Rev. 052313 AL1002ULADAJ NAC Power Extender Installation Guide (See Application Guide for additional information) Altronix Corp. 140 58th St. Brooklyn, NY

Transcript of NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender....

Page 1: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

Rev. 052313

AL1002ULADAJNAC Power Extender

Installation Guide(See Application Guide for additional information)

Altronix Corp.140 58th St. Brooklyn, NY

Page 2: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

- 2 - AL1002ULADAJ

Agency Listings:• ULListedControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuildingsApproved.• CSFM-CaliforniaStateFireMarshalApproved.• FM-FactoryMutualApproved.• NFPA72Compliant.Input:• Powerinput120VAC60Hz,5amp.• Two(2)ClassA,StyleZortwo(2)ClassB, StyleW,YFACPinputs.• Two(2)NCdrycontacttriggerinputs.Output:• Class2Ratedpower-limitedoutputs.• 24VDC@10ampmaxtotalalarmcurrent.• 2.5ampmaxcurrentperoutput.• Separate1.0ampauxiliaryoutput.• Programmablesupervisedindicatingcircuitoutputs: Four(4)ClassB,StyleW,YorTwo(2)ClassA, StyleZorOne(1)ClassA,StyleZandTwo(2)ClassB, StyleW,Y(see Application Guide).•Thermalandshortcircuitprotectionwithautoreset.Battery Backup:•Built-inchargerforsealedleadacidorgeltypebatteries.•Automaticswitchovertostand-bybatterywhen ACFails.• Zerovoltagedropwhenswitchingoverto batterybackup.

Supervision: •ACfailsupervision(form“C”contact,1amp/28VDC). Factorysetfor1.5hourswithoptional30seconds delaysetting(fieldselectable).• InstantlocalACtroublereportingrelay (form“C”contact,1amp/28VDC).•Batterypresenceandlowbatterysupervision (form“C”contact,1amp/28VDC).Visual Indicators: •InputandoutputstatusLEDindicators.Special Features:• 2-wirehorn/strobeSyncmodeallowsaudible notificationappliances(horns)tobesilenced whilevisualnotificationappliances(strobes) continuetooperate.• SyncprotocolsincludePotter/Amseco,Faraday, Gentex®,SystemSensor®,andCooperWheelock®.• TemporalCode3,SteadyMode,InputtoOutput FollowerMode(maintainssynchronizationof notificationappliancescircuit).• Compatiblewith12VDCor24VDCfirepanels.•Outputloopsupervisionsteeredtoinput1orinput2.• Signalcircuittroublememory(helpsidentify intermittentloopproblems).• Commontroubleinputandoutput.• Groundfaultdetection.•Unitincludespowersupply,redenclosure,camlock, andbatteryleads.Enclosure Dimensions (approx. H x W x D):18”x14.5”x4.5”(457.2mmx368.3mmx114.3mm).

Overview:TheAltronixAL1002ULADAJisanextremelycosteffective10ampremotepowersupply/batterycharger.Itmaybecon-nectedtoany12or24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupportsystemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,YorClassA,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputforfour(4)-wiresmokedetectorsisavailable.The10ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputisratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput.i.e.MarchTimeInput,MarchTimeOutput).Innon-alarmconditionindependentloopsupervisionforClassA,StyleZand/orClassB,StyleW,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedviathesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals(NC,C,NO)whichareusedtoindicategeneralloop/systemtrouble.AcommontroubleinputisprovidedforoptionalNC(normallyclosed)devicestoreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionandpowerdeliverytoanycombinationofthefour(4)outputs.

Note:TheinformationinthisdocumentisvalidformodelsAL1002ULADAJandAL1002UL2ADAJ.ModelAL1002ULADAJisequivalenttomodelAL1002UL2ADAJ.

Specifications:

AL1002ULADAJ - NAC Power Extender

Page 3: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

AL1002ULADAJ - 3 -

Power Supply Specifications:AC Input: 120VAC60Hz,5ampsuppliedbyamaximum15ampdedicatedbranchcircuit.

