Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are...

31
Miami-DERM Submittal Packet What’s included? 1. Trapzilla99 Grease Interceptor Spec Sheet 2. Trapzilla99 Grease Interceptor Test Report 3. Trapzilla Solids Separator Spec Sheet 4. Trapzilla Sample Port Spec Sheets 5. Flow Control Spec Sheets 6. FOG 2.0 RER-DERM Summary 7. Trapzilla99 Grease Interceptor Manual Questions? Need more information? Contact Seth Markwood [email protected] 800-633-4204 x228

Transcript of Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are...

Page 1: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

Miami-DERM Submittal Packet

What’s included?

1. Trapzilla99 Grease Interceptor Spec Sheet

2. Trapzilla99 Grease Interceptor Test Report

3. Trapzilla Solids Separator Spec Sheet

4. Trapzilla Sample Port Spec Sheets

5. Flow Control Spec Sheets

6. FOG 2.0 RER-DERM Summary

7. Trapzilla99 Grease Interceptor Manual

Questions? Need more information?

Contact Seth Markwood

[email protected]

800-633-4204 x228

Page 2: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

Trapzilla® Grease Interceptor

©2019 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 16/19

TZ-1826-ECA Specifications

PRODUCT FEATURESConstructed of corrosion resistant materials suitable for installation in virtually any location. Compact footprint.Ba e structure retains separated grease increasing retention e ficienc o separator.Included lid rated or oot-tra fic onlIncludes dual 0-18 extension collars or in-ground installation.

eets (or exceeds) iami 99 e ficienc re uirement

SPECIFICATIONSConstruction: Single-Piece otationall olded Pol eth lene xterior Tan with Inlet/ Outlet Inverts secured using Patented Interior adial Compression ing

low ating 100 gpm (6.31 l/s)i uid Capacit 274 gallons (1,037 )

Grease Capacity: 248.77 Gallons (941 L) 1,826 lbs. (828 g)

emoval ficienc 99.2% Solids Capacity: 74 gallons (280 )Inlet/Outlet 4” (101 mm)Product eight 250 lbs. (113 g)

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

END VIEWCOLLARFLUSH

(TRIMMED)

SIDE VIEWMAXIMUMCOLLAR

EXTENSION

10 in [25.4 cm] CLEARANCE FROMTOP OF TANK REQUIRED FOR LID REMOVAL

18.0 in[45.7 cm]

MAXEXTENSION

13.1 in[33.3 cm]

14.1 in[35.9 cm]

OUTLET4 inPIPESIZE

INLET4 inPIPESIZE

TOP VIEW

2 in VENT

41.1 in[104.5 cm]

40.1 in[101.9 cm]

34.0 in[86.4 cm]

54.3 in[137.8 cm]

4.5 in[11.4 cm]

INLET

4.5 in[11.4 cm]OUTLET

78.5 in[199.4 cm]

39.0 in[99.1 cm]

73.0 in[185.4 cm]

12.8 in[32.4 cm]

28.0 in[71.1 cm]

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

END VIEWCOLLARFLUSH

(TRIMMED)

SIDE VIEWMAXIMUMCOLLAR

EXTENSION

10 in [25.4 cm] CLEARANCE FROMTOP OF TANK REQUIRED FOR LID REMOVAL

18.0 in[45.7 cm]

MAXEXTENSION

13.1 in[33.3 cm]

14.1 in[35.9 cm]

OUTLET4 inPIPESIZE

INLET4 inPIPESIZE

TOP VIEW

2 in VENT

41.1 in[104.5 cm]

40.1 in[101.9 cm]

34.0 in[86.4 cm]

54.3 in[137.8 cm]

4.5 in[11.4 cm]

INLET

4.5 in[11.4 cm]OUTLET

78.5 in[199.4 cm]

39.0 in[99.1 cm]

73.0 in[185.4 cm]

12.8 in[32.4 cm]

28.0 in[71.1 cm]

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

END VIEWCOLLARFLUSH

(TRIMMED)

SIDE VIEWMAXIMUMCOLLAR

EXTENSION

10 in [25.4 cm] CLEARANCE FROMTOP OF TANK REQUIRED FOR LID REMOVAL

18.0 in[45.7 cm]

MAXEXTENSION

13.1 in[33.3 cm]

14.1 in[35.9 cm]

OUTLET4 inPIPESIZE

INLET4 inPIPESIZE

TOP VIEW

2 in VENT

41.1 in[104.5 cm]

40.1 in[101.9 cm]

34.0 in[86.4 cm]

54.3 in[137.8 cm]

4.5 in[11.4 cm]

INLET

4.5 in[11.4 cm]OUTLET

78.5 in[199.4 cm]

39.0 in[99.1 cm]

73.0 in[185.4 cm]

12.8 in[32.4 cm]

28.0 in[71.1 cm]

®®Conforms to ASME StandardASME A112.14.3-2000

Page 3: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2019 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without notice6/19 Thermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 2

Trapzilla® Grease Interceptor

TZ-1826-ECA SpecificationsNOTES1. A instruction manual included with s stem be ore installing/operating.2. nit re uires 6 (15.24 cm) o clearance all the wa around the lid rom walls or other structures to allow or servicing.3. a e piping connections with rubber No ub connectors.4. eep outlet piping as straight as possible. se onl sweep connections.5. Install vent on outlet piping.6. I installing in conjunction with other Trapzilla products, include cleanout port be ore, a ter, and/or between each unit.7. o not install P Trap on outlet connection o tan (unit alread has internal gas trap).8. o not reduce pipe size on outlet piping9. Do not pressure test unit.

uipment must be installed in compliance with all applicable laws, regulations and codes, including plumbing codes. Instal-lation should be per ormed b a ualified plumbing contractor.

JOB SPECIFICATIONrease separator(s) shall be Thermaco Trapzilla99 h dromechanical grease interceptor s stem(s) as manu actured b Ther-

maco, Inc., Asheboro, North Carolina as noted on plans.

SEPARATOR SPECIFICATIONSurnish and install Thermaco Trapzilla99 odel No. T -1826- CA, rotationall molded pol eth lene grease

interceptor(s) or above ground installation, shall be P I- 101 and AS A112.14.3 rated at 100 P (6.31 l/s) with 248.77 allons (941 ) / 1,826 lbs. (828 g) o total grease storage capacit with at separation e ficienc curve capable o holding

90 o volume in ree- oating oils at capacit , with removable cover or grease and solids removal access, integral anti- otation anchor ring or in-ground installation, integral horizontal ba e, laminar inlet ow diverter, integral vessel vent, separate storage compartments or oil and heavier than water solids, a unitar tan bod and 4 (101mm) inlet/outlet structures without gas et inter aces, utilizing an interior radial compression ring conjoining invert to tan outlet/inlet structures without bul head fittings and/or gas ets, invert top and bottom secured attachment points, sloping conical bottom or solids retention, integral sewer gas trap, and a ull removable pol eth lene sel -positioning cover with sealed thread asteners. Includes dual-entr extension collar assembl , linear low-densit rotationall molded pol eth lene or field adjustabilit to optimal installation depth.

SUBMITTAL OPTIONS 6 (150mm) Inlet/Outlet - odel T -1826- CA-6 Two CA-T -29 xtension Collars (Two re uired or each T -1826- CA) T SP-40- CA Sampling Port with 4 Inlet/Outlet, 0.5 all with 29 (73.7 cm) xtension Collar Assembl T SP-48- CA Sampling Port with 4 Inlet/Outlet, 7.8 all with 29 (73.7 cm) xtension Collar Assembl TSS-95 Solids Interceptor or additional Solids Capacit TSS-95- CA Solids Interceptor or additional Solids Capacit with 18 (45.7 cm) adjustable extension collar CA-100 ented low Control Assembl or installation at plumbing fixture level to limit ow to 100 gpm or installations with

head height greater than 6 S -44 olded low Splitter Assembl or evenl diverting ow to two separate 4 Trapzilla units S -66 olded low Splitter Assembl or evenl diverting ow to two separate 6 Trapzilla units 20/Tra fic ated Installation, see lin or installation drawings

Page 4: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

Report Number: 907-15010 Report Issued: March 2nd, 2015 Client: Thermaco Project Number: 24390 646 Greensboro St. Asheboro, NC 27203 Contact: Bill Batten Source of Samples: Samples were manufactured at the Thermaco facility in Asheboro, North

Carolina and witnessed tested by Dale E. Holloway of IAPMO R&T Lab. Samples are manufactured in good condition.

