NOTICE OF APPROVAL AVIS D’APPROBATION … · Instrument Transformer: Current TYPE D’APPAREIL...

5
AE-1818 APPROVAL No. - N° D’APPROBATION Page 1 of/de 5 Project/Projet: AP-AE-10-0178 Measurement Canada Mesures Canada An agency of Industry Canada Un organisme d’Industrie Canada NOTICE OF APPROVAL AVIS D’APPROBATION Issued by statutory authority of the Minister of Industry for: Émis en vertu du pouvoir statutaire du ministre de l’Industrie pour: TYPE OF DEVICE Instrument Transformer: Current TYPE D’APPAREIL Transformateur de mesure: courant APPLICANT REQUÉRANT Alstom Grid Inc., One Ritz Avenue Waynesboro, Georgia, 30830 USA MANUFACTURER FABRICANT Alstom Grid Inc., One Ritz Avenue Waynesboro, Georgia, 30830 USA MODEL(S)/MODÈLE(S) RATING/ CLASSEMENT OSKF 72.5 2000 x 1000 MR Accuracy class / Classe de précision: See“Summary Description”/Voir “description sommaire” Rating factor / Facteur de surcharge: 1.2 Frequency / Fréquence: 60 Hz Voltage Class/Catégorie de tension 72.5 kV

Transcript of NOTICE OF APPROVAL AVIS D’APPROBATION … · Instrument Transformer: Current TYPE D’APPAREIL...

AE-1818APPROVAL No. - N° D’APPROBATION

Page 1 of/de 5 Project/Projet: AP-AE-10-0178

Measurement Canada

Mesures Canada

An agency of Industry Canada Un organisme d’Industrie Canada

NOTICE OF APPROVAL AVIS D’APPROBATION

Issued by statutory authority of the Minister of Industryfor:

Émis en vertu du pouvoir statutaire du ministre del’Industrie pour:

TYPE OF DEVICE

Instrument Transformer: Current

TYPE D’APPAREIL

Transformateur de mesure: courant

APPLICANT REQUÉRANT

Alstom Grid Inc.,One Ritz Avenue

Waynesboro, Georgia, 30830USA

MANUFACTURER FABRICANT

Alstom Grid Inc.,One Ritz Avenue

Waynesboro, Georgia, 30830USA

MODEL(S)/MODÈLE(S) RATING/ CLASSEMENT

OSKF 72.5 2000 x 1000 MR

Accuracy class / Classe de précision:See“Summary Description”/Voir “description sommaire”

Rating factor / Facteur de surcharge: 1.2Frequency / Fréquence: 60 HzVoltage Class/Catégorie de tension 72.5 kV

AE-1818APPROVAL No. - N° D’APPROBATION

Page 2 of/de 5 Project/Projet: AP-AE-10-0178

NOTE: This approval applies only to meters, thedesign, composition, construction and performance ofwhich are, in every material respect, identical to thatdescribed in the material submitted, and that aretypified by samples submitted by the applicant forevaluation for approval in accordance with sections 13and 14 of the Electricity and Gas InspectionRegulations. The following is a summary of theprincipal features only.

REMARQUE: Cette approbation ne vise que lescompteurs dont la conception, la composition, laconstruction et le rendement sont identiques, en toutpoint, à ceux qui sont décrits dans la documentationreçue et pour lesquels des échantillons représentatifsont été fournis par le requérant aux fins d’évaluation,conformément aux articles 13 et 14 du Règlement surl’inspection de l’électricité et du gaz. Ce qui suit estune brève description de leurs principalescaractéristiques.

SUMMARY DESCRIPTION: DESCRIPTION SOMMAIRE:

The OSKF-72.5 is a post type current transformer.This transformer is equipped with a primaryreconnect.

Le modèle OSKF-72.5 est un transformateur decourant de type poteau. Cet transformateur utilize unprimaire de reconnection.