Output:Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmaximumcurrent.One(1)aux.specialapplication24VDCpoweroutputcircuit1amp,non-supervisedtotaloutputcurrentmustnotexceedcurrent10ampinAlarmCondition.

Battery:Usetwo(2)12VDC/12AHortwo(2)12VDC/7AHbatteriesconnectedinseries.

Stand-by/Alarm Current Consumption:

130mA/300mA

EOL Resistor (end of line): 2.2K(2200ohm),AltronixModel#AL-EOL22(included).Ground fault maximumtest impedance:

1000ohm.

Stand-by Specifications:

Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output24VDC/7AH 24Hours 10amp/5minutes ---

24VDC/12AH(usetwo(2)12VDCbatteriesinseries)

24Hours 10amp/5minutes 50mA

24VDC/36AH 24Hours 10amp/5minutes 1ampNote: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 10 amp total alarm current (example: AUX = 1 amp, outputs up to 9 amp).

Installation Instructions:WiringmethodsshallbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/ANSI,andwithalllocalcodesandauthoritieshavingjurisdiction.Productisintendedforindooruseonly. Carefully review: Application Guide for AL802ULADAJ, AL1002ULADAJ Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3) Output Programming Selection Table (pg. 4) Sync Mode Selection Table (pg. 4) Terminal Identification Table (pgs. 5-6) LED Status Indication Table (pg. 6)1.Mountunitinthedesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholesinthe enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s upperkeyholesoverthetwoupperscrews;levelandsecure.Markthepositionofthelowertwoholes.Removethe enclosure.Drillthelowerholesandinstalltwofasteners.Placetheenclosure’supperkeyholesoverthetwoupper screws.Installthetwolowerscrewsandmakesuretotightenallscrews(Enclosure Dimensions, pg. 12). Secureenclosuretoearthground(Fig. 1, pg. 3).2. Connectgreenleadtoearthground (Fig 1).Connecttheline(L)andneutral(N)terminalstoaseparateunswitched ACcircuit(120VAC,60Hz)dedicatedtotheFireAlarmSystem.3. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.4. Connectbatterytotheterminalsmarked[+BAT--]onthePowerSupplyBoard(batteryleadsincluded). Note:IfbatteriesbeingusedinyourinstallationdonotfitintotheAL1002ULADAJunit,itisrequiredtoinstalla separateenclosure,ULListedforappropriateapplication.Separatebatteryenclosureisrequiredtohave50cubicinches ofadditionalopenspace.AllwiringmethodsshallbeinaccordancewiththeNationalElectricalCode NFPA70/NFPA72/ANSIandwithalllocalcodesandauthoritieshavingjurisdiction.Batterycircuitsarenotpower- limited;provide0.25”spacingfrompower-limitedcircuitsanduseseparateknockout.Ifadditionalbatteryenclosure isrequired,itmustbeULListedfortheapplicationandmountedwithin5’oftheAL1002ULADAJenclosureinthe sameroom;minimum12AWGwireinappropriateconduitisrequiredforconnection.Whenusingconduit,make sureitisinstalledinamannerwhereitcannotturn.5.Setoutputselectionswitchesmarked[OUT1throughOUT4]tofollowcorrespondinginput[IN1&IN2]and desiredoutputsignaltype (Output Programming Selection Table, pg. 4).

L G Nline

ground

neutral

Fig. 1

Page 4: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

- 4 - AL1002ULADAJ

6.ConnectFACPoutputtothedesiredAL800LGKlogicboardinputs,andnotificationappliancestothedesired AL800LGKlogicboardoutputs(see Application Guide). Note:The2-wirehorn/strobesyncmodewillonlysynchronizehorns,horn/strobes,strobeswith synchronizationcapability.7.Forconnectionofsmokedetectors,digitaldialerseeOptional Hookup Diagram, pg. 7.

Class A, Style Z Class B, Style W, Y, SW1 & SW2 Settings:• ForallClassB,StyleW,Y,hookupsSW1&SW2ontheAL800LGKlogicboardmustbeopen. ForallClassA,StyleZhookupsSW1&SW2ontheAL800LGKlogicboardmustbeclosed.

