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated

    refrigerant (please see nameplate) within the refrigeration cycle.

    Rupture and injury caused by abnormal high pressure can result from such mixing.

    Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this

    company can result in water leakage, electric shock, fire and refigerant leakage.

    The position of indoor unit must be above the floor 2.5m.

    WARNING

    Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone

    ground wire.

    Improper placement of ground wires can result in electric shock.

    The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not

    installing an earth leakage breaker may result in electric shock.

    Do not install the unit where there is a concern about leakage of combustible gas.

    The rare event of leaked gas collecting around the unit could result in an outbreak of fire.

    For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to

    prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.

    CAUTION

    -15

    SAFETY PRECAUTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    20/149

    185 185

    30

    52

    88Screw Hole

    (M10)

    580

    950

    Power wiring Terminal

    7018

    18

    38

    340

    38

    380

    1250

    25

    16

    3 Net dimensionsof indoor unit and outdoor unit

    1)Outdoor unit

  • 8/11/2019 Op Manual AU42NAIBEA

    21/149

    1340

    9 5 0

    840

    30

    2 2 0

    2 0

    5 0

    2 8 0

    260

    315270

    1 3 5

    160 3

    0 0

    295

    1070

    7 8 0

    8 6 0

    - 8 9 0

    615

    615

    1250-1280 (ceiling hole)

    over 1

    0 0 0

    mm

    1 5 5

    123055 55

    2 2 0

    over1500

    over1500

    ove

    r1500

    ove

    r1500

    (hanging position)

    Model: AB36NACBEA Cassette type Indoor unit

    - 17 -

    NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

    2)Indoor unit

  • 8/11/2019 Op Manual AU42NAIBEA

    22/149

    Model: AC36NACBEA Convertible Indoor unit

    R15

    85

    100

    19

    5

    19201800

    600

    690

    630

    100

    85

    310

    590

    545

    4 0

    2 3 5

    1 5 0

    1 8 0

    85 150

    60

    195

    600

    105

    600

    300300

    555

    30

    1 1 0

    60

    8 5

    3 0 0

    1010

    25

    6 5

    4 5

    drainage pipe

    NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

    18

  • 8/11/2019 Op Manual AU42NAIBEA

    23/149

    NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

    A-A

    gas

    pipe

    liquid

    pipe

    drainage

    pipe

    Model: AD36NAMBEA AD42NAMBEA

    19

  • 8/11/2019 Op Manual AU42NAIBEA

    24/149

    Model: AD36NAHBEA AD42NAHBEA

  • 8/11/2019 Op Manual AU42NAIBEA

    25/149

    5.1.1 Installation tools

    1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner,

    shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter

    7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor

    11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump

    15 .Flat screwdriver

    5.1.2 Standard accessories

    Part name

    QTY

    Shape

    Clamp

    2 Piece

    Washer

    8 Piece 6 Piece

    Clamp Paper pattern

    1 Set

    6321

    3 Piece

    Screw(M5 size)

    For installationofpaper pattern

    Drain hose

    1 Piece

    Please check if your unit is delivered with following

    Part name

    QTY

    Shape

    Dry batteryInsulator Sealing pad Sealing pad Sealing pad7

    8 9 12

    1 Piece 1 Piece

    Insulator

    2 Piece 1 Piece 1 Piece 2 Piece

    Small sizeMedium sizeLarge sizeFor liquid pipeFor gas pipe R03, 7#

    [Other]

    OperationManual

    Ornamentpanel

    Remotecontroller

    54

    1110

    5.1.3 Installation of indoor unit

    5.1.3.1 Before installationDetermine the way kto carry unit to installation place.

    Don't remove packing until unit reaches installation place.

    If unpacking is unkavoidable, protect unit properly.

    5.1.3.2 Selection of installation place

    (1) Installation place shall meet the following and agreed by customers:

    Place where proper air flow can be ensured.

    No block to air flow.

    Water drainage is smpoth.

    Place strong enough to support unit weight.

    Place where inclination is not evident on ceiling.

    Enough space for mainenance.

    Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. Thisis helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio

    wave is strong)

    - 20 -

    INSTALLATION INSTRUCTIONS

    5 INSTALLATION INSTRUCTIONS

    5.1 Cassette type

  • 8/11/2019 Op Manual AU42NAIBEA

    26/149

    8

    260

    260

    (2) Ceiling heightIndoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and InstallationManual of ornament panel.)

    (3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take

    necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced)

    Installation space

    Air inletAir outlet

    2500Over

    Air ou tle t

    1500 Over1500 Over 1500 Over 1500 Over

    Air ou tle tAir inlet

    Air inlet

    5.1.3.3 Preparation

    (1) Position of ceiling opening between unit and suspending bolt.Unit: mm

    - 21 -

    INSTALLATION INSTRUCTIONS

    50~100

    Roof

    Anchor bolt

    Long nut

    Suspending bolt

    Ceiling

    (2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)

    Refer to paper pattern for dimension of ceiling hole.

    Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before

    installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent

    vibration. Contact your real estate dealer

    (3) Install a suspending bolt.

    (Use a M10 bolt)

    To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new

    ceiling, use built-in type bolt or parts prepared in the field.

    Before going on installing adjust space between ceiling.

    Note: All the above mentioned parts shall be prepared in field.

    890(Ceiling opening)

    ( D i s t a n c e b e t w e e n s u s p e n d in g b o l t s )1070515

    515

    (D

    istance

    betw

    eens

    uspendingb

    olts)

    860(Ceilingop

    ening)

    780 20 Over

  • 8/11/2019 Op Manual AU42NAIBEA

    27/149

    5.1.3.4 Installation

    4 5

    7

    (2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.

    (1) Install unit temporally

    In the case of new ceiling

    Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.

    < After installation on the ceiling >

    (3) Adjust unit to its right position. (Refer to preparation for the installation-(1))

    (4) Check unit's horizontal level.

    Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using

    horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem

    may occur on floating switch, causing water leakage.)

    (5) Remove the washer mounlting , and tighten the nut above.

    (6) Remove the paper pattern.

    (1) Install unit temporally

    Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the

    bracket. Fix the bracket firmly.

    (2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).

    (3) Proceed with and of "In the case of new ceiling".

    LevelPolythene pipe

    3 4

    In the case of ceiling already exists

    Scrtews at the piping outlet is fixed at the cornerof drain pan.

    Center of ceiling hole Paper pattern 4Paper pattern

    5Screw (accessory)5Screw(accessory)

    [Fix the paper pattern]

    5.1.3.5 Refrigerant piping

    As for outdoor piping, please refer to installation Manual of outdoor unit.

    6 9

    Apple refrigerant oil

    Torque spanner

    spanner

    Piping joing

    Flare nut

    Medium size seal pad 9 (accessory)

    Clip 3

    Gas pipe

    Liquid pipe

    Insulator (accessory)

    (For liquid pipe)

    Insulator (accessory)

    (For gas pipe)

    7

    6

    (Cover the piping joint with seal pad.)R0.4 ~ 0.8

    A

    Pipesize

    Tightentorque

    A(mm) Flare shape

    9.52 3270~3990N.cm

    (333~407kgf.cm)

    19.059720~11860N.cm

    (990~1210kgf.cm)

    12.0~12.4

    22.9~23.3

    90

    0.5

    45

    2

    Outdoor is precharged with refrigerant.Be sure to see the Fig.1, when connecting and removing piping from unit.For the size of the flare nut, please refer to Table 1.

    Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it.Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).Check piping joints for gas leakage. Insulate piping as shown in Fig. below.Cover joint of gas piping and insulator with seal .

    Table 1

    Diameter of PipeLiquid Pipe 9.52mm

    Gas Pipe 19.5mm

    Tighten Torque42N. m

    60N. m

    - 22 -

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    28/149

    5.1.3.6 Installation of drainage pipe

    1-1.5m

    Use the self-provided stiff pipe and clip with unit. Insert water pipe into water plug until it reaches the white tape.Tighten the clip until head of the screw is less than 4mm from hose.Wind the drain hose to the clip using seal pad 8 .Insulate drain hose in the room.

    2

    Clip 2

    Tape (White) Self-provided stiff pipe

    Clip 2

    4mm below

    (accessory)

    (accessory)

    Large size seal pad

    Clip 2

    10

    Installation height shall be less than 280mm.There should be a right angle with unit, 300mm from unit.

    Waterring can of plastic

    (1) Install water drainage pipe

    Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)

    Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.

    If downward slope can't be made, take other measures to lift it up.Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.

    Slope over 1/100

    75below

    Self-provided stiff pipe

    (accessory)

    500below

    300mm below 1~1.5m

    280below

    500below

    220

    Drain hose 1(accessory) drain water lifting pipe

    Suspending bracket

    Clip

    (accessory)

    2

    Over100

    (Note)

    If several water hoses join together, do as per following proceedures.

    Connect water hoses with a T joint.

    Specifieations of the water hoses shall meet the requirements for the unit running.

    The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.

    Method of water charging

    11

    When wiring is not complete

    Charge water fromair outlet

    Charge water frominspecting hole

    Watering can of plastic

    pipe should be about

    100 mm long

    100mm

    Water drainage port formaintenance

    (Drain water fromthis hole)

    Self-provided stiff pipe Maintenance

    Inspecting hole

    Cover of controll box

    PCB on indoor

    Terminal

    Terminal blockConnect withoutdoor unit

    1 2 3

    L N

    Power

    1 2 3

    Indoor

    Outdoor

    H07RN-F3G 4mm

    2

    H05RN-F4G 0.75mm

    2

    1 2 3R S T

    1 2 3

    N

    Indoor

    Power Outdoor

    H05RN-F4G 0.75mm

    2

    H07RN-F5G 2.5mm

    2

    (2) Check if water drainage is smooth after installation.

    Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.

    After wiring

    Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uperpart of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.Note, in this operation, fan will be running.Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove shortconnection of "CHECK" terminal.

