Neutral Earthing Final

download Neutral Earthing Final

of 29

Transcript of Neutral Earthing Final

  • 7/30/2019 Neutral Earthing Final

    1/29

    SYSTEM NEUTRAL EARTHING

    THE PURPOSE OF EARTHING

    A number of points from Generators to consumers installations are earthed (orGrounded).

    In our country we have an effectively grounded system.

    The purpose ofearthing is:

    To provide a low impedance path to facilitate satisfactory operation ofprotective schemes during fault conditions.

    To ensure that living beings in the vicinity of sub stations are notexposed to unsafe potentials under steady state or fault conditions.

    To retain system voltages within reasonable limits under faultconditions and ensure that insulation breakdown voltages are notexceeded.

    To provide an alternative path for induced current and there byminimize electrical noise in communication circuits.

    5/7/2013 1

  • 7/30/2019 Neutral Earthing Final

    2/29

    SYSTEM NEUTRAL EARTHING

    UNGROUNDED SYSTEM

    A system, circuit, or apparatus without an intentional connection toground.

    Though called ungrounded, this type of system is in reality coupled to

    ground through the distributed capacitance of its phase windings and

    conductors.

    In the absence of a ground fault, the neutral of an ungrounded systemunder reasonably balanced load conditions will usually be close to earth

    potential, being held there by the balanced electrostatic capacitance

    between each phase conductor and earth.

    GROUNDED SYSTEM

    A system of conductors in which at least one conductor or point(neutralpoint of transformer or generator windings) is intentionally grounded,

    either solidly or through an impedance.

  • 7/30/2019 Neutral Earthing Final

    3/29

    SYSTEM NEUTRAL EARTHING EFFECTIVELY GROUNDED SYSTEM

    Grounded through a sufficiently low impedance suchthat for all system conditions the ratio of zero sequencereactance to positive sequence reactance (X0 / X1) is

    positive and less than 3, and the ratio of zero sequenceresistance to positive sequence reactance (R0 / X1) ispositive and less than 1.

    The effectively grounded system permits the applicationof surge arresters with less than line- to- line voltageratings. Ground fault currents will be approximately ofthe same magnitude as threephase fault currents.

  • 7/30/2019 Neutral Earthing Final

    4/29

    SYSTEM NEUTRAL EARTHING Advantage of neutral grounding

    The system is not subjected to over voltage surges due toarcing grounds during earth faults as the current flowingthrough the neutral to ground connection will be almostequal and opposite to the capacitive current from healthy

    lines to ground.

    During a line to ground fault the voltage of healthy line donot increase beyond 3 times thenormal value.

    Earthing the neutral point secures maximum effectivenessof automatic protective gear immediately after an earthfault occurs.

  • 7/30/2019 Neutral Earthing Final

    5/29

    SYSTEM NEUTRAL EARTHING

    Advantage of neutral grounding

    Earth fault relaying is simple and isolation of faulty circuit is quickand fast.

    Earth fault can be located easily as compared with ungroundedsystem.

    Improved service reliability.

    Due to stable neutral point, the voltages are held nearer thedeclared voltages.

    The over voltage due to lightning is discharged to earth as an easyearth path is provided.

  • 7/30/2019 Neutral Earthing Final

    6/29

    SYSTEM NEUTRAL EARTHING

    Advantage of neutral grounding When solidly earthed, the voltage of any live conductorcannot exceed the voltage from line to neutral and neutral is

    held at earth potential(almost zero).

    It is possible to effect appreciable reductions in the insulation

    to earth of cables and over head lines and hence saving in

    cost.

    Similar insulation reductions can be made in major insulation

    of transformers by grading down from line terminal to the

    neutral point.

  • 7/30/2019 Neutral Earthing Final

    7/29

    SYSTEM NEUTRAL EARTHING

    Advantage of neutral grounding In EHV systems, on account of their electrostatic capacitance,the voltage of the two sound lines may, at the first instant of

    the fault, reach a value approaching twice the normal line

    voltage.

    If the neutral point is earthed, the induced static charges on

    lines are conducted to earth as they appear, and all danger to

    the insulation of the line and apparatus is removed.