Date of Testing: February 23rd, 2015 through February 27th, 2015 Sample Description: Model “TZ-1826” Grease Interceptor. Refer to the manufacturer’s drawings and installation instructions for more

detailed measurements and information. Scope of Testing: The above grease interceptor was witnessed tested to meet the

requirements of ASME A112.14.3-2000 (Reaffirmed 2004) “Grease Interceptors”.

Conclusion: The “TZ-1826” Grease Interceptor DID COMPLY with the

requirements of ASME A112.14.3-2000 (Reaffirmed 2004) for “Grease Interceptors”.

By the signature below, I certify that all the testing and preparation for this report was performed under direct supervision of IAPMO R&T Lab, unless otherwise stated. Witness tested and reported by,

Dale E. Holloway, Regional Technical Manager IAPMO R&T Lab

Page 5: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

Report No. 907-15010 Page 13 of 13

TZ-1826 Grease Interceptor INCREMENTAL ACCUMULATED Test No. Grease

Sink Water Sink

Drop Time (sec)

Flow Rate

(GPM)

Lbs added

Lbs skimmed

Lbs retained

Efficiency (%)

Lbs added

Lbs skimmed

Lbs retained

Efficiency (%)

90 2 1 112 101.8 20 0.35 19.65 98.3% 1800 12.41 1787.59 99.3% 91 1 2 111 102.7 20 0.48 19.52 97.6% 1820 12.89 1807.11 99.3% 92 2 1 111 102.7 20 0.38 19.62 98.1% 1840 13.27 1826.73 99.3% 93 1 2 111 102.7 20 19.99 0.01 0.1% 1860 33.26 1826.74 99.2% 94 2 1 111 102.7 20 9.35 10.65 53.3% 1880 42.61 1837.39 97.7%

Performance Requirement Maximum Capacity

Page 6: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

T. BORN 9-JAN-171/2" = 1'-0"

TZ-1826 CONCRETE RELIEVING SLABTHERMACO, INC.

SECTION & SPECIFICATIONSRELIEVING SLAB PLAN,

1 RELIEVING SLAB PLAN

2 RELIEVING SLAB SECTION

TZ-1826 H20/TRAFFIC RATED RELIEVING SLAB PLAN & SPECIFICATIONS

A THERMACO® Technology

PO Box 2548, Asheboro, NC 27204-2548Phone: (336) 629-4651 • Toll-Free: (800) 633-4204

[email protected] • www.trapzilla.com

The installation techniques, handling, and use of this product are beyond Thermaco’s control. Therefore, Thermaco assumes no responsibility for

loss, damage or expense resulting from improper handling, or use.

Page 7: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

Trapzilla® Solids Separator

A THERMACO® Technology

©2016 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 17/16

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

4.5 in[11.4 cm]

4.5 in[11.4 cm]

42.5 in[108.0 cm]38.3 in

[97.2 cm]

36.0 in[91.4 cm]

14.1 in[35.9 cm]

31.0 in[78.7 cm]

18.0 in[45.7 cm]

12.5 in[31.8 cm]

37.0 in[94.0 cm]

36.5 in[92.7 cm]

13.0 in[33.0 cm]

49.5 in[125.7 cm]

10 in [25.4 cm] CLEARANCE FROMTOP OF TANK REQUIRED FOR LID REMOVAL

2 in VENT

SIDE VIEWMAXIMUMCOLLAR

EXTENSION

END VIEWCOLLARFLUSH

(TRIMMED)

� in PIPE INLETAND OUTLET

TOP VIEW

OUTLET

INLET

INLET PIPE

OUTLET PIPE

TSS- -ECA Specifications

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

4.5 in[11.4 cm]

4.5 in[11.4 cm]

42.5 in[108.0 cm]38.3 in

[97.2 cm]

36.0 in[91.4 cm]

14.1 in[35.9 cm]

31.0 in[78.7 cm]

18.0 in[45.7 cm]

12.5 in[31.8 cm]

37.0 in[94.0 cm]

36.5 in[92.7 cm]

13.0 in[33.0 cm]

49.5 in[125.7 cm]

10 in [25.4 cm] CLEARANCE FROMTOP OF TANK REQUIRED FOR LID REMOVAL

2 in VENT

SIDE VIEWMAXIMUMCOLLAR

EXTENSION

END VIEWCOLLARFLUSH

(TRIMMED)

� in PIPE INLETAND OUTLET

TOP VIEW

OUTLET

INLET

INLET PIPE

OUTLET PIPE

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

4.5 in[11.4 cm]

4.5 in[11.4 cm]

42.5 in[108.0 cm]38.3 in

[97.2 cm]

36.0 in[91.4 cm]

14.1 in[35.9 cm]

31.0 in[78.7 cm]

18.0 in[45.7 cm]

12.5 in[31.8 cm]

37.0 in[94.0 cm]

36.5 in[92.7 cm]

13.0 in[33.0 cm]

49.5 in[125.7 cm]

10 in [25.4 cm] CLEARANCE FROMTOP OF TANK REQUIRED FOR LID REMOVAL

2 in VENT

SIDE VIEWMAXIMUMCOLLAR

EXTENSION

END VIEWCOLLARFLUSH

(TRIMMED)

� in PIPE INLETAND OUTLET

TOP VIEW

OUTLET

INLET

INLET PIPE

OUTLET PIPE

PRODUCT FEATURESConstructed of corrosion resistant materials suitable for installation in virtually any location. Compact footprint.Ba e structure retains separated solids permitting ow o grease, oil, and water.Included lid rated or oot-tra fic onl .Includes one ECALA-TSS-18 Extension Collar Adapter Lid Assembly or in-ground installation.

SPECIFICATIONSConstruction: Single-Piece otationall olded Pol eth lene xterior Tan with Inlet/ Outlet Inverts secured using Patented Interior adial Compression ing

low ating 150 P (9.46 l/s)Liquid Capacity: 95 gallons (359 l)Solids Capacity: 95 gallons (359 l)Inlet/Outlet 4 (101 mm)

Page 8: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2016 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without notice7/16 Thermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 2

Trapzilla® Solids Separator

A THERMACO® Technology TSS- -ECA Specifications

NOTES1. A instruction manual included with s stem be ore installing/operating.2. nit re uires 6 (15.24 cm) o clearance all the wa around the lid rom walls or other structures to allow or servicing.3. a e piping connections with rubber No ub connectors.4. eep outlet piping as straight as possible. se onl sweep connections.5. Install vent on outlet piping.6. I installing in conjunction with other Trapzilla products, include cleanout port be ore, a ter, and/or between each unit.7. o not install P Trap on outlet connection o tan (unit alread has internal gas trap).8. o not reduce pipe size on outlet piping9. o not pressure test unit.

uipment must be installed in compliance with all applicable laws, regulations and codes, including plumbing codes. Instal-lation should be per ormed b a ualified plumbing contractor.

JOB SPECIFICATIONSolids separator(s) shall be Thermaco Trapzilla solids interceptor s stem(s) as manu actured b Thermaco, Inc., Asheboro, North Carolina as noted on plans.

SEPARATOR SPECIFICATIONSurnish and install Thermaco Trapzilla odel No. TSS-95- CA, rotationall molded pol eth lene solids separator(s)

or below ground installation, shall be rated at 150 gpm (9.46 l/s) with 95 gallons (359 l) o total solids storage capacit , with re-movable cover or solids removal access, integral anti- otation anchor ring or in-ground installation, laminar inlet ow diverter, integral vessel vent, a unitar tan bod and 4 (101 mm) inlet/outlet structures without gas et inter aces, utilizing an interior radial compression ring conjoining invert to tan outlet/inlet structures without bul head fittings and/or gas ets, sloping conical bottom, integral sewer gas trap, and a ull removable pol eth lene sel -positioning cover with sealed thread asteners. Includes one extension collar assembl , linear low-densit rotationall molded pol eth lene or field adjustabilit to optimal installation depth.