    Check water drainage in cooling operation. See also test run.

    - 23 -

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    29/149

    5.1.3.7 Wiring

    Terminal block

    Clip A

    Cover of control box 1

    Rubber tube A

    Grounding lead

    Cover of control box 2

    Terminal blockConnect withoutdoor unit

    OutIn

    Field wiringAttach seal pad

    Don't fail to seal it, or, water may come in.

    Rubber tube Note: Have it sealed, leaving no space.

    Seal pad (small size)( )

    (Wind around wire)

    12

    All supplied parts. materials and wiring operation must in appliance with local code and regulations.

    Use copper wire only.

    When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians.

    A circuit breaker must be installed, which can cut power supply to all system.

    See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.

    Connecting of unitRemove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,tighten clamp A. Connect wires of correct pole to the terminal block inside.Wind seal (12) around wires. (Be sure to do that, or, dew may occur).Upon connecting, replace control box cover (1) and (2).

    Obscrve the following when connecting power supply terminal block: Don't connect wires of different specifications to the same terminal block. (Loose wire may cause overheating of circuit)

    Connect wires of same specifications as shown in right Fig.

    Connect wires of the same

    specifications at two sides.

    Don't connect wires of the

    same specifications at one side.

    Don't connect wires of the

    different specifications.

    5.1.3.8 Wiring example

    As for outdoor unit c ircuit, please see Installation Manual of outdoor unit.

    Note:All electric wires have their own poles, poles must match that on terminal block.

    5.1.3.9 Installation of ornament panel

    1. Prepare ornament panel

    Handling of ornament panel

    Ornament panel shall not be placed face down or against wall, neither on an uneven object.

    Don' t bend carelessly the swing flap, or, problem may occur.

    (1)Remove air inlet grill from ornament panel:

    Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)

    Lift it up for about 45 degree and remove it from ornament.Tear off adhesive tape fixing air filter on the back of the air

    inlet grill. (Refer to Fig. 2)

    Cautions for the installation

    Be sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read also

    the Installation Manual of indoor unit.

    With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.

    2

    Accessory Pad Pad

    1

    Bar

    - 24 -

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    30/149

    5_ 8mm

    3

    2

    2

    1

    4

    Holding ring

    Piping h ole position

    Swing flap motor

    Fig. 7

    SealIndoor unit

    Ceiling material

    Ornament panel

    (2) Remove cover plate at corner

    Tear off the adhesive tape,

    and slide it off.

    (Refer to Fig. 3)

    (1)

    (2)

    2. Install ornament panel on indoor unit.

    As shown in Fig . 7, match the position of

    swing flap motor with that of the indoor unit

    piping hole , so that ormament panel can be

    placed on to indoor unit.

    Installation of ornament panel

    Place the holding ring on swing flao motor

    side teporarily on hooks of the indoor unit.

    (2 pcs)Put the other two holding rings on the hooks atboth side of the indoor unit. (Care should be

    taken not to push wiring of swing flap motor

    into seals).

    Screw in all 4 screws under holding ring for

    about 15mm. (Pancl will rise).

    Adjust the ornament panel as per Fig. 7 to

    cover opening on the ceiling.

    Tighten screws to redrce the thickness of sealsbetween ornament and indoor unit to 5-

    8mm.

    1

    2

    3

    4

    5

    If indoor unit is at horizontal leveland water drainage is smooth,

    then, indoor unit height can be ad-justed throrgh holes at corners ofornament panel.

    If screws are not tighten tight, problems in Fig, 8

    might occur. Tighten screws properly.If there are still space after tightening

    of screws, please readjust the height

    of indoor unit. (Refer to Fig. 9)

    Leave no space.Fig. 9

    Gas leakage.

    Gas leakage from roof.

    Contamination Mist exists and drop down.

    Fig. 8

    45

    Fig. 2

    Adhesive tape

    Slide

    Fig. 3

    For indoor unit installation, please refer to Installation Manual.Hook

    Caution

    1

    2

    Leave no space.

    Fig. 6

    3. Mounting on high ceiling

    (1) Ornament panel can be mounted on ceiling as high as 3 m.

    (2) Please install pad as accessary.

    Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4)

    Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.

    Fig. 4

    (3)Wiring on ornament panel Connecting of wiring of the swing flap motor on ornament panel. (2 places) (Refer to Fit . 10 )

    50

    Cutting line

    100ab

    Place it on the frame.

    Part a of the padPart a of the pad

    Swing flap motor Fig. 5

    Side of ornament panel

    Fig. 10

    Wiring diagramSide of indoor unit

    If connecting is not made, error code(A7) appears on remote controller. So,

    make proper connecting.

    - 25 -

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    31/149

    1

    2

    4. Installation of inlet grill and cover plate

    Installation of inlet grillInstall in reversed order ofPrepare ornament pandl.Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as

    per customers request.

    (1)

    When installing inlet grill, take care not to twist wiring of swing flap motor.

