  • MotorpactMV motor starters7.2kV

    Web-enabled Power & Control

  • Motorpact 2007-TL 2

    Abbreviations

    LPCT Low Power Current Transducer

    LV Low Voltage MV Medium VoltageO/L Over LoadPLC Programmable Logic StarterRMS Root Mean SquareRVAT Reduced Voltage Auto

    TransformerRVSS Reduced Voltage Soft StartSCR Silicon Controlled RectifiersSSM Soft Starter ModuleATM Auto Transformer ModuleS3 Sequential Smart StarterFVR Full Voltage Reversing SSM Soft Start Module

    TVSS Transient Voltage Surge Suppressor

    VSD Variable Speed DriveVPIS Voltage Presence Indicator

    SystemVT Voltage Transformer

    (Potential Transformer)CPT Control Potential TransformerCTD Capacitor Trip Device

  • Motorpact 2007-TL 3

    MV motor starter Rated voltage

    7.2 kV

    Short Circuit withstand 40kA/3s or 50kA/2s

    Motor range Up to 3800 kW

    Motor type Asynchronous (Squirrel cage)

    Starter : FVNR RVAT RVSS

    Enclosure types Up to IP 3X or 4X Arc resistant Optional: roof for IP X2

  • Motorpact 2007-TL 4

    Motorpact = low cost of ownership

    Low installation cost

    Space saving footprint High reliability Reduced maintenance Easy to use Safety focus Global product

    (meets IEC and NEMA standards)

  • Motorpact 2007-TL 5

    Low installation cost

    2 unit pre-assembled shipment available shipment in units pre-assembled of 5 FVNR reduces installation time and labor minimizes risks field installation errors

    Integrated low voltage wireway simplifies field wiring and installation of protection, control

    and communication

    Front and rear access to cable compartment simplifies field wiring and installation of protection, control

    and communication

    Low cost of ownership

  • Motorpact 2007-TL 6

    Space saving footprint

    400A FVNR 375 mm wide Perfect for retrofit or extension Floor space maximum economy Two FVNR single tier more compact

    than one double tier

    Low cost of ownership

    375Depth : 946 mmHeight : 2300 mm

  • Motorpact 2007-TL 7

    High reliability

    Disconnector housing and contactor cradle moulds

    Fewer bolted connections and parts Simple component-to-component support

    assemblies

    Fewer busbar connections Requires only two-bolts per phase for

    a main bus connection

    Pre-engineered solutions with LPCT and Sepam digital relay

    Provides proven designs for the full range of motor applications

    KEMA Certified

    Low cost of ownership

  • Motorpact 2007-TL 8

    Auto Transformer Module (ATM)

    Reduced Voltage Auto Transformer Non-Reversing (RVAT)

    FVNR Module

    Full Voltage Non-Reversing (FVNR)

    Mechanically Latched Magnetically Held

    Soft Start Module (SSM)

    Reduced Voltage Soft Start Non-Reversing (RVSS)

    FVNR Module

    FVNR & ATM & SSM descriptions3 types of Motorpact starters

  • Motorpact 2007-TL 9

    N

    e

    t

    w

    o

    r

    k

    Protection LoadMotor

    FVNR base module descriptionDirect stator starting on full voltage Locked rotor current on starting is around 4 to 7 In

    depending on motor characteristics Starting time of 1 to 10 seconds depending on the

    moment of total inertia (motor + machine), motor torque and load torque

    The network must be able to withstand the starting current without disturbing other loads

    The machine being driven must be able to withstand the mechanical impact due to the motor torque

    This mode is very popular (simple, robust, not expensive)

    Main contactor

  • Motorpact 2007-TL 10

    N1

    N

    e

    t

    w

    o

    r

    k

    Ct3

    Ct2

    Ct1

    Protection

    LoadMotor

    Auto Transformer module descriptionReduced voltage by auto-transformer

    This system is recommended for high power motors. It has the advantage of not dissipating energy.

    It can be used to obtain, for the same decrease in current, less reduction in torque than with the reactor starter.

    Auto-transformer

    CT1 : Start ContactorCT2 : Main Contactor CT3 : Run Contactor

  • Motorpact 2007-TL 11

    Soft starter setting: torque control

    T1 = k.I1 1

    LoadMotor

    Network

    Pro. Soft starter

    Reduced Voltage SoftStart motor starter (RVSS)SoftStart motor starter provides smooth, stepless acceleration and deceleration regardless of the load.This starting method lowers the starting current of the motor, reduces electrical stresses on the network and the motor.It reduces peak starting torque stresses on both the motor and mechanical load components, thereby providing longer service life and less downtime.