SUBMITTAL OPTIONS 6 (150mm) Inlet/Outlet - odel TSS-95- CA-6 CA-TSS-29 xtension Collar with additional 29 (73.7 cm) o extension T SP-40- CA Sampling Port with 4 Inlet/Outlet, 0.5 all with 29 (73.7 cm) xtension Collar Assembl T SP-48- CA Sampling Port with 4 Inlet/Outlet, 7.8 all with 29 (73.7 cm) xtension Collar Assembl CA-75 ented low Control Assembl or installation at plumbing fixture level to limit ow to 75 gpm or installations with

head height greater than 6 S -44 olded low Splitter Assembl or evenl diverting ow to two separate 4 Trapzilla units S -66 olded low Splitter Assembl or evenl diverting ow to two separate 6 Trapzilla units TCA-22 abricated Top Cover Assembl with 22 (55.9 cm) diameter diamond plate aluminum sur ace or heav dut

oot-tra fic, pallet jac s, ood carts etc. eplaces standard 22 STC-T -22 Cover (not rated or vehicle tra fic) 20/Tra fic ated Installation, see lin or installation drawings

Page 9: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

Trapzilla® Sampling Port

A THERMACO® Technology

©2017 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 15/17

TZSP-48-ECA Specifications

1

1

2

2

3

3

4

4

A A

B B

C C

D D

�� �� � � � � ���� �THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

END VIEW

MAXIMUM

COLLAR

EXTENSION

(TRIMMED)

10 in [25.4 cm]

CLEARANCE FROM

TOP OF TANK

REQUIRED FOR LID

REMOVAL

SIDE VIEW

MAXIMUM

COLLAR

EXTENSION

OUTLET

INLET

4.5 in

[11.4 cm]

� 4.5 in

[11.4 cm]

26 in

[66 cm]

26.5 in

[67.3 cm]

22 in

[55.9 cm]

4 in

[10.2 cm]

17.8 in

[45.2 cm]

29.3 in

[74.3 cm]

7.8 in

[19.8 cm]

15.6 in

[39.5 cm]

4" PIPE

INLET/OUTLET

6 in

[15.3 cm]

PRODUCT FEATURES

Constructed of corrosion resistant materials suitable for installation

in virtually any location.

Compact footprint.

7.8 (198 mm) all to meet vertical water all filling access.Patent-pending ume technolog narrows and accelerates incoming ows allowing sampling despite lac o substantial all gradient.

Includes one CA-T -29 xtension Collar or in-ground installation.

SPECIFICATIONS

Construction: Single-Piece otationall olded Pol eth lene xterior Tan with Patented Interior adial Compression ing Securing Patent-Pending oationall olded Inlet lume

all radient 7.8” (198 mm)

Inlet/Outlet: 4” (102 mm)

1

1

2

2

3

3

4

4

A A

B B

C C

D D

�� �� � � � � ���� �THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

END VIEW

MAXIMUM

COLLAR

EXTENSION

(TRIMMED)

10 in [25.4 cm]

CLEARANCE FROM

TOP OF TANK

REQUIRED FOR LID

REMOVAL

SIDE VIEW

MAXIMUM

COLLAR

EXTENSION

OUTLET

INLET

4.5 in

[11.4 cm]

� 4.5 in

[11.4 cm]

26 in

[66 cm]

26.5 in

[67.3 cm]

22 in

[55.9 cm]

4 in

[10.2 cm]

17.8 in

[45.2 cm]

29.3 in

[74.3 cm]

7.8 in

[19.8 cm]

15.6 in

[39.5 cm]

4" PIPE

INLET/OUTLET

6 in

[15.3 cm]

1

1

2

2

3

3

4

4

A A

B B

C C

D D

�� �� � � � � ���� �THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

END VIEW

MAXIMUM

COLLAR

EXTENSION

(TRIMMED)

10 in [25.4 cm]

CLEARANCE FROM

TOP OF TANK

REQUIRED FOR LID

REMOVAL

SIDE VIEW

MAXIMUM

COLLAR

EXTENSION

OUTLET

INLET

4.5 in

[11.4 cm]

� 4.5 in

[11.4 cm]

26 in

[66 cm]

26.5 in

[67.3 cm]

22 in

[55.9 cm]

4 in

[10.2 cm]

17.8 in

[45.2 cm]

29.3 in

[74.3 cm]

7.8 in

[19.8 cm]

15.6 in

[39.5 cm]

4" PIPE

INLET/OUTLET

6 in

[15.3 cm]

Page 10: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2017 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without notice5/17 Thermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 2

Trapzilla® Sampling Port

A THERMACO® Technology TZSP-48-ECA Specifications

NOTES

1. A instruction manual included with s stem be ore installing/operating.2. nit re uires 6 (15.24 cm) o clearance all the wa around the lid rom walls or other structures to allow or servicing.3. a e piping connections with rubber No ub connectors.4. eep outlet piping as straight as possible. se onl sweep connections.5. Install vent on outlet piping.6. I installing in conjunction with other Trapzilla products, include cleanout port be ore, a ter, and/or between each unit.7. o not install P Trap on outlet connection o tan (unit alread has internal gas trap).8. o not reduce pipe size on outlet piping9. o not pressure test unit.

uipment must be installed in compliance with all applicable laws, regulations and codes, including plumbing codes. Instal-lation should be per ormed b a ualified plumbing contractor.

JOB SPECIFICATION

astewater Sampling Port(s) shall be Thermaco Trapzilla Sampling Port as manu actured b Thermaco, Inc., Asheboro, North Carolina as noted on plans.

SAMPLING PORT SPECIFICATIONS

urnish and install Thermaco Trapzilla odel No. T SP-48, linear low-densit rotationall molded pol eth lene waste-

water sampling port(s) or below-ground installation with ull removable pol eth lene sel -positioning e ed cover e uipped with brass asteners or sampling access, 7.8 (198mm) all or veritcal water all filling access, 4 (102 mm) Inlet/Outlet interior diameter, and patent-pending ume technolog or preventing sediment build-up in inlet. Includes one CA-T -29 extension collar assembl , linear low-densit rotationall molded pol eth lene or field adjustabilit to optimal installation depth.

SAMPLING PORT INTERNAL COMPONENTS AND OPERATION

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

TSP-48 for "offset"pipe installations

Inlet

Outlet

Sample Jar in Carrier -Jar sits vertically on

flat bottom

Flume narrows flow,accelerates flow, and

directs flow into jar

rab Sampler ( S-1) and Sample Jar Sold Separately

Page 11: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2017 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without notice5/17 Thermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 1

Trapzilla® Sample Ports

A THERMACO® Technology TZSP-40 Specifications

TECHNICAL DATAMaterials:Inlet/Outlet Size:Fall Gradient:

Rotationally Molded Polyethylene4” (102 mm)

0.5” (12.7 mm)

FEATURES:• Constructed of corrosion resistant materials

suitable for installation in virtually any location.

• Compact footprint.• 0.5” (12.7 mm) fall for horizontal filling access.• Optional field-modifiable extension collar

available to bring lid up to grade.• Patent-pending flume technology narrows and

accelerates incoming flows allowing sampling despite lack of substantial fall gradient.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

�� �� � � � � ���� �THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

4.5 in[11.4 cm]

4.5 in[11.4 cm]

26 in[66.0 cm]

8.3 in[21.1 cm]

7.8 in[19.8 cm]

11.1 in[28.1 cm]

7 in[17.8 cm]

10 in [25.4 cm]CLEARANCE FROMTOP OF TANK REQUIRED FOR

LID REMOVAL

INLETOUTLET

SIDE VIEW

END VIEW

4" PIPEINLET/OUTLET

TOP VIEW

22 in[55.9 cm]

Page 12: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2017 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without notice5/17 Thermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.trapzilla.com 2

Trapzilla® Sample Ports

READ instruction manual included with system before doing anything.

Install unit allowing for the minimum clearances shown.

Make piping connections with rubber “No Hub” connectors.

Keep outlet piping as straight as pos-sible. Use only “sweep” connections.

If installing in conjuction with other Thermaco products, include cleanout port between each unit.

DO NOT reduce pipe size on outlet piping.

DO NOT install “P” trap on outlet connection.

INSTALLATION INFORMATION

Suggested Minimum Footprint Dimensions

NOTE: Drawing for reference only. Equip-ment must be installed in compliance with all applicable laws, regulations and codes, including plumbing codes. Installation should be performed by a qualified plumber.

A THERMACO® Technology TZSP-40 Specifications

Job Specification:

Wastewater Sampling Port(s) shall be Thermaco Trapzilla Sampling Port as manufactured by Thermaco, Inc., Asheboro, North Carolina as noted on plans.

Sampling Port Specifications:

Furnish and install ___ Thermaco Trapzilla Model No. TZSP-40, linear low-density rotationally molded polyethylene wastewater sampling port(s) for below-ground installation with fully removable polyethylene self-positioning keyed cover equipped with brass fasteners for sampling access, 0.5” (12.7 mm) fall, 4” (102 mm) Inlet/Outlet interior diam-eter, and patent-pending flume technology for preventing sediment build-up and allowing horizontal filling access.