    Install cover plate on the cornerAs shown in Fig. 11 tie thecover plate onto the bolt onornament plate.Install cover plate onto ornament p late. (Refer to Fig. 12)

    (2)

    Slide all five hold rings

    to let them drop in holes

    on ornament plate,

    Fig. 12Fig. 11

    bolt

    5.1.3.10 Test running

    Refer to

    Take special care during installation, check after working

    (1)

    (2)

    (3)(4)

    (5)

    (6)

    Proce-dure Operation

    Open check valve on gas pipe.

    Open check valve on liquid pipe.

    Press ON/OFF button, select Cooling mode.Let it run for 3 min.

    Press air flow adjust button to make unit run properly

    Confirm unit functions according to Operation Manual.

    Upon installation of piping, water drainage and w iringwork, make test run to ensure proper unit operation.

    (1)

    (2)

    (3)

    (4)

    (5)

    Procedure Operation

    Open check valve on gas pipe.

    Open check valve on liquid pipe.

    Press ON/OFF button, select Cooling mode.

    Let it run for 3 min.

    Cut main power supply after operation.

    Conduct test run before installing ornament panel

    Note:If unit doesnt run due to certain problem, please seeNote to unit maintenance.

    Conduct test run after installation of ornament panel

    - 26 -

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    32/149

    5.1.4 Installation of outdoor unit

    580

    380

    5.1.4.1 Selection of installation place

    Place strong enough to support the unit and will not cause vibration and noise.

    Place where discharged wind and noise do not cause a nuisance to the neighbors.

    Place where is less affected by rain or direct sunlight and is sufficiently ventilated, or to install a shield.

    Place with enough space for smooth air flow.

    The unit shall not be installed on an unspecifised metal frame (e.g. theft guard net).

    If the outdoor unit is installed close to a street, it shall be no less than 2.5m from the ground.

    5.1.4.2 Fixing of the unit

    Fix outdoor unit using M10 bolt to concrete floor horizontally.

    If installed on the wall or on top of a roof, bracket should be fixed securely to resist earthquake or storms.

    Use rubber pad during installation against unit vibration.

    Install the unit so that the angle of inclination must be less than 3 degrees.

    2

    Liquid(Thin)

    Gas(Thick)

    3way V.

    2way V.

    Vacuum pump

    Gaugemanifold

    2 Open

    3

    5.1.4.3 Air purging method: To use vacuum pump

    For those models which adopt R407C refriengerant shall only use vacuum pump topurg air.

    Detach the service port's cap of 3-way valve, the valve rod'scap for 2-way valve and 3-way's, connect the service portinto the projection of charge hose (low) for gaugemanifold.Then connect the projection of charge hose (center) forgaugemanifold into vacuum pump.

    1

    Open the handle at low in gaugemanifold, operatevacuum pump. If the scale-moves of gause (low)reach vacuum condition in a moment, check 1 again.

    Vacuumize for over 15min. And check the levelgauge which should read -0.1 MPa (-76 cm Hg)at low pressure side. After the completion of

    vacuumizing, close the handle 'Lo' in gaugemanifoldand stop the operation of the vacuum pump.Check the condition of the scale and hold it for1-2min. If the scale-moves back in spite of

    tightening, make flaring work again, the returnto the beginning of 3 .

    185 185

    Installation dimension of outdoor unit (mm)

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    33/149

    4

    5

    6

    8

    7

    90

    3

    3way V.

    2way V.

    6

    6

    for 6 sec.

    Service port

    3way V.

    2way V.

    90

    4

    If it does not stop gas leakage, discharge whole

    refrigerants from the serice port. After flaring workagain and vacuumize, fill up prescribed refrigerant

    from the gas cylinder.

    Open the valve rod for the 2-way valve to andangle of anticlockwise 90 degree.

    After 6 seconds later, close the 2-way valve andmale the inspection of gas leakage.

    In case of gas leakage, tightenparts of pipe connection. If leakagestops, then proceed steps.

    No gas leakage?6

    Detach the charge hose from the service port, open2-way valve and 3-way. Turn the valve rodanticlockwise until hitting lightly.

    After attaching the each caps, check the gas leakagearound the caps.

    To prevent the gas leakage, turn the service port'scap, the valve rod'd cap for 2-way valve and 3-way'sa lottle more than the point where the torque increasessuddenly.

    7 Valve rod cap

    7 Valve rod cap

    3way V.

    2way V.

    5 Service port cap

    If needing to remove the refrigerant gas when installation or repair , please refer to the

    following procedures:

    1. Cut off the power

    2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure

    pressure-switch out.

    3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After

    powering on the unit again and switch to COOLING mode,perform refrigerant gas removing

    according to the normal refrigerant gas removing procedure.

    4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals

    of the low-pressure pressure-switch properly.

    - 28 -

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    34/149

    INSTALLATION INSTRUCTIONS

    GAS LEAKAGE INSPECTION

    After connecting the piping, check the joints for gas leakage with gas leakage detector.