  • Motorpact 2007-TL 12

    Soft starter setting: usual setting

  • Motorpact 2007-TL 13

    FVNR & ATM descriptions Starting mode selection table

    RVSS

    Network requirement

    - accepts the current oscillation during an open transition?

    -accepts the starting reactive consumption power?

    Investment Increase

    - deceleration control ?

    - constant torque with high starting torque as crushers, grinders, mixers ......

    - the drive between motor and loadis able to withstand the mechanical stress of a direct on line start

    - accepts full starting current?- accepts starting voltage drop?

    yes

    yes

    yes

    yes

    no

    no

    no

    nono

    no

    yes

    yes

    no

    no

    - accepts the harmonics during the starting period

    VSDspecific

    no

    FVNR RVAT

    yes

    yes

    yes

    Motor & Load requirements

  • Motorpact 2007-TL 14

    OTHER TYPE OF MOTORPACT PANEL

    750

    2300

    2S2W: 2 Speed 2 Windingfull voltage non reversingasynchronous motor starter

  • Motorpact 2007-TL 15

    OTHER TYPE OF MOTORPACT PANEL

    750

    2S1W: 2 Speed 1 Windingfull voltage non reversingasynchronous motor starter (Star delta starter)

    375 750

    2300

  • Motorpact 2007-TL 16

    S3: Sequential Smart Start reduced voltage non reversing asynchronous motor starter

    375 750 750 750

  • Motorpact 2007-TL 17

    Dimension and weight

    FVNR RVAT RVSS

  • Motorpact 2007-TL 18

    Maximum motor ratings*

    200 AService Voltage kW (single fuse)3.3 kV 9005.5 kV 15006.6 kV 1800400 AService Voltage kW (single fuse) kW (double fuse)3.3 kV 950 19005.5 kV 1600 30006.6 kV 1900 3800

    *Maximum Rating depend on full load current, locked rotor current and run up time of motor.

  • Motorpact 2007-TL 19

    MotorpactTM MV motor starter

    Case : DOL (FVNR) Starter connected to the load as follow: Motor power : 750 kW Service voltage : 3.3 kV Freq : 50 Hz Cos Q : 0.85 Motor efficiency : 0.96 Service factor : 100% (Load Factor: 1) Starting current : 5 In Starting time : 10 s Number start per hours : 3

    Questions?How many ampere motor current ?How many ampere rating of the contactor ?How many ampere rating of the fuse ?

    Fuse calculator

  • Motorpact 2007-TL 20

    MotorpactTM MV motor starter

    Low voltage compartment (A) Disconnector (B) HRC fuses (C) Vacuum contactor (D) Complete motor protection

    with Sepam digital relay or others (E)

    A

    B

    C

    D

    E

  • Motorpact 2007-TL 21

    Easy to use

    All controls located at the same convenient operator height

    Disconnector operator & pilot devices

    Disconnector position viewing window Visible isolation and earthed indication

    at eye-level Optional back-light to view contact position

    Simple direct drive disconnectormechanism

    Ensures reliability and operator ease

    Mechanical interlocks Prevent access to MV compartment

    when the unit is energised

    Low cost of ownership

    Viewing window

  • Motorpact 2007-TL 22

    Operating panel

    Disconnector Closed Disconnector Open

  • Motorpact 2007-TL 23

    Disconnector

    2 positions Closed and Earthed

    Positive operation Earthed position by spring

    operation Interlocked to close

    MV door closed and contactor open

    Visible contacts Back-light for easy viewing

    (optional) Supports top fuse holders

  • Motorpact 2007-TL 24

    Voltage Presence Indication System (VPIS) (option) Line side available for

    Incoming cubicle(directincoming)

    Load side available at load terminal pads of motor starter

  • Motorpact 2007-TL 25

    Safety focus

    Loss of service continuity category LSC2A

    Partition Class PI(Cable earthing switch required)

    Closed door operation (only if MV door close)

    Electrical and mechanical interlocks Arc resistant type AFLR (optional) Cable earthing switch (optional) Voltage Presence Indication System

    (optional)