Trapzilla Sample Ports require 6” (15.24 cm) of clearance all the way

around the lid from walls or other structures to allow for servicing.

11

22

33

44

AA

BB

CC

DD

��

��

��

��

�����

THIS DRAWING CONTAINS PROPRIETARY AND PATENTED M

ATERIAL. THIS DRAWING M

AY NOT BE REPRODUCED IN WHOLE OR PART W

ITHOUTW

RITTEN CONSENT FROM THERM

ACO, INC. POSSESSIO

N OF THIS DRAWING

DOES NOT CONSTITUTE THE RIG

HT TO M

ANUFACTURE.POSSESSION OF THIS DRAW

ING DOES CONSTITUTE AN IM

PLIED NONDISCLOSURE AG

REEMENT BETW

EEN THERMACO, INC. AND THE HOLDER OF

THIS DRAWING. DO NO

T DESTROY THIS DRAWING

, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND M

UST BE RETURNED UPON REQUEST.

MA

TER

IAL (U

NLE

SS

NO

TED

)

FINIS

H (U

NLE

SS

NO

TED

)

646 GR

EEN

SBO

RO

STREE

TPO

BO

X 2548, A

SHEB

OR

O, N

C 27203

VO

ICE 336-629-4651 FA

X 336-626-5739D

ecimals

.XX +/- .03.XXX +/- .015

Unless otherw

ise specifiedD

imensions are in inches

TolerancesA

ngular+/- 1°

CH

EC

KE

DS

IZER

EV

. NO

.D

WG

NO

.

PA

RT N

O.

CSC

ALE

RE

LEA

SE

DA

TES

HE

ET O

F

EN

GIN

EE

RIN

G

DR

AW

ND

ATE

THIR

D A

NG

LE P

RO

JEC

TION

Flume narrow

s flow,

accelerates flow, and

directs flow into jar

Sample Jar in Carrier -

Jar lays almost flat in

bottomInlet

Outlet

TSP-40 for "straight"pipe installations

1

1

2

2

3

3

4

4

A A

B B

C C

D D

�� �� � � � � ���� �THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

4.5 in[11.4 cm]

4.5 in[11.4 cm]

26 in[66.0 cm]

8.3 in[21.1 cm]

7.8 in[19.8 cm]

11.1 in[28.1 cm]

7 in[17.8 cm]

10 in [25.4 cm]CLEARANCE FROMTOP OF TANK REQUIRED FOR

LID REMOVAL

INLETOUTLET

SIDE VIEW

END VIEW

4" PIPEINLET/OUTLET

TOP VIEW

22 in[55.9 cm]

Page 13: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

1

1

2

2

3

3

4

4

A A

B B

C C

D D

P.O. BOX 2548,ASHEBORO, NC 27204VOICE: 336-629-4651FAX: 336-626-5739

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

TOLERANCESDecimals.XX +/- .03.XXX +/- .015

Angular+/- 1°

All dimensions in inchesunless stated otherwise

N/A

TSS-95, TZ-525, TZSP-40PART NO.

DRAWNZac Rubeor

DATE1/15/2020

REV.1

SIZEC

SCALE1/11

SHEET1 OF 1

3RD ANGLE PROJECTION

N/A

N/ANOTE: THE VESSEL VENT AND THE VENTED FLOW CONTROL SHOULD NOT BECONNECTED TO THE FACILITY VENT AND SHOULD BE VENTED INDEPENDENTLY.HOWEVER, THE OUTLET VENT CAN BE CONNECTED TO THE FACILITY VENT.

A

B

CEG

HJ

K

L

INSTALLATION FEATURESCALLOUT FEATURE

A UPSTREAM PIPINGB CLEANOUT PORTC TSS-95D TSS-95 VESSEL VENTE CLEANOUT PORTF VENTED FLOW CONTROLG TZ-525H TZ-525 VESSEL VENTI OUTLET VENTJ CLEANOUT PORTK TZSP-40L DOWNSTREAM PIPING

UPSTREAMDOWNSTREAM

.505.20

D

36.51 37.0136.51 37.01

13.00 12.50 13.00 12.50

7.808.30

4.50 OD(4" PIPE EVERYWHERE)

I F

1

1

2

2

3

3

4

4

A A

B B

C C

D D

P.O. BOX 2548, ASHEBORO, NC 27204VOICE: 336-629-4651FAX: 336-626-5739

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

TOLERANCESDecimals.XX +/- .03.XXX +/- .015

Angular+/- 1°

All dimensions in inches unless stated otherwise

N/A

TSS-95, TZ-525, TZSP-40PART NO.

DRAWNZac Rubeor

DATE1/15/2020

REV.1

SIZEC

SCALE1/11

SHEET1 OF 1

3RD ANGLE PROJECTION

N/A

N/ANOTE: THE VESSEL VENT AND THE VENTED FLOW CONTROL SHOULD NOT BE CONNECTED TO THE FACILITY VENT AND SHOULD BE VENTED INDEPENDENTLY.HOWEVER, THE OUTLET VENT CAN BE CONNECTED TO THE FACILITY VENT.

A

B

CEG

HJ

K

L

INSTALLATION FEATURESCALLOUT FEATURE

A UPSTREAM PIPINGB CLEANOUT PORTC TSS-95D TSS-95 VESSEL VENTE CLEANOUT PORTF VENTED FLOW CONTROLG TZ-525H TZ-525 VESSEL VENTI OUTLET VENTJ CLEANOUT PORTK TZSP-40L DOWNSTREAM PIPING

UPSTREAMDOWNSTREAM

.505.20

D

36.51 37.0136.51 37.01

13.00 12.50 13.00 12.50

7.808.30

4.50 OD(4" PIPE EVERYWHERE)

I F

TSS-95, TZ-525, LHFC, & TZSP-40 INSTALLED IN SERIES

A THERMACO® Technology

PO Box 2548, Asheboro, NC 27204-2548Phone: (336) 629-4651 • Toll-Free: (800) 633-4204

[email protected] • www.trapzilla.comNOTE: THE OPTIONAL VESSEL VENT AND THE VENTED FLOW CONTROL SHOULD NOT BE CONNECTED TO THE FACILITY VENT AND SHOULD BE VENTED INDEPENDENTLY. HOWEVER, THE OUTLET VENT CAN BE CONNECTED TO THE FACILITY VENT.

FLOW CONTROL

FLOW CONTROL LOCATION- FOR REFERENCE ONLY

Page 14: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2020 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-LHFC-TZ

A THERMACO® Technology

Trapzilla® Grease Interceptors

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations and codes, including plumbing codes. Installation should be performed by a qualified plumber.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

Low Head Flow Control Assembly Installation Instructions

Flow Control Vent/Air Intake Flow control must be independently vented to atmosphere.NEVER CONNECT TO FACILITY VENT

LHFC Low Head Flow Control InstallationThe Trapzilla unit is shipped with the LHFC-160 (for Model TZ-160) or LHFC-400/600 (for Models TZ-400, TZ-600, TZ-525, and TZ-1826) Low Head Height, Vented Flow Control. This needs to be installed directly at the inlet of the Trapzilla. The Flow Control Vent may be independent direct connect to atmosphere or code-approved air admittance valve. NEVER CONNECT TO FACILITY VENT.

Flow Control OrificeThe flow control orifice should be located upstream of vent pipe.

Low Head Flow Control (Provided with system)

Page 15: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

Trapzilla External Flow Control

©2019 Thermaco, Inc. • All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • PO Box 2548 • Asheboro, NC 27204-2548 • (336) 629-4651 • www.thermaco.com 17/19

4” Inlet/Outlet Flow Control

Side View

Outlet View

The Trapzilla grease interceptors ship with an external flow control to be used when necessary. The flow control above is a 4” inlet/outlet flow control.

