Table of Contents NORTH DAVIS SEWER DISTRICT Detail No. Detail Title Pages ND-01 NOTICE TO CONTRACTORS 1 ND-02 MANHOLE CONSTRUCTION NOTES AND INDEX 2 ND-03 MANHOLE DIAMETER REQUIREMENTS 2 ND-10 STANDARD MANHOLE CONNECTION 2 ND-11 STANDARD MANHOLE DETAIL 54" DIA OR LARGER DISTRICT PIPE 2 ND-12 STANDARD MANHOLE DETAIL CCFRPM DISTRICT PIPE 2 ND-13 STANDARD MANHOLE DETAIL FRP 2 ND-14 STANDARD MANHOLE DETAIL POLYMER CONCRETE 3 ND-15 STANDARD GREASE INTERCEPTOR 2 ND-16 STANDARD MANHOLE DETAIL CIPP REPAIR 1 ND-20 STANDARD SERVICE CONNECTION - CONCRETE PIPE 1 ND-21 STANDARD SERVICE CONNECTION - CIPP LINED PIPE 2 ND-22 STANDARD SERVICE CONNECTION - CCFRPM FIBERGLASS PIPE 1 ND-23 STANDARD SERVICE CONNECTION - ABANDONMENT 1 ND-30 CRACKED PIPE REPAIR 1 ND-31 STRUCTURAL SUPPORT AT CROSSING 2 NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS

Transcript of NORTH DAVIS SEWER DISTRICT STANDARD …ndsd.org/documents/NDSD std details.pdf · NORTH DAVIS SEWER...

Table of Contents

NORTH DAVIS SEWER DISTRICT

Detail No. Detail Title

Pages

ND-01 NOTICE TO CONTRACTORS 1

ND-02 MANHOLE CONSTRUCTION NOTES AND INDEX 2

ND-03 MANHOLE DIAMETER REQUIREMENTS 2

ND-10 STANDARD MANHOLE CONNECTION 2

ND-11 STANDARD MANHOLE DETAIL 54" DIA OR LARGER DISTRICT PIPE 2

ND-12 STANDARD MANHOLE DETAIL CCFRPM DISTRICT PIPE 2

ND-13 STANDARD MANHOLE DETAIL FRP 2

ND-14 STANDARD MANHOLE DETAIL POLYMER CONCRETE 3

ND-15 STANDARD GREASE INTERCEPTOR 2

ND-16 STANDARD MANHOLE DETAIL CIPP REPAIR 1

ND-20 STANDARD SERVICE CONNECTION - CONCRETE PIPE 1

ND-21 STANDARD SERVICE CONNECTION - CIPP LINED PIPE 2

ND-22 STANDARD SERVICE CONNECTION - CCFRPM FIBERGLASS PIPE 1

ND-23 STANDARD SERVICE CONNECTION - ABANDONMENT 1

ND-30 CRACKED PIPE REPAIR 1

ND-31 STRUCTURAL SUPPORT AT CROSSING 2

NORTH DAVIS SEWER DISTRICT

STANDARD COLLECTION DETAILS

ND-01 Notice to Contractors

NORTH DAVIS SEWER DISTRICT

1.a)

b)c)

2.a)

b)

c)

d)e)

3.a)b)

c)

4.a)

Effective immediately, the following will be accomplished by all contractors before starting any work or excavationaround or on any sewer line owned by the North Davis Sewer District:

Hours of OperationThe District's working hours are 7:00 a.m. to 3:30 p.m., Monday through Friday. No sewer inspection willbe done on weekends, holidays or after 3:00 p.m.All inspections lasting after 3:30 p.m. will result in overtime being billed to the contractor.Multiple inspection visits required for work that is incomplete, not to District standards, or not ready for inspection will result in additional time being billed to the contractor.

Sewer Lateral Connections:No work shall begin until the proper fees of $240.00 for connection and inspection, plus impact fees as calculated by the City or District (whichever may apply) are certified to the District as having been paid. The District only accepts cash or check.No work shall begin until the proper building permits and licenses have been obtained from the City, County, or Sewer District.Minimum notice of 48 hours shall be given to the District prior to any work commencing on or digging being done on District-owned lines.No digging or work shall be done on District-owned lines without the presence of a District Inspector.All sewer taps must be Core Drilled, INSERTA TEE, GPK 4, or equivalent.

Setting of Manholes on District owned-lineManholes are required to be set for connecting lines 6 inches or larger.No manholes shall be set on District-owned lines without prior approval by the District. Contractors shallsubmit design drawings and manhole details of proposed manholes on District line for approval 14 daysprior to work commencing. Design drawings shall be submitted in PDF electronic format unless otherwiserequested by the District.After approval of drawings, a minimum of 48 hours notice shall be given to the District inspectors beforeany manhole is set on a District-owned line. The manhole must be set in the presence of a District inspector.

Flow Control and Bypass Pumping OperationsWhere required to complete the Work, the Contractor shall provide bypass pumping and flow control. Contractor shall submit a bypass pumping plan prior to commencement of the work for review and acceptance by the District. The plan shall at a minimum provide materials, equipment and flow calculationsand be of sufficient detail to demonstrate the system's capacity to control flows. The Contractor shall coordinate with the District to determine the required capacity.

Concrete BatchingReady mix concrete shall be provided in accordance with ASTM C94, Standard Specification for Ready-Mixed Concrete.The design water content of the mix (w/c ratio) shall not be exceeded. Addition of water, air entrainment orsuperplasticizer shall only be performed by the Supplier.Non-air entrained concrete shall be discharged ninety (90) minutes after batching. Air entrained concreteor concrete that includes silica fume shall be discharged within sixty (60) minutes of batching.Requests for longer batching times shall be submitted and accepted by the District prior to procurement ofconcrete by the Contractor.The District shall not be responsible for the cost of rejected batches exceeding time limitations, loss of air-entrainment or slump.

Warranty:Contractor shall guarantee work for a period of one year from the date of installation.

Failure of contractors to comply with these guidelines could result in the contractor being barred from working onDistrict lines. If there are any questions on a line being a District line, please contact the District office @801-825-0712.

5.a)

6.a)

b)

c)

d)

e)

Revision 1, Adopted 8/14/2014

STANDARD MANHOLE ON EXISTING SEWER LINE

1. Manhole shall be constructed so as to prevent load to the existing pipe. The base of the manhole shallprovide a minimum of 9 inches of concrete beneath the existing pipe unless otherwise shown, placed on 12inches of one inch gravel bedding compacted to 95% density.

2. Manhole floor elevation shall be a minimum of 2 inches above top of pipe, have a 12:1 slope to the pipe, anda smooth finish.

3. Connection to manhole shall be made using a flexible, watertight connection per ASTM C923,Kor-n-seal or equal. Flexible couplings shall be correctly sized, flexible water tight couplings per ASTMC1173, Fernco Inc, Mission Rubber Company or approved equal. All hardware shall be 316 series stainlesssteel, unless otherwise approved.

4. Manhole shall be constructed using a pre-cast eccentric type sections and cast iron traffic type frame andcover marked "NORTH DAVIS SEWER". Section joints shall be sealed with rubber gaskets and shall bewatertight.

5. Wrap exterior joints. Wrap shall conform to ASTM C877 Type II or Type III. Press-seal Ez-Wrap, CretexWrap, Conseal 2/2 or approved equal.

6. Invert of branch line at manhole connection shall be adjusted to be at or near crown of existing main line.

7. Branch line channel to be formed with same slope, size, depth, and shape as pipe with smooth finish; it shallbe curved in direction of flow with uniform radius and minimize dropping and splashing of flow.

8. Cutting into existing line shall be made by smooth saw cuts.

9. Installing contractor shall be responsible for proper slope and installation of connecting line.

10. Installing contractor shall be responsible for proper backfilling, compacting, and pavement restoration.

11. Contractor shall notify District 48 hours before installation begins and a District inspector must be presentbefore installation takes place.

12. Contractor shall meet all restoration requirements of the agency, city or UDOT where the manhole isinstalled and shall coordinate any additional installation or inspection requirements with the agency.