Output Programming Selection Table:Outputs must be programmed independently (OUT1 - OUT4)

FunctionSwitch Positions

DescriptionsON OFF

InputtoOutputFollowerMode 1 2,3Outputfollowssignalitreceivesfromthecorrespondinginput(i.e.FACPSyncmodule-maintainssynchronizationofnotificationappliancecircuit).

TemporalCode3Mode 3 1,2EnablesTemporalCode3signalgenerationoutput.Thismodewillacceptasteadyorapulsinginput.

SteadyMode 1,2,3Asteadyoutputsignalwillbegenerated.Thismodewillacceptsteadyorpulsinginput.

For the above modes Dip Switch 4 determines which Input controls the corresponding output:Switch 4 in the ON position causes output(s) to be controlled by input 1.Switch 4 in the OFF position causes output(s) to be controlled by input 2.

Sync Mode Selection Table:

FunctionSwitch Positions

DescriptionsON OFF

AmsecoSyncMode*

1,3,4 2

ThismodeisdesignedtoworkwiththeAmsecoseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

FaradaySyncMode*

2,4 1,3

ThismodeisdesignedtoworkwiththeFaradayseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

Gentex®

SyncMode*GentexisaregisteredtrademarkofGentexCorporation.

1,2,3,4

ThismodeisdesignedtoworkwiththeGentex®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

SystemSensor®SyncMode*SystemSensorisaregisteredtrademarkofHoneywell.

1,2,4 3

ThismodeisdesignedtoworkwiththeSystemSensor®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

CooperWheelock®

SyncMode*CooperWheelockisaregisteredtrademarkofCooperWheelock.

2,3,4 1

ThismodeisdesignedtoworkwiththeCooperWheelockseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

*Note:TheAL1002ULADAJwillonlysynchronizehorns,horn/strobesandstrobesthatcontainsynchronizationcapabilityContactsignalmanufacturerformoredetailedinfo.Thesamesynchronizationmodemustbeselectedforalloutputs.

(AL800LGK Board)Output Dip Switches

INPUT SELECTTEMPORAL

STROBE SYNCIN>OUT SYNC

Page 5: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

AL1002ULADAJ - 5 -

Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.

Amount of Notification Appliances per unit:Amseco 27perNAC* SystemSensor® 32perNAC*Faraday 39perNAC* CooperWheelock® 32perNAC*Gentex® 32perNAC*

*Not to exceed a maximum of 2.5 amp per NAC.

Terminal Identification Table:AL800LGK Logic Board

TerminalLegend Function/Description

IN1+,IN1-IN2+,IN2-(Supervised)

Theseterminalsconnecttothe12VDCor24VDCFACPnotificationappliancecircuitoutputs. (ClassA,StyleZorClassB,StyleW,Y)Inputtriggervoltageis8-33VDC@5mAmin.Terminalpolarityisshowninalarmcondition.Duringanalarmconditiontheseinputswillcausetheselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4). AtroubleconditiononanoutputloopwillcausethecorrespondinginputtotriptheFACPbyopeningtheFACPloop.Analarmconditionwillalwaysoverridetroubletodrivenotificationappliances.

RET1+,RET1-RET2+,RET2-(Supervised)

For(ClassA,StyleZhookupstheseterminalpairsreturntoFACPNAC1and/orNAC2.ForClassB,StyleW,YhookupstheFACPEOLresistorfromtheNAC1and/orNAC2outputsareterminatedattheseterminals.

C“DRY1”NC C“DRY2”NC (Dryinputtrigger)

Anopenacrosstheseinputs,willcausetheselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4).Notetheseinputsareunidirectionalandwillnot reportatroubleconditiontotheFACP.

+OUT1--+OUT2--+OUT3--+OUT4--(Supervised)

Notificationappliancesareconnectedtotheseregulatedoutputs (see Application Guide pg. 2-4). Eachpower-limitedoutputwillsupply2.5amp.Totalsupplycurrentis10amp(see note below). Outputsarecontrolledbydesignatedinput1[IN1]orinput2[IN2](Output ProgrammingSelection Table, pg. 4). Maximumlinelossorvoltagedrop(testedwith2.5V).

C“FAULT”NC(Commontroubleinput)

Anopencircuitacrossthispairofterminalswillcause[IN1andIN2]tosimultaneouslysignalatroubleconditionbacktotheFACP(TypicallyusedtoreportACorBATFail).(form“C”contact1amp/28VDC)(Fig. 2, pg. 7).

NC,C,NO(Commontroubleinput)

Thesearedrycontacttroubleoutputsthatfollowanygeneralloop/systemtroubleconditions.(Typicallyusedtotriggeradigitalcommunicatororotherreportingdevice).(form“C”contact1amp/28VDC0.35PowerFactor)(Fig. 2, pg. 7) .

--AUX+Thisseparate1ampmaxauxiliarySpecialApplicationPoweroutputcircuitistypicallyusedto power4-wiresmokedetectors.Seeattachedlistofdevices(Appendix A, pgs. 10-12).

+DC-- 24VDCfrompowersupply.

Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 10 amp total alarm current (example: AUX = 1 amp, outputs up to 9 amp).

Page 6: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

- 6 - AL1002ULADAJ

Terminal Identification Table:Power Supply Board*Terminal Legend Function/DescriptionL,N Connect120VACtotheseterminals:Ltohot,Ntoneutral.-DC+ 24VDC@10ampinalarmnonpower-limitedoutput.

ACFAILNO,C,NC

Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.

ACLOCALNC,NO,C

Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.

BATFAILNO,C,NC

Form“C”drycontactsusedtosignallowbatteryvoltageorlossofbatteryvoltage.UndernormalconditionsterminalsmarkedNOandCareopen,NCandCareclosed.DuringatroubleconditionterminalsmarkedNOandCareclosed,andNCandCareopen(Fig. 3, pg. 8).

+BAT- Stand-bybatteryinput(leadsprovided)(Fig. 3, pg. 8).

*Power Board Parameter Specifications:• ACFailconditionwillreportapproximately1.5hoursafterlossofAC.TosetACDelayto30seconds,powertheunit down(ACsupplyandBattery)priortochangingswitchposition.• OpenSwitch“ACDelay”orclose“ACDelay”switch,respectively.• Lowbatteryconditionwillreportatapproximately20VDC.• Batterypresencedetectionwillreportwithin180secondsafterbatteryremainsundetected(missingorremoved). Arestoredbatterywillreportwithin30seconds.

LED Diagnostics:Power Supply BoardRed (DC) Green (AC) Power Supply StatusON ON Normaloperatingcondition.ON OFF LossofAC,Stand-bybatterysupplyingpower.OFF ON NoDCoutput.OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.

AL800LGK - Logic BoardLED OFF ON BLINK (LONG)* BLINK (SHORT)**ON Normal AlarmCondition TroubleCondition TroubleConditionMemoryON Normal AlarmCondition TroubleCondition TroubleConditionMemoryOFF Normal AlarmCondition TroubleCondition TroubleConditionMemoryOFF Normal AlarmCondition TroubleCondition TroubleConditionMemoryInput1 Normal AlarmCondition TroubleCondition ---Input2 Normal AlarmCondition TroubleCondition ---Fault Normal AlarmCondition --- ---

* Indicatescurrenttroublecondition.Whentrouble(open,shortorground)occursonaspecificoutput,the correspondingredoutputLED,[OUT1-OUT4]willblink.ThecorrespondinggreeninputLEDwill blinkaswell.Looptroublewillreportwithin30seconds.

**Indicatestroubleconditionmemory.Whenatroubleconditionrestores,theunitsredoutputLED,[OUT1-OUT4] willblinkwithashorteranddistinctlyadifferentduration.ThegreeninputLEDswillbeoff(normalcondition). Toresetthememorydepresstheresetbutton(Fig. 2c, pg. 7).TheLED(s)willextinguish.Note:Ifindicatingcircuitshavebeenrestored,memoryresetisnotrequiredfornormaloperationoftheunit.