1

1

2

2

3

3

4

4

A A

B B

THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

B

7.875

2.750

2.250

NOTES: 1. TRIM EACH MOLDED LHFCAS SHOWN TO PRODUCE TWOPARTS

LLDPE

AS MOLDED

B. KYLES 04/28/06

SEE TABLE

LOW HEAD HEIGHT FLOW CONTROLFOR TRAPZILLA - TRIM DETAILS

4 LHFC-400/6001/2 4/28/06 2 2

REVISION HISTORYZONE REV DESCRIPTION DATE APPROVEDSH 1 1 ADDED BOTTOM VIEW AND EMBOSSING 7/25/06 BWKSH 2 1 SPECIFY 3" HOLE DIA FOR TRIM 7/25/06 BWKALL 2 UPDATED PART NUMBER 8/21/09 BWKSH2 4 ADDED TABLE FOR TRIM HOLE 5/23/19 ZMR

Table

P/N "A" DIAM (IN)

LHFC-400/600 3.00LHFC-525 2.25

"A" (SEE TABLE)BOTTOM OF TRIM HOLE TO BETANGENT TO INSIDE DIAMETER OF MOLDING AT BOTTOM

FLOW CONTROL ORIFICE

8”

Page 16: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

FOG 2.0 RER‐DERMHydromechanical FOG Control Device (H‐FCD)

Required Information    Tank No. 1    Tank No. 2    Tank No. 3    Tank No. 4

Capacity (gpm)

FOG Load Capacity (lbs)  at 99% Efficiency

Manufacturer

Model No. 

3rd Party Certifier (i.e., PDI, CSA,  ASME)

Interceptor Monitoring Alarm Model No.

Interceptor Monitoring Device Model No.

Solid Separator Make and Model

Updated:6/27/2018

MODEL NUMBERS HAVE TO BE VISSIBLE AT THE TIME OF THE DERM/BUILDING INSPECTION

1826 lbsThermaco, Inc.

TZ-1826

N/AN/A

Thermaco TSS-95

100

ASME

Page 17: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

FOG 2.0 RER‐DERMHydromechanical FOG Control Device (H‐FCD)

Required Information    Tank No. 1    Tank No. 2    Tank No. 3    Tank No. 4

Capacity (gpm)

FOG Load Capacity (lbs)  at 99% Efficiency

Manufacturer

Model No. 

3rd Party Certifier (i.e., PDI, CSA,  ASME)

Interceptor Monitoring Alarm Model No.

Interceptor Monitoring Device Model No.

Solid Separator Make and Model

Updated:6/27/2018

MODEL NUMBERS HAVE TO BE VISSIBLE AT THE TIME OF THE DERM/BUILDING INSPECTION

1826 lbsThermaco, Inc.

TZ-1826

N/AN/A

Thermaco TSS-95

1001826 lbs

Thermaco, Inc.

TZ-1826 ASME

N/AN/A

100

ASME

Page 18: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

FOG 2.0 RER‐DERMHydromechanical FOG Control Device (H‐FCD)

Required Information    Tank No. 1    Tank No. 2    Tank No. 3    Tank No. 4

Capacity (gpm)

FOG Load Capacity (lbs)  at 99% Efficiency

Manufacturer

Model No. 

3rd Party Certifier (i.e., PDI, CSA,  ASME)

Interceptor Monitoring Alarm Model No.

Interceptor Monitoring Device Model No.

Solid Separator Make and Model

Updated:6/27/2018

MODEL NUMBERS HAVE TO BE VISSIBLE AT THE TIME OF THE DERM/BUILDING INSPECTION

1826 lbsThermaco, Inc.

TZ-1826

N/AN/A

Thermaco TSS-95

1001826 lbs

Thermaco, Inc.

TZ-1826 ASME

N/AN/A

1001826 lbs

Thermaco, Inc.

TZ-1826 ASME

N/AN/A

100

ASME

Page 19: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

FOG 2.0 RER‐DERMHydromechanical FOG Control Device (H‐FCD)

Required Information    Tank No. 1    Tank No. 2    Tank No. 3    Tank No. 4

Capacity (gpm)

FOG Load Capacity (lbs)  at 99% Efficiency

Manufacturer

Model No. 

3rd Party Certifier (i.e., PDI, CSA,  ASME)

Interceptor Monitoring Alarm Model No.

Interceptor Monitoring Device Model No.

Solid Separator Make and Model

Updated:6/27/2018

MODEL NUMBERS HAVE TO BE VISSIBLE AT THE TIME OF THE DERM/BUILDING INSPECTION

1826 lbsThermaco, Inc.

TZ-1826

N/AN/A

Thermaco TSS-95

1001826 lbs

Thermaco, Inc.

TZ-1826 ASME

N/AN/A

1001826 lbs

Thermaco, Inc.

TZ-1826 ASME

N/AN/A

1001826 lbs

Thermaco, Inc.

TZ-1826 ASME

N/AN/A

100

Thermaco TSS-95

ASME

Page 20: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

For additional information on Trapzilla or other Thermaco products, please visit www.trapzilla.com or call at 1-800-633-4204.

Copyright ©2019 Trapzilla® Thermaco, Inc. • P.O.Box 2548 • Asheboro, NC 27204

Toll Free: (800) 633-4204 • Phone: (336) 629-4651 • Fax: (336) 626-5739

[email protected] • www.trapzilla.com

Installation & Maintenance Instructions

For Trapzilla99® TZ-1826

Part# MNL-TZ-1826AEF

*Please consult Thermaco, Inc. for specific models tested, certified and/or listed by these organizations.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

®

Conforms to ASME StandardASME A112.14.3-2000

Please consult Thermaco, Inc. for specific models tested,certified and/or listed by these organizations.

®

Page 21: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 3

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 2

1. System Overview

The Thermaco, Inc. Trapzilla99® series Grease Interceptor collects 99% of free-oating grease oils contained in itchen

drain water ows. As most ood service acilit managers alread now, grease buildup inside a building s grease containment s stem is a major cause o problems due to e terior drain line bloc ages. These problems jeopardi e normal operations as well as create health and sa et ha ards within the acilit itsel .

The proper installation of a Trapzilla99 series grease interceptor can reduce or eliminate grease problems and costl sewer surcharges and fines through 99 e ficient separation and retention o ree- loating grease oils.

Trap illa99 grease interceptors o ers patented at separation curve technolog . This means that the unit does not lose grease separation e ficienc as it fills with retained grease. Thus, the grease interceptor stores large uantities o grease without losing e ficienc . The uni ue compact design o the Trap illa allows or installation into most acilities. ptions are available that enable a Trap illa unit to be installed on the oor, suspended rom the ceiling or in-ground outside the acilit .

Trap illa99 units are designed to treat high ows o itchen drainwater with large grease storage capacit within a small ootprint unit. These units are eas to maneuver into position and just as eas to plumb.

dromechanical grease interceptors, automatic recover units, grease removal devices and other similar plumbing devices receiving itchen ows rom sin s, oor drains, wo s and other ood bearing sources ma generate odors. There are man actors in uencing odor evolution and dissemination. These include room ventilation, itchen menu, ambient temperatures, ware washing practices, grease/oil input, dail input uid volume, saniti ers, installation plumbing design and product maintenance/up eep.

dors are usuall prevented b good area ventilation, re uent uid inputs, good product maintenance practices and proper product installation. Additional steps, including aeration, chlorination, p control, improved area ventilation and additional maintenance ma be needed at some sites.

*Devices formerly referred to as grease traps are now called hydromechanical grease interceptors.

Contents

1. S stem verview.................................................................................................................................... 32. Models and Options................................................................................................................................ 4 2.1 Models ........................................................................................................................................... 4 2.2 Options .......................................................................................................................................... 53. Plumbing Installation .............................................................................................................................. 6 3.1 Plumbing Considerations Prior to Installation ................................................................................ 6 3.1.1 ocating the nit ................................................................................................................... 6 3.1.2 Inlet/ utlet Piping ................................................................................................................. 6 3.1.3 low Controls ........................................................................................................................ 6 3.1.4 enting the utlet ................................................................................................................. 6 3.1.5 igh ead eight Applications ver Si (6) eet (1.95 m) .................................................. 6 3.2 essel ent Connection .................................................................................................................. 7 3.3 Plumbing Configurations ................................................................................................................ 8 3.3.1 One TZ-1826 ......................................................................................................................... 8 3.3.2 Installing ultiple Trap illa nits in Parallel ........................................................................... 9 3.3.3 Installing ultiple Trap illa nits in Series ............................................................................. 104. Above-Ground Installation ...................................................................................................................... 11 4.1 Components or Above-Ground Installations .................................................................................. 11 4.2 Instructions or Assembling and Attaching ternal race ............................................................. 12 4.3 Instructions or Installing ultiple Trap illa nits Above-Ground .................................................... 12 4.3.1 Installing T -1826-SSA with TSS-95-SSA in Series .............................................................. 12 4.3.2 Construction o iser or TSS-95-SSA installation in series with T -1826-SSA .................... 13 4.3.3 Installing ultiple T -1826-SSA in Series ............................................................................. 13 4.3.4 Installation o Pipe angers with Above-Ground nits .......................................................... 145. In-Ground Installation Instructions .......................................................................................................... 15 5.1 Single T -1826 Installed In-Ground ............................................................................................... 15 5.2 T -1826 with ptional CA-T -29 tension Collars .................................................................... 16 5.3 Concrete Specifications or In-Ground Installation ......................................................................... 17 5.4 Concrete Calculations or T -1826 odels/Components ............................................................. 17 5.5 Trimming and Setting the CA-T -18 Single-Piece tension Collar ............................................ 186. nit aintenance.................................................................................................................................... 20 6.1 easuring Grease/Solids evels .................................................................................................... 20 6.2 Pumping/Servicing nit .................................................................................................................. 217. imited arrant and emed ............................................................................................................... 22