    Low cost of ownership

  • Motorpact 2007-TL 26

    Key InterlockLow cost of ownership

    DiSCONNECTOR KEY LOCK :Lock open only, key captiveMax 2 key lock

    EARTH SWITCH KEY LOCK :Max 1 key lockOpen or close lock

    LDA Key lock

    Disconnector key lock

  • Motorpact 2007-TL 27

    Busbar compartment

    Busbars up to 3150 A Bar cooper bar (standard) Tinned coated busbar (option) Silver coated busbar (option)

    Encapsulated/heatshrink busbars are available as an option

    Mounted and supported by the disconnector

    Short time withstand 50 kA 2s 40 kA 3s 31.5 kA 3s 25 kA 3s

  • Motorpact 2007-TL 28

    Busbar

    Spacer (intermediate panel)

    Main Busbar

    2000-2500A1250A 3000-3150A

    Intermediate Insulator support

  • Motorpact 2007-TL 29

    Busboot

    Intermediate bus boot For rating : 630A,1250A,2500A, 3150A Disconnector or Insulator

    End bus boot For rating : 630A,1250A,2500A, 3150A Disconnector or Insulator

  • Motorpact 2007-TL 30

    Main busbar jointing

  • Motorpact 2007-TL 31

    Load compartment

    Accessible only if contactor open and disconnector and cable are earthed

    Comprises :1. HRC fuses2. vacuum contactor3. LPCT4. cable termination optional :

    A. cable earthing switch with position viewing window B. Control Power Transformer C. Voltage Presence Indication System D. Fuse blown indicator

    2

    14vA

    Bv

    3

    CD

  • Motorpact 2007-TL 32

    LPCT or CT mounted on contactor (fixed contact mould assembly)

    Load compartment - instrument transformers

    Optional fused CPT (floor mounted)

    Optional VT for protection and meteringCPT

  • Motorpact 2007-TL 33

    Load compartment - MV fuses

    HRC DIN fuses independently mounted Easy to inspect and maintain Stricker blown fuse indicator Supplier: Fusarc(Schneider), SIBA, Bussman, Fuses for motor or non-motor loads 2 x 250 A Maximum

    Fuselogic Blown-fuse Indication (optional) With viewing window in door Blown-fuse fuse protection 2 Fuse blown aux contacts (SPDT)

  • Motorpact 2007-TL 34

    Load compartment - contactor In : 200 A and 400 A Withdrawable contactor truck Patented finger design Compact and lightweight

    20 kg - easy to handle Independently mounted from power fuses Contactor removed only for maintenance

    Magnetically held or mechanically latched Mechanically Close Open indicator Mechanical operating counter Aux power supply AC or DC,with range:

    DC range: 100/125 240/250V andAC range:115/120 230/240 (+10% ~ -15%). Voltage selection by using dip switch inside the contactor

    AC or DC aux power supply: internal supplied by CPT(AC) or external (AC or DC)

    Open release (for mech.latch) with DC supply only (48V, 125V and 250V).Additional tripping capasitor for AC aux supply (120VAC and 240VAC)

    Capasitor Trip (optional) install when using mech. Latched contactor and internal supply from CPT.

    Mismatch location

  • Motorpact 2007-TL 35

    Contactor aux Contact Additional Aux contact

  • Motorpact 2007-TL 36

    Contactor finger assembly Patented finger design Tests Temperature rise

    400 A continuous

    Mismatch/Blocking Contactorrating and type mismatch

    200 A unlatch

    200A latch 400A unlatch

    400A latch

  • Motorpact 2007-TL 37

    Contactor to outgoing terminal Cable : 200A 400A Differentiation by

    means blocking truck/mismatch

    Mismatch/Blocking Contactorrating and type mismatch

    200 A unlatch

    200A latch

    400A unlatch

    400A latch

  • Motorpact 2007-TL 38

    Load compartment - contactor

    Standard Operation for Magnetically held contactor

  • Motorpact 2007-TL 39

    Load compartment - contactor

    Standard Operation for Mechanically latch contactor w/o CTD

  • Motorpact 2007-TL 40

    Load compartment - contactor

    Standard Operation for Mechanically latch contactor with CTD

  • Motorpact 2007-TL 41

    TEST POSITION in MOTORPACT

    1. Open Disconnetor switch

    2. Supply aux power from external3. Contactor still connected4. Test the operation by control pushbutton sepam

    External supply

    K1K1

    From CPT

    Aux contact

  • Motorpact 2007-TL 42

    Low voltage compartment

    Ample space for : Sepam series 20/series 40

    and series 80 digital relay or Multilin PowerLogic Power Meter

    or Circuit Monitor Control devices

    Isolated from other compartments(busbar and load compartments)