Page 7: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

AL1002ULADAJ - 7 -

NEC Power-Limited Wiring Requirements for AL1002ULADAJ Models:Power-limitedandnonpower-limitedcircuitwiringmustremainseparatedinthecabinet.Allpower-limitedcircuitwiringmustremainatleast0.25”awayfromanynonpower-limitedcircuitwiring.Furthermore,allpower-limitedcircuitwiringandnonpower-limitedcircuitwiringmustenterandexitthecabinetthroughdifferentconduits.Onesuchexampleofthisisshownbelow.Yourspecificapplicationmayrequiredifferentconduitknockoutstobeused.Anycon-duitknockoutsmaybeused.Forpower-limitedapplications,useofconduitisoptional.AllfieldwiringconnectionsmustbemadeemployingsuitablegaugeCMorFPLjacketedwire(orequivalentsubstitute).OptionalbatteryenclosuremustbemountedadjacenttothepowersupplyviaClass1wiringmethods.Note:RefertowirehandlingdrawingbelowfortheproperwaytoinstalltheCMorFPLjacketedwire,(Fig, 2a).

Fig, 2

Fig, 2a

ExternalJacketedShield

Incorrect WireHandling

Correct WireHandling

Pull backexternal jacketedshield approx. 1/2”.

WireInsulation

Solid CopperConductors

120VACInput60Hz

(nonpower-limited)

SupervisoryConnections(power-limited)non-supervised

Aux.Output(power-limited)non-supervised

NACCircuits(power-limited)supervised

SignalingCircuitsfromFACP(nonpower-limited)

supervised

BatteryConnections(nonpower-limited)supervised

Page 8: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

- 8 - AL1002ULADAJ

Optional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to reportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional supervisorymonitoring. ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 3a, pg. 8)tothe commontroubleinput.2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule). Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.4- ACLocal[NC,NO,C]shouldconnecttothehostcontrolpanelforlocalannunciationof thetroublecondition. Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 3b, pg. 8).

Optional Hookup Diagram:Fig. 3

Maintenance:Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel(26.2-26.4VDC recommended range).Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltagebothatbatteryterminalandattheboardterminalsmarked[+BAT--]toensurethatthereisnobreakinthebatteryconnectionwires.Fuses:Checkinputandoutputfusesonthepowersupplyboard,replaceifnecessary.Inputfuseratingis6.3amp@250V,Outputfuseratingis15amp@32VNote:Maximumchargingcurrentis1.5amp.Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.

These circuits are used to monitor AC andBat Fail and will cause a simultaneous trouble

condition to the FACP's IN1 and IN2 (Non-Supervised)

4-wire SmokeDetector

+

--

+

--

4-wire SmokeDetector

Fire AlarmControl Panel

(FACP)

EOL PowerSupervision Relay

(Not Supplied)

EOLResistor

from FACP

SW1

-- DC +

SW2

+ OUT1 --

OUT1 OUT2 OUT3 OUT4

INP1 INP2

FAULT

NC

C N

O

C "F

AULT

" N

C

OUT1 OUT3

OUT2 OUT4INPUT SELECT

TEMPORALSTROBE SYNC

IN > OUT SYNC

IN1+ IN1-- IN2-- IN2+ C "DRY1" NC RET1+ RET1-- RET2-- RET2+ C "DRY2" NC

+ OUT2 -- + OUT3 -- + OUT4 --

INPUT SELECTTEMPORAL

STROBE SYNCIN > OUT SYNC

-- AUX +

UPPER TERMINALSLOWER TERMINALS

Addressable ControlModule Trigger Output

See Note 2(Non-Supervised)

RESET

Supervised

Non-Supervised Input fromPower Supply

BAT

FAIL

AC F

AIL D

CA

C

AC D

ELAY

NC C NO NC C NOAC

LOC

AL NC C NOL N

6.3A

250

V

Digital Communicatoror Local AnnunciatorDry output Contact(Form "C" contacts)

Power-Limited Outputs2.5 amp per output in alarm

Total = 10 amp(Supervised)

AC

FAIL

NC

C N

OB

AT

FAIL

NC

C N

O

Fig. 3a

-- DC +

OUT1 OUT3

OUT2 OUT4 INPUT SELECT

TEMPORAL STROBE SYNC

IN > OUT SYNC

INPUT SELECT TEMPORAL

STROBE SYNC IN > OUT SYNC

RESET

Fig. 3cTroubleMemoryResetButton

Fig. 3bCommontroubleInput/Output

NC

CN

OC

"FA

ULT

" N

C

Page 9: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

AL1002ULADAJ - 9 -

Battery Calculation Worksheet

DeviceNumber of Devices

Current per DeviceStand-by Current

Alarm Current

Foreachdeviceusethisformula: Thiscolumn x Thiscolumn = Equals Currentpernumberofdevices.

AL1002ULADAJ(Currentdrawfrombattery)

1Stand-by: 130mA 130mA

Alarm: 300mA 300mA

A AL1002 Current 130mA 300mA

AuxiliaryDevices Refertodevicemanualforcurrentratings.

Alarm/Stand-by mA mA mA

Alarm/Stand-bymA

mA mA

Alarm/Stand-by mA mA mA

B Auxiliary Devices Current (must not exceed 1 amp)

Refertodevicemanualforcurrentratings.

Alarm: mA 0mA mA

Alarm:mA

0mA mA

Alarm: mA 0mA mAAlarm:

mA 0mA mA

C NotificationAppliancesCurrent must notexceed10amp(10000mA) 0mA mA

D Totalalarmcurrent mA mA

E Totalcurrentratingsconvertedtoamperes(lineDx.001) A A

F Numberofstandbyhours(24forNFPA72,Chapter1,1-5.2.5). H

G MultiplylinesEandF. Totalstand-byAH AH

HAlarmsoundingperiodinhours.(Forexample,5minutes=.0833hours.)

H

I MultiplylinesEandH. TotalalarmAH AH

J AddlinesGandI. Totalstand-byandalarmAH AH

KMultiplylineJby1.30.(30%extrainsurancetomeetdesiredperformance)Totalampere-hoursrequired

AH

Unitsarecapableofrecharging36AHbatterymax.Iftotalampere-hourrequiredexceeds36AH,decreaseAUXcurrenttoprovideenoughstand-bytimefortheapplication.

Page 10: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

- 10 - AL1002ULADAJ

Appendix A - UL Listed Compatible Devices

A.1 Four (4) Wire Smoke Detectors

TableA-1belowlistsfour(4)wiresmokedetectorscompatiblewithAL1002ULADAJAUXoutput.

Smoke Detector/Base Detector Type Max StandbyCurrent (mA)

AlarmCurrent (mA)

FenWalCPD-7021(w/70-201000-005Base) Ionization 0.10 *FenWalPSD-7125 Photoelectric 0.10 *FenWalPSD-7125(w/70-201000-005Base) Photoelectric 0.10 *Fire-LiteBLP-12-4W Base * *Gentex824 Photoelectric 0.50 *Gentex824T Photoelectric 0.50 *Gentex824CP Photoelectric 0.50 *Gentex824CPT Photoelectric 0.50 *HochikiHSC-4R Base * *HochikiSPB-24 ProjectedBeam 0.25 *SystemSensorB112LP Base 0.12 36SystemSensorB114LP Base * *SystemSensorB404B Base * *SystemSensorDH100ACDC Photoelectric 0.15 0.70SystemSensorDH100ACDCLP Photoelectric 0.15 0.70SystemSensorDH100ACDCLPW Photoelectric 0.15 0.70SystemSensorDH400ACDCI IonizationDuct 25 95SystemSensorDH400ACDCP PhotoelectricDuct 25 95SystemSensor1112/24/D Ionization 0.05 50SystemSensor1424 Ionization 0.10 41SystemSensor1451(w/B402BBase) Ionization 0.10 39SystemSensor2112/24ATR Photoelectric 0.50 60/70SystemSensor2112/24AITR Photoelectric 0.50 60/70SystemSensor2112/24/D Photoelectric 0.05 50SystemSensor2112/24R Photoelectric 0.50 60/70SystemSensor2112/24TR Photoelectric 0.50 60/70SystemSensor2112/24T/D Photoelectricw/135oThermal 0.05 50

