Neutral Hazards

download Neutral Hazards

of 18

Transcript of Neutral Hazards

  • 8/7/2019 Neutral Hazards

    1/18

    Potential Hazards with

    Neutral Conductors

    Click to Advance

  • 8/7/2019 Neutral Hazards

    2/18

    Neutrals are grounded but carry current under load.

    Neutrals Are Current Carrying

    Conductors

    The source of neutral current cannot always beidentified.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    3/18

    Potential Hazards with Neutral

    Conductors

    Breaking a neutral under load could create a

    shock hazard.

    Individuals contacting a lifted neutral potentially

    provide an alternate path to ground.

    A broken neutral or lifted neutral could result in a

    shock or an arc.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    4/18

    Energized Neutral Examples

    A neutral was misidentified and inadvertently openedcreating an arc (ORPS EM-SR-WSRC-FTANK-2005-0009)

    A circuit was moved to a different distribution panel, butthe neutral was spliced in the original panel (ORPS EM-RL-PHMC-PFP-2005-0011)

    An electrician received a shock after lifting a neutral from

    its bus bar. The neutral received its power through anemergency light that received power from anotherdistribution panel. (ORPS SC-PNSO-PNNL=PNNLBOPER-2005-0018)

    Click to Advance

  • 8/7/2019 Neutral Hazards

    5/18

    Configuration That Requires

    Additional Precautions:

    Click to Advance

  • 8/7/2019 Neutral Hazards

    6/18

    Notes:

    3 current carrying

    conductors in a

    raceway.

    Copper ground wire

    omitted for simplicity.

    Highlighted in yellow

    indicates energized.

    Component labels

    For the purpose of this presentation, please review the following labels:

    Circuit Breaker

    Circuit A Ungrounded Conductor

    CircuitB

    Ungrounded Conductor

    Grounded Conductor (Neutral Conductor)

    Ground

    Ballast / Fluorescent Light

    Ballast / Fluorescent Light enclosure

    Click to Advance

  • 8/7/2019 Neutral Hazards

    7/18

    The Multi-Wire Branch Circuit is an

    acceptable configuration accordingto the National Electrical Code

    (NEC) Section 210.4.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    8/18

    This circuit has also been referred to as:

    The Edison Circuit

    Common Neutral Circuit

    Shared Neutral Circuit

    Click to Advance

  • 8/7/2019 Neutral Hazards

    9/18

    These circuits are typically found on 120 / 240 volt

    single phase systems, but can be found on 208Y /120

    and 277Y / 480 volt systems as well.

    The Grounded Neutral wire carries the unbalancedload current. (Grounded Conductor)

    Click to Advance

  • 8/7/2019 Neutral Hazards

    10/18

    CktA

    CktB

    Click to Lock Out

    Circuit BClick to Energize Circuits

    The desiredtechnique used to

    remove a device Isto cut the neutrallead or disconnectthe device leaving aneutral pigtail. (Click)

    The Neutral Will

    Remain at Ground

    Potential

    X

    Ckt A

    Ckt BCkt A

    Ckt B

    Click to Advance

  • 8/7/2019 Neutral Hazards

    11/18

    CktA

    CktB

    If You Break TheNeutral Bundle, It

    Will Become

    Energized From

    Circuit A(Click)You May See an Arc

    when disconnecting

    If You Contact The

    Neutral Conductor

    You May Feel A

    Shock.

    X

    AvoidAvoid

    Breaking TheBreaking The

    Neutral BundleNeutral Bundlein a Multiin a Multi--WireWire

    Branch Circuit!Branch Circuit!

    Click to Advance

  • 8/7/2019 Neutral Hazards

    12/18

    Use the following guidance when the neutral conductor must be interrupted:

    Treat the neutral as energized even though the circuit is locked out at the

    source. (Use PPE that is appropriate for the hazard, i.e. gloves and eye

    protection)

    Measure absence of voltage to ground immediately after lifting leads when

    more than one neutral is lifted from a device or when a splice is broken.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    13/18

    Use the following guidance when the neutral

    conductor must be interrupted:

    y If known, Lock out both / all load breakers.

    y If both circuit breakers in a multi-wire branch circuit are not known?

    o Test the neutral circuit with a clamp-on type current detector to identify

    if the neutral is carrying current before lifting neutral leads or breaking

    a neutral connection.

    NOTE: Current will exist only if one or more circuits sharing the neutral

    have a load energized at the time of measurement.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    14/18

    When a common neutral hazard is discovered at a device:

    y Stop work and remove the hazardous condition or plan a new work

    package considering known energized conductors.

    y It should be corrected by installation of pigtails or other means, to maintain

    continuity of the neutral wiring in accordance with NFPA 70 National

    Electrical Code.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    15/18

    Other general precautions include:

    Label the doors of lighting and power panels where common neutrals are

    known to exist. This will alert LOTO planners and workers of potential

    problems.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    16/18

    Other general precautions include:

    Provide instructions in work packages where common neutrals are known to

    exist to remind workers to be alert to wiring that may indicate a common

    neutral and to maintain neutral circuit continuity.

    Click to Advance

  • 8/7/2019 Neutral Hazards

    17/18

    Other general precautions include:

    Suspect a multi-wire branch circuit when three or more neutral conductors are

    spliced together in a junction box, outlet box, or lighting fixture.

    Click to Advance

    11

    33

    22

  • 8/7/2019 Neutral Hazards

    18/18

    Click to End Show

    Questions or Comments?Contact Bobby Gray orJerald Kinz

    Potential Hazards with

    Neutral Conductors