    Therefore, no part of the system can reach more than line to

    neutral voltage. The insulation of line can be limited to the

    line to neutral voltage.

  • 7/30/2019 Neutral Earthing Final

    8/29

    SYSTEM NEUTRAL EARTHING

    EQUIPMENT GROUNDING

    Equipment grounding is different from system neutral grounding.

    Equipment grounding is to ground the non-current carrying parts withground connection.

    The objective of equipment grounding is ;

    1. To ensure freedom from dangerous electric shock voltage exposureto persons in the area.

    2. To provide current carrying capability both in magnitude andduration, adequate to carry ground fault current permitted by overcurrent protective system without creating a fire or explosive hazard.

    3. To contribute to better performance of the electrical system.

  • 7/30/2019 Neutral Earthing Final

    9/29

    SYSTEM NEUTRAL EARTHING

    5/7/2013 9

    SUB STATION EARTH

  • 7/30/2019 Neutral Earthing Final

    10/29

    SYSTEM NEUTRAL EARTHING

    5/7/2013 10

    SUB STATION EARTH

  • 7/30/2019 Neutral Earthing Final

    11/29

  • 7/30/2019 Neutral Earthing Final

    12/29

    SYSTEM NEUTRAL EARTHING

    Causes of over voltages

    Neutral displacement

    When a line to ground fault occurs, even on a solidlygrounded system, the line to ground voltage of the healthy

    phases increases because of the neutral displacement.

    For effectively grounded systems, during single line to groundfault, the voltage rise of the healthy phase (phase to neutral)

    is up to 80 % of the line to line voltage.

  • 7/30/2019 Neutral Earthing Final

    13/29

    SYSTEM NEUTRAL EARTHING

    Causes of over voltages

    Operation of switching and over current protective

    equipment.

    The operation of switches and over current protective devices

    produces a short time transient over voltage or switching

    surge.

    The normal operation of these devices will not produce

    voltages exceeding twice normal voltage.

    During switching of capacitors the voltage may rise to 2.5

    times the normal due to re-striking phenomenon

  • 7/30/2019 Neutral Earthing Final

    14/29

    SYSTEM NEUTRAL EARTHING

    Causes of over voltages Resonance effects

    Ferro resonance is another potential source of

    transient over voltages. In three phase circuits, singlephase switching can result in over voltages when

    ferroresonance occurs between the magnetising

    impedance of a transformer and the system

    capacitance of isolated phase or phases. The term ferro is used because of the steel core of

    the transformer.

  • 7/30/2019 Neutral Earthing Final

    15/29

    SYSTEM NEUTRAL EARTHING

    Causes of over voltages There is an external cause for over voltages due to

    the atmospheric conditions of lightning discharges-

    inter clouds, intra clouds and cloud to ground or line.

    These may be in the form of direct lightning strokes,and indirect lightning, i.e., induced strokes.

    Basically, lightning is a gigantic spark resulting from

    the development of millions of volts between cloudsor between a cloud and the earth. It is akin to the

    dielectric breakdown of a huge capacitor.

  • 7/30/2019 Neutral Earthing Final

    16/29

    A: Coupling driven effects B : Direct effectsC: Increases in site potential D : Direct conducted effects

    Effects of Lightning

  • 7/30/2019 Neutral Earthing Final

    17/29

    SYSTEM NEUTRAL EARTHING INSULATION CO-ORDINATION

    Transformers are subjected to over voltages.

    The insulation level of a transformer should co-ordinate with theprotective level of the surge arrester.

    Neutral grounding at each voltage level from generation to distributionis necessary from the view point of over voltages.

    The transformers experience the over voltage at power frequency andalso impulse voltage due to lightning and switching surges.

    Switching transients and travelling waves are the major cause for overvoltages.

    The surge arresters (lightning arresters) divert the transient overvoltages to earth and protect the transformer insulation.