    CAUTION

    HOW TO CONNECT WIRING TO THE TERMINALSA. For solid core wiring (or F-cable)(Fig.28A)

    (1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw driver.

    B. For strand wiring(Fig.28B)

    (1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring.(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.

    Fig. 28

    Screw withspecial washer

    Roundterminal

    Wire

    Terminalboard

    Screw with

    special washer

    Roundterminal

    Wire

    A. Solid wire

    Insulation

    Strip25mm

    Loop

    B. Strand wire

    Strip10mm

    Roundterminal

    After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.29

    HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP

    Fig. 29

    Cord clamp

    Insulation tube

    Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

    Item to the checked

    5.5 Pay special care to the following and check after installation

    Unproper installation may cause Check

    Is indor indoor unit firmly installed?

    Is gas leakage dheck performed?

    Is unit properly insulated?

    Is water drainage smooth?

    Is power voltage meet that stipulated on the nameplate?

    Is wiring and piping correctly arranged?

    Is unit safely grounded?

    Is wire size correct?

    Are there any obstacles on air inlet and outlet grill of

    indoor and outdoor unit?

    Is record made for piping length and refrigerant

    charging amount?

    Unit might fall down, make vibration or noise.

    This may lead to gas shortage.

    Dew or water drop may occur.

    Dew or water drop may occur.

    Problem may occur or parts got burned.

    Problem may occur or parts got burned.

    There might be a danger of electric shock.

    Problem may occur or parts got burned.

    This may cause poor cooling.

    It is hard to control refrigerant charging

    amount.

  • 8/11/2019 Op Manual AU42NAIBEA

    35/149

    (1) If possible, do not install the unit where it will be exposed to direct sunlight.(If necessary, install a blind that does not interfere with the air flow.)

    (2) Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible.(3) Install the unit where connection to the indoor unit is easy.(4) During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed.(Reverse cycle model only)(5) Do not place animals and plants in the path of the warm air.(6) Take the weight of the air conditioner into account and select a place where noise and vibration are small.

    (7) Select a place where the warm air and noise from the air conditioner do not disturb neighbors.(8) Provide the space shown in Fig.2 so that the air flow is not blocked. Also for efficient operation, leave open three of the four directions front, rear, and both sides.

    For authorized service personnel only

    5.2.1SELECTING THE MOUNTING POSITION 2. OUTDOOR UNIT

    Decide the m ounting position with the customer

    as follows:

    1. INDOO R UNIT

    (1) Install the indoor unit level on a strong wall, floor, ceiling which is not subject to vibration.(2) The inlet and outlet ports should not be obstructed: the air should be able to blow all over the room.(3) Install the unit near an electric outlet or special branch circuit.(4) Do n ot install the unit where it will be exposed to direct sunlight.(5) Install the unit where connection to the outdoor unit is easy.(6) Install the unit where the drain pipe can be eas ily installed.(7) Take servicing, etc. into consideration and leave the spaces shown in Fig.1. Also install the unit where the filter can be removed.

    NOT E: The appearance ma y be dif ferent from m odels.

    (1) Install the unit where it will not be tilted by more than 5

    (2) When installing the outdoor unit where it may be

    exposed to the strong wind, fasten it securely.

    Install at a place that can withstand the weight of theindoor and outdoor units and install positively so thatthe units will not topple or fall.

    CAUTION(1)Do not install where there is the danger of com-

    bustible gas leakage.

    (2) Do not install near heat sources.

    (3) If children under 10 years old may approach the

    unit, take preventive measures so that they can-

    not reach the unit.

    L2

    L3

    L1

    500

    (Servicingspace)

    Air outlet

    Air inlet

    Airinlet

    Series 36 42

    CaseDistance

    L1

    L2

    L3

    open open open open500 500

    300 300open open0 0

    100 300 150 150 150300

    I II III I II III

    Be careful not to scratch the room air conditioner when handing it.After installation, explain correct operation to the customer, accord ing to the operating manual.

    Let the customer keep this installation manual because it will be used when the room air conditioner is serviced

    or moved.

    WARNING(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation manual.

    (2) Connect the indoor unit and outdoor un it with the room air conditioner piping and cords available from our

    standard parts. This installation manual describes for the correct connections so that the installation set

    available from our standard parts should be used.

    (3) Installation work must be performed in accordance w ith national wiring standards by authorized personnel only.

    (4) Never cut the power cord, lengthen or shorten the cord, or change the plug.

    (5) Also, do not use an extension cord.

    (6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.

    (7) Do not turn on the power until all installation work is done.

    WARNINGWARNING

    5.2INSTALLATION INSTRUCTIONS--Convertible type

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    36/149

    Floor console

    Fig. 1

    2 cmor more

    Ceiling

    Indoor unit

    30 cmor more

    30 cmor more

    Left

    Right

    30 cmor more 30 cmor more

    1.5m

    1.5m

    1.5m

    Left Right

    may be different

    For series 36,42

    Note: For series 36, 42 no floor console type, the function

    below about floor console is invalid to the series.