CONNECTION TO AN EXISTING MANHOLE

1. Item numbers 3, 5, 8, 9, 10 and 11 above shall apply.

2. In addition, the manhole junction channel shall be constructed to the same size, shape, and slope of theincoming line. Channel shall curve in the direction of flow with uniform radius and minimize dropping andsplashing of flow.

3. No manhole connection shall be made until complete design drawings of the manhole and line installationsare submitted to the District for approval - 14 days prior to work commencing.

ND-02 Manhole Construction Notes and Index 1 of 2

NORTH DAVIS SEWER DISTRICT

ND-02 Manhole Construction Notes and Index 2 of 2

NORTH DAVIS SEWER DISTRICT

Detail no. Detail Title Use

ND-10 STANDARD MANHOLE CONNECTIONConcrete, RCP, and PVC District Pipe <54" DIA. (See Note 1)

ND-11STANDARD MANHOLE DETAIL 54" DIA OR LARGERDISTRICT PIPE RCP District Pipe ≥ 54" DIA

ND-12 STANDARD MANHOLE DETAIL CCFRPM DISTRICT PIPE CCFRPM Pipe ≥ 18" DIA

ND-13 STANDARD MANHOLE DETAIL FRPLined Concrete and RCP, CCFRPM or asdirected by District

ND-14 STANDARD MANHOLE DETAIL POLYMER CONCRETELined Concrete and RCP, CCFRPM or asdirected by District

ND-15 STANDARD GREASE INTERCEPTOR As directed by District

ND-16 STANDARD MANHOLE DETAIL CIPP REPAIR CIPP Lined District Pipe

NOTE

1. District reserves the right to require precast FRP or polymer manholes on pipes that are planned to berehabilitated by cured-in-place (CIPP) or other methods within two years of drawing submittal.

MANHOLE DIAMETER

ND-03 Manhole Diameter Requirements 1 of 2

NORTH DAVIS SEWER DISTRICT

For alternative configurations, manhole sizing recommendations may be provided by the precast fabricator. Theminimum structural support between openings is 6-inches. Recommendations must be supported by designmethods (drawings, calculations) provided by the precast manufacturer in accordance with applicable industrystandards such as NPCA.

INLET

OUTLET(a.) SINGLE INLET & OUTLET

STRAIGHT THROUGH

OUTLET(a.) SINGLE INLET & OUTLETTROUGH ANGLE MIN. 135°

OUTLET(b.) MAXIMUM 2 INLETS

& 1 OUTLET

OUTLET(c.) MAXIMUM 3 INLETS

& 1 OUTLET

INLET

INLET INLETINLET

INLET INLET

180°135°

90°

135°135°

90° 90°

90°90°

ND-03 Manhole Diameter Requirements 2 of 2

NORTH DAVIS SEWER DISTRICT

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPEAND CONSTRUCTION OF CONNECTING PIPELINE.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OFEXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING,COMPACTING, AND PAVEMENT RESTORATION.

3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONEYEAR.

5. PRECAST MANHOLE BASES SHALL BE USED FOR CONSTRUCTIONOF ALL NEW DISTRICT SEWER SYSTEMS. PRECAST MANHOLEBASES OR CAST-IN-PLACE MANHOLE BASES MAY BE USED ATTHE CONTRACTOR'S OPTION FOR NEW MANHOLES INSTALLEDON EXISTING DISTRICT SANITARY SEWERS. CONTRACTORSHALL PROVIDE A SUITABLE FOUNDATION IN ALL AREAS.

6. CAST-IN-PLACE BASE SHALL BE COMPLETED IN A SINGLE POUR.CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTMC150 WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 4000PSI PER ASTM C39. NO ADDITIVES SHALL BE PERMITTEDWITHOUT PRIOR APPROVAL BY THE DISTRICT.

7. PRECAST MANHOLE BASES SHALL CONFORM TO ASTM C478.CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTMC150 WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 4000PSI PER ASTM C39. CONNECTIONS TO PRECAST BASES SHALLBE FACTORY INSTALLED AND MEET THE REQUIREMENTS OFASTM C923, Z-LOK, PRES-SEAL PSX OR APPROVED EQUAL.

8. MANHOLES ON CCFRPM OR CIPP LINED DISTRICT SEWERSSHALL BE PRECAST FRP (HOBAS, LF MANUFACTURING INC OREQUAL) OR POLYMER (ARMOROCK OR EQUAL) UNLESSOTHERWISE APPROVED BY THE DISTRICT. SEE DETAIL ND-12,ND-13 AND ND-14.

9. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION.GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINKTYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUT ORAPPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINSTHYDROGEN SULFIDE ATTACK.

10. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CASTCONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIREBRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN,DURABLE SURFACE. SECURE WATERSTOP TO PIPE USINGMANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OFGREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEENWATERSTOP AND PIPE.

2'-0"MAX.

6" (TYP)JUNCTION CHANNEL SHALL BE

FORMED WITH SAME SLOPE, SIZE,DEPTH, AND SHAPE AS CONNECTING

PIPE WITH SMOOTH FINISH -CHANNEL SHALL CURVE IN DIRECTION

OF FLOW WITH UNIFORM RADIUSAND MINIMIZE DROPPING AND

SPLASHING OF FLOW

EXISTING DISTRICTPIPE

FLOW

CUTTING OF EXISTING LINE TO FORMCHANNEL SHALL BE ACCOMPLISHED

WITH SMOOTH SAW CUTS

CONNECTING PIPE

PLAN

AA

ND-10 Standard Manhole Connection 1 of 2

NORTH DAVIS SEWER DISTRICT

Revision 2, Adopted 11/7/2014

HYDROPHILLIC WATERSTOP ALLAROUND EXISTING DISTRICT PIPE AND

CONNECTING PIPE(S) (TYPICAL),GREENSTREAK HYDROTITE (OR

APPROVED EQUAL), SEE NOTE 10.

MINIMUM INTERNALMANHOLE DIAMETER

PER ND-03

6"

30" DIA.

12"

9" MIN

30" MANHOLE RING AND COVERMARKED "NORTH DAVIS SEWER"(D & L SUPPLY A-1180-18, OR APPROVED EQUAL)

GRADE RINGS - A MINIMUM OF ONE 6-INCH RING, BUTNOT MORE THAN 18" TOTAL HEIGHT INCLUDING FRAME,RINGS, AND GROUT, SHALL BE USED

SEAL ALL JOINTS WITH RAMNECK OR EQUAL(ALL JOINTS SHALL BE TESTED FORWATERTIGHTNESS) TAPE WRAP EXTERIORJOINTS. WRAP SHALL CONFORM TO ASTM C877TYPE II OR TYPE III. (PRESS-SEAL EZ-WRAP,CRETEX WRAP, CONSEAL 2/2 OR APPROVED EQUAL)

PRECAST CONCRETE MANHOLESECTIONS PER ASTM C-478.

IF LOCATED IN UNIMPROVEDGROUND SET COVER 6" ABOVE GRADEUNLESS DIRECTED OTHERWISEBY DISTRICT

PRECAST OR CAST-IN-PLACEMANHOLE BASE

UNDISTURBEDNATIVE SOIL

1" MINUSGRAVEL BASE

CONNECTING PIPE SHALL BE INSTALLEDIN CORE DRILLED OPENING WITH A

FLEXIBLE WATERTIGHT BOOT. (PSX,PRESS SEAL, KOR-N-SEAL OR EQUAL)

TOP OF FLOOR SHALLBE 2" MIN. ABOVE PIPE

MINIMUM INTERNAL DIAMETER PER ND-03 FORDISTRICT PIPE SIZES TO 48". SEE DETAIL ND-11

FOR DISTRICT PIPES 54" OR LARGER

PRECAST ECCENTRIC CONE (SHALL MEET ASTMC-478 STANDARDS) WHEN INSUFFICIENT DEPTH

PREVENTS THE USE OF A CONE, A CONCRETEPRECAST H-20 FLAT LID SHALL BE USED.