    Integrated low voltage wireway (*) simplifies field wiring and installation of

    protection, control and communication

    Customer connection

  • Motorpact 2007-TL 43

    Motorpact aux contactsDisconnector switch aux contacts(Q1) : 4 SPDT , additional : 4 SPDT Fuse blown /Fuse logic aux contacts(FU1) : 2SPDT Earthing switch aux contacts (Q21): 4 SPDTMain contactor aux contacts (K1): 3NO+3NC, additonal : 3NO+3NC

    Note: SPDT stand for single pole double trip

  • Motorpact 2007-TL 44

    Motorpact contact resistance

    Descriptions Nominal valuesDisconnection Swicth 450 micro Ohm

    Busbar to the outgoing terminal 50.000 micro Ohm (including DS, VCU and outgoing terminal) (50 mili Ohm)

    Vacuum Contactor upper pole to lower pole (without load cable)

    < 200 micro Ohm

  • Motorpact 2007-TL 45

    Load compartment - contactor

    Connected position Withdrawn positionRail extended

  • Motorpact 2007-TL 46

    Load compartment - cable termination Front access or front and rear accessibility

    simple cable termination with rear access

    Full height cable pulling area Load cable box allows for up to 1-240 mm2

    or 2- 120mm per phase Formex cover over cable terminations

    provides coverage at cable terminations

  • Motorpact 2007-TL 47

    Typical cable termination

    Top and Bottom cable connection Line connection and load connection

  • Motorpact 2007-TL 48

    Typical cable termination for single section and single controller

    Top and Bottom cable connection

  • Motorpact 2007-TL 49

    Load compartment - cable earthing switch(option)

    Load cable termination

    Cable earthingswitch

    Formex cover

  • Motorpact 2007-TL 50

    Top cable clamp assy

    Top cable assy3 or 6 single core cable

    Top cable assy1 or 2 cores cable

  • Motorpact 2007-TL 51

    Lower cable clamp assy

    Top cable assy3 or 6 single core cable

    Lower cable assy2 cores cable

  • Motorpact 2007-TL 52

    Predictive maintenance

    Thermal diagnosis system (optional) Improved power availability

    detects abnormal temperaturerise at the heart of power circuit

    Increased safety of electrical installation help to prevent damage to the installation

    (deterioration can lead to an internal arc) Continuous monitoring of temperature rise

    reduces maintenance costs no local human intervention.

    Sensors installed in the sensitive areas cable connexions top MV fuses holders

    Activates 2 trip levels pre-alarm threshold alarm threshold

    Low cost of ownership

    Hold at the moment this offer

  • Motorpact 2007-TL 53

    Temperature monitor module (DT1)

    Provides continuous monitoring of joints in the equipment for predictive maintenance

  • Motorpact 2007-TL 54

    POWER FACTOR CORRECTION CAPASITOR

    3 phase capacitors without internal fuse Possible for FVNR with 750mm width Be careful for RVSS and S3

  • Motorpact 2007-TL 55

    Enclosure - internal arc withstand (option) Tested at KEMA

    following IEC 62271-200 standard in all MV compartments

    Protection on all 4 sides by pressure venting to the top

    25 kA 1s 40 kA 0.5s 50 kA 0.25s

    Tunnel for ceiling below < 4m

    With IP X1

  • Motorpact 2007-TL 56

    Enclosure IPX1 (option)

    IPX1 : Tunnel + roof No top entry cable (standard) non std for top entry

  • Motorpact 2007-TL 57

    Enclosure main earth bar

  • Motorpact 2007-TL 58

    Enclosure - internal arc withstand (option)

    8-point latching door

    Heavy-duty vault style door handle

    Interlocking of hinge side

    DoorFrame

  • Motorpact 2007-TL 59

    Enclosure - internal arc withstand (option) Pressure relief flaps

    Bolted rear panelsTop View

    Interlocked rear panel to frame construction Top and Bottom Access Panels Easy Removal

