Multivariable Control-Oriented Modeling of a Direct
Transcript of Multivariable Control-Oriented Modeling of a Direct
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9
www. i ifi i r .org
ava i lab le at www.sc iencedi rec t . com
journa l homepage : www.e lsev i er . com/ loca te / i j r e f r ig
Multivariable control-oriented modeling of a directexpansion (DX) air conditioning (A/C) system
Qi Qi, Shiming Deng*
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong SAR
a r t i c l e i n f o
Article history:
Received 28 June 2007
Received in revised form
17 October 2007
Accepted 18 October 2007
Published online 9 January 2008
Keywords:
Cooling system
Air conditioning
Direct expansion
Modelling
Simulation
Comparison
Experiment
* Corresponding author. Tel.: þ852 2766 5859E-mail address: [email protected] (S.
0140-7007/$ – see front matter ª 2007 Elsevidoi:10.1016/j.ijrefrig.2007.10.009
a b s t r a c t
A dynamic mathematical model for a DX A/C system has been developed. The dynamic
model, written in state-space representation which was suitable for designing multivari-
able control, was linearized at steady state operating points. The linearized model has
been validated by comparing the model simulation results with the experimental data ob-
tained from an experimental DX A/C system. The simulated results agreed well with the
experimental data, suggesting that the model developed was able to capture the transient
characteristics of the DX A/C system modeled. It is expected that the model developed can
be useful in designing a multi-input multi-output (MIMO) controller to simultaneously
control indoor air temperature and humidity in a space served by a DX A/C system.
ª 2007 Elsevier Ltd and IIR. All rights reserved.
Modelisation aux variables multiples axee sur la regulationd’un systeme de conditionnement d’air a detente directe
Mots cles : Systeme frigorifique ; Conditionnement d’air ; Detente directe ; Modelisation ; Simulation ; Comparaison ; Experimentation
1. Introduction
Direct expansion (DX) air conditioning (A/C) systems are
widely used in small- to medium-scaled buildings in recent
decades. Compared to central chilled water-based A/C sys-
tems, the use of DX A/C systems is advantageous since they
are simpler in configuration, more energy efficient and gener-
ally cost less to own and maintain. In the US, according to
; fax: þ852 2765 7198.Deng).er Ltd and IIR. All rights
Department of Energy, packaged rooftop DX A/C systems
accounted for approximately 60% of the total installed cooling
capacity (Bordick and Gilbridge, 2002).
Residential buildings are most likely served by DX A/C sys-
tems, but controlling indoor humidity at an appropriate level
using a DX A/C system is both challenging and important
since this directly affects occupants’ thermal comfort and in-
door air quality (IAQ) (Fanger, 2001). Most DX A/C units are
reserved.
Nomenclature
A, B, C coefficient matrices (in Eq. (18))
A1 heat transfer area of the DX evaporator in dry-
cooling region, m2
A2 heat transfer area of the DX evaporator in wet-
cooling region, m2
Cp specific heat of air, kJ kg�1 K�1
f air volumetric flow rate, m3/s
M moisture load in the conditioned space, kg/s
Mref mass flow rate of refrigerant, kg/s
Pr Prandtl number
Qload sensible heat load in the conditioned space, kW
Qspl heat gain of supply fan, kW
SH super heat of refrigerant, �C
T1 temperature of air leaving the DX evaporator, �C
T2 air temperature in the conditioned space, �C
T3 air temperature leaving the dry-cooling region of
the DX evaporator, �C
Tw temperature of the DX evaporator wall, �C
V volume of the conditioned space, m3
Vh1 air side volume of the DX evaporator in dry-cooling
region on air side, m3
Vh2 air side volume of the DX evaporator in wet-
cooling region on air side, m3
Vcom swept volume of the rotor compressor, m3
W1 moisture content of air leaving the DX evaporator,
kg/kg dry air
W2 moisture content of air-conditioned space, kg/kg
dry air
a1 heat transfer coefficient between air and the DX
evaporator wall in dry-cooling region, kW m�2 �C�1
a2 heat transfer coefficient between air and the DX
evaporator wall in wet-cooling region, kW m�2 �C�1
r density of moist air, kg/m3
hfg latent heat of vaporization of water, kJ/kg
hr1 enthalpy of refrigerant at evaporator inlet, kJ/kg
hr2 enthalpy of refrigerant at evaporator outlet, kJ/kg
je1, je2 Colburn factors
kspl coefficient of supply fan heat gain, kJ/m3
vs specific volume of superheated refrigerant,
m3 kg�1
e rotor eccentricity, m
l stroke of cylinder, m
r radius of rotor, m
s speed of compressor, rpm
l compressor’s displacement coefficient
lsys eigenvalue (in Eq. (23))
3 rotor relative eccentricity
Superscript
w evaporator wall
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9842
currently equipped with single-speed compressors and supply
fans, relying on on–off cycling compressors as a low-cost
approach to maintain only indoor air dry-bulb temperature,
resulting in either space overcooling or an uncontrolled equi-
librium indoor relative humidity (RH) level.