12" WIDE MIN, 8" DEEP CONCRETECOLLAR IN PAVED AREAS

INVERT OF CONNECTING PIPESHALL BE AT OR NEAR

CROWN OF EXITINGDISTRICT SEWER PIPE

1:12 FLOOR SLOPEWITH SMOOTHTROWELED FINISH

DISTRICT SEWERPIPE

REINFORCEMENT REQUIRED(1) #4 BAR ALL AROUND

SECTION A

ND-10 Standard Manhole Connection 2 of 2

NORTH DAVIS SEWER DISTRICT

GROUT FOR SETTING GRADE RINGS AND FRAME SHALLPROVIDE A WATERTIGHT BARRIER TO PREVENTINFILTRATION AND BE PLACED ACROSS THE FULLWIDTH, 1/2-INCH MIN AND 1-INCH MAX THICK.

PRECAST RISER TO BE SET IN CONCRETE (TYP)(CAST-IN-PLACE BASE)

Revision 2, Adopted 11/7/2014

IF A BOOTED CONNECTION IS NOTPOSSIBLE, PLACE HYDROPHILLIC

WATERSTOP ALL AROUND EXISTINGDISTRICT PIPE AND CONNECTING PIPE(S)

(TYPICAL), GREENSTREAK HYDROTITE(OR APPROVED EQUAL), SEE NOTE 10.

MIN

LE

NG

TH P

ER

TA

BLE

"A"

MIN WIDTH PER TABLE "A"

MIN DIA PERTABLE "A"

MIN WIDTH PER TABLE "A"

8" MIN3" MIN

1'-0

" MIN

45° TYP

VARIESSEE TABLE "A"

1'-0" MIN

3" MIN (TYP)

1'-0

"M

IN

#5 BAR 12" OC BOTH WAYSTOP & BOTTOM GRADE 60

CLE

AR

HE

IGH

T

6' M

IN T

O T

RA

NS

ITIO

N(M

IN 4

8" R

ISE

RTO

GR

AD

E)

PRECAST MANHOLEPER STANDARDMANHOLE CONNECTIONDETAIL

SAW CUT & REMOVEEXISTING PIPE CROWN

FLO

W

FRAME & COVER PERDETAIL ND-10

PRECAST MANHOLE PERSTANDARD DETAIL

PER TABLE "A" CONNECTINGPIPE

PLAN

SECTION A

L VARIES

HYDROPHILLIC WATERSTOPALL AROUND EXISTING

DISTRICT PIPE ANDCONNECTING PIPE(S)

(TYPICAL), GREENSTREAKHYDROTITE (OR APPROVED

EQUAL), SEE NOTE 4.

"L" M

IN

EXISTING DISTRICTSEWER PIPE

CONNECTING PIPE

AA

12" GRANULAR BEDDINGCOMPACTED TO 95% DRYDENSITY (OR CONTROLDENSITY FILL)

UNDISTURBED NATIVESOIL

ND-11 Standard Manhole Detail 54" DIA or Larger District Pipe 1 of 2

NORTH DAVIS SEWER DISTRICT

PROVIDE STAINLESS STEEL BAND

(NON-SHEAR) TYPE.(FERNCO OR

APPROVED EQUAL)

HYDROPHILLICWATERSTOP ALL AROUND

EXISTING DISTRICT PIPEAND CONNECTING PIPE(S)(TYPICAL), GREENSTREAK

HYDROTITE (ORAPPROVED EQUAL), SEE

NOTE 4.

6"MAX

6" FROM WATERSTOPTO OUTSIDE EDGEOF MANHOLE

6" MIN FROM EDGE OFCONCRETE

PRECAST RISER TO BESET IN CONCRETE (TYP)(CAST-IN-PLACE BASE)

NOTES:

1. THIS STANDARD DRAWING SHALL BE USED FOR ACCESS TOEXISTING DISTRICT SEWER PIPES WITH DIAMETERS 54" DIA ORLARGER. THIS DETAIL SHALL NOT APPLY TO NEW DISTRICTSANITARY SEWER AND MANHOLE CONSTRUCTION.

2. WHERE DEPTH OF COVER OVER THE TOP OF PIPE EXCEEDS 10FEET, REINFORCEMENT REQUIREMENTS SHALL BE REVIEWEDAND VERIFIED BY A UTAH LICENSED CIVIL OR STRUCTURALENGINEER.

3. CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM 4000 PSICOMPRESSIVE STRENGTH AT 28 DAYS UNLESS OTHERWISEDIRECTED BY THE DISTRICT.

4. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CASTCONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIREBRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN,DURABLE SURFACE. SECURE WATERSTOP TO PIPE USINGMANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OFGREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEENWATERSTOP AND PIPE.

5. MINIMUM MANHOLE DIAMETER SHALL BE AS SHOWN IN TABLE A.MANHOLE COMPONENTS SHALL BE PROVIDED IN ACCORDANCEWITH DETAIL ND-10.

6. WHERE EXISTING DISTRICT PIPES HAVE BEEN REHABILITATEDWITH CURED-IN-PLACE PIPE LINERS, CIPP LINERS SHALL BE CUTAND THE CIPP LINER ROUGHENED AND SEALED WITH ANAPPROVED EPOXY PER DETAIL ND-16.

7. CONNECTING PIPE SHALL MATCH THE CROWN OF EXISTINGDISTRICT PIPE. SAW CUT AND REMOVE EXISTING PIPE FROMCROWN TO SPRINGLINE. CONSTRUCT SLOPING INLET CHANNELAND SHAPE CHANNEL TO FORM A SMOOTH FLOW SURFACE.

8. PIPE CONNECTIONS SET IN THE CONCRETE BASE SHALL BEWATERTIGHT. PROVIDE HYDROPHILIC WATER STOPS, GROUTRINGS OR CAST-IN-PLACE RUBBER BOOTS MEETING APPLICABLEREQUIREMENTS OF ASTM C923. (PRESS SEAL, LINK-SEAL, ORAPPROVED EQUAL) SUBMIT PRODUCT DETAILS AND PROPOSEDCONNECTION FOR APPROVAL BY THE DISTRICT.

TABLE "A"

DISTRICT PIPEDIA (IN)

MIN MANHOLEDIA (IN)

ENCASEMENTMIN WIDTH (IN)

ENCASEMENTMIN LENGTH (IN)

60" OR LESS 60" 96" 96"

78" OR LESS 72" 118" 118"

84" OR LESS 84" 124" 124"

ND-11 Standard Manhole Detail 54" DIA or Larger District Pipe 2 of 2

NORTH DAVIS SEWER DISTRICT

EQ EQ

MIN

WID

TH P

ER

TA

BLE

"A"

2'-0"

MIN LENGTH PER TABLE "A"

24" MIN

MIN DIA PERTABLE "A"

CCFRPM TEE BASEOR FITTING

EXISTING DISTRICT PIPE(CCFRPM, 18" DIAOR GREATER)

PRECAST MANHOLE PERDETAIL ND-13 OR ND-14

CONNECTING PIPEPROVIDE WATERTIGHT SEAL(INSERTA TEE OR APPROVED EQUAL WHERE CONNECTING TO CCFRPM)

FIELD CUT EXISTING PIPE,CLOSURE COUPLINGPER CCFRPM MFR

PRECAST MANHOLE PERDETAIL ND-13 OR ND-14. CCFRPM TEE BASE

OR FITTING

MIN.

2'-0"MIN.

12" GRANULAR BEDDINGCOMPACTED TO 95%DRY DENSITY (ORCONTROLLED DENSITYFILL)

CONCRETEENCASEMENT

2'-0"MIN.

NOTES:

1. THIS STANDARD DRAWING SHALL APPLY WHEREMANHOLES ARE CONSTRUCTED ON CCFRPM(FIBERGLASS) DISTRICT PIPES. AT THE CONTRACTORSOPTION, A PRECAST MANHOLE BASE MAY BEINSTALLED. CONTRACTOR SHALL BE RESPONSIBLEFOR PROPER MANHOLE CONNECTIONS AS ACCEPTEDBY THE DISTRICT.