  • Motorpact 2007-TL 60

    Joining the shipping splits

  • Motorpact 2007-TL 61

    Sepam series 20, 40 and series 80

    Protection functions 50/51, 50N/51N, 46 49 R 38/49T 37, phase undercurrent 48/51LR, excessive starting time and locked

    rotor 66 starts per hour

    Options User Machine Interfaces Logic I/Os Communication interfaces Temperature monitoring Analog output

  • Motorpact 2007-TL 62

    current sensor (standard CT) One block sensor consits of 3 CTs Low burden < 2.5VA (ratio 50A) Protection class : 5P5 and 10P5 Metering class : 0.5, 1 and 3 Single depth and Double depth (

  • Motorpact 2007-TL 63

    Low power current transducer (standard LPCT)

    One sensor for all applications (50A ~ 400A)

    High accuracy for protection and metering

    Linear across a wide current range

    Saturation value above 16 kA

    2500/1 0.5625

    100A / 22.5 mV Sepam

    Measuring andProtection

    5A 20A 100A 800A 1000A 16000 A0.5%

    0.75%

    1.5%

    5.0%

    10.0%Accuracy

  • Motorpact 2007-TL 64

    Control Power Transformer (CPT) Auxiliary Control Power supply :

    External DC or AC supply Internal AC supply by using CPT

    CPT or VRCR(small burden:200VA) Power CPT : 300VA, 500VA, 750VA and 2000VA MV Primary fuse for CPT (Ph-Ph) : 0.63A, 1A, 2A and 3.15A.

    Ferraz fuse. Fuse holders are loacated below the contactor.

    Secondary of CPT is protected by MCB Primary Voltage : 2400V, 3300, 4160, 4800, 5000, 5500,

    6000V, 6600V,6900V

    Secondary voltage: 110/220V (dual voltage) Freq: 50/60Hz

    CPT & VT Fuse holder

  • Motorpact 2007-TL 65

    Voltage Transformer (VT) Voltage for metering device or protection relay Power Output: 50VA/Phase (100VA) at 30 deg. C.

    Accuracy : 2.4% at 15VA Primary VT is protected by MV fuses Secondary side is protected by MCB Primary Voltage : 2400V, 3300, 4200, 4800, 5000, 5500,

    6000V, 6600V,6900V(6300V under development) Freq; 50/60Hz Insulation level : 6.9kV (60kV BIL) Secondary voltage: 110V

    CPT & VT Fuse holder

  • Motorpact 2007-TL 66

    Fuse tube

    Fuse holder for primary fuse of CPT or/and VT Long tube : (20mm x 190mm) for voltage > 5.5kV Short tube : (20mm x 127mm) for voltage < 5.5kV

    Thermal rating max : 5A . Insulation level : 6.9kV (60kV BIL) No special tools to remove or insert the MV fuse Located below the contactor chassis

  • Motorpact 2007-TL 67

    Ground Fault sensor

    With Sepam relay If solidly Grounded (low resistance)

    ZCT 50/5A(AAF00309) + CSH 30 or CSH 120 or 200

    If High Resistance Grounded (un grounded system) CSH 280 (470/1 - AAF 00311) + Resistor for zero sensor

    Others relay (Without Sepam relay ) If solidly Grounded (low resistance)

    ZCT 50/5A If High Resistance Grounded (un grounded system)

    Zero seq. Sensor 2000/1 (AAF00310) or Zero seq. Sensor 50/0.025 (AAF00308)

    Note: the above sensor is installed on the same place of the block CT

    AAF00309AAF00311AAF00310AAF00308

    CSH 120/200

  • Motorpact 2007-TL 68

    Surge Arrestor Distribution Class and Intermediate Class

    distribution class : near the load (low kA) Intermediate class : outgoing feeders with

    several downstream feeders (high kA) Line side or Load side

    Line side : install on the busbar side Load side : install on the cable load side

    Rated Voltage : 3kV, 6kV and 9KV 6kV for service voltage : < 5kV 9 kV for service voltage : > 5kV

  • Motorpact 2007-TL 69

    MV motor starter FVNR basic single line diagram

    HRC fuses

    Withdrawable vacuum contactor

    LPCT

    Cable earthingswitch (optional)

    Sepam series 20,40 or 80

    Disconnectorclosed/ earthed

  • Motorpact 2007-TL 70

    MV motor starter FVNR with options

    Second set of CTs

    Control PowerTransformer

    CPT fuses

  • Motorpact 2007-TL 71

    Reduced Voltage Solid State (RVSS)