Recent developments in variable speed drive (VSD) tech-
nology offer tremendous opportunities for improving indoor
thermal comfort and energy efficiency for DX-based space
air conditioning. Compressor speed can be continuously var-
ied to modulate the output cooling capacity to match the ac-
tual thermal load. The supply fan speed can be also altered
to affect both sensible heat and latent heat transfer rate across
heat exchangers. Therefore it is possible to improve indoor
thermal comfort control using DX A/C systems equipped
with variable speed compressor and supply air fan.
In the open literature available, a considerable number of
previous investigations have focused on the dynamic model-
ing of vapor compression refrigeration cycles. He et al. (1997)
developed an overall dynamic model for a vapor compression
refrigeration cycle, and the simulation results indicated that
there were strong cross-couplings among system inputs and
outputs. Linear Quadratic Gaussian (LQG) technique was
then used to design a multi-input multi-output (MIMO) con-
troller with guaranteed stability and robustness (He et al.,
1998). The possibility of using a model-based nonlinear con-
troller was also investigated numerically for a vapor compres-
sion refrigeration system (Tao et al., 2004, 2005). Rasmussen
and Alleyne (2004) presented a reduced order dynamic model
of a transcritical vapor compression cycle. It was demon-
strated that the reduced order model was adequate for predict-
ing the dominant system dynamics. Therefore the reduced
order model with minimal loss in accuracy was very useful
for designing an MIMO controller. Shah et al. (2004) developed
a model for the vapor compression refrigeration cycle in an
automotive air conditioning system with a variable speed
compressor, and applied the multivariable adaptive control
strategy to the air conditioning system to improve its capacity
control and system efficiency. Lin and Yeh (2007) developed
a low-order linear model for an air conditioning system
through system identification. Experimental results indicated
that an MIMO-based controller can both achieve satisfactory
transient responses in indoor air temperature and improve
energy efficiency at steady states. However, the model estab-
lished through system identification was only valid for certain
particular systems.
In mechanical cooling based on A/C systems, dehumidifi-
cation is less straightforward because of the dual function of
cooling and dehumidification taking place in cooling coils.
This has led to the controlled variables of air temperature
and humidity becoming coupled, which was confirmed by ex-
perimental investigations (Li and Deng, 2007a). Krakow et al.
(1995) suggested that space air temperature and relative hu-
midity could be controlled by varying compressor speed and
varying evaporator fan speed, separately, using a propor-
tional–integral–derivative (PID) control method. However,
the study focused on the feasibility of such a PID control
method, without looking at the coupling effect of air temper-
ature and humidity by treating the two controlled variables
separately. A DDC-based control algorithm developed by Li
and Deng (2007b,c) considered the coupling effect of air tem-
perature and humidity and used space sensible heat ratio
(SHR) as a controlled variable to simultaneously control space
Thermal space
EEVVariable speedcompressor
Evaporator
Condenser
Variable speedsupply fan
T1,W1
T2,W2 Supply air
hr1hr2
Fig. 1 – The schematic diagram of the experimental DX A/C
system.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9 843
air temperature and relative humidity. However, the sensitiv-
ity of the DDC-based controller was poor as it had to wait for
a long time for the controller to be fed with the required infor-
mation to take the next control action.
