OC Protection
-
Upload
eyad-a-feilat -
Category
Documents
-
view
216 -
download
0
Transcript of OC Protection
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 1/17
OVER CURRENT RELAY
The relay
has
two
settings.
These
are
the
time
setting and the plug setting. The time setting
decides the operating time of the relay while
the plug setting decides the current required
for the relay to pick up.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 2/17
The
current setting of relay
is expressed in percentage
ratio of relay pick up
current
to rated
secondary
current
of
CT.That means,
Current setting = Pick up current * 100
Rated secondary
current
of
CT
For example, suppose ,we want that, an
over
current
relay should operate when the system
current
just crosses
125%
of
rated
current.
If the relay is rated with 1 A, the normal pick upcurrent
of
the
relay
is
1
A
and
it
should
be
equal
to
secondary
rated
current
of
current transformer
connected to the
relay.
Then, the
relay
will
be
operated
when
the
current
of CT
secondary becomes more than or equal 1.25 A.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 3/17
As per definition,
Current setting
=
1.25
*
100
=
125 %
• 1
The
current
setting is
sometimes
referred
as
current
plug setting.
The
current
setting of over
current
relay is
generally ranged from 50% to 200%, in steps
of 25%.
For
earth
fault
relay
it
is
from
10%
to
70% in steps of 10%.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 4/17
Plug Setting Multiplier of Relay
Plug setting multiplier of relay
is referred as ratio of
fault
current
in
the
relay
to
its
pick
up
current.
Suppose we have connected on protection CT of ratio 200/1 A
and
current
setting is
150%.
Hence, pick up
current
of the relay is, 1 × 150 % = 1.5 A
Now, suppose fault
current
in the CT primary is 1000 A.
Hence, fault
current
in the CT secondary i.e. in the relay coil is,
1000 ×
1/200 = 5 A
Therefore PSM of the relay is, 5 / 1.5 =3.33
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 5/17
Time Multiplier Setting
Overcurrent
relays normally play the dual roles of
primary and
backup
protection.
Backup action requires a wait state.
By providing
the
additional
setting
feature
of
TMS,
this
can be achieved.
TMS is defined as the ratio T/Tm
, where T is the
desired relay
operating
time
for
a given
PSM
and
Tm
is
the
corresponding operating time at TMS=1.
Relay
operating
time
can
be
varied
by
varying
the
TMS
setting.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 6/17
Calculation of Relay Operation Time
For calculating actual relay operating time, we
need to
know
following
• Current setting.
• Fault
current
level.
• Ratio of
current transformer.
• Time / PSM
curve.
• Time setting.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 7/17
The plug
‐setting
multiplier,
PSM,
is
defined
as
follows:
where Irelay
is the current through the relay operating coil and PS is the plug‐setting of the relay = pickup current.
The value
of
PSM
tells
us
about
the
severity
of
the
current as seen by the relay
A PSM less than 1 means that normal load current is
flowing. At
PSM
> 1,
the
relay
is
supposed
to
pick
up.
Higher values of PSM indicate how serious the fault is.
For example, let us consider a 1.0 A relay (i.e. a relay with
current coil
designed
to
carry
1.0
A
on
a continuous
basis)
whose plug has been set at 0.5 A, i.e. at 50%. Assume
that, for a certain fault, the relay current is 5.0 A. The
relay, therefore,
is
said
to
be
operating
at
a PSM
of
(5.0/0.5) = 10.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 8/17
Inverse Time Over‐current Relay
Inverse time characteristic fits in very well, with the requirement that
the more
severe
a fault
is,
the
faster
it
should
be
cleared
to
avoid
damage to the apparatus
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 9/17
Inverse definite minimum time (IDMT) over ‐current relay
This is possibly the most widely used characteristic.
The characteristic
is
inverse
in
the
initial part, which tends to a definite minimum
operating time as the current becomes very high. The
operating
time
is
Very inverse time over ‐current relay
The inverseness
of this
characteristic
is
higher
than
that of the IDMT characteristic.
The operating time is
Extremely inverse
time
over
‐current
relay
The inverseness
of this characteristic is higher than
that of
the
very
inverse
characteristic.The operating time is
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 10/17
Guidelines for Setting Pickup Current for Phase Fault
Relays
• Pickup current
should
be
above
the
maximum
load
current.
•
Pickup current
should
be
below
minimum
fault
current.
• Pickup current should also be below the minimum
fault current
of
the
feeder
that
it
has
to
back
up.
• The back up relay also should provide time for
primary relay to operate. This time interval is known
as coordination time interval.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 11/17
Application of IDMT Relays for Protection of a Distribution Feeder
The purpose of relay RB
is to provide primary protection to line BC.
The purpose of relay RA
is to provide primary protection to line AB
and
back‐up to line BC.
We start
the
setting
process
from
the
tail
end
of
the
system.
(a) Deciding the CT ratios and plug settings (pickup current):
(i) At relay B, the maximum load current, assuming 25% overload is:
80 A
+ (0.25
x 80
A)
= 100
A
Assuming 1 A relay to be used, the CT ratio can be selected to be 100 : 1. The plug setting PS can be done at 100%, i.e. PS = 1.0 A.
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 12/17
(ii) At relay A the maximum load current, assuming 25%
overload is
(160+80)+0.25(160+80)
=
300Assuming 1 A relay to be used, the CT ratio can be selected to
be 300 : 1. The plug
1)setting
can be done at 100%, i.e. PS = 1.0 A.
(b) Deciding the time‐multiplier settings: Starting from the
most remote
relay
RB
(i) Since RB
does not have to maintain selectivity with any
other relay, it can be made to operate the fastest. Thus the
TMS of
RB
can be
selected
as
0.1.
(ii) Now, to maintain selectivity between R A
and RB ,
the
following
constraint
must
be
met:
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 13/17
The
operating
time
of
RB
for
maximum
fault
just
beyond
bus
B
can
be
found from
For maximum fault at B, fault current = 3000 A on primary side which
becomes(3000/100) = 30 A secondary. Since plug setting is done at 1.0 A,
The TMS of RB
has already been set at 0.1. Substituting these values, we
get
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 14/17
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 15/17
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 16/17
8/19/2019 OC Protection
http://slidepdf.com/reader/full/oc-protection 17/17