    Ranges 2300V up to 2300kw 3300V up to 3400kw 4160V up to 4300kw 6900V up to 7100kw

    50 / 60 Hz

    Full Digital Control

    Motorpact Soft Start

  • Motorpact 2007-TL 72

    Reduced Voltage Solid State (RVSS)

    Advanced Motor Protection Options:

    Ground Fault RTD modules

    Heavy Duty Silicon Control Rectifier (SCR) stack

    Arc Resistant

    Motorpact Soft Start

  • Motorpact 2007-TL 73

    Motorpact RVSS - HMI Full digital control

    LCD operator interface Non-Volatile memory

    Digital sequencer Ensures proper contactor sequence

    Fiber-Optic isolation between digital controller and

    power module/SCR Metering functions

    Voltage Current Power Factor KVAR kW

  • Motorpact 2007-TL 74

    Pumps Blowers Compressors Chillers Fans Chippers

    Ball Mills Rod Mills Conveyors Natural Gas Compressors Centrifugal Blowers Other Applications

    Motorpact Soft Start Controller Applications

  • Motorpact 2007-TL 75

    Protect the Motor and Load Reduce Mechanical Stress Limit Starting Current Reduce Stress on the Electrical Grid Reduce Electrical System Disturbance Provide Soft Stopping

    Meter and Record Communicate

    6 Goals Beyond On-OffMotorpact SoftStart

  • Motorpact 2007-TL 76

    Benefits

    Eliminate Torque Shock Damage Prevent belt slipping, coupling damage Increases motor AND drive train reliability

    Keep Starting kVA to a Minimum Maintain future flexibility

    Soft Start and Soft Stop Pumps Reduce hydraulic / mechanical problems

    Low Cost Ratio vs. MV VFDs Can be considered as an alternate in some cases

    Motorpact SoftStart

  • Motorpact 2007-TL 77

    Heavy Duty Ratings 500% for 60 Seconds

    Nearest competitor is 500% for 30 sec. 600% for 30+ Seconds

    Capable of Class 30 Mill Duty motors 200% for up to 2 Minutes

    Allows for long accel times Tested at 50C

    Most others tested at 40 C

    Motorpact SoftStart

  • Motorpact 2007-TL 78

    Line disconnectorIsolates motor starter from power supply

    Vacuum contactorProvides start sequence to SCR stack (in main contactor cubicle)SCR stackProvides voltage ramp and advanced protection features

    By-pass contactorBy-passes the SCR when motor is at full speed

    LV controlControl and HMI of motor starter with power system

    1

    2

    3

    4

    5

    1

    3

    2

    4

    5

    3

    4

    5

    Compartment 1 Compartment 2

    Compartment 2

    Motorpact SoftStart

  • Motorpact 2007-TL 79

    High MV to LV Electrical Isolation Magnetic isolation of Gate Pulses Fiber optic isolation

    for firing control and signal interfaces

    Door Interlocking Isolated LV Compartment

    Designed for Safety

    Motorpact SoftStart

  • Motorpact 2007-TL 80

    Sensing Systems

    = 28V

    = MV

    MTRMTR

    Magnetic Isolation

    OpticalIsolation

    = Fiber Optic

    = 120V

    Gate Drive

    Electrical Isolation Diagram

    LVControls

    Motorpact SoftStart

  • Motorpact 2007-TL 81

    Reduced voltage auto-transformer motor starter (RVAT)

    Line current lower than motor current Provides high torque per A of

    line current Medium or heavy duty 3 Contactors Main(1), Run(2), Start(3) Includes surge protection

    Provides switching transient protection for autotransformer

    50, 65, and 80 % Taps (4) Closed transition from start to run 1125 mm or 1500 mm width. Internal arc withstand Auto Transformer capacity (50Hz)

  • Motorpact 2007-TL 82

    Reduced voltage auto-transformer motor starter

    MAIN CONTACTOR

    STARTCONTACTOR

    RUNCONTACTOR

    AUTO TRANSFORMER

    1 2

    3

    4

  • Motorpact 2007-TL 83

    M

    (A)

    (C)

    (B)

    M

    (A)

    (C)

    (B)

    M

    (A)

    (C)

    (B)

    First stage :C is openA and B are closedB must be closed before A.

