Bonding & Earthing (Final)
-
Upload
vardaa-impex -
Category
Documents
-
view
274 -
download
1
Transcript of Bonding & Earthing (Final)
-
8/3/2019 Bonding & Earthing (Final)
1/67
-
8/3/2019 Bonding & Earthing (Final)
2/67
BONDINGBond means an electrical
connection between two or
more conductors or non currentcarrying metallic parts oftraction masts or structures or
supports and rails.
-
8/3/2019 Bonding & Earthing (Final)
3/67
Transverse Bond It means a bond
between two rails of a track or tworails of adjacent tracks.
Longitudinal BondIt is an electricalconnection across a rail jointbetween consecutive lengths of rails.
TYPES OF BOND
-
8/3/2019 Bonding & Earthing (Final)
4/67
Impedance Bond It is a bond
installed by signal and telecomdepartment, which provides a low
impedance path for the tractionreturn current and relatively highimpedance path for track circuit
current.
-
8/3/2019 Bonding & Earthing (Final)
5/67
Fig.1. Impedance Bond
-
8/3/2019 Bonding & Earthing (Final)
6/67
Fig.2. Impedance Bond
-
8/3/2019 Bonding & Earthing (Final)
7/67
Fig.3. Impedance Bond
-
8/3/2019 Bonding & Earthing (Final)
8/67
Structure Bond Bondconnecting the non-current
carrying metallic parts oftraction mast or structure or
support to the traction rail.
-
8/3/2019 Bonding & Earthing (Final)
9/67
Fig: Structure Bond
-
8/3/2019 Bonding & Earthing (Final)
10/67
Signal bond It is an electricalconnection across a rail joint,provided by the Signalling &
Telecommunication Department,to facilitate flow of track circuit
current.
-
8/3/2019 Bonding & Earthing (Final)
11/67
Terminal Bond It allows delimiting
the track circuit at a boundary with aninsulated Rail joints.
Cross Bond It means a bond
between two rails of a track or two
rails of adjacent tracks. It is also called
a transverse bond.
-
8/3/2019 Bonding & Earthing (Final)
12/67
INTEGRAL TRANSVERSAL LINK ( ITL )
It is interconnection of Dn line OPC,
BEC and Up line OPC, BEC and tracks
direct or through impedance bond.
This shall be provided at an
interval of 1 Km or less than one km.
-
8/3/2019 Bonding & Earthing (Final)
13/67
TYPICAL ARRANGEMENT
INTEGRAL TRANSVERSE LINK (ITL)
ABB LIMITEDALTERNATE ARRANGEMENT
INTEGRAL TRANSVERSE LINK ( TYPICAL LOCATION AT SUBHASH NAGAR FP)
AT SUBHASH NAGAR FP
-
8/3/2019 Bonding & Earthing (Final)
14/67
OVERHEAD PROTECTION CABLE (OPC)
It is an ACSR conductor run on traction masts or
structures or supports and clamped to their
metallic parts/supports and connected to earth
through ITL.
ACSR conductor consists of 7 steel wires and 12
aluminium wires each 2.5 mm dia .
Its cross sectional area is 93.3 sq mm andoverall diameter is 12.5mm.
Its tension should be 400kgf.
-
8/3/2019 Bonding & Earthing (Final)
15/67
BURIED EARTH CABLE (BEC)It is a flexible Copper Conductors having 7 strands
each of 2.5 mm ,35 sq mm x-sectional area and overall dia of 7.5 mm.
It is run along the viaduct with which all themetallic reinforcement steel bars of via duct, piers
parapet and equipments at viaduct are connected
to maintain proper earthing.
It is connected to earth to earth grid of Auxiliarysubstation through ITL
-
8/3/2019 Bonding & Earthing (Final)
16/67
PLINTH OR CONTINUITY JUMPER
An insulated stranded flexible copper
conductors of approx.35 sq mm is used forinter connecting two track plinth to maintaincontinuity.
