    1. Before Installation

    1.1 To install

    Please follow the installation guide because the performance

    can be decreased if the product is installed incorrectly.

    1.2 Product package

    Product Pictures Qty Use

    Terminal 1ea Access Controller

    Adapter 1ea

    Power cord 1ea

    Supplying power for

    the terminal

    Rear case 1ea Fastening the terminal

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    4/20

    - 5 -

    4ea Fastening the terminalBolt

    6ea Fastening the rear

    case

    1ea

    5ea

    Connecting door cable

    S/W CD 1ea

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    5/20

    - 6 -

    2. Installation Environment

    Please keep in mind the following conditions when you install the

    product. You might need to obtain the user's consent if necessary.

    This product is originally designed to install indoors. If you

    have to install it outdoors, however, do not expose the terminal

    to direct sunlight, snow or rain.

    The connection cables should not be exposed outside, and it

    is highly recommended to bury them underground. If that is

    impossible, you must obtain the user's consent beforeinstallation.

    Power supply should begin after all connections are completed.

    Do not disconnect the lines or make any additional

    connections while the power is supplied.

    If you install the product as an access controller at a proper

    height for the users and in a near place that facilitates control

    of the entrance, you can use it more efficiently.

    The power requirement for the system is AC 100~240V,

    50/60Hz.

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    6/20

    - 7 -

    3. System Configuration

    3.1 Network mode

    Terminals are connected by network and it can be remote

    control.

    Terminal

    Lock

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    7/20

    - 8 -

    3.2 Standalone mode

    One terminal is used independently. All settings such as user

    registration, deletion, and access control are performed in the

    terminal alone.

    Figure 3.2 Terminal Block Diagram

    Locking Device

    Door Open S/W

    Interphone

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    8/20

    - 9 -

    4. Installation

    The overall installation procedure is as follows:

    Fasten the bracket

    Attach other devices except terminal(locking device, interphone,

    etc.)

    Connect the external cables

    Fasten the terminal

    4.1 Fastening the auxiliary plate

    Decide where you want to install the product, and cut the

    rear case as shown Figure 4.1 to make the hole for wiring.

    Figure 4.1 Making the hole for wiring in the rear case

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    9/20

    - 10 -

    Align the bracket with the hole for wiring as shown Figure

    4.2, and fasten it with 6 bolts supported in the packet.

    Figure 4.2 Fastening rear case

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    10/20

    - 11 -

    4.2 Attaching other devices except terminal

    You can attach the following devices. Refer to the specifications

    of each device for more information on installation.

    Locking device

    Door Open button

    Types of installable locking devices and specifications

    Type Specifications RemarksDeadbolt input: DC12V,

    1A or lower

    Voltage output,

    Fail Safe/Secure

    Electronic

    Magnetic-Lock

    input: DC12V,

    1A or lower

    Voltage output,

    Fail Safe/Secure

    Electric Strike input: DC12V,

    1A or lower

    Voltage output,

    Fail Safe/Secure

    Auto Door *Maximum Switching Voltage:

    220V DC,250V AC.

    *Maximum Switching Current:

    2A DC,AC or lower

    Contact output

    Fail Safe Type: UNLOCKED, Open Type on EmergencyFail Secure Type: LOCKED, Close Type on Emergency

    4.3 Connecting the external cables

    You should connect the following external cables.

    But you don't have to install the network cables if the customer

    doesn't request them.

    Door control cable

    Network cable

    Power cable

    Wiegand signal cable

    RS485 cable

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    11/20

    - 12 -

    4.3.1 Connecting the door control cable (Main board J2)

    Specifications of the cable and material

    Housing Receptacle Cable

    5264-06 5263PBT UL Cable, 24~28AWG

    Connection Note

    Pay attention to terminal numbers when connecting the cable to

    the connector.

    Contact output is used when installing on the auto door. So makesure to set the terminal [JP1] as OPEN. The factory default of

    the terminal [JP1] is JUMPER.

    Some locking devices may not have door monitoring signals.

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    12/20

    - 13 -

    How to connect cables by types of locking devices

    Deadbolt/Strike/Electronic Magnetic-Lock

    PIN

    NO.Feature Fail

    Safe Type

    Fail

    Secure

    Type

    Door

    Monitoring

    Door

    Open

    1 GND GND GND COMOpen

    button

    2 Door Open buttonOpen

    button

    3 Door MonitoringMonitor

    (12/24V)

    4 CONTACT_BVCC(12/24

    V)

    5 COMMON (COM)

    6 CONTACT_AVCC(12/24

    V)

    *The Relay Boad [JP1]=>Close

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    13/20

    - 14 -

    Auto DoorPIN

    NO.Feature Normal

    Open

    Normal

    Close

    Door

    Monitoring

    Door

    Open

    1 GND COMOpen

    button

    2 Door Open buttonOpen

    button

    3 Door MonitoringMonitor

    (12/24V)

    4 CONTACT_B Contact

    5 COMMON Contact Contact

    6 CONTACT_A Contact

    *The relay board [JP1]=>Open

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    14/20

    - 15 -

    4.3.2 Connecting the network cable (Network board J3)

    Connect network lines as follows (pay attention to PIN numbers):

    SchematicHousing Cable

    PIN No Feature

    1 TXP

    2 TXN

    3 RXPRJ45, 8PIN UTP

    6 RXN

    4.3.3 Connecting the power cable

    Connect 12V adapter to Relay Board J4.

    Connect 5V adapter ro Main Board J3

    4.3.4 Wiegand output (Main board J5)

    Check if the external device is pull up. If it is not, connect J16 and

    J17.

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    15/20

    - 16 -

    4.3.5 RS-485 (Main board J1)

    * If the device needs a termimal resistance, connect J18.

    4.3.6 Wiegand input (Main board J9)

    * Wiegand input cannot be used with RF module.

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    16/20

    - 17 -

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    17/20

    - 18 -

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    18/20

    - 19 -

    Fasten the terminal

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    19/20

    - 20 -

  • 8/9/2019 Nitgen NAC 2500 PLUS Fingerprint Access Controller Terminal Installation Manual

    20/20

    - 21 -

    5. Check After Installation

    When you finish the installation of the entire system, check if it is

    installed correctly before supplying power.

    Check if locking device and other devices work normally as the

    following order. For more information, please refer to

    "NAC-2500 Terminal User Manual" and "Access Manager

    User Manual ".

    When power is supplied, the initial screen with NITGEN logo

    will appear.

    Press the menu button to choose System Option > Terminal

    Mode and check if the terminal is in SO mode.

    Choose User Manager from the menu and then register user

    ID and fingerprint. (By default, user ID is set to 4 digits long.)

    Test the devices (including locking device) attached to the

    terminal by performing fingerprint authentication.

    If there's no problem, delete the fingerprint you registered for

    the test.

    If you manage terminals via the network after installation,

    proceed the following test:

    Install the program on a server PC for manager registration

    and initial settings.

    Set the terminal mode to NL or NS from the terminal menu.

    Set the network environment from the terminal menu.

    Run Remote Manager to check the terminal connection and

    then register it.

    In the server PC, register a terminal user and check if the

    authentication is performed normally.

    If there's no problem, delete both server and terminal users.