    Fig. 2

    Under ceiling

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    37/149

    Mark Parts name

    Adhesive tape

    Saddle (L.S) with screws

    Connecting electric cablefor indoor and outdoor

    Drain hose

    Heat insulation material

    Piping hole cover

    PuttyPlastic clamp

    Optional parts

    A

    B

    C

    D

    E

    F

    GH

    5.2.2 STANDARD PARTSThe following installation parts are furnished.

    Use them as required.

    ACCESSORIESName and shape Q'ty Application

    6

    For fixing the wall

    bracket.

    For series 24,28,36,42

    no this part.

    Tapping screw( 4x20)

    Coupler heat insulator(large)

    1For indoor side pipe

    join t (Large p ipe)

    Coupler heat insulator(small) 1 For indoor side pipejoin t (S mall p ipe)

    Nylon fastener1

    For fixing the drain

    hose

    Drain hose

    Non-adhesive tape

    1

    1

    VT wire1

    For fixing the drain

    hose L 280mm

    For series 24,28,36,42

    VT wire is not available

    Remote

    controller

    Battery

    1

    2

    Use for air conditioner

    operation

    For remote controller

    unit

    Name and shape Q'ty Application

    1For series 24,28, 36,42

    the two cover plate are

    not available

    Cover plate (left)

    Cover plate (right)

    Installationtemplate

    Anchor bolt

    Spring washer

    Special nut

    Pipe hole cover

    Wall hole cover

    Main pipes

    Connecting cables

    1

    2

    1

    4

    4

    4

    1

    1

    1

    1

    For positioning the

    indoor unit

    For under ceiling type.

    For suspending the

    indoor unit from ceiling

    4

    Tapping sc rew( 4x10)

    Cushion

    Drain-elbow1

    Only for the heat pump

    type

    Wall bracket2

    For suspending the indoor

    unit on the wall.For series

    24,28,36,42 no this part.

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    38/149

    INSTALLATION PROCEDURE

    PREPARING INDOOR UNIT INSTALLATION

    1. REMOVE THE INTAKE GRILL

    Install the room air conditioner as follows:

    Open the intake grill and remove the three or four or six screws.

    (Fig. 3)

    5.2.3CONNECTION PIPE REQUIREMENTTable 1

    SeriesDiameter

    Liquid side Gas side

    Maximum length

    Maximum height(between indoor and outdoor)

    9.52 mm 19.05mm 50 m 15 m36

    Remark: The main unit can be wired before the indoor unit is installed. Select the most appropriate installation order.

    For series36,42 not the power plug, but 3-core connecting cable.

    Fig. 3Machine screw

    Tapping screw

    Tapping screw

    Intake grill

    INSTALLATION INSTRUCTIONS

    42 9.52 mm 19.05mm 50 m 15 m

    Select piping and drain directions. only have rear side(Fig.13)

    A. UN DER CE ILING TYPE-THE ON LY WAY

    Using the installation template, drill holes for piping and anchor bolts(forholes).(Fig.12)

    1. DRILLING FOR PIPING

    Fig. 13

    CAUTION

    Install the drain hose at the rear; it should not be installed

    on the top or right side.

    When the directions are selected, drill 80mm and 50mm or 150mm

    dia. hole on the wall so that the hole is tilted downward toward the

    outdoor for smooth water flow.

    AB

    40 40

    100mm

    720mm

    87.5mm

    147mm

    326mm

    247mm

    85

    53

    series A B

    36

    42 1920 1840

    18401920

    Rear (Install the drain hosein the direction.)

    Right

    Wall

    6mm

    60to70mm

    12.7mm

    Fig. 16

    Insert the anchor bolts into the drilled holes, and drive the pins

    completely into the anchor bolts with a hammer. (Fig. 16)

    2. DRILLING HOLES FOR ANCHOR BOLTS AND

    INSTALLING THE ANCHOR BOLTS

    Fig. 15

    With a concrete drill, drill four 12.7 mm dia. Holes.(Fig.15)

    3. INSTALLING BRACKETS

    Fig. 17

    Install the brackets with nuts, washers and spring

    washers.(Fig. 17)

    Spring washer

    Special nutBracket

  • 8/11/2019 Op Manual AU42NAIBEA

    39/149

    4. INSTALLING INDOOR UNIT

    68 16 21 28

    381

    232

    26.5

    26.5

    2-R2.510

    18

    7

    .5

    4-R

    5

    68162128

    381

    232

    26.5

    26.5

    2-R2.510

    18

    7

    .5

    4-R5

    Reset the hex bolts as shown in Fig.18.

    Hex bolt

    8 to 13mmIndoor unit

    Fig. 18

    Apply the indoor unit to the brackets.(Fig.19)

    Now, securely tighten the hex bolts in both sides.

    Fig. 19

    Bolt Bracket

    Indoor unit

    INSTALLATION INSTRUCTIONS

    5. INSTALL THE DRAIN HOSE

    Select whether the drain hose will be connected to the left or right

    side.(Fig.5)

    Insert the drain hose into the drain pan, then secure the drain hose

    with a nylon fastener.(Fig.8)

    Wrap the insulation (drain hose)around the drain hose connection.

    (Fig.9)

    Be sure to arrange the drain hose correctly so that it is leveled lower

    than the drain hose connecting port of the indoor unit.(Fig.20)

    Fig. 20Remove the hole cover.

    Fig. 21

    When drain hose is arranged backward.Secure the drain hose with

    the VT wire. (Fig. 21)

    OK

    Arrange the drain hoselower than this portion

    Drain hose

    NO

    VT wire hole

    Drain hose

    Piping hole

    5.2.4 GAS LEAKAGE INSPECTION

    After connecting the pip ing , ch eck the joints for gas leakage with gas le akage dete ctor.

    CAUTION

    HOW TO CONNECT WIRING TO THE TERMINALS

    A. For solid core wiring (or F-cable )(F ig.28A)

    (1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.(4) Shape the loop wire properly, place it on the terminal board an d tighten securely with the terminal screw using a screw driver.

    B. For strand wiring(Fig.28B)

    (1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand w iring.(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.

    Fig. 28

  • 8/11/2019 Op Manual AU42NAIBEA

    40/149

    INSTALLATION INSTRUCTIONS

    Fig. 28

    Screw withspecial washer

    Roundterminal

    Wire

    Terminalboard

    Screw withspecial washer

    Roundterminal

    Wire

    A. So lid wire

    InsulationS

    trip25mm

    Loop

    B. Strand wire

    Strip10mm

    Roundterminal

    After passing the connection cord and p ower cable through the insula tion tub e, fas ten it w ith the cord clamp , as shown in Fig .29

    HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP

    Fig. 29

    Cord clamp

    Insulation tube

    Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

    1. INDOOR UNIT SIDE

    (1) Remove the electric component box.

    ELECTRICAL REQUIREMENT

    Electric wire size and fuse capacity:

    Table 5

    ELECTRICAL WIRING

    Series

    Connection

    cord (mm2)

    Fuse capacity(A)

    MA X

    MIN

    36 42

    3.5

    2.5

    30

    CAUTION(1) Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.

    (2) Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.

    (3) Always fasten the outside covering of the connection cord with the cord clamp.(If the insulator is chafed, electric leakage may occur.)

    (4) Always connect the ground wire.

    3.5

    2.5

    30

    INDOOR UNIT SIDE

    Fig. 30

    Electric component box

    Fig. 31Electric component box

    Remove the four tappingscrews.

    CAUTION

    Do not remove the s crews. If the screwsare removed, the electric componentbox will fall.

  • 8/11/2019 Op Manual AU42NAIBEA

    41/149

    (2) Pull out the electric component box.

    Fig. 32

    (3) Remove the e lectric component bo x cover.

    Fig. 33

    (1) Remove the cord clamp.

    (2) Process the end of the connection cords to the

    dimensions shown in Fig.34.

    (3) Connect the end of the connection cord fully into the

    terminal block.

    (4) Wiring

    CAUTION

    Be careful not to pinch the lead wiresbetween the electric component boxand base.

    (4) Fasten the connection cord with a cord clamp.(5) Fasten the end of the connection cord with the screw.(6) The power cable and connecting are self-provided

    Outdoorunit

    Indoorunit

    Outdoorunit

    1 2 3

    1 2 3NTSR

    Base

    Electric component box cover

    Remove the three tapping screws.

    Electric component box

    INSTALLATION INSTRUCTIONS

    5.2.5TEST RUNNING

    (1) The power source capacity must be the sum of the

    room air conditioner current and the current of other

    electrical appliances. When the current contracted

    capacity is insufficient, change the contracted capacity.

    (2) When the voltage is low and the air conditioner is dif-

    ficult to start, contact the power company the voltage

    raised.

    CAUTION

    1. CHECK ITEMS

    (1) INDOOR UNIT

    (1) Is operation of each button on the remote control unit normal?

    (2) Does each lamp light normally?(3) Do not air flow direction louvers operate normally?

    (4) Is the drain normal?

    (2) OUTDOOR UNIT

    (1) Is there any abnormal noise and vibration during operation?

    (2) Will noise, wind, or drain water from the unit disturb the neighbors?

    (3) Is there any gas leakage?

    ELECTRICAL WIRING

    (1) Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner.

    (2) Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.

    (3) The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3mm between the contacts of each pole.

    WARNING

    (4) Perform wiring work in accordance with standards so

    that the room air conditioner can be operated safely

    and positively.

    (5) Install a leakage circuit breaker in accordance with the

    related laws and regulations and electric company

    standards.

    5.2.6 CUSTOMER GUIDANCE

    Explain the following to the customer in accordance with the

    operating manual:

    (1) Starting and stopping method, operation switching, temperature

    adjustment, timer, air flow switching, and other remote control

    unit operations.

    (2) Air filter removal and cleaning, and how to use air louvers.

    (3) Give the operating and installation manuals to the customer.

  • 8/11/2019 Op Manual AU42NAIBEA

    42/149

    For inspection and maintenance

    When you change your address or the installation place

    Electric work

    Installation placeAvoid installing the air conditioner

    near the place where possibility of

    inflammable gas leakage exists.

    Install the unit at well ventilated

    place.Install the air conditioner firmly

    on the foundation that can fully

    support the weight of the unit.

    If not, it may cause vibration or noise.If some obstacle exist, it may cause

    capacity reduction or noise increase.

    Explosion (Ignition) may occur.

    Select the place so as not toannoy neighbor with the hot air

    or noise.

    Snow protection work isnecessary where outdoor unit is

    blocked up by snow.

    It is advisable not to install the air con-ditioner at the following special place.It may cause malfunction, consult thesales dealer when you have to installthe unit on such a place.

    The place where corrosive gas generates(Hot spring area etc.)The place where salt breeze blows(Seaside etc.)The place where dense soot smoke existsThe place where humidity is extraordina-rily highThe place where near the machine whichradiates the electromagnetic waveThe place where voltage variation is con-siderably large

    For details consult your sales dealer.

    The electric work must be burden on the authorized engineer with qualification for electric work and

    grounding work, and the work must be conducted in accordance with electric equipment technical standard.

    The power source for the unit is to be of exclusive use.

    An earth leakage breaker should be installed.(This is necessary to prevent electric shock.)

    The unit must be grounded.

    Special technology is required for removal or reinstallation of air conditioner, consult the salesdealer. Besides, construction expense is charged for removal or reinstallation.

    The capacity of air conditioner will decrease by contamination of inside of unit when it is used for

    about three years although depending upon the circumstances under which it is used, and so in

    addition to the usual maintenance service, special inspection/maintenance service is necessary.

    It is recommended to make a maintenance contract (charged) by consulting your sales dealer.

    5.3INSTALLATION INSTRUCTIONS-Duct type

    INSTALLATION INSTRUCTIONS

  • 8/11/2019 Op Manual AU42NAIBEA

    43/149

    a. Remove upper part of wire

    Remove upper part of wire controller

    b. Install wire

    (1) For exposed installation, use 2 wood screws(accessory).

    Note: Try as far as possible a flat surface for installation. Don't use excessive

    PCB is mounted on lower part of wire

    controller, be careful not to damage

    Lower part of wire

    controller

    Upper part of wire

    controller

    (2) For recessed installation, use 2 wood screws(accessory).

    c. Indoor unit wiringConnect terminals (A,B,C,D) on lower

    part of wire controller to terminals (A,

    B,C,D) on PCB of indoor unit.

    Hint:

    When make wiring, please

    keepa distance between wires

    and power supply cord.

    Cord kind

    Size

    Shield wire (4 core) (refer to Hint 3,4)

    0.33mm2

    Wire size

    Use shielede wires for telecommunication

    between wire controller and indoor unit;indoor unit and outdoor unit. Ground theshield on one side.Otherwise misoperation because of noisemay occur.Signal wire is self-provided.

    Shielded wire

    ground

    Lower part of

    wire controller

    A B C D

    Upper part of

    wire controller

    wiring from here

    d. Replace the upper part of wire controller

    Hint: 1. Switch box and cord for wiring are not supplied.Be careful not to press the wiring.

    2. Don't touch PCB with hand.

    Hint: Tread surface of the terminal well so that shielding may not contact other part.

    INSTALLATION INSTRUCTIONS

    5.3.1 Installation of the wired remote controlller

  • 8/11/2019 Op Manual AU42NAIBEA

    44/149

    Edging

    (2) Installation where the area with strong winds.

    Install the unit so that the air outlet section of the unit must NOT be faced

    toward wind direction.

    (1) Open space requirement around the unit

    b. Selection of the place of installation

    a. Accessories

    "Edging" for protection of electric wires from an

    opening edge.

    Select the place of installation satisfying the following conditions and, at the same time, obtain

    a consent from the client or user.

    Place where air circulates.Place free from heat radiation from other heat sources.

    Place where drain water may be discharged.

    Place where noise and hot air may not disturb the neighborhood.

    Place where there is not heavy snowfall in the winter time.

    Place where obstacles do not exist near the air inlet and air outlet .

    Place where the air outlet may not be exposed to a strong wind.

    Place surrounded at four sides are not suitable for installation. A 1m or more of overhead

    space is needed for the unit.

    Mount guide-louvers to place where short-circuit is a possibility.

    When installing several units, secure sufficient suction space to avoid short circuiting.

    WARNING

    BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNINGINSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS

    INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.

    BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.

    Unit

    Concrete foundationFoundation anchor

    Note (1) Give enough room for the

    concrete foundation to fix by anchor bolts.

    (a)

    Note (1) Place the concrete foundation deep

    enough.

    Install the unit so that the angle of inclination must be less than 3 degrees.

    c. Installation of outdoor unit

    Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .

    (1) Installation

    L2

    L3

    L1

    500

    (Servicingspace)

    Air