Page 22: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 5

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 4

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

TZ-1826

1,826 pounds o grease storage, P I and AS rated at 100 gpm. uipped with 4 inlet/outlet, 2 vessel vent connection, and 4 ow- ead low Control Accessor to limit ow to 100 gpm.Comes with tension Collar Adapter id Assembl with two 18 tall e tension collars and two 22 diameter lids.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

TZ-1826-SSA

1,826 pounds o grease storage, P I and AS rated at 100 gpm. uipped with 4 inlet/outlet, 2 vessel vent connection, and 4 ow- ead low Control Accessor to limit ow to 100 gpm.Comes with tension Collar Adapter id Assembl with two 18 tall e tension collars, two 22 diameter lids,e ternal brace (not pictured) and SSA-1826 Support Stand.

odels available with 6 Inlet/ utlet, add su fi -6 to model.

2. Models and Options

Thermaco o ers di erent models and options specificall designed to assist the owner/installer meet site conditions while compl ing with local pretreatment and plumbing code.

2.1 Models

2.2 Options (Some options must be purchased separately)

FTCA-22

ptional 22 diameter cover available or In-Ground installations. Provides a non-slip, diamond patterned aluminum replacement for the standard STC-22 cover. ach T -1826

would re uire two (2) TCA-22 covers.

SSA-1826

Support Stand or T -1826 or Above-Ground Installations. ust be ull supported, not to

be installed over grates.Included with T -1826-SSA odels

ECA-TZ-29

(purchase separatel )ptional, field-modifiable e tension

col lars avai lable to provide additional depth or e isting itchen drainage piping. • T -1826- CA odels ship with

two (2) built-in 0-18 e tension collars.

• CA-T -29 adds 0-29 depth to - CA model.

• Contact Thermaco be ore installing an Trap illa more than 60 below grade rom center of outlet pipe or in location where water table will ever rise above bottom o unit.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

0-1

8” B

uilt-

In

Exte

nsio

nE

CA

-TZ

-29

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO. CSCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

21.13 in[53.7 cm]

R10.56 in[26.8 cm]

R11.56 in[29.4 cm]

1.50 in[3.8 cm]

23.10 in[58.7 cm]

ANGLE STIFFENERS

Bottom ViewTop View

Side View

DIAMOND PLATE SURFACE

1

1

2

2

3

3

4

4

A A

B B

C C

D D

�� �� � � � � ���� �THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

Page 23: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 7

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 6

3. Plumbing Installation

3.1 Plumbing Considerations Prior to Installation

3.1.1 Locating the Unit

The s stem should be visible and easil accessible or maintenance and inspection. ptions are available to install the Trap illa in a basement, suspended rom a ceiling or in-ground in an e terior location. a e sure ade uate room is provided around the unit to allow eas access or a pump truc operator. a e sure the height above the Trap illa access cover is enough to properl service the s stem.

3.1.2 Inlet/Outlet Piping

The inlet and outlet piping connections re uire e ible sleeve pipe couplings. eep outlet piping as straight as possible. Thermaco, Inc. recommends installation o Two- a Cleanouts on both the Inlet and Outlet of Trapzilla Interceptors and Solids Separators in accordance with all applicable laws, regulations and codes. These cleanouts should match the size of the Inlet and Outlet Piping (i.e. for 4” Inlet/Outlet piping, a 4” cleanout should be used). se onl sweep connections. o not reduce the pipe si ing on the outlet piping. o not install P trap on outlet connection o s stem. (Note The s stem alread has a internal gas trap)

3.1.3 Flow Controls

Trap illa s stems are supplied with a ow- ead low Control module ( C). This should be connected to the inlet o the Trap illa unit in situations where ow rate needs to be restricted to the AS rated ow or when vented ow control is re uired b local code.

3.1.4 Venting the Outlet

An outlet vent or approved air admittance valve o at least 1/2 the diameter o the s stem s outlet connection must be present as close as possible to the Trap illa outlet to prevent possible siphonage problems. The ent on the utlet piping is to be installed in accordance with all applicable laws, regulations and codes. ailure to provide a vent or the s stem voids Thermaco s imited arrant or the s stem.

3.1.5 High Head Height Applications Over Six (6) Feet (1.95 m)

or installations where there is head height o greater than 6 eet (1.95 meters), Thermaco, Inc. recommends installation o a code-approved ented low Control Assembl (Thermaco CA not included with Trap illa).

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

3.2 Vessel Vent Connection

enting o the tan is recommended b the manu acturer and re uired or in-door installations. • ent the tan through the provided 2 NPT threaded connector on the side o the tan (This vent ma be located above the outlet or on the side o the tan depending on model). • emove and discard the plug and connect appropriate vent lines as indicated below ( or 2 vent connection, use 2 pipe).

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

Vessel Vent ConnectionCan be connected to the outlet vent,

acilit vent, or independentl vented to atmosphere

Page 24: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 9

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 8

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

3.3 Plumbing Configurations

3.3.1 One TZ-1826

ach Trap illa unit is shipped with a ow ead low Control module (see C bo or additional instructions). hen applicable, this needs to be installed to the inlet o the Trap illa and connected to a code-approved air inta e. Thermaco, Inc. recommends installation o Two- a Cleanouts on both the Inlet and utlet o Trap illa in accordance with all applicable laws, regulations and codes. These cleanouts should match the si e o the Inlet and utlet Piping (i.e. or 4 plumbing, a 4 cleanout should be used). A ent on the utlet piping is also to be installed in accordance with all applicable laws, regulations and codes.

*Use a Two-Way Cleanout before and after all Trapzilla Installations

Outlet

Inlet

Cleanout

Cleanout

Outlet Vent(Connect to acilit vent)

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

ow- ead low Con-trol (not pictured) to be installed as close as possible to inlet when necessar .

3.3.2 Installing Multiple Trapzilla Units in Parallel

Trap illa Grease Interceptors should be installed in parallel with a Trap illa low Splitter ( S -44 or S -66) diverting the ow. Place Two- a Cleanouts be ore, between and a ter the units as shown

below, including be ore and a ter the ow splitter. a e sure to connect an outlet vent a ter each Trap illa Grease Interceptor. A ow ead low Control ( C) is shipped with each unit, and i needed should onl be installed a ter the first Cleanout and be ore the low Splitter.

*Use a Two-Way Cleanout before and after all Trapzilla Installations

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

Outlet

Inlet

Cleanout

Cleanout

Outlet Vents(Connect to acilit vent)

ow- ead low Con-trol (not pictured) to be installed as close as possible to inlet when necessar .

Cleanout

Cleanout

Page 25: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 11

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 10

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

3.3.3 Installing Multiple Trapzilla Units in Series

Alternativel , two Trap illa Grease Interceptors, Solids Separators or a combination ma be installed in series. A single Trap illa Solids Separator and Trap illa Grease Interceptor should alwa s be installed in series. Place Two- a Cleanouts be ore, between and a ter the units as shown below. a e sure to connect an outlet vent a ter the Trap illa Grease Interceptor. A ow ead low Control ( C) is shipped with each grease interceptor and should onl be installed a ter the first Cleanout and be ore the first grease interceptor.

*Use a Two-Way Cleanout before and after all Trapzilla Installations

Outlet

Inlet

Cleanout

Cleanout

Outlet Vents(Connect to acilit vent)

ow- ead low Control (not pictured) to be installed as close as possible to inlet o first grease interceptor.

Cleanout

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

The SSA-1826 Support Stand is a one-piece assembl with a conical center that sits on the oor. It does not add appreciable height to the assembl .