It can therefore be seen that the previous studies mainly
focused on either the modeling and control of vapor compres-
sion refrigeration system or the control of air temperature and
humidity by using conventional control such as PID control
method without much consideration on the coupling effect
of air temperature and humidity. The PID control method
was in fact to have two separate control loops, i.e., controlling
indoor air temperature by varying compressor speed and in-
door air humidity by varying supply fan speed. The two con-
trol loops have been traditionally treated as two separate
single-input single-output (SISO) systems, while the coupling
effect between the two parameters has been often ignored.
The performance of the conventional SISO control has been
inherently poor. Therefore developing an MIMO control strat-
egy for coupled air temperature and humidity is urgently re-
quired. Consequently, dynamic modeling of a DX A/C
system suitable for developing MIMO control algorithms
which consider the coupling effect of air temperature and hu-
midity becomes highly necessary.
This paper presents the development of a dynamic mathe-
matical model for a DX A/C system, written in state-space repre-
sentation which was suitable for designing multivariable
control. The organization of the paper is as follows. Section 2 de-
scribes briefly an experimental DX A/C system. The develop-
ment of the dynamic model of the experimental DX A/C
system and its linearization process are presented in Section
3. Simulation results using the linearized model and the results
obtained for the experimental DX A/C system are compared in
Section 4 for model validation. Section 5 presents conclusions.
2. Description of the experimentalDX A/C system
The experimental DX A/C system was mainly composed of
two parts, i.e., a DX refrigeration plant (refrigerant side) and
an air-distribution sub-system (air side). Its simplified sche-
matic diagram is shown in Fig. 1. The major components in
the DX refrigeration plant included a variable speed rotor com-
pressor, an electronic expansion valve (EEV), a high-efficiency
tube-louver-finned DX evaporator and an air-cooled tube-
plate-finned condenser. The evaporator was placed inside
the supply air duct to work as a DX air cooling coil. The design
air face velocity for the DX cooling coil was 2.5 m/s. The nom-
inal output cooling capacity from the DX refrigeration plant
was 9.9 kW (2.8 RT). The working fluid of the plant was refrig-
erant R22, with a total charge of 5.3 kg.
The air-distribution sub-system included an air-distribution
ductwork with return air dampers, a variable speed centrifugal
supply fan, and a conditioned thermal space. Inside the space,
there are sensible heat and moisture load generating units
(LGUs). The units are intended to simulate the cooling load in
the conditioned space.
The experimental DX A/C system has been fully instru-
mented. High-precision sensors/transducers were used for
measuring all operating parameters including temperatures
and flow rates of both air and refrigerant, pressures in the
DX A/C unit, etc. All measurements were computerized, so
that all the measured data can be recorded for subsequent
analysis.
3. Dynamic modeling of the experimentalDX A/C system
The dynamic mathematical model for the DX A/C system was
mainly derived from the energy and mass conservation prin-
ciples. The following assumptions were made in developing
the mathematical model: (1) perfect air mixing inside all
heat exchangers and the thermal space, and no fresh air in-
take to the system; (2) two regions on the air side of the DX
evaporator, i.e., dry-cooling region and wet-cooling region;
and (3) negligible thermal losses in air ducts.
In the DX A/C system to be modeled, the temperature
and moisture content of the air leaving the DX cooling
coil, as shown in Fig. 1, were T1 and W1, respectively. With
the air perfect mixing assumption, air temperature, T2, and
air moisture content, W2, leaving the conditioned space
can be regarded as being equal to those in the conditioned
thermal space. Based on the energy conservation principle,
the sensible energy balance equation for the conditioned
space was:
CprVdT2
dt¼ CprfðT1 � T2Þ þ Qload þ Qspl (1)
where V was the volume of the conditioned space, Qload the
space sensible load, Qspl heat gain of the supply fan, f the air
volumetric flow rate. The heat gain of supply fan increased
with the air flow rate.
Qspl ¼ ksplf (2)
On the other hand, the moisture mass balance inside the
conditioned space was
rVdW2
dt¼ rfðW1 �W2Þ þM (3)
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9844
where M was the moisture load generation in the conditioned
space.Corresponding to the assumed two regions on the air side,
the refrigerant side in the DX A/C systems was assumed to
have a two-phase region and a superheated region, as shown
in Fig. 2.
At the air side of the evaporator, with the assumption of no
fresh air, the temperature and moisture content of the air en-
tering evaporator were T2 and W2, respectively. The air tem-
perature decreased along the evaporator wall and was equal
to T3 at the end of dry-cooling region. Since the dry-cooling
region was usually small, the temperature of the entire evap-
orator wall was assumed at the same Tw. Applying the energy
balance principle in the dry-cooling region on the air side
yielded
CprVh1dT3
dt¼ CprfðT2 � T3Þ þ a1A1
�Tw �
T2 þ T3
2
�(4)
On the other hand, in the wet-cooling region, there was not
only sensible heat transfer between the air and evaporator
wall but also latent heat transfer. The coupled air cooling
and dehumidification mainly took place in the wet-cooling re-
gion. Therefore the energy balance in the wet-cooling region
can be written in enthalpy form:
rVh2dh1
dt¼ rfðh3 � h1Þ þ a2A2
�Tw �
T3 þ T1
2
�(5)
The relationship among air enthalpy, temperature and
moisture content was
h ¼ CpTþ hfgW (6)
where hfg was the latent heat of vaporization of water.
Substitute Eq. (6) into Eq. (5) to obtain
CprVh2dT1
dtþ rVh2hfg
dW1
dt¼ CprfðT3 � T1Þ þ rfhfgðW2 �W1Þ
þ a2A2
�Tw �
T3 þ T1
2
�(7)
The degree of refrigerant sub-cooling in a condenser with
a receiver is normally rather small, and the refrigerant in the
receiver can be assumed to be the saturated liquid refriger-
ant at condensing pressure. Therefore, after knowing the
real-time measured condensing pressure, the enthalpy of
refrigerant leaving the receiver, hre2, can be obtained using
the R22 State Equations (Cleland, 1986). Neglecting the en-
ergy loss in the refrigerant line and approximating the
wT3
dry-region
T2,W2
Air side
Tw
h2 superheated region two-p
Fig. 2 – The schematic di
refrigerant throttling process in an EEV as being isenthalpic,
the enthalpy of refrigerant entering the DX evaporator is
given by
hr1 ¼ hre2 (8)
The enthalpy of superheated refrigerant at compressor suc-
tion, hrc1, can be evaluated based on the real-time measured
pressure and the temperature of superheated refrigerant us-
ing the R22 State Equations. Neglecting the energy loss in
the refrigerant line between DX evaporator and compressor
suction owing to good thermal insulation, the enthalpy of
the refrigerant leaving the DX evaporator is given by
hr2 ¼ hrc1 (9)
The swept volume of the rotor compressor, Vcom, was calcu-
lated using the related compressor’s geometric parameters as
follows:
Vcom ¼ pr2l3�2� 3
�(10)
where l is the stroke of cylinder; r the radius of rotor and 3 the
rotor relative eccentricity.
The compressor displacement coefficient, l, was given by
l ¼ 1� 0:015
"�Pc
Pe
�1b
�1
#(11)
where b is the compression index which was assumed to be
constant at 1.18. Pc and Pe were the condensing pressure and
evaporating pressure, respectively.
Therefore, the refrigerant mass flow rate can be deter-
mined by
Mref ¼sVcom
vs
�1� 0:015
hðPc=PeÞ
1b�1
i�(12)
where s is the compressor speed, vs specific volume of super-
heated refrigerant, which can be obtained from measured
pressure and temperature of refrigerant at compressor suc-
tion using the R22 State Equations.
Due to the significant difference in thermal inertia for both
refrigerant and air, dynamic responses to changes on the air
side were much slower than that on the refrigerant side. When
the airside waited for a long time to fully respond, the refrigerant
side was already in its steady state for a quite while. Thus the
same refrigerant mass flow rate at both the inlet and the outlet
of the DX evaporator was assumed. Therefore the energy
balance equation for the evaporator wall can be written as
Refrigerant side
h1
Evaporator wall
T1,W1
et-region
hase region
agram of evaporator.
0 200 400 600 800 1000 120023.00
23.25
23.50
23.75
24.00
24.25
24.50
Simulation
Experiment
Tem
pera
ture
(ºC
)
Time (s)
Fig. 3 – Simulated and measured air temperature in the
conditioned space in response to a step change in
compressor speed.
11.2
11.4
11.6
cont
ent
(g/k
g)
Simulation
Experiment
Table 1 – Numerical values of the system parameters
Cp 1.005 kJ/kg A1 4.14 m2
r 1.2 kg/m3 A2 17.65 m2
hfg 2450 kJ/kg Vh1 0.04 m3
V 77 m3 Vh2 0.16 m3
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9 845
�CprV
�w
dTw
dt¼ a1A1
�T2 þ T3
2� Tw
�þ a2A2
�T3 þ T1
2� Tw
��Mrefðhr2 � hr1Þ (13)
The airside convective heat transfer coefficients for the
louver-finned evaporator in both dry-cooling and wet-cooling
regions were evaluated as follows (Chen, 2005):
a1 ¼ je1ryCp
Pr23
(14a)
a2 ¼ je2ryCp
Pr23
(14b)
where je1, je2 are the Colburn factors, y the air velocity.
The supply air leaving the DX evaporator was assumed to
be at 95% saturated. The relationship between air moisture
content and temperature can be derived by plotting and curv-
ing fitting:
W1 ¼�0:0198T2
1 þ 0:085T1 þ 4:4984��
1000 (15a)
Therefore
dW1
dt� ð2� 0:0198T1 þ 0:085ÞdT1
dt=1000 ¼ 0 (15b)
Eqs. (1), (3), (4), (7), (13) and (15b), all of which were first order
differential equations, formed the dynamic model of DX A/C
system. Since the objective of the model development was
to assist the design of a multivariable controller, it was sug-
gested (Tewari, 2002; Skogestad and Postletheaite, 1996) that
these differential equations should be written in state-space
representation, such that it did not formally distinguish be-
tween a multivariable system and a single variable system,
allowing an efficient design and analysis for a multivariable
system in the same manner as for a single variable system.
Hence the model in state-space representation may be
expressed in the following compact format:
_X ¼ D�1$g1
�X;U
�þ D�1$g2
�Z�
(16)
where the state variables X ¼ ½T1;T2;T3;Tw;W1;W2�T and_X ¼ ðdX=dtÞ, the input variables U ¼ ½f ; s�T, and the disturbance
variables Z ¼ ½Qload;M�T, g1, g2 are the functions, defined as
follows:
Table 2 – Operating condition of the DX A/C system
T1 13.25 �C Pc 1.812� 106 Pa
W1 9.03/1000 kg/kg dry air Pe 0.486� 106 Pa
T2 24 �C Qload 4.49 kW
W2 11.35/1000 kg/kg dry air M 0.96/1000 kg/s
T3 17 �C Mref 0.042 kg/s
Tw 13 �C s 3960 rpm
SH 6 �C f 0.347 m3/s
g1ðX;UÞ¼
26666664
CprfðT1�T2ÞþksplfrfðW1�W2ÞCprfðT2�T3Þþa1A1
�Tw�T2þT3
2
�CprfðT3�T1ÞþrfhfgðW2�W1Þþa2A2
�Tw�T3þT1
2
�a1A1
�T2þT3
2 �Tw
�þa2A2
�T3þT1
2 �Tw
��s vs
Vcomlðhr2�hr1Þ
0
37777775
(17a)
g2ðZÞ¼
26666664
Qload
M0000
37777775
(17b)
D¼
26666664
0 CprV 0 0 0 00 0 0 0 0 rV0 0 CprVh1 0 0 0
CprVh2 0 0 0 rVh2hfg 00 0 0
�CprV
�w
0 01 0 0 0 ð2�0:0198T1þ0:085Þ=1000 0
37777775
(18)
0 200 400 600 800 1000 120010.6
10.8
11.0
Moi
stur
e
Time (s)
Fig. 4 – Simulated and measured air moisture content in
the conditioned space in response to a step change in
compressor speed.
0 200 400 600 800 1000 120012.00
12.25
12.50
12.75
13.00
13.25
13.50
Tem
pera
ture
(ºC
)
Time (s)
Simulation
Experiment
Fig. 5 – Simulated and measured temperature of the air
leaving evaporator in response to a step change in
compressor speed.