2. CUT EXISTING PIPE TO NEAT STRAIGHT LINES WITHCUTTING TOOLS SUITABLE FOR THE PIPE MATERIAL.DAMAGED PIPE SHALL BE REPAIRED OR REPLACED ATNO ADDITIONAL COST TO THE DISTRICT. EXISTINGDISTRICT PIPELINES SHALL BE FULLY SUPPORTED ATALL TIMES.

3. CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM4000 PSI COMPRESSIVE STRENGTH AT 28 DAYS.

4. MINIMUM MANHOLE DIAMETER SHALL BE AS SHOWN INTABLE "A". PRECAST MANHOLES COMPONENTS SHALLBE PROVIDED IN ACCORDANCE WITH DETAIL ND-13 ORND-14.

5. ADDITIONAL DETAIL AND REINFORCING REQUIREMENTSSHOWN ON PAGE 2 OF 2.

6. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPEAND CAST CONCRETE, BOTH SIDES, ALL AROUND.CLEAN PIPE USING WIRE BRUSH, POWER WASH ORSAND BLAST TO PROVIDE A CLEAN, DURABLESURFACE. SECURE WATERSTOP TO PIPE USINGMANUFACTURER'S RECOMMENDED METHODS. APPLYLAYER OF GREENSTREAK LEAKMASTER OR APPROVEDEQUAL BETWEEN WATERSTOP AND PIPE.

TABLE "A"

DISTRICTPIPE DIA

(IN)

MINMANHOLE

DIA (IN)

MINENCASEMENT

WIDTH (IN)

MINENCASEMENTLENGTH (IN)

18" TO 45" 48" 74" 78"

60" ORLESS 60" 88" 102"

84" ORLESS 90" 112" 132"

UNDISTURBEDNATIVE SOILPLAN SECTION A

AA

ND-12 Standard Manhole Detail CCFRPM District Pipe 1 of 2

NORTH DAVIS SEWER DISTRICT

PRECAST RISER TO BESET IN CONCRETE (TYP)(CAST-IN-PLACE BASE)

HYDROPHILLIC WATERSTOP ALLAROUND EXISTING DISTRICT PIPE

AND CONNECTING PIPE(S) (TYPICAL),GREENSTREAK HYDROTITE (OR

APPROVED EQUAL), SEE NOTE 6.

HYDROPHILLIC WATERSTOP ALLAROUND EXISTING DISTRICT PIPE

AND CONNECTING PIPE(S) (TYPICAL),GREENSTREAK HYDROTITE (OR

APPROVED EQUAL), SEE NOTE 6.

NON SHRINK GROUT

(18 @ 20°) #4 X 1'-4"TYP. EACH END

#4 H2E @ 12" - TYP.4 SIDES

#4 H2E - TYP. 4 SIDES

#6

ADD (2) #6 EACHSIDE OF MANHOLE

CCFRPM TEE BASEOR FITTING

EXISTING DISTRICTPIPE (CCFRPM, 18" DIAOR GREATER)

PRECAST MANHOLE PER DETAIL

ND-13 OR ND-14

(4) #6 @ 12"

2'-0"MIN.

#5 @ 12" EW

(18 @ 20°) #4

#6 @ 12" -LAP 2'-4"

#5 H2E @ 12" EF

#5 @ 12" EF

#5 @ 12"#5 H2E @ 12"

VA

RIE

S

2'-0

"1'

-0"

SECTION BREINFORCING

SECTION AREINFORCING

B

B

ND-12 Standard Manhole Detail CCFRPM District Pipe 2 of 2

NORTH DAVIS SEWER DISTRICT

30"

12"

MIN

30" MANHOLE RING AND COVERMARKED "NORTH DAVIS SEWER"(D & L SUPPLY A-1180-18, OR APPROVED EQUAL)

FINISHED GRADE

EPOXY COATED PRECAST CONCRETE,POLYMER, OR EPP GRADE RINGS 12" MIN / 18"MAX. GROUT FOR SETTING GRADE RINGS ANDFRAME SHALL PROVIDE A WATERTIGHT BARRIERTO PREVENT INFILTRATION AND BE PLACEDACROSS THE FULL WIDTH, 1/2-INCH MIN AND1-INCH MAX THICK.

FACTORY-BONDED JOINT

FACTORY INSTALLEDPVC STUBOUTS ORCONNECTIONS

DISTRICT SEWERPIPE

#4 REBAR 12" OCEW

PROVIDE MIN 12",1" MINUS GRAVEL

BASE

ANTI-FLOTATION RING

WATER TIGHT, FLEXIBLE PIPECONNECTION, APPROVED

BY THE DISTRICT

CONCRETE BASE ASREQUIRED TO

COUNTERACT FLOTATION

FACTORY CAST FLOW CHANNELWITH FRP CHANNEL SUPPORTS

FRP MANHOLE. WALL THICKNESS PERMANUFACTURER PRODUCT SUBMITTAL

MIN 1/2" WALL THICKNESS

FRP NECK TO EXTEND INSIDEGRADE RINGS. GRADE RINGS TO

EXTEND A MINIMUM OF 1" PASTFLAT SURFACE OF MANHOLE CONE

PLACE AND COMPACT MANHOLE BACKFILL IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS

NORTH DAVIS SEWER DISTRICT

ND-13 Standard Manhole Detail FRP 1 of 2

MINIMUM INTERNAL MANHOLE DIAMETER PERND-03 FOR DISTRICT PIPE SIZES TO 48". SEEDETAIL ND-11 FOR DISTRICT PIPES 54" ORLARGER

EXISTING PAVEMENT

UNDISTURBED NATIVE SOIL

CONNECTING PIPE

12" WIDE MIN, 8" DEEP CONCRETECOLLAR IN PAVED AREAS

REINFORCEMENT REQUIRED(1) #4 BAR ALL AROUND

Revision 2, Adopted 11/7/2014

NORTH DAVIS SEWER DISTRICT

ND-13 Standard Manhole Detail FRP 2 of 2

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPEAND CONSTRUCTION OF CONNECTING PIPELINE.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OFEXISTING SEWER AND OTHER UTILITIES, PROPERBACKFILLING, COMPACTING, AND PAVEMENT RESTORATION.

3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OFONE YEAR.

5. MANHOLE BASE SHALL BE PRECAST FRP UNLESS OTHERWISEAPPROVED BY THE DISTRICT.

6. THE CONTRACTOR SHALL BE A LICENSED OR CERTIFIED INSTALLERBY THE MANUFACTURER OF THE MANHOLE PROVIDED.

7. MANHOLES AND THEIR BASES SHALL BE CIRCULAR FIBERGLASSREINFORCED POLYESTER MANHOLES DESIGNED, FABRICATED ANDTESTED TO MEET OR EXCEED THE REQUIREMENTS OF ASTM D3753.HOBAS, L.F. MANUFACTURING OR APPROVED EQUAL.

8. PRECAST CONCRETE AND CAST-IN-PLACE COMPONENTS SHALL NOTBE ALLOWED UNLESS OTHERWISE APPROVED BY THE DISTRICT.

9. ALL MANHOLES SHALL BE PROVIDED WITH ANTI-FLOTATION RINGSFULLY ENCASED IN A CONCRETE PAD OF SUFFICIENT SIZE ANDTHICKNESS TO PREVENT FLOTATION.

10. WHERE APPROVED BY THE DISTRICT, CONCRETE GRADE RINGS ANDALL OTHER EXPOSED CONCRETE SURFACES SHALL BE CORROSIONPROTECTED WITH AN APPROVED EPOXY COATING. EPOXY SHALL BEA SOLVENT-FREE, 100% SOLID, MOISTURE TOLERANT HIGH BUILDEPOXY COATING, RAVEN 405, ENVIRONMENTAL COATINGS SEWERSHIELD 100, SAUEREISEN SEWERGARD 210 OR APPROVED EQUAL.SURFACE PREPARATION AND APPLICATION SHALL BE ASRECOMMENDED BY THE MANUFACTURER.