RATIO/TAPS

The following ratios are approved for revenuemetering:

RAPPORT/ENROULEMENT

Les rapports suivants sont approuvés aux fins defacturation:

1X2W (Parallel) 2000-5A

RatioRapport

TapEnroulement

Accuracy classClasse de précision

Rating FactorFacteur de surcharge

2000-5A X1-X5 Y1-Y5 Z1-Z5 W1-W5 0.3B1.8

1.2

1600-5A X2-X5 Y2-Y5 Z2-Z5 W2-W5 0.3B1.8

1200-5A X1-X4 Y1-Y4 Z1-Z4 W1-W4 0.3B1.8

1000-5A X1-X3 Y1-Y3 Z1-Z3 W1-W3 0.3B0.9

800-5A X4-X5 Y4-Y5 Z4-Z5 W4-W5 0.6B0.9

600-5A X2-X3 Y2-Y3 Z2-Z3 W2-W3 0.6B0.5

AE-1818APPROVAL No. - N° D’APPROBATION

Page 3 of/de 5 Project/Projet: AP-AE-10-0178

2X1W (Series / Serie) 1000-5A

RatioRapport

TapEnroulement

Accuracy classClasse de précision

Rating FactorFacteur de surcharge

1000-5A X1-X5 Y1-Y5 Z1-Z5 W1-W5 0.3B1.8

1.2

800-5A X2-X5 Y2-Y5 Z2-Z5 W2-W5 0.3B1.8

600-5A X1-X4 Y1-Y4 Z1-Z4 W1-W4 0.3B1.8

500-5A X1-X3 Y1-Y3 Z1-Z3 W1-W3 0.3B0.9

400-5A X4-X5 Y4-Y5 Z4-Z5 W4-W5 0.6B0.9

300-5A X2-X3 Y2-Y3 Z2-Z3 W2-W3 0.6B0.5

EVALUATED BY

Michael RozeboomLegal Metrologist

ÉVALUÉ PAR

Michael RozeboomMétrologiste légal

AE-1818APPROVAL No. - N° D’APPROBATION

Page 4 of/de 5 Project/Projet: AP-AE-10-0178

NAMEPLATE AND MARKINGS PLAQUE SIGNALÉTIQUE ET MARQUAGES

AE-1818APPROVAL No. - N° D’APPROBATION

Page 5 of/de 5 Project/Projet: AP-AE-10-0178

APPROVAL:

The design, composition, construction andperformance of the meter type(s) identified hereinhave been evaluated in accordance with regulationsand specifications established under the Electricityand Gas Inspection Act. Approval is hereby grantedaccordingly pursuant to subsection 9(4) of the saidAct.

The sealing, marking, installation, use and manner ofuse of meters are subject to inspection in accordancewith regulations and specifications established underthe Electricity and Gas Inspection Act. The sealingand marking requirements are set forth inspecifications established pursuant to section 18 of theElectricity and Gas Inspection Regulations.Installation and use requirements are set forth inspecifications established pursuant to section 12 of theRegulations. Verification of conformity is required inaddition to this approval for all metering devicesexcepting instrument transformers. Inquiriesregarding inspection and verification should beaddressed to the local inspection office of IndustryCanada.

APPROBATION:

La conception, la composition, la construction et lerendement du(des) type(s) de compteurs identifié(s)ci-dessus, ayant fait l’objet d’une évaluationconformément au Règlement et aux prescriptionsétablis aux termes de la Loi sur l’inspection del’électricité et du gaz, la présente approbation estaccordée en application du paragraphe 9(4) de la diteLoi.

Le scellage, l’installation, le marquage, et l’utilisationdes compteurs sont soumis à l’inspectionconformément au Règlement et aux prescriptionsétablis aux termes de la Loi sur l’inspection del’électricité et du gaz. Les exigences de scellage et demarquage sont définies dans les prescriptions établiesen vertu de l’article 18 du Règlement sur l’inspectionde l’électricité et du gaz. Les exigences d’installationet d’utilisation sont définies dans les prescriptionsétablies en vertu de l’article 12 du dit règlement. Saufdans les cas des transformateurs de mesure, unevérification de conformité est requise. Toute questionsur l’inspection et la vérification de conformité doitêtre adressée au bureau local d’Industrie Canada.

Original copy signed by:

Isabelle TremblayLaboratory Manager - Electricity MeasurementFORAdnan RashidSenior Engineer – Electricity MeasurementEngineering and Laboratory Services Directorate

Copie authentique signée par :

Isabelle TremblayGestionnaire de laboratoire -Mesure de l’électricitéPOURAdnan RashidIngénieur principal – Mesure de l’électricitéDirection de l’ingénierie et des services delaboratoire

Date: 2011-06-23

Web Site Address / Adresse du site internet:http://mc.ic.gc.ca