0 200 400 600 800 1000 120058.0
58.5
59.0
59.5
60.0
60.5
61.0
RH
(
)
Time (s)
Simulation
Experiment
Fig. 7 – Simulated and measured relative humidity in the
conditioned space in response to a step change in
compressor speed.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9846
The developed dynamic model expressed in state-space
representation, i.e., Eq. (16), was nonlinear since the relation-
ship between state variables and input variables was nonlin-
ear. In most cases, a DX A/C system was designed to operate
in the vicinity of a predetermined set point given that thermal
space cooling load did not significantly change. As long as the
control system can properly regulate the dynamic deviation of
the controlled objectives from the set points, the controlled
system can be well represented by a linearized model around
the set points. Hence, the state variables, X, and control in-
puts, U, can be expressed as follows, respectively:
X¼xþx0 (19a)
U¼uþu0 (19b)
where x0 and u0 are the state vector and input vector, both evalu-
ated at a steady state operating point, and x and u represent the
small dynamic deviation from x0 and u0, respectively. For the DX
A/C system to be modeled, the sensible and moisture content load
disturbance can be regarded as being constant at a steady state.
Therefore the linearized model describing the system’s dynamic de-
viation at an operating point can be written as
0 200 400 600 800 1000 12008.0
8.2
8.4
8.6
8.8
9.0
9.2
Moi
stur
e co
nten
t (g
/kg)
Time (s)
Simulation
Experiment
Fig. 6 – Simulated and measured moisture content of the
air leaving evaporator in response to a step change in
compressor speed.
_x¼vg1
vX
x0 ;u0
xþvg1
vU
x0 ;u0
u¼A�x0;u0
�xþB
�x0;u0
�u (20)
Therefore the linearized dynamic model of the DX A/C sys-
tem in state-space representation, which is highly suitable for
designing multivariable control, can be written as8<:
_x¼AxþBu
y¼Cx(21)
where the output variables y¼½dT2;dW2�T, the dynamic devia-
tions of air temperature and moisture content from their set
points, respectively, and A, B, C were the coefficient matrices.
At a particular operating point, where T2¼ 24 �C,
W2¼ 0.0135 kg/kg dry air, T1¼ 13.25 �C, W1¼ 0.00903 kg/kg
dry air and the air flow rate f¼ 0.347 m3/s, the system matrices
A, B and C were calculated as follows:
A ¼
26666664
�5:731 0 0:0756 4:1883 �5287 52870:0045 �0:0045 0 0 0 0
0 4:6577 �12:692 8:0346 0 00:0139 0:0067 0:0206 �0:0412 0 00:0006 0 0 0 0 0
0 0 0 0 0:0045 �0:0045
37777775
(22a)
0 200 400 600 800 1000 12000
1
2
3
4
5
6
7
8
Latent cooling capacity
Sensible cooling capacity
Coo
ling
capa
city
(kW
)
Time (s)
Total cooling capacity Simulation
Experiment
Fig. 8 – Simulated and measured output cooling capacities
in response to a step change in compressor speed.
0 200 400 600 800 100011.0
11.5
12.0
12.5
13.0
13.5T
empe
ratu
re (
ºC)
Time (s)
Simulation
Experiment
Fig. 9 – Simulated and measured temperature of the air
leaving evaporator in response to a step change in supply
fan speed.
0 200 400 600 800 100023.00
23.25
23.50
23.75
24.00
24.25
24.50
Tem
pera
ture
(ºC
)
Time (s)
Simulation
Experiment
Fig. 11 – Simulated and measured air temperature in the
conditioned space in response to a step change in supply
fan speed.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9 847
B ¼
26666664
55:035 0�0:098 0172:5 0
0 �5:9310 0
�0:00003 0
37777775; C ¼
0 1 0 0 0 00 0 0 0 0 1
�(22b)
The eigenvaluesofthe linearizedmodel for theDXA/Csystem
are shown in Eq. (23) for the operating point. All the eigenvalues
have the negative real parts, suggesting that the DX A/C system
represented by the linearized model was asymptotically stable.
lsys ¼
26666664
�2:46e� 017�4:51e� 003�2:85e� 002�6:15e� 001�5:12eþ 000�1:27eþ 001
37777775
(23)
4. Model validation
Simulation results using the linearized dynamic model, i.e.,
Eq. (18), have been compared with the experimental data
0 200 400 600 800 10008.0
8.2
8.4
8.6
8.8
9.0
9.2
Moi
stur
e co
nten
t (g
/kg)
Time (s)
Simulation
Experiment
Fig. 10 – Simulated and measured moisture content of the
air leaving evaporator in response to a step change in
supply fan speed.
obtained from the experimental DX A/C system for the pur-
pose of model validation. The simulation results and experi-
ment results were the open-loop responses to step changes
in compressor and supply fan speeds, respectively.
When the system was operating around a steady state con-
dition, step changes were introduced to the controllable in-
puts such as compressor speed and supply fan speed. The
same operating conditions and step changes were also input
to the model to obtain simulation results to facilitate the
comparison.
The following comparisons were based on the steady state
operational condition of around 24 �C indoor air temperature
and 11.3 g/kg moisture content, or 60% RH in conditioned
space. The numerical values of both the system parameters
used in the simulation and the operating condition of the
DX A/C system are given in Tables 1 and 2, respectively. The
linearization of the model was also based on this operating
condition. Figs. 3–8 present the comparisons between the sim-
ulation results and experimental data in response to a step
change in compressor speed from 3960 rpm to 4488 rpm
(from 66 Hz to 75 Hz), introduced at 420 s. When the compres-
sor speed increased, the temperature and moisture content of
0 200 400 600 800 100011.00
11.05
11.10
11.15
11.20
11.25
11.30
11.35
11.40
Moi
stur
e co
nten
t (g
/kg)
Time (s)
Simulation
Experiment
Fig. 12 – Simulated and measured air moisture content in
the conditioned space in response to a step change in
supply fan speed.
0 200 400 600 800 100058.0
58.5
59.0
59.5
60.0
60.5
61.0
RH
(
)
Time (s)
Simulation
Experiment
Fig. 13 – Simulated and measured relative humidity in the
conditioned space in response to a step change in supply
fan speed.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9848
the air in conditioned space decreased due to the increased
output cooling capacity of the DX A/C system, as shown in
Figs. 3 and 4. As seen in both figures, there existed a good
agreement between the simulated responses and the experi-
mental results. Similar observations can be obtained for other
operating parameters such as the temperature and moisture
content of air leaving the DX evaporator (Fig. 5 and 6), indoor
air relative humidity (Fig. 7) and output cooling capacities
(Fig. 8). In Fig. 8, it is seen that the increase in output latent
cooling capacity was more than that in output sensible cooling
capacity, when the total output cooling capacity was in-
creased due to the increase in compressor speed, which
resulted in a lower evaporating temperature or a lower evap-
orator wall temperature. Hence, as seen in Fig. 7, indoor air
RH was reduced due to the increased output latent cooling
capacity.
On the other hand, the comparisons between the simula-
tion results and experimental data, in response to a step
change in supply fan speed from 2448 rpm to 2160 rpm (from
41 Hz to 36 Hz), introduced at 290 s, are illustrated in Figs. 9–14.
When the supply fan speed was reduced, the temperature and
moisture content of the air leaving the DX evaporator de-
creased, as shown in Figs. 9 and 10, respectively. Again, in
both figures, a good agreement between the simulated results
0 200 400 600 800 10000
1
2
3
4
5
6
7
8
Latent cooling capacity
Sensible cooling capacity
Cap
acit
y (k
W)
Time (s)
Total cooling capacity
Simulation
Experiment
Fig. 14 – Simulated and measured output cooling capacities
in response to a step change in supply fan speed.
and measured experimental data can be observed. Similar ob-
servations of agreement can also be found for other systems
parameters as shown in Figs. 11–14.
The comparisons shown in Figs. 3–14 confirmed that the
developed model after linearization was experimentally vali-
dated to be able to both capture the transient change of sys-
tem parameters in a timely manner, and to represent the
steady state operation with an acceptable accuracy. Although
there were a number of points where there existed noticeable
differences between the measured and the simulated re-
sponses possibly due to the fact that the model developed
was a simplified one, the general trends for both were consis-
tent. Hence, this model was a good representation of the DX A/
C system during both the steady state and transient operating
conditions. More importantly, the model was written in state-
space representation, thus suitable for multivariable control-
ler design.
5. Conclusions
A dynamic mathematical model of a DX A/C system has been
developed based on the principle of energy and mass conser-
vation, and is reported in this paper. The dynamic model writ-
ten in state-space representation was linearized at its
operating point, which makes it highly suitable for designing
a multivariable control algorithm, such as MIMO control.
The linearized model was experimentally validated. It is
expected that the validated model could pave the way for fu-
ture work of designing an MIMO controller for simultaneously
controlling indoor air temperature and humidity in a space
served by a DX A/C system.
Acknowledgments
The authors acknowledge the financial supports from both
the Research Grant Council of Hong Kong (B-Q796) and The
Hong Kong Polytechnic University for the work reported in
this paper.
r e f e r e n c e s
Bordick, J., Gilbridge, T.L., 2002. Focusing on buyer’s needs: DOE’sengineering technology program. Energy Engineering 99 (6),18–38.
Chen, W., 2005. Modeling and Control of a Direct Expansion (DX)Variable-air-volume (VAV) Air Conditioning System. PhDthesis, Department of Building Services Engineering, HongKong Polytechnic University.
Cleland, A.C., 1986. Computer sub-routines for rapid evaluation ofrefrigerant thermodynamic properties. International Journalof Refrigeration 9, 346–351.
Fanger, P.O., 2001. Human requirements in future air-conditionedenvironments. International Journal of Refrigeration 24, 148–153.
He, X.D., Liu, S., Asada, H.H., 1997. Modeling of vaporcompression cycles for multivariable feedback control ofHVAC systems. Transaction of the ASME: Journal of DynamicSystems, Measurement, and Control 119, 183–191.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 1 ( 2 0 0 8 ) 8 4 1 – 8 4 9 849
He, X.D., Liu, S., Asada, H.H., Itoh, H., 1998. Multivariable controlof vapor compression systems. HVAC & R Research 4 (3),205–230.
Krakow, K.I., Lin, S., Zeng, Z.S., 1995. Temperature and humiditycontrol during cooling and dehumidifying by compressor andevaporator fan speed variation. ASHRAE Transactions 101 (1),292–304.
Li, Z., Deng, S.M., 2007a. An experimental study on the inherentoperational characteristics of a direct expansion (DX) airconditioning (A/C) unit. Building and Environment 42, 1–10.
Li, Z., Deng, S.M., 2007b. A DDC-based capacity controller ofa direct expansion (DX) air conditioning (A/C) unit forsimultaneous indoor air temperature and humidity control.Part I: Control algorithms and preliminary controllability tests.International Journal of Refrigeration 30, 113–123.
Li, Z., Deng, S.M., 2007c. A DDC-based capacity controller ofa direct expansion (DX) air conditioning (A/C) unit forsimultaneous indoor air temperature and humidity control.Part II: Further development of the controller to improvecontrol sensitivity. International Journal of Refrigeration 30,124–133.
Lin, J.L., Yeh, T.J., 2007. Modeling, identification and control of airconditioning systems. International Journal of Refrigeration30, 209–220.
Rasmussen, B.P., Alleyne, A.G., 2004. Control-oriented modelingof transcritical vapor compression systems. Transaction of theASME: Journal of Dynamic Systems, Measurement, andControl 126, 54–64.
Skogestad, S., Postletheaite, I., 1996. Multivariable FeedbackControl Analysis and Design. John Wiley & Sons Ltd.
Shah, R., Rasmussen, B.P., Alleyne, A.G., 2004. Application ofa multivariable adaptive control strategy to automotive airconditioning systems. International Journal of AdaptiveControl and Signal Processing 18, 199–221.
Tao, C., He, X.D., Asada, H.H., 2004. Nonlinear observer design fortwo-phase flow heat exchangers of air conditioning systems.Proceedings of the American Control Conference, USA, 1534–1539.
Tao, C., He, X.D., Asada, H.H., Kasahara, S., 2005. Heat exchangerdynamic observer design. ASHRAE Transactions 111, 328–335.
Tewari, A., 2002. Modern Control Design with Matlab andSimulink. John Wiley & Sons Ltd.