11. GRADE RINGS SHALL BE GROUTED TO PREVENTINFILTRATION. GROUT SHALL BE FULL STRENGTH,NON-METALLIC, NON-SHRINK TYPE V GROUT (MASTERFLOW713, FIVESTAR GROUT OR APPROVED EQUAL) WITH ADDITIVESFOR PROTECTION AGAINST HYDROGEN SULFIDE ATTACK.

12. CONNECTING PIPE SHALL MATCH CROWNS WITH DISTRICT PIPEUNLESS OTHERWISE DIRECTED BY THE DISTRICT,

Revision 2, Adopted 11/7/2014

30"

BELL O.D.

I.D.

BARREL O.D.

PRECAST POLYMER MANHOLEMIN WALL THICKNESS PERMANUFACTURER PRODUCTSUBMITTAL

FINISH GRADE (PAVED AND UNPAVED)

CONCRETE COLLAR, 12" WIDE, 8" DEEP (ALL LOCATIONS)W/ (1) #4 REINFORCEMENT BAR ALL AROUND

30" MANHOLE RING AND COVERMARKED "NORTH DAVIS SEWER"

(D & L SUPPLY A-1180-18, OR EQUAL)

DISTRICT SEWERPIPE

PROVIDE MIN 12",1" MINUS GRAVEL BASEOVER UNDISTURBEDNATIVE SOIL

FACTORY CAST FLOW CHANNEL

WATER TIGHT, FLEXIBLEPIPE CONNECTIONS

APPROVED BY DISTRICT

BUTYL MASTIC

BUTYL MASTIC

NORTH DAVIS SEWER DISTRICT

ND-14 Standard Manhole Detail Polymer 1 of 3

MINIMUM INTERNAL DIAMETER PER ND-03 FORDISTRICT PIPE SIZES TO 48". SEE DETAIL ND-11FOR DISTRICT PIPES 54" OR LARGER

PLACE AND COMPACT BACKFILL INACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS

EPOXY COATED CONCRETE, POLYMEROR EPP GRADE RINGS AS APPROVED

BY THE DISTRICT. 18" MAX TOTALHEIGHT INCLUDING

FRAME, RINGS & GROUTGROUT FOR SETTING GRADE RINGS AND FRAME SHALLPROVIDE A WATERTIGHT BARRIER TO PREVENTINFILTRATION AND BE PLACED ACROSS THE FULLWIDTH, 1/2-INCH MIN AND 1-INCH MAX THICK.

PRECAST POLYMER BASEOR CAST-IN-PLACE BASE ASDIRECTED BY THE DISTRICT

Revision 2, Adopted 11/7/2014

NORTH DAVIS SEWER DISTRICT

ND-14 Standard Manhole Detail Polymer 2 of 3

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERSLOPE AND CONSTRUCTION OF CONNECTING PIPELINE.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTIONOF EXISTING SEWER AND OTHER UTILITIES, PROPERBACKFILLING, COMPACTING, AND PAVEMENTRESTORATION.

3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OFONE YEAR.

5. MANHOLE BASE SHALL BE PRECAST POLYMER UNLESSOTHERWISE APPROVED BY THE DISTRICT.

6. THE CONTRACTOR SHALL BE A LICENSED OR CERTIFIEDINSTALLER BY THE MANUFACTURER OF THE MANHOLEPROVIDED.

7. MANHOLES AND THEIR BASE SHALL BE CIRCULAR PRECASTPOLYMER DESIGNED, FABRICATED AND TESTED TO MEETOR EXCEED THE REQUIREMENTS OF D6783. POLYMERCOMPONENTS SHALL BE A MIXTURE OF UNSATURATEDISOPHTHALIC POLYESTER RESIN, SAND AND AGGREGATE.NO CEMENTIOUS OR CALCIUM CARBONATE MATERIALSSHALL BE ALLOWED. ARMOROCK OR APPROVED EQUAL.

8. PRECAST CONCRETE AND CAST-IN-PLACE COMPONENTSSHALL NOT BE ALLOWED UNLESS OTHERWISE APPROVEDBY THE DISTRICT.

9. ALL MANHOLES SHALL BE PROVIDED WITH ANTI-FLOTATIONRINGS FULLY ENCASED IN A CONCRETE PAD OFSUFFICIENT SIZE AND THICKNESS TO PREVENT FLOTATION.

10. WHERE APPROVED BY THE DISTRICT, CONCRETE GRADERINGS AND ALL OTHER EXPOSED CONCRETE SURFACESSHALL BE CORROSION PROTECTED WITH AN APPROVEDEPOXY COATING. EPOXY SHALL BE A 100% SOLID, EPOXYCOATING, ARMORROCK EPOXY OR APPROVED EQUAL.

11. GRADE RINGS AND DOG HOUSE MANHOLE CONNECTIONSSHALL BE GROUTED TO PREVENT INFILTRATION. GROUTSHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINKTYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUTOR APPROVED EQUAL) WITH ADDITIVES FOR PROTECTIONAGAINST HYDROGEN SULFIDE ATTACK.

12. CONNECTING PIPE SHALL MATCH CROWNS WITH DISTRICTPIPE UNLESS OTHERWISE DIRECTED BY THE DISTRICT.

Revision 1, Adopted 8/14/2014

NORTH DAVIS SEWER DISTRICT

ND-14 Standard Manhole Detail Polymer 3 of 3

MANHOLE I.D.

BA

SE

HE

IGH

TP

ER

MA

NU

FAC

TUR

ER

6" MIN, 12" MAX FROMEXTERIOR OF

MANHOLE OR BELLOD IF GREATER

12" M

IN

PRECAST POLYMER RISERSET IN CONCRETE WITHWATER TIGHT SEAL

CAST-IN-PLACECONCRETE BASEOR ENCASEMENT

SAWCUT ANDREMOVE TOP OF

PIPE PRIOR TOCOATING

FIELD APPLIED EPOXYCOATING, ARMORROCK

EPOXY OR APPROVEDEQUAL

PRECAST POLYMER BASE CAST-IN-PLACE BASE

BASE OPTION NOTES:

1. CONTRACTOR SHALL PROVIDE SUITABLE FOUNDATION AS DIRECTED BYTHE DISTRICT IN AREAS OF UNSTABLE TRENCH BOTTOM, WET CONDITIONS,OR OVER EXCAVATION.

2. CAST-IN-PLACE CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM4000 PSI COMPRESSIVE STRENGTH AT 28 DAYS UNLESS OTHERWISEDIRECTED BY THE DISTRICT. BASE SHALL BE CURED A MINIMUM OF THREEDAYS PRIOR TO STACKING MANHOLE.

3. BENCH TO HAVE 1:12 FLOOR SLOPE WITH TROWELLED FINISH.

4. EPOXY COATING TO BE APPLIED MIN 4" ABOVE BENCH AND OVERLAP CUTOUT SEWER PIPE.

5. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CAST CONCRETE,BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIRE BRUSH, POWER WASHOR SAND BLAST TO PROVIDE A CLEAN, DURABLE SURFACE. SECUREWATERSTOP TO PIPE USING MANUFACTURER'S RECOMMENDED METHODS.APPLY LAYER OF GREENSTREAK LEAKMASTER OR APPROVED EQUALBETWEEN WATERSTOP AND PIPE.

FACTORY CASTFLOW CHANNEL

RESIN AGGREGATEWALL & BENCH

Revision 1, Adopted 8/14/2014

HYDROPHILLIC WATERSTOP ALLAROUND EXISTING DISTRICT PIPEAND CONNECTING PIPE(S)(TYPICAL), GREENSTREAKHYDROTITE (OR APPROVEDEQUAL), SEE NOTE 5.

TEE - 6" MIN.PRECAST CONCRETETANK

RISER SECTION / GRADE RINGS (NOTTO EXCEED 12" TOTAL HEIGHT).GROUT FOR SETTING GRADE RINGSAND FRAME SHALL PROVIDE AWATERTIGHT BARRIER TO PREVENTINFILTRATION AND BE PLACED ACROSSTHE FULL WIDTH, 1/2-INCH MIN AND1-INCH MAX THICK.