The each end of deck is connected with theBEC for proper earthing.
-
8/3/2019 Bonding & Earthing (Final)
17/67
EARTHING
OF
ELECTRICL
SYSTEM
-
8/3/2019 Bonding & Earthing (Final)
18/67
WHAT IS EARTHING?Earthing is an essential requirement to drain the potential
deposition on any machine frame, structure, support,electrical installation etc due to poor insulation for
achieving a safe working upon.
E E
FAULT CURRENT THROUGH EARTH
LINK
FUSE
R
YB
N
230VFAULT TO
EARTH
IN WINDING
-
8/3/2019 Bonding & Earthing (Final)
19/67
WHY EARTHING?
Earthing is designed primarily to preserve the securityof the system by ensuring that the potential on each
conductor is restricted to such a value as is consistent
with the level of insulation applied.
Earthing shall generally be carried out in accordance
with the requirement of Indian Electricity rules1956(I.E.Rule 2003) & IS 30431987.
-
8/3/2019 Bonding & Earthing (Final)
20/67
OBJECTIVE OF EARTHING
It should stabilise circuit potential with respect toground potential and limit the potential rise.
It should protect men & materials from injury or
damage due to over voltage or touching.
It should provide a low impedance path to fault
currents to ensure prompt & consistent operation of
protective devices.
-
8/3/2019 Bonding & Earthing (Final)
21/67
It should keep the maximum voltage gradient
along the surface inside & around the substation
within safe limits during ground fault.
It should protect underground cables fromoverall ground potential rise & voltage gradient
during ground fault in the system.
-
8/3/2019 Bonding & Earthing (Final)
22/67
IMPORTANT I.E. RULE
RELATED TO EARTHING:
RULE No: 33.Earth terminal on consumers premises.
RULE No: 61.
(A) MAX: PERMISSIBLE RESISTANCE OFEARTHING SYSTEM.
Large power station: - 0.5 ohms.
Major sub-station: - 1.0 ohms.
Small sub-station: - 2.0 ohms.In all other cases : - 8.0 ohms.
The earth continuity: - 1.0 ohms.
inside an installation
-
8/3/2019 Bonding & Earthing (Final)
23/67
(B) CONNECTION WITH EARTH
Earthing of neutral conductor of a 3-phase, 4-wire
system.
Earthing of all metal casing / covering of electric supply
lines or apparatus.
Testing of such earth resistance not less than once in
every two years during a dry day of a dry season shall
be conducted and recorded.
Test results should be recorded and shall be made
available to the EIG or Assisting officer to EIG, when
required.
-
8/3/2019 Bonding & Earthing (Final)
24/67
RULE No: 67.
CONNECTION TO EARTH
All equipments associated with HV /EHV installation,
shall be earthed by not less than two distinct and
separate connection with the earth having its own
electrode, except an earth mat
Testing of such earth resistance not less than once inevery year during a dry day of a dry season shall be
conducted & recorded.
-
8/3/2019 Bonding & Earthing (Final)
25/67
RULE No: 90. EARTHING
In distribution system, all metal supports and allreinforced/pre-stressed cement concrete supports of
overhead line and and metallic fittings attached shall be
permanently and effectively earthed.
Each stay wire shall be similarly earthed, unlessinsulators have been provided in it at a height not less
than three mtrs from the ground.
Every 5th pole as a minimum shall be grounded, if the
foundations are not cements concrete blocks.
RULE N 91
-
8/3/2019 Bonding & Earthing (Final)
26/67
RULE No: 91.
SAFETY AND PROTECTIVE
DEVICE
Every overhead line erected over any part of street or
public place shall be protected with a device, approved
by the EIG, for rendering the line electrically harmless
in case it brakes.
The owner of every high and extra high overhead line,
shall be protected to the satisfaction of the EIG, to
prevent unauthorised persons from ascending any of
the supports of such overhead lines.