  • 7/30/2019 Neutral Earthing Final

    18/29

    SYSTEM NEUTRAL EARTHING

    INSULATION LEVEL OF A TRANSFORMER

    Basic insulation level is a term which includes the

    following characteristics of a transformer;

    1. Power frequency voltage withstand level

    2. Lightning impulse voltage withstand level

    3. Switching impulse voltage withstand level

  • 7/30/2019 Neutral Earthing Final

    19/29

    SYSTEM NEUTRAL EARTHING

    Insulation co-ordination is correlation ofinsulation of equipment and circuit with thecharacteristics of protective devices such that theinsulation is protected from over voltages.

    The surge arrester provided for transformerprotection should spark over at a voltage lessthan the insulation withstand voltage of the

    transformer. In other words , the protectivedevice must have a lower break down voltagethan insulation to be protected.

  • 7/30/2019 Neutral Earthing Final

    20/29

    INSULATION COORDINATION

    Insulation coordination is the process ofbringing the insulation strengths of electrical

    equipment into the proper relationship with

    expected over voltages and with the

    characteristics of surge protective devices.

    The insulation withstand level of equipment is

    usually defined at three points through the

    use of the standard switching surge and the

    full wave(basic impulse insulation level BIL -)

    and the chopped wave tests.

  • 7/30/2019 Neutral Earthing Final

    21/29

    Intrument Transformers

    Lightning impulse test - Full wave (1.2/50 ms)

    100 %

    T

    90

    30

    T1

    T1=1,67 x ( t90 - t30 )

    50

    T2

    U

    t

    FrontQueue

    Simulates a lightning stroke

    overvoltage travelling along a HV

    transmission line

    Lighting impulse

    BIL

  • 7/30/2019 Neutral Earthing Final

    22/29

    Intrument TransformersSwitching impulse test (250/2500 ms)

    Tcr= 250 ms

    T2 = 2500 ms

    U

    t

    100 %

    Tcr

    Tc

    50

    T2

    90

    Simulates

    overvoltages resulting

    from line switching

    operations

  • 7/30/2019 Neutral Earthing Final

    23/29

    Intrument TransformersLightning impulse (chopped wave)

    U

    t

    100 %90

    30

    Tc

    a

    Imulse wave is

    chopped byusing sparking

    gaps after 2

    5 ms

    Simulates a flash over on an

    insulator resulting from a

    lightning stroke

    f

  • 7/30/2019 Neutral Earthing Final

    24/29

    Instrument transformers

    Lightning impulse - chopped on the front

    U

    t

    100 %90

    30

    Tc

    Tc < 1,2 ms

    Simulates a direct lightning on the

    transformer. The quick voltage

    increase provoke a floshover.

  • 7/30/2019 Neutral Earthing Final

    25/29

    INSULATION COORDINATION

    The insulation withstand of electrical

    equipment is generally quantified in terms of

    its basic impulse insulation level (BIL) which is

    based on tests made with a voltage surgerising to crest in 1.2 micro seconds and falling

    to half value in 50 micro seconds, which is

    denoted as a 1.2/50 wave. The three point method is usually applied for

    insulation coordination.

  • 7/30/2019 Neutral Earthing Final

    26/29

    INSULATION COORDINATION

    The minimum protective ratios recommended

    by ANSI and IEEE standards for satisfactory

    coordination are

    Switching-surge withstand

    ------------------------------------------------ >= 1.15

    Switching surge protection level

  • 7/30/2019 Neutral Earthing Final

    27/29

    INSULATION COORDINATION

    BIL

    ------------------------------------- >= 1.2

    Lightning protection level

    Chopped wave withstand------------------------------------------ >=1.2

    Front-of-wave protective level

  • 7/30/2019 Neutral Earthing Final

    28/29

    SYSTEM NEUTRAL EARTHING STANDARD VALUES OF WITHSTAND VOLTAGES

    Normal voltage kV Highest system

    voltage kV

    Impulse withstand

    standard wave kV

    (peak)

    One minute power

    frequency

    withstand kV (rms)

    11 12 75 35

    33 36 170 75

    66 72.5 325 140

    110 123 550 230

    132 145 650 275

    220 245 1050 450

    400 420 1550 680

  • 7/30/2019 Neutral Earthing Final

    29/29

    THANK YOU