SystemSensor2112/24TSRB Photoelectricw/135o

ThermalSupervisoryRelay 15 45

SystemSensor2312/24TB Photoelectric 0.12 50SystemSensor2412(12volt) Photoelectric 0.12 77SystemSensor2412AT(12volt) Photoelectric 0.12 58SystemSensor2412TH(12volt) Photoelectric 0.12 77SystemSensor2424 Photoelectric 0.10 41SystemSensor2424TH Photoelectric 0.10 41SystemSensor2451 Photoelectric 0.10 39SystemSensor2451TH(with/B402BBase) Photoelectric 0.10 39SystemSensor2W-MOD LoopTest/MaintenanceMod. 30 50SystemSensor4W-B(12/24volt) PhotoelectricI3 0.05 23SystemSensor4WT-B(12/24volt) PhotoelectricI3w/Therm 0.05 23SystemSensor4WTA-B(12/24volt) I3Photow/Therm/Sounder 0.05 35SystemSensor4WTR-B(12/24volt) I3Photow/Therm/Relay 0.05 35

Page 11: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

AL1002ULADAJ - 11 -

A.1 Four (4) Wire Smoke Detectors (cont.)

Smoke Detector/Base Detector TypeMax Stand-byCurrent (mA)

AlarmCurrent (mA)

SystemSensor4WTR-B(12/24volt)I3Photow/Therm/Sounder/Relay

0.05 50

SystemSensor4WITAR-B(12/24volt) I3Photow/IsolatedTherm/Sounder/Relay 0.05 50SystemSensor2W-MOD2 I3LoopTest/MaintenanceMod. 0.05 *SystemSensorRRS-MOD I3ReversingRelay/SyncModule 0.05 *SystemSensor6424 ProjectedBeam 10 28.4SystemSensorBeam1224(S) ProjectedBeam 17 38.5

*Contactmanufacturerforcurrentdraws

A.2 Door Holders

TableA-2belowlistsdoorholderscompatiblewithAL1002ULADAJAUXoutput.

Manufacturer Model Type Current (mA)Edwards DH150A FloorMount 96Edwards DH154A FloorMount 96Edwards DH158A SurfaceMount 96RixonFiremark FM-980 FloorMount,single 68RixonFiremark FM-996 SurfaceWiring 68RixonFiremark FM-998 ConcealedWiring 68

A.3 Relays

TableA-3belowlistsrelayscompatiblewithAL1002ULADAJAUXoutput.

Manufacturer Model Current (mA) Manufacturer Model Current (mA)

AirProducts&Controls,LTD

MR-101/CMR-201/CPAM-1PAM-2PAM-SDA77-716B

153515151520

SystemSensor

PR-1PR-2PR-3EOLR-1R-10TR-14TR-20TR-24TR-10ER-14ER-20ER-24E

153030302323404023234040

Page 12: NAC Power Extender Installation Guide - TC Life Safety · AL1002ULADAJ - NAC Power Extender. AL1002ULADAJ - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp supplied

- 12 - AL1002ULADAJ

Altronixisnotresponsibleforanytypographicalerrors.

14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056website:www.altronix.com,e-mail:[email protected],LifetimeWarranty,MadeinU.S.A.IIAL1002ULADAJ I06M MEMBER

1.5”(38.1mm)

1.0”(25.4mm)

4.5”(114.3mm)

1.0”(25.4mm)

1.0”(25.4mm)

1.25”(31.75mm)

1.25”(31.75mm)

1.0”(25.4mm)

1.5”(38.1mm)

1.5”(38.1mm)

1.5”(38.1mm)

1.5”(38.1mm)

8.5”(215.9mm)

18.0”(457.2mm)

18.0”(457.2mm)

18.0”(457.2mm)

6.0”(152.4mm)

2.5”(63.5mm)

2.75”(69.85mm)

2.75”(69.85mm)

4.5”(114.3mm)

4.5”(114.3mm)

14.5”(368.3mm)

14.5”(368.3mm)

1.0”(25.4mm)

1.0”(25.4mm)

14.5”(368.3mm)

2.5”(63.5mm)

1.5”(38.1mm)

2.5”(63.5mm)

Enclosure Dimensions (H x W x D approximate):18”x14.5”x4.5”(457.2mmx368.3mmx114.3mm)