FINISH GRADE(PAVEMENT ORLANDSCAPING)

DOUBLESWEEP

CLEANOUT

SANITARYTEES

LIQUIDLEVEL

GREASESTORAGE

MANHOLE RING AND NON-VENTEDCOVER MARKED "SEWER" - (TYPICAL)

(D & L A-1024, OR EQUAL)

6"

1" MINUSGRAVEL BASE

UNDISTURBEDNATIVE SOIL

20"MIN. DIA.

OUTLETINLET

INLET OUTLET

MANHOLE COVERSLOCATED TO ALLOWVIEWING OF ANDSAMPLING FROM INLETAND OUTLET TEES(TYPICAL)

PLAN

SECTION

SEWER

SST PIPE SUPPORTSREQUIRED (TYP)

12"

SEWER

1'-6" WIDE, 6" DEEP CONCRETECOLLARS IN PAVED AREAS.REINFORCEMENT REQUIRED.(1) #4 BAR ALL AROUND

ND-15 Standard Grease Interceptor 1 of 2

NORTH DAVIS SEWER DISTRICT

Revision 2, Adopted 11/7/2014

ND-15 Standard Grease Interceptor 2 of 2

NORTH DAVIS SEWER DISTRICT

NOTE:

ALL HARDWARE316 STAINLESSSTEEL

NOTES:

1. GREASE INTERCEPTOR SHALL BE LOCATED TO BECONTINUOUSLY AND EASILY ACCESSIBLE FOR INSPECTION ANDCLEANING AND AS CLOSE AS PRACTICAL TO THE SOURCE OFWASTEWATER. IT SHALL NOT BE LOCATED IN DRIVE-UP LANES,OR SIMILAR AREAS THAT COULD BE PERIODICALLY BLOCKED.

2. WHEN LOCATED IN PAVED AREA, THE TRAP, MANHOLE COVERS,ETC, SHALL BE TRAFFIC RATED.

3. INLET AND OUTLET TEES SHALL BE LOCATED DIRECTLY BELOWMANHOLE ACCESSES.

4. GREASE INTERCEPTORS SHALL HAVE A MINIMUM OF TWOCOMPARTMENTS.

5. MINIMUM HYDRAULIC VOLUME OF THE TRAP SHALL BE 1000GALLONS.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ALLUTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENTRESTORATION.

7. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

8. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONEYEAR.

9. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION.GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINKTYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUT ORAPPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINSTHYDROGEN SULFIDE ATTACK.

2 SS EXP ANCHORSEACH CLAMP

WALL

"Z" SHAPED STEELSTRAP FITTING,TYP

SST PIPE SUPPORT

Revision 2, Adopted 11/7/2014

NOTES:

1. THIS STANDARD DRAWING SHALL APPLY WHERE MANHOLES ARECONSTRUCTED ON DISTRICT PIPES REHABILITATED WITHCURED-IN-PLACE PIPE LINERS(CIPP).

2. CUT CIPP LINER TO NEAT STRAIGHT LINES WITH CUTTING TOOLSSUITABLE FOR THE LINER MATERIAL. DAMAGED LINERS SHALL BEREPAIRED AT NO ADDITIONAL COST TO THE DISTRICT.

3. REMOVE POLYETHYLENE LAYER IF PRESENT AND ROUGHEN CIPPSURFACE AT ALL CUT EDGES. WHERE FRP LINERS ARE CUT,REMOVE PRE LINER SHEET AND FOIL (IF INSTALLED). SMOOTHLINER EDGE PRIOR TO COATING.

4. CONTRACTOR SHALL COAT CIPP LINER AND EXPOSED CONCRETEAT CHANNEL AND BENCH WITH AN APPROVED EPOXY COATINGSYSTEM; NEOPOXY, SEWER SHIELD 100, SAUEREISENSEWERGARD 210, RAVEN 405 OR APPROVED EQUAL. COATINGSSHALL BE PROVIDED BY A CERTIFIED CONTRACTOR/APPLICATORIN STRICT ACCORDANCE WITH THE MANUFACTURER'SREQUIREMENTS.

5. WHERE EXISTING HOST PIPE AND LINER ARE REMOVED PROVIDEA SMOOTH TRANSITION BETWEEN MANHOLE INVERT AND CUTEDGE OF CIPP LINER PER DETAIL B.

4" MIN

MANHOLE WALL(PRECAST FRP OR POLYMERMANHOLES ONLY ON CIPPLINED PIPES)

GROUT ANNULAR SPACEAS REQ.

CUT AND BEVEL CIPP LINER 45°(ALL AROUND) PRIOR TO COATING

COAT 4" MIN OF CIPP LINERAT CUT EDGE (SEE NOTE 3)

MANHOLE INVERT

MANHOLE BASE(VIEW SHOWN FORMANHOLE WITH HOSTPIPE & LINER REMOVED)

EXISTING CIPPLINER

EXISTINGDISTRICT

PIPE

4" MINTYP

GROUT ANNULARSPACE AS REQ.

EXISTING CIPPLINER

EXISTINGDISTRICTPIPE

45°

MANHOLE BASECAST AROUNDEXISTING PIPEDETAIL A

DETAIL B

REMOVE EXISTING HOSTPIPE CROWN W/ CIPP LINER

COAT 4" MIN OFCIPP LINERAT CUT EDGE(SEE NOTE 3)

ND-16 Standard Manhole Detail CIPP Repair

NORTH DAVIS SEWER DISTRICT

45° BEND

PEA GRAVEL FILL SHALL BE PLACEDAND COMPACTED BENEATH CONNECTING

SERVICE TO UNDISTURBED SUBGRADEAND TO A MINIMUM DEPTH OF 6" ABOVE PIPE

CONNECTING SERVICE LATERAL(MATERIAL AND CONSTRUCTIONSHALL CONFORM TOREQUIREMENTS OF APPLICABLEJURISDICTIONAL AGENCY)

EXISTING DISTRICT PIPE.CONTRACTOR TO VERIFYPIPE MATERIAL PRIOR TOCONSTRUCTION

LATERAL SHALL BEFLUSH WITH INSIDEOF PIPE

CORE DRILLED OPENING(INSTALLATION OF ANCHOR BOLTSIN THE PIPE WALL OR HAMMER DRILLINGSHALL NOT BE ALLOWED AS PART OF THECORE DRILLING OPERATION)

FLEXIBLE AND WATERTIGHT CONNECTIONFITTING - FITTING SHALL HAVE POSITIVE STOPTO PREVENT PROTRUSION INTO SEWER LINE(INSERTA TEE, GPK 4, OR EQUAL)

45°

NOTES:

1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TO THESERVICE LATERAL AND FURNISH MEASUREMENT TO DISTRICT.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTIONOF CONNECTING SERVICE LATERAL.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWERAND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENTRESTORATION.

4. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS.

5. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

6. CONCRETE CORES SHALL BE RETAINED AND NOT ALLOWED TO FALL INTO THESEWER LINE.

ND-20 Standard Service Connection - Concrete Pipe

NORTH DAVIS SEWER DISTRICT

Revision 2, Adopted 11/7/2014

PROVIDE ENCASED FULL STAINLESS STEELBAND (NON-SHEAR) TYPE. (FERNCO OR

APPROVED EQUAL) WHERE CONNECTING TOEXISTING SERVICE LATERAL

ENCASE IN CONCRETE,MINIMUM 12" BELOW &6" ABOVE

45° SHOPFABRICATEDBEND

PEA GRAVEL FILL SHALL BE PLACEDAND COMPACTED BENEATH CONNECTINGSERVICE TO UNDISTURBED SUBGRADEAND TO A MINIMUM DEPTH OF 6" ABOVE PIPE

CONNECTING SERVICE LATERAL,(MATERIAL AND CONSTRUCTION SHALL CONFORM

TO REQUIREMENTS OF APPLICABLEJURISDICTIONAL AGENCY)

CORE DRILLED OPENING IN HOST PIPE

FLEXIBLE AND WATERTIGHT CONNECTIONFITTING - FITTING SHALL HAVE POSITIVE STOPTO PREVENT PROTRUSION INTO SEWER LINEAND ENGAGE AT CIPP LINER - (INSERTA TEEOR EQUAL - SEE NOTE 12)

NOTES:

1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TOTHE SERVICE LATERAL AND FURNISH MEASUREMENT TO DISTRICT.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE ANDCONSTRUCTION OF CONNECTING SERVICE LATERAL.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTINGSEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, ANDPAVEMENT RESTORATION.

4. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATIONBEGINS.

5. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

6. SERVICE CONNECTION BANDS, SCREWS, HOUSING AND HARDWARE SHALLBE 316 SST. RUBBER MATERIALS SHALL BE NITRILE OR NEOPRENE UNLESSOTHERWISE DIRECTED BY THE DISTRICT.

7. CONTRACTOR SHALL MANUALLY BACKFILL AND COMPACT AROUND INSERTATEE OR SADDLE UNTIL A MIN OF 12” OF COVER IS PLACED OVER THECONNECTION.

8. CORE DRILLING OF CONCRETE PIPE SHALL USE THE WET DIAMOND BITPROCESS. DO NOT ATTACH GUIDES TO THE EXISTING PIPE TO PERFORMCORE DRILLING. CORE DRILL DIAMETER SHALL BE PER THE CONNECTIONMANUFACTURER'S REQUIREMENTS FOR INSTALLATION OF THE PROVIDEDPRODUCT. CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACEDAMAGED PIPE AND LINER.

9. CORE DRILLING OF THE CIPP LINER SHALL BE ACCOMPLISHED EITHERROBOTICALLY FROM INSIDE THE PIPE OR EXTERNALLY. DIAMETER OF THEHOLE SHALL BE SIZED FOR THE FLEXIBLE AND WATERTIGHT CONNECTIONFITTING.

10. FILL VOIDS, OVER CUT OR REMOVED CONCRETE PIPE WITH NON SHRINK NONMETALLIC CEMENT GROUT.

11. CONCRETE AND CIPP LINER CORES SHALL BE RETAINED AND NOT ALLOWEDTO FALL INTO THE SEWER LINE.

12. INSERTA TEE PROVIDED SHALL BE PER TABLE 1 UNLESS OTHERWISERECOMMENDED BY THE MANUFACTURER BASED ON THE EXISTINGREHABILTATED DISTRICT PIPE DIAMETER, SERVICE CONNECTION DIAMETER,AND EXISTING CIPP LINER THICKNESS. CONTRACTOR SHALL VERIFY THELINER THICKNESS PRIOR TO INSTALLING THE CONNECTION INTO THE COREDLINER.

EXISTING CIPP LINERTHICKNESS AS PROVIDEDBY THE DISTRICT - SEENOTE 12.

EXISTING REHABILITATEDDISTRICT PIPE (NTS)

PROVIDE ENCASED FULLSTAINLESS STEEL BAND

(NON-SHEAR) TYPE. (FERNCOOR APPROVED EQUAL) WHERE

CONNECTING TO EXISTINGSERVICE LATERAL

45°

NON SHRINK, NON METALLIC GROUT

ENCASE IN CONCRETE, MINIMUM12" BELOW & 6" ABOVE

NORTH DAVIS SEWER DISTRICT

ND-21 Standard Service Connection - CIPP Lined Pipe 1 of 2

CORE DRILLED OPENING IN CIPP LINER

Revision 1, Adopted 8/14/2014

PVC LATERALSERVICE

NORTH DAVIS SEWER DISTRICT

ND-21 Standard Service Connection - CIPP Lined Pipe 2 of 2

Revision 1, Adopted 8/14/2014

TABLE 1

Rehabilitated District

Concrete Pipe

CIPP Liner Thickness

INSERTA - TEE ORDERING INFORMATION

Lateral Nominal Diameter (inch)

Standard CIPP

INSERTA-TEE

LINER: RUBBER

SLEEVE

THICKNESS*

Nominal Pipe Diameter(in)

Minimum LinerThickness (mm)

Maximum LinerThickness (mm) 4 6 8

Minimum LinerThickness (mm)

12 3.5 5.0 4P26FB12CIP 6P26FB12CIP 8P3512CIP 8.0

15 4.5 6.0 4P26FB15CIP 6P26FB15CIP 8P3515CIP 10.5

18 5.0 8.0 4P26FB18CIP 6P26FB18CIP 8P3518CIP 10.5

21 5.5 7.0 4P26FB21CIP 6P26FB21CIP 8P3521CIP 10.5

24 7.0 9.0 4P26FB24CIP 6P26FB24CIP 8P3524CIP 14.0

27 8.0 10.0 4P26FB27CIP 6P26FB27CIP 8P3527CIP 14.0

30 8.0 12.0 4P26FB30CIP 6P26FB30CIP 8P3530CIP 16.0

36 8.0 12.0 4P26FB36CIP 6P26FB36CIP 8P3536CIP 19.0WHEN ORDERRING INSERTA TEE, CONTRACTOR SHALL PROVIDE THE NOMINAL DISTRICT PIPE DIAMETER, LATERAL DIAMETER ANDMATERIAL TO BE INSTALLED, AND EXISTING CIPP LINER THICKNESS TO VERIFY PROPER SIZING OF THE RUBBER SLEEVE. INSERTA TEEWITH RUBBER SLEEVE THICKNESS SIZED FOR STANDARD CIPP LINER THICKNESS WITHOUT VERIFICATION SHALL NOT BE ACCEPTED BYTHE DISTRICT.

45° SHOPFABRICATEDBEND

CONNECTING SERVICE LATERAL,(MATERIAL AND CONSTRUCTION SHALL CONFORM

TO REQUIREMENTS OF APPLICABLEJURISDICTIONAL AGENCY)

CORE DRILLED OPENING

FLEXIBLE AND WATERTIGHT CONNECTIONFITTING - FITTING SHALL HAVE POSITIVE STOPTO PREVENT PROTRUSION INTO SEWER LINE(INSERTA TEE OR EQUAL)

EXISTING CCFRPM (FIBERGLASS)DISTRICT PIPE (18" DIA OR GREATER) NTS.

PEA GRAVEL FILL SHALL BE PLACEDAND COMPACTED BENEATH CONNECTINGSERVICE TO UNDISTURBED SUBGRADE ANDTO A MINIMUM DEPTH OF 6" ABOVE PIPE

PROVIDE ENCASED FULL STAINLESS STEELBAND (NON-SHEAR) TYPE. (FERNCO OR

APPROVED EQUAL) WHERE CONNECTING TOEXISTING SERVICE LATERAL

NOTES:

1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TO THESERVICE LATERAL AND FURNISH MEASUREMENT TO DISTRICT.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTIONOF CONNECTING SERVICE LATERAL.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER ANDOTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENTRESTORATION.

4. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS.

5. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

6. SERVICE CONNECTION BANDS, SCREWS, HOUSING AND HARDWARE SHALL BE 316SST. RUBBER MATERIALS SHALL BE NITRILE OR NEOPRENE UNLESS OTHERWISEDIRECTED BY THE DISTRICT.

7. CONTRACTOR SHALL MANUALLY BACKFILL AND COMPACT AROUND INSERTA TEEUNTIL A MIN OF 12” OF COVER IS PLACED OVER THE CONNECTION.

8. CORE DRILLING OF PIPE SHALL BE PERFORMED USING CUTTING EQUIPMENTRECOMMENDED BY MANUFACTURERS OF FIBERGLASS PIPE. DO NOT ATTACHGUIDES TO THE EXISTING PIPE TO PERFORM CORE DRILLING. CONTRACTOR SHALLBE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED PIPE.