    Second stage :A remains closedC remains openand B is opened

    Third stage :A remains closedB remains openand C is closed

    The current path is shown in red.It is obvious that the motor is always supplied even during the second stage, when B is open.

    First stage : the motor is starting with reduced voltage.Second stage: the motor is running in series with part of the autotransformer winding.Third stage: the motor runs at full voltage.

    RVAT

  • Motorpact 2007-TL 84

    Incoming LV cables from below,cubicle by cubicle

    1 2

    3 4

  • Motorpact 2007-TL 85

    Incoming LV cables from top,cubicle by cubicle

  • Motorpact 2007-TL 86

    Civil engineeringLined up with MCset switchgear Incomer - Bus sectioning - IncomerMC set Motorpactinterface

  • Motorpact 2007-TL 87

    Civil engineeringstand-alone motor control with RVSS SoftStartTM motor starter

    3150 A Busbar

    Incoming cable and metering

    Front

  • Motorpact 2007-TL 88

    Incoming cable and metering

    Front

    MotorpactMV motor startersSmart choice for MV- MCC application

  • Motorpact 2007-TL 89

    Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity

    Loss of Service Continuity

    Class (LSC) Architecture based on safe compartment access

    LSC 2A Safe access to compartment

    With power flow in busbar and the other units

    MV Cables must be earthed

    Safe access to compartment

    With power flow in busbar and the other units

    MV Cable in separate compartment

    Cable of unit under maintenance can remain energized

    LSC 2B

    Metal enclosed not of LSC2 class

    LSC 1

    Maintainability of defined parts with no need of cable disconnection (separate cable compartment)

    Maintainability of one functional unit allowing normal service of the remaining units of the switchboard (busbar in a separate compartment)

    Several levels of service continuity during maintenance

    MOTORPACTMOTORPACT

  • Motorpact 2007-TL 90

    Partition Class PM

    All partitions and shutters of safe access compartment shall be metallic with some current carrying capacity

    Metal enclosedcompliant during maintenanceApplicable mainly to withdrawable system

    Partition ClassI or M

    Classification based on electrical field presence in safe access compartment

    Partition Class PI

    Partitions or shutters may be partially or totally of insulating material

    Electrical and mechanical safety according to IEC 60466 or 60137

    Personnel comfort during maintenance

    3.110 ShutterPart of metal-enclosed switchgear and controlgear that can be moved from a position where it permits contacts of a removable part, or moving contact of a disconnector to engage fixed contacts, to a position where it becomes a part of the enclosure or partition shielding the fixed contacts.

    MotorpactMotorpact

    Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity

    Definition

  • Motorpact 2007-TL 91

    Motorpact to IEC 62271-200Fully enclosed in metal enclosure and having current carrying capacity

    IAC classified No projection of parts towards accessible sides

    No ignition of indicators

    Safety in case of internal fault during service conditionDemonstrated by type tests(completely defined by the standard)

    Internal Arc ClassIAC

    Classification based on consequences of internal arc on personnel safety

    Personnel safety in case of internal arc

    IAC not classified

    No tests performed to assess behavior of enclosure under arc conditions

    A : restricted to authorized personnel only.

    B : unrestricted, including general public.

    Enclosure Identification code: F - for Front side

    L L - for Lateral sideR - for Rear side

    Accessibility Types Motorpactcomplies with AFLR type

  • Motorpact 2007-TL 92

  • Motorpact 2007-TL 93

  • Motorpact 2007-TL 94

  • Motorpact 2007-TL 95

  • Motorpact 2007-TL 96

  • Motorpact 2007-TL 97

  • Motorpact 2007-TL 98

  • Motorpact 2007-TL 99

  • Motorpact 2007-TL 100

  • Motorpact 2007-TL 101

  • Motorpact 2007-TL 102

  • Motorpact 2007-TL 103

  • Motorpact 2007-TL 104

  • Motorpact 2007-TL 105

  • Motorpact 2007-TL 106

  • Motorpact 2007-TL 107

  • Motorpact 2007-TL 108

  • Motorpact 2007-TL 109

  • Motorpact 2007-TL 110

  • Motorpact 2007-TL 111

  • Motorpact 2007-TL 112

  • Motorpact 2007-TL 113

  • Motorpact 2007-TL 114

    Redundant S3Alternate Configuration

    One SoftStart used to start all motors Second SoftStart used as back up in case first fails. SoftStart has incoming and outgoing contactors for isolation