4. Above-Ground Installation

4.1 Components for Above-Ground Installations

sing a model-specific Support Stand, a Trap illa unit ma be installed directl on top o the oor in a location such as a basement or mechanical room.

T -1826-SSA comes with SSA-1826 and e ternal brace or above-ground installations. All T -1826 units come with built-in 18 isers which must be cut down and secured in field.

The ternal race must be installed in above-ground installations or the warrant will be voided.

NOTE: SUPPORT STAND MUST BE INSTALLED OVER A CONTINUOUS SURFACE. N O N - C O N T I N U O U S SURFACES SUCH AS GRATES ARE NOT SUITABLE FOR SUPPORT.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

TZ-1826

ternal race (installation instructions on ne t page)

SSA-1826

Page 26: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 13

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 12

4.3.2 Construction of Riser for TSS-95-SSA installation in series with TZ-1826-SSA

or the installation o a TSS-95-SSA prior to the T -1826-SSA, a riser must be constructed to raise the smaller unit b 8 and provide ull support or the weight o the interceptor and its contents.

4.3.3 Installing Multiple TZ-1826-SSA in Series

hen installing multiple Trap illa units in series, the change in elevation rom the inlet to the outlet o a unit re uires that each preceding unit be installed 1.5 higher than the unit a ter it. or above-ground units, pressure treated pl wood ma be placed ull beneath the support stand to create the height di erence.

All installations inside o a building must have a vessel vent installed and be piped to atmosphere.

4.2 Instructions for Assembling and Attaching External Brace

4.3 Instructions for Installing Multiple Trapzilla Units Above-Ground

4.3.1 Installing TZ-1826-SSA with TSS-95-SSA in Series

hen installing a T -1826-SSA Interceptor with a TSS-95-SSA Solids Interceptor in series, the change in elevation rom the outlet o one o these smaller units to the inlet o the T -1826-SSA to the re uires that the preceding unit be installed 8 higher than the unit a ter it.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

8" ELEVATION DIFFERENCE(MINIMUM) BETWEEN TSSAND TZ TO ENSURE FLOWAND TO COMPENSATE FORHEIGHT DIFFERENCES. A

RISER MADE FROM TREATEDLUMBER OR CONCRETE MAY

BE USED.LAMINATEDPLYWOOD

RISER

FRAMED FLOOR RISERWITH PLYWOOD TOPFOR CONTINUOUSSUPPORT

36" SQUARE MINIMUM

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

1.5" ELEVATION DIFFERENCE(MINIMUM) BETWEEN FRONT

UNIT AND REAR UNIT TOENSURE FLOW AND TO

COMPENSATE FOR HEIGHTDIFFERENCES

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

PLYWOOD STACK RISERASSEMBLE SHEETS OF PRESSURETREATED PLYWOOD (MINIMUM36 INCHES [92CM] SQUARE) TOTHE DESIRED HEIGHT. SECURE

EACH LAYER TO THE ONE BELOWWITH CORROSION RESISTANT

SCREWS.

FRAMED FLOOR RISERCONSTRUCT A FLOOR SUPPORT FRAME

(MINIMUM 36 INCHES [92CM] SQUARE) FROMPRESSURE TREATED LUMBER OF 2 IN [50MM]NOMINAL THICKNESS AND OF THE DESIRED

HEIGHT. SPACE FRAME MEMBERS NO MORE THAN10 IN [25CM] APART. COVER THIS STRUCTURE

WITH PRESSURE TREATED PLYWOOD. SECURE ALLJOINTS WITH CORROSION RESISTANT SCREWS.

1

2

3

1

1

2

2

3

3

4

4

A A

B B

C C

D D

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKED SIZE REV. NO. DWG NO.

PART NO.C

SCALE RELEASE DATE SHEET OF

ENGINEERING

DRAWN DATE

THIRD ANGLE PROJECTION

RAIL

PLATE

UPPER SUPPORT RIB

CENTER SUPPORT RIB

LOWER SUPPORT RIB

1. PLACE ONE RAIL ONEACH SIDE OF TZ-1826WITH TABS ON TOP ANDBOTTOM OF CENTERSUPPORT RIB.2. PLACE ONE PLATE ON TOP

OF CENTER SUPPORT RIB ANDONE ON THE BOTTOM ON EACHEND OF THE TZ-1826. ALIGNHOLES IN THE PLATES AND RAILS. 3. INSERT 2 BOLTS

INTO HOLES AT EACHCORNER. ADD NUTSAND TIGHTEN TOCOMPLETE ASSEMBLY.

Page 27: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 15

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 14

4.3.4 Installation of Pipe Hangers with Above-Ground Units

Trap illa units installed indoors, above-ground re uire the use o pipe hangers (purchased separatel ) to properl support plumbing and reduce stress on connections with unit. Thermaco recommends the use o our (4) inc-plated Steel oop St le hangers with 1000 lbs. wor load limit or a single Trap illa installation with two (2) hangers placed be ore inlet side cleanout and two (2) hangers placed a ter final cleanout. Place each pair o hangers 35 apart (space-permitting) and no closer than 5 rom an joint. hen multiple units are installed place one (1) additional pipe hanger in between each unit, leaving 5 distance rom unit and cleanout. ollow pipe hanger manu acturer s instructions or ph sical installation.

5. In-Ground Installation Instructions

5.1 Plumbing Instructions for Single TZ-1826 Installed In-Ground

A Trap illa unit ma also be installed in the ground inside or outside o the acilit . or instances where the acilit drainage piping re uires an e tension collar that is more than the 18 provided b the built-in e tension, the CA-T -29 tension Collar Assembl ma be installed to align the Trap illa inlet with the drainage piping. Thermaco, Inc. strongl recommends surrounding the in-ground Trap illa with concrete to provide additional structural strength and to o set buo anc e ects. or uo anc Calculations suggested concrete ill uantities please see page 17.

In-Ground Installations inside of a building must have a vessel vent installed and be piped to

atmosphere.

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

Outlet Vent - e tend to grade

and cover or con-nect to acilit

Vessel Vent - to atmosphere

uilt-in 18 extension collars

Trapzilla cover - placed on top-most extension collar, to be accessible rom

ground levelGrade

Two-wa cleanout be ore and a ter

each unit, extend to grade.

Concrete surround-ing unit bod and extension collar.

Inlet Outlet

5/8 -11 ods

oop-St le Pipe anger

35 between hangers

5 between hangers and an joints

nit must be supported b Trap illa Support Stand Assembl .

No Trap illa unit ma be hung using pipe hangers.

Page 28: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 17

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 16

5.3 Concrete Specifications for In-Ground InstallationIn order to o set the e ects o buo anc caused b groundwater (high water tables), strengthen the sideload o the unit, and prevent movement o the unit in the event o shi ting earth, Thermaco, Inc. recommends concrete be poured around the entiret o Trap illa® units installed in-ground in the amounts o concrete specified in the table below. The concrete must to be poured continuousl and completel surrounding the Trap illa® bod (and tension Collars i applicable) to ensure proper strength and securit at a compression strength o 4000 psi (C28/35).

5.4 Concrete Calculations for TZ-1826 Models/Components*

Amount o ConcreteTrapzilla Model eight in lbs. ( g) olume in Cubic ards (m3)

TZ-1826 3950 1.0CA-T -29 (each) 600 0.20

5.2 Plumbing Instructions for TZ-1826 with Optional ECA-TZ-29 Extension Collars (purchased

separately)

In some cases, T -1826 ma be installed in locations where built-in e tension collar will not reach grade. In these cases, the two-piece CA-T -29 tension Collar (purchased separatel ) ma be used to ma e lid accessible at ground level. ollow instructions included in CA-T -29 pac aging or installations.

ach T -1826 would re uire two (2) CA-T -29 i pipe depth re uires.* In-ground installation instructions only applicable for units installed where center of outlet pipe is

no more than 60” below grade. For all installations deeper than this, Thermaco must be contacted

to verify site conditions and provide further instructions for proper installation. Failure to abide by

this instruction will result in voiding the warranty of the unit.

In-Ground Installations inside of a building must have a vessel vent installed and piped to at-

mosphere.

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

ECA-TZ-29

Two-piece extension collar with 4-29 o e tension. Connect bottom piece to built-in extension collar and use original lid

provided.

Built-in

extension

Follow instructions on pages 18-19 to set built-in e tension collar. When pos-sible adjust height o built-in e tension collar be ore trimming

CA-T -29.