-
8/3/2019 Bonding & Earthing (Final)
27/67
RULE No: 92.
PROTECTION AGAINST LIGHTENING
The owner of every overhead line which is so exposed
, as may be liable to injury from lightening, shall
adopted efficient means for diverting to earth, any
electrical surge during lightening.
The earthing lead for any lightening arrester shall not
pass through any iron or steel pipe but shall be taken
as directed as possible from the lightening arrester to aseparate earthing electrode / mat.
-
8/3/2019 Bonding & Earthing (Final)
28/67
DISTINCTION BETWEEN
GROUNDING AND EARTHING
Grounding: Grounding implies connection of currentcarrying parts to ground.It is mostly either generator ortransformer neutral. Hence it is popularly called neutralgrounding.
Grounding is for equipment safety.
In case of resistance grounding system, it limits the core
damage in stator of rotating machines. In case of solidlygrounded system, substantial ground fault current flowsenabling sensitive fault detection and fast clearance.
-
8/3/2019 Bonding & Earthing (Final)
29/67
Earthing: Earthing implies connection of non currentcarrying parts to ground like metallic enclosures.
Earthing is for human safety.
Under balanced operating condition of power systems,earthing system does not play any role. But under anyground fault condition, it enables the ground faultcurrent to return back to the source without endengeringhuman safety.
-
8/3/2019 Bonding & Earthing (Final)
30/67
Generator Transformer
NG NG
Earthing
Neutral Grounding and Earthling
-
8/3/2019 Bonding & Earthing (Final)
31/67
Earth As Conductor:
Resistivity() of earth is typically 100-M.
Resistivity() of copper is 1.7x 10 -8-M.
Resistivity() of G. I. is 1.7x 10-7
-M.Take as reference, 25x4mm copper strip.
To obtain the same resistance, the size of G.I. Will be65x10mm.
The corresponding figure for earth is 800x800 meters (158
acres.)Hence, it shows metallic conductor is a preferred alternative
conductor to earth to bring the fault current back to source.
EARTH AS CONDUCTOR
-
8/3/2019 Bonding & Earthing (Final)
32/67
Generator Transformer
NG NG
Earthing
-
8/3/2019 Bonding & Earthing (Final)
33/67
ELECTROD RESISTANCE TO EARTH
Conventional practice by Electrical engineer to measure
the earth resistance is by using ohms law.
This is similar to CT, where the flow of primary current
results in voltage appearing across CT secondary. Which
drives the current through the connected relay(burden).
For electrode resistance to earth, current is injected to earth
by electrode and electric field travels through the earth.The
voltage appears at certain distance from electrode and the
resulting impedance is electrode resistance to earth.
-
8/3/2019 Bonding & Earthing (Final)
34/67
IF
CT RV
x
v1
Resistance area of driven earth rod
-
8/3/2019 Bonding & Earthing (Final)
35/67
HEMISPHERICAL ELECTORD
Consider a hemispherical electrode used for injection of
current.Current flows through a series of hemisphericalshells of earth of continuously increasing cross section.
The resistance offered by earth to spread of electrical field
is given by:
RX = dX / 2 X2.
The resistance as a function of distance from electrode.
The most interesting aspect is that almost 95% of final
resistance is contributed by soil within 5meters of the
electrode.
-
8/3/2019 Bonding & Earthing (Final)
36/67
dx
1
x
Spherical shells
Resistance to earth of hemispherical electrode
-
8/3/2019 Bonding & Earthing (Final)
37/67
Now consider two location A & B 100 Km apart from each
other with respect to earth grids.Assume current is
discharged at A. Only the soil within first 5 to 10 metersfrom A offers substantial resistance.
The resistance offered by earth subsequently to reach B is
very minimal.
This the reason of our practice to treat earth pits with lime ,
charcoal, & watering the pits. This reduces the resistance ofthe soil locally around the earth electrode. As the resistance
away from the earth electrode is minimal.
-
8/3/2019 Bonding & Earthing (Final)
38/67
100
90
80
70
60
50
40
30
20
10
00 5 10987621 3 4
4(-100MM)RadiusHemi-sphere
Distance in Met.
Resistancein%
RESISTANCE TO EARTH OF HEMISPHERICAL ELECTRODERESISTANCE TO EARTH OF HEMISPHERICAL ELECTRODE
INFLUENCING FACTORS FOR ELECTRODE
-
8/3/2019 Bonding & Earthing (Final)
39/67
INFLUENCING FACTORS FOR ELECTRODE
RESISTANCE
The major factor is the length.
Diameter or width(Cross section) has very minor influence.
The resistance of pipe electrode is given by:-
R = ( / 2 L) [ LN{ 8L / ( x 2.7183)}].Where, L = Length in Met.(pipe)LN=Nominal length(buried conductor)
= Diameter in MetLet, consider the case of a length = 6 Met.
For = 2.5Cm, R = 16.4 .
For = 10 Cm, R = 15.3.
-
8/3/2019 Bonding & Earthing (Final)
40/67
A horizontal earth strip of 75x10mm Cu and 45x10mm GI
both of same length will offer almost same electrode
resistance.
Other interesting observation is that the electrode resistance
is not much dependent on type of electrode materials like
Cu,Al or GI.Resistance is the function of physicaldimension, mainly length.
So, it is observed that 300% increase in diameter, resistance
decreases by app: 7% only.
-
8/3/2019 Bonding & Earthing (Final)
41/67
PLATE ELECTRODE
In early days only plate electrode were used.
It was presumed that to get low electrode resistance toearth,surface area should be large as per conventional ohms
law resistance.
In some cases efforts were made to cover the entire site
with plate electrode.
One solid plate & another annular ring both with same
radius of 50cm are taken for using as earth electrode.
Calculation shows that resistance to earth in both the cases
is 29.2 .
-
8/3/2019 Bonding & Earthing (Final)
42/67
Resistance for strip or horizontal wire electrode is
measured by RYDERs formula:-
R = ( / 2 L) [ LN(8L/T)+LN(L/h)- 2
+(2h/L)-(h2/L2)].
Where,
L = Length in Met.(electrode)
LN=Nominal length(buried conductor)
h = Depth in Met.
T = Width in Met.(for strip).
= 2 x diameter in Met.(for wire)
-
8/3/2019 Bonding & Earthing (Final)
43/67
-
8/3/2019 Bonding & Earthing (Final)
44/67
1 MET
5 CM
50 CM50 CM
RESISTANCE TO EARTH OF PLATE ELECTRODE
-
8/3/2019 Bonding & Earthing (Final)
45/67
Similarly, one plate electrode & one strip electrode of
same volume are taken. But resistance to earth of plate
electrode is almost three times that of strip electrode.
The linear dimension of plate electrode is perimeter,
i.e,4M., where as for strip electrode is 13M.
Hence, hypothesis is that electrode resistance is
dominated by length of the electrode buried.
Thus, it is concluded that plate electrode is inefficient.
-
8/3/2019 Bonding & Earthing (Final)
46/67
1 M
75 mmX 8 mm X 13.3M
0.008M3
REL= 9. 5
1 M
P =100 -M
1 M X 1M X 8 mm
0.008M3
REL = 26..2
-
8/3/2019 Bonding & Earthing (Final)
47/67
PARALLEL ELECTRODES
To obtain low effective earth grid resistance, electrodes are
connected in parallel. So that the total resistance will be halfof individual resistance.
This is again due to our extrapolation of conventional ohms
law concept. But it is true only when the separationdistance between electrodes are adequate.
For discharging the field effectively, each electrode needs
exclusive soil below it. If the rods are too close, resistance
area of one electrode will interfere with that of other and
expected gain is not realised. As a thumb rule if the rod
length is L, separation distance shall be 2L.
-
8/3/2019 Bonding & Earthing (Final)
48/67
I
Over lapping resistance areas of two earth rods
-
8/3/2019 Bonding & Earthing (Final)
49/67
L
Separation distance
2L
I
SEQUENCE IMPEDANCE TRANSMISSION LINE
-
8/3/2019 Bonding & Earthing (Final)
50/67
SEQUENCE IMPEDANCE TRANSMISSION LINE
The values can be obtained from any line parameter
evaluation program considering one circuit or bothcircuit. S/C D/C
ZPOS(ohm/Km) 0.15 + j 0.41 0.08 + j 0.22
ZZERO(ohm/Km)0.37 + j 1.29 0.29 + j 1.04Positive sequence impedance of D/C line is almost 0.5
times of S/C as expected. But Zero sequence impedance
of D/C line is only about 0.8 times of S/C line.This is
because positive sequence does not involve earth returnbut zero sequence involves earth return.Only if the separation distance is large enough, they will
behave like two single circuit line. This is seldom
achieved in practice.
RESISTANCE OF EARTH GRID
-
8/3/2019 Bonding & Earthing (Final)
51/67
RESISTANCE OF EARTH GRID
In EHV switchyard, earthing grid is formed by a mesh
of horizontal strip electrode & vertical rod electrode.
The resistance to earth of the entire grid is calculated
by SVERAK formula :
RG = C1 +C2 1+(1/C3) .C1 = 1/L; C2 = 1/ 20A ; C3 = 1+ h 20/A.A = Area of earthing grid.
L = total length of buried conductor includingrod electrode in Meter.
= resisvity in ohm-meter.
-
8/3/2019 Bonding & Earthing (Final)
52/67
h
Switchyard earthing grid
METHODS TO REDUCE ELECTRODE
-
8/3/2019 Bonding & Earthing (Final)
53/67
METHODS TO REDUCE ELECTRODE
RESISTANCE TO EARTH
1.To reduce soil resistivity() to a low value.Typical values for different type of soil:
Soil type Wet Moist Dry Bed rock
( in -M) 10 100 1000 10,000Treatment of soil--- such as watering, adding cock,
wood charcoal, bentonite clay, common salt.
After treatment there is a gradual decrease in soil
resistivity, However there will be gradual increase in soil
resistivity with passage of time as salt is washed away by
continual water seepage.
-
8/3/2019 Bonding & Earthing (Final)
54/67
200
160
120
80
40
0
025 40353010
5 15 20
Resistance,o
hm-Met
Months
Before Treatment
EFFECT OF ARTIFICIAL TREATMENTEFFECT OF ARTIFICIAL TREATMENT
After Treatment
After
Retreatment
-
8/3/2019 Bonding & Earthing (Final)
55/67
Second method is to increase the length of
buried conductor to the maximum extent
possible, the increase in cost has to be borne at
the beginning budget.
If parallel electrodes are considered for
individual earth pits to get low resistance, it
must be emphasized that unless sufficient
spacing exists between electrodes,desired
reduction in earth resistance is not realized in
practice.
ELECTRODE SIZING
-
8/3/2019 Bonding & Earthing (Final)
56/67
ELECTRODE SIZING
The choices for materials & size are only with respect to the
amount of fault current to be discharged to earth.
The current density(A/mm2)as per IS-3043.
Materials Cu Al GI
0.5 sec rating 290 178 113
1 sec rating 205 126 80
Earthing grid for EHV switchyards are designed for 0.5 sec duty
& for others 1sec duty is selected.
HUMAN ELEMENT & ELECTRIC SHOCK
-
8/3/2019 Bonding & Earthing (Final)
57/67
HUMAN ELEMENT & ELECTRIC SHOCK
Electric shock is possible only when the human bodybridges two points of unequal potential.
This is the reason why a bird can sit comfortably on a220kv
line conductor without getting electrocuted as the voltagebetween its leg (IR drop) is insignificant.
Max: tolerable current for human body is 160mA for one
second.If this limit exceeds, it will result in death due to
ventricular fibrillation(heart attack)
Allowable body current IB(Amperes) for two body weights,
-
8/3/2019 Bonding & Earthing (Final)
58/67
as per IEEE Std:-80. is given:
IB = 0.116/TS for body weights of 50kg.= 0.157 /TS for body weight of 70kg.
TS =duration of current exposure (fault clearance time).
TS IB ( 50kg) IB (70kg).0.2sec 259mA 351mA.
0.5sec 164mA 222mA.
1.0sec 116mA 157mA.
Average value for human body resistance under dry
condition is 8 to 9k-ohms. But for design purpose, assumed
as 1k-ohm.
-
8/3/2019 Bonding & Earthing (Final)
59/67
GROUND POTENTIAL RISE
Ground potential rise(GPR) is the voltage to which theearth mat is going to rise when it discharges the
current.
If IG is the current discharge to earth & RG is the
earth grid resistance,
GPR = IG X RG,
IG = K x IF ( IF is the fault current).
IG is always not equal to fault current.
FAULT IS WITHIN THE SWITCHYARD & TRANSFORMER
-
8/3/2019 Bonding & Earthing (Final)
60/67
CONNECTION IS STAR-DELTA.
Here, entire fault current is discharged to earth to return to
source 2. In this case K = 1.
Source 2Source 1 Switchyard
IF
IF
IG = IF
Fault within sub-station (star-delta)Fault within sub-station (star-delta)
FAULT IS WITHIN THE SWITCHYARD & TRANSFORMER IS
-
8/3/2019 Bonding & Earthing (Final)
61/67
CONNECTED IN DELTA- STAR.
Part of the fault current (IF1) returns to local transformer via metallic
conductor ( earth mat) and does not contribute to GPR. The other part
(IF2) is discharged to earth to return to source2 and contributes to GPR.
In this case, K
-
8/3/2019 Bonding & Earthing (Final)
62/67
CONNECTION IS DELTA-STAR.
Part of fault current (IF1) returns to transformer at source 1 via earth & contributes
to GPR. The other part IF2 returns to source2 via earth & contributes to GPR at the
other switch yard. Where K
-
8/3/2019 Bonding & Earthing (Final)
63/67
STEP & TOUCH POTENTIAL
Step & touch potential refer to the potential experienced by a
person standing on a surface when earth mat buried, say
750mm, below surface has risen to GPR.
Step potential is the difference in surface potential experiencedby a person bridging a distance of 1 meter with his feet
without contacting any other grounded object.
Touch potential is the difference between GPR & the surface
potential at the point where person is standing, while his hand
is in contact with grounded structure.
-
8/3/2019 Bonding & Earthing (Final)
64/67
Touch and step potentials
IG
RGPF = 2R
RGPF= R/2
RR RR Gravel
VTOUCH
VTSTEP
Soil
-
8/3/2019 Bonding & Earthing (Final)
65/67
If resistance offered by each foot is R,
Then for step potential the resistance is 2Rwhile for touch potential is R/2
Touch potential is the difference between
GPR & surface potential while step
potential is the difference between twosurface potential
-
8/3/2019 Bonding & Earthing (Final)
66/67
EFFECT OF THIN LAYER OF
CRUSHED ROCK
In outdoor switchyard,a thin layer of crushed
rock is spread on the surface.
The resistivity of gravel ( ) is 2000 -M whilethat of soil is 100 -M. Since of gravel is high ,only a high voltage can force the current throughthe body to cause injuries. The gravel act like
insulator & throws the electric field generated
by GPR back to soil.
-
8/3/2019 Bonding & Earthing (Final)
67/67