9. FLEXIBLE AND WATERTIGHT FITTING SHALL BE SIZED FOR THE CCFRPM PIPE.

10. FIBERGLASS CORES SHALL BE RETAINED AND NOT ALLOWED TO FALL INTO THESEWER LINE

45°

NON SHRINK, NON METALLIC GROUT

ENCASE IN CONCRETE, MINIMUM12" BELOW & 6" ABOVE

NORTH DAVIS SEWER DISTRICT

ND-22 Standard Service Connection - CCFRPM Fiberglass Pipe

Revision 1, Adopted 8/14/2014

EXISTING SERVICE LATERAL, VARIES

EXISTING DISTRICTPIPE

EXISTING SERVICE LATERAL, ABANDON IN PLACE

INSTALL WATER TIGHT EXPANSIONPLUG AT EXISTING SERVICELATERAL CONNECTION TO MAIN

RO

W

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHERUTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION.

2. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS.

3. CONCRETE THRUST BLOCKS SHALL BE A MINIMUM ONE CUBIC FOOT IN SIZE PLACED AT CAP TOPREVENT DISPLACEMENT OF CAP DURING SEWER CLEANING AND OTHER MAINTENANCEACTIVITIES. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150 WITH A MINIMUMCOMPRESSIVE STRENGTH OF 4000 PSI PER ASTM C39.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

REMOVE INTERFERINGPORTIONS OF EXISTINGSERVICE LATERAL, CUT ANDCAP PIPE (TYP)

ND-23 Standard Service Connection Abandonment

NORTH DAVIS SEWER DISTRICT

ENCASE CAP INCONCRETETHRUST BLOCK

Revision 1, Adopted 8/14/2014

NOTES:

1. REPAIR COUPLINGS SHALL PROVIDE A WATER TIGHT SEALAND BE MANUFACTURED FOR USE WITH THE GRAVITYSEWER PIPE MATERIAL TO BE REPAIRED. CONTRACTORSHALL SUBMIT PRODUCT DATA FOR REVIEW ANDACCEPTANCE BY THE DISTRICT.

2. ALL HARDWARE (SHELLS, NUTS, BOLTS, WASHERS, TAKE UPCLAMPS OR RINGS) SHALL BE TYPE 304 STAINLESS STEELPER ASTM A240 UNLESS OTHERWISE APPROVED BY THEDISTRICT.

3. GASKETS SHALL BE FULL LENGTH CIRCUMFERENTIAL SBROR NITRILE (BUNA-N) UNLESS OTHERWISE APPROVED BYTHE DISTRICT.

4. REPAIRS SHALL BE INSPECTED AND APPROVED BY THEDISTRICT PRIOR TO ENCASEMENT AND BACKFILLING.

5. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PERASTM C150 WITH A MINIMUM COMPRESSIVE STRENGTH OF4000 PSI PER ASTM C39. NO ADDITIVES SHALL BEPERMITTED WITHOUT PRIOR APPROVAL BY THE DISTRICT.

6. MINIMUM ENCASEMENT SHALL BE AS FOLLOWS:

REINFORCED CONCRETEENCASEMENT

STAINLESS STEELREPAIR COUPLINGOVER CRACKS

REINFORCEMENTSTEEL, 4 - CONT #4#4 @ 24" OC MIN (2)

EACH SIDE OF REPAIRCOUPLING, MIN 3" CLR

GRAVEL BEDDING

CRACKED PIPE SECTION

DISTRICT PIPE

NOMINAL DIAMETER (IN) A (IN) ENCASEMENT

24" OR LESS 6 OD + 12

33" OR LESS 8 OD + 16

39" OR LESS 10 OD + 20

42" OR LARGER 12 OD + 24

2 x EXISTING PIPE ODBUT NOT LESS THAN 12"

A

ND-30 Cracked Pipe Repair

NORTH DAVIS SEWER DISTRICT

Revision 1, Adopted 8/14/2014

ND-31 Structural Support at Crossings 1 of 2

NORTH DAVIS SEWER DISTRICT

Revision 2, Adopted 11/7/2014

6" M

IN24

" MA

X(S

EE

NO

TE3

AN

D 4

)

1/2

OD

6" MIN6" MINOD

12"MIN

12"MIN

1/2" FELT EXPANSIONJOINT FILLER

EXIST PIPE

CONCRETE PER NOTE 1 & 2

1/2"EXPANSION JOINTFILLER MATERIAL ALLAROUND, SEE NOTE 2

PROVIDE BEDDING PER DISTRICTREQUIREMENTS

NEW SEWERPIPE

6" SCH 80 PVCDRAIN HOLEFILL W/ PEAGRAVEL (TYP)

TRENCH WIDTH

EXISTING PIPE OVER NEW SEWER MAIN

NOTES:

1. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PERASTM C150 WITH A MINIMUM COMPRESSIVE STRENGTH OF300 PSI PER ASTM C39. NO ADDITIVES SHALL BEPERMITTED WITHOUT PRIOR APPROVAL BY THE DISTRICT.

2. CONCRETE OR FLOWABLE FILL SHALL NOT BE INSTALLEDTO SUPPORT OR BACK FILL ASBESTO CEMENT PIPE (ACP).WHERE ACP REQUIRES SUPPORT OR BACKFILL, PROVIDE3/4-INCH MINUS OR IMPORTED SAND MATERIALS.

NOTES:

1. INSTALL #15 FELT OR NEOPRENE WATERSTOPAROUND NEW WATER PIPE PRIOR TO THEPOUR OF CONCRETE ENCASEMENT TOPREVENT BONDING.

2. BACKFILL TO BE BROUGHT UP UNIFORMLY ONBOTH SIDES OF CONC. SUPPORT.

3. THIS DETAIL SHALL APPLY WHERE VERTICALCLEARANCE OUTSIDE TO OUTSIDE OF SEWERPIPE OR LATERAL IS LESS THAN 24-INCH.

4. WASTEWATER LINES SHALL BE INSTALLEDBELOW POTABLE WATER LINES. A MINIMUMSEPARATION OF 18 INCHES BETWEEN THEBOTTOM OF THE POTABLE WATER LINE ANDTHE TOP OF THE WASTEWATER LINE SHALL BEMAINTAINED. WHERE A POTABLE WATERLINECROSSES UNDER A WASTEWATER OR STORMLINE, A FULL LENGTH OF PIPE SHALL BECENTERED ABOVE THE WATER LINE SO THATBOTH JOINTS WILL BE AS FAR FROM THEPOTABLE WATER LINE AS POSSIBLE.ADDITIONAL MITIGATION MEASURES MAY BEREQUIRED PER UTAH DEQ ANDR309-105-6(2)(b).

5. CONCRETE SHALL BE TYPE II/V PORTLANDCEMENT PER ASTM C150 WITH A MINIMUMCOMPRESSIVE STRENGTH OF 300 PSI PERASTM C39. NO ADDITIVES SHALL BEPERMITTED WITHOUT PRIOR APPROVAL BYTHE DISTRICT.

6. CONCRETE OR FLOWABLE FILL SHALL NOT BEINSTALLED TO SUPPORT OR BACK FILLASBESTO CEMENT PIPE (ACP). WHERE ACPREQUIRES SUPPORT OR BACKFILL, PROVIDE3/4-INCH MINUS OR IMPORTED SANDMATERIALS.

ND-31 Structural Support at Crossings 2 of 2

NORTH DAVIS SEWER DISTRICT

Revision 2, Adopted 11/7/2014

6"M

IN

SP

RIN

GLI

NE6"MIN6"MIN

D

-

12"MIN

12"MIN TRENCH WIDTH

CONCRETE PER NOTE 5 & 6

1/2"EXPANSION JOINTFILLER MATERIAL ALLAROUND, SEE NOTE 2

EXIST PIPE

1/2" FELT EXPANSIONJOINT FILLER IFCONCRETE EXTENDUP TO BOTTOM OFNEW PIPE

DO NOT DISTURBEXISTING PIPEBEDDING BELOWSPRINGLINE OF PIPE

UNDISTURBED SOIL (TYP)

NEW SEWER PIPE

SECTION D

EXISTING PIPE UNDER NEW SEWER MAIN

24" M

AX

(SE

E N

OTE

3 A

ND

4)

OD