Page 29: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 19

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 18

5.5 Trimming and Setting the ECA-TZ-18 Single-Piece Extension Collar

In-Ground Trap illa odels ship with a built-in, single-piece, 18 e tension collar that must be trimmed and then set to the correct height to bring the Solid Top Cover to grade.

Follow the steps below to set the extension

collar prior to backfilling the hole with

concrete.

Amount o e tension collar needed to bring Solid Top Cover to grade.

Step 2 emove the e tension collar adapter ring rom the unit with the extension collar still in place. On the underside o the cover, mar the e cess e tension collar length at the bottom o the our (4) s irt portions o the adapter ring. Chec the e tension collar height dimension re uentl during this mar ing to ensure that the collar has not moved.

tend this mar between the gaps in the s irt so that the collar is mar ed all around.

Step 1 ith the Trap illa unit installed in its permanent location, raise the telescoping e tension collar to finished grade or oor level. easure the height rom the top o the unit to this finished e tension collar height and record this dimension.

Note I the oor will have a tile covering, allow or the tile thic ness when determining the e tension collar height.

8.25"

Extension collar

Skirt

Mark excess extension collar lengthat the four (4) "skirt" portions of

the adapter ring.

8.25

Step 5 or ing rom the bottom o the assembl , install eight (8) sel -drilling, sel -tapping screws (provided) through the e tension collar wall and into the adapter ring. Two o these screws should be installed in each o the our (4) s irt areas o the adapter ring. Chec the e tension collar height dimension re uentl during this operation to ensure that the collar has not moved. Note se caution when tightening these screws to ensure that the do not strip.

Step 6 Place the adapter ring/e tension collar assembl onto the Trapzilla unit. Position the small cover onto the e tension collar. Secure the adapter ring and the small cover with the brass nuts and at washers provided. Seal the gap between the 18 e tension collar and e tension collar adapter ring using a silicone sealant.

Step 3 emove the e tension collar rom the adapter ring and, with an appropriate saw, cut along the line created in Step 2 to remove the excessive extension collar.

Step 4 einsert the e tension collar into the adapter ring ensuring that the cover alignment e on the e tension collar is aligned with its recess in the adapter ring.

eset the e tension collar height to the dimension determined in Step 1.

Line marking the bottom

of the "skirt" (adapter ring has

been removed

for clarity)

Excess part of extension collar to be discarded after cutting along line

Reinsert extension collar into adapterring to insure alignment.

Adapter ring

Extension collar

Modified extension collar

Self-tapping screws8 Places

Adapter ring

"Skirt"

5/16-inch Hex Nut4 Places

5/16-inch Washer4 Places

Note: Tighten down the flatwashers and brass nuts usinga 5/16-inch socket and rachet.

Do not over tighten.

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

IMPORTANT: Excess extension collar must be trimmed on all units. Do not allow additional extension collar to extend beyond bottom of adapter ring. On units where extension collar is completely recessed, the extension collar should still be secured and the excess extension removed as in step 3.

Page 30: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 21

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 20

6. Unit Maintenance

6.1 Measuring Grease/Solids Levels

ue to its uni ue design, Trap illa is capable o retaining high uantities o grease in a compact ootprint. There ore, unli e traditional interceptors, Trap illa can hold an e traordinaril high percentage o its volume in grease without losing separation e ficienc . To determine the current levels o grease/solids in our Trap illa grease interceptor, ollow the instructions below.1. emove our nuts/washers securing the 22 Solid Top Cover.2. Place a grease/sludge dipstic into the center o the opening, ma ing sure that it goes through the

hole in the hori ontal ba e.3. nce the dipstic has ound its natural resting place at the lowest point in the conical shaped bottom,

ta e the measurement.4. emove dipstic and compare grease/sludge levels to the corresponding unit in the charts below.

Grease Solids

Total

Capacity

(depth):

Ready to

pump at

(depth):

Total

Capacity

(height):

Ready to

pump at

(height):

TZ-1826 25 20 13.5 10.75

Ta e solids/sludge measurement rom bottom o unit upward and compare to chart above.

Ta e grease measurement rom top o li uid level downward and compare to chart above.

Note: Drawing for reference only. Equipment must be installed in compliance with all applicable laws, regulations

and codes, including plumbing codes. Installation should be performed by a qualified plumber.

6.2 Pumping/Servicing Unit

Periodicall , the Trap illa unit will need to be serviced which involves pumping out all accumulated grease and solids. Pumping re uenc ma be set at a regular interval b sewer district (ever 30-90 da s). I not, determine pumping re uenc using instructions in 6.1 to periodicall measure grease/solids levels to determine appropriate timing or pumping. ollow instructions below to pump/clean out TZ-1826.1. ach lid has our brass nuts securing the lid. emove the our brass nuts rom the bolts and ull

remove the 22 lid to pump out. It is not necessar to remove adapter lid to pump out Trap illa. 2. egin b ta ing the grease rom the top o the main chamber until all grease is removed.3. pon reaching the hori ontal ba e, ou will see a hole through which ou ma access the rest o

the grease and the solids. e sure to lower the hose all the wa to the bottom o the Trap illa unit on the outlet side so that solids ma be entirel removed. The conical shape and natural grade o the unit will allow solids and grease to run to outlet side o unit.

4. ave itchen run water into unit to ush an remaining solids to the outlet end o the unit.5. I necessar , use a water hose with spra no le to rinse o inside o unit.6. Secure lids in place and instruct itchen to run water into unit until ull.

N T use mechanical crust brea ing devices to brea down an mat that has ormed inside the Trapzilla unit.

N T use grinding augers in maintenance o the Trap illa unit.

1

1

2

2

3

3

4

4

AA

BB

CC

DD

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203VOICE 336-629-4651 FAX 336-626-5739

Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKEDSIZEREV. NO.DWG NO.

PART NO.C

SCALERELEASE DATESHEET OF

ENGINEERING

DRAWNDATE

THIRD ANGLE PROJECTION

1

1

2

2

3

3

4

4

AA

BB

CC

DD

6*'4/#%1��+0%THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUTWRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OFTHIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREETPO BOX 2548, ASHEBORO, NC 27203VOICE 336-629-4651 FAX 336-626-5739

Decimals.XX +/- .03.XXX +/- .015

Unless otherwise specifiedDimensions are in inches

TolerancesAngular+/- 1°

CHECKEDSIZEREV. NO.DWG NO.

PART NO.C

SCALERELEASE DATESHEET OF

ENGINEERING

DRAWNDATE

THIRD ANGLE PROJECTION

2

3

Page 31: Miami-DERM Submittal Packet - Thermaco · .XXX +/- .015 Unless otherwise specified Dimensions are in inches Tolerances Angular +/- 1° CHECKED SIZE REV. NO. DWG NO. PART NO. C SCALE

©2018 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without noticeThermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • (336) 629-4651 MNL-TZ-1826 23

Trapzilla99® Grease InterceptorInstallation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826 22

7. Limited Warranty and Remedy

Thermaco Incorporated warrants to the original user that the outer tan and inner tan components o the product manu actured b Thermaco and delivered with this warrant (the Product ) shall be ree rom material de ects in wor manship and materials during the li etime o the plumbing s stem in which the Product is initiall installed. Notwithstanding the oregoing, this warrant shall not cover, and Thermaco shall have no obligation to repair or replace, an o the ollowing component parts o the Product lid, gas ets, brac ets, nuts, and ow control.

An and all warrant claims must be made in writing to Thermaco at 646 Greensboro Street, Asheboro, NC 27203 promptl a ter discover o the de ect giving rise to the warrant claim. ollowing and subject to Thermaco s pre-liminar approval o a warrant claim, the warrantied Product must be delivered, prepaid, to Thermaco, together with proo o purchase and a return authori ation number issued b Thermaco. I Thermaco determines that the Product is de ective, the de ect is covered b this warrant , and the warrant conditions are satisfied, Thermaco s sole obligation under this warrant , and the sole and e clusive remed with respect to an such de ect, is the repair or replacement, at Thermaco s option, o the de ective e uipment, component, or parts. An replacements will be urnished . . . point o shipment. Thermaco reserves the right to ship the user replacement parts with installation instructions. If Thermaco determines that the part, component, or the Product is not defective or that an condition o this warrant is not satisfied, then Thermaco shall have no obligation to repair or replace an such part, component, or the Product, and an costs associated with the return o such part, component, or the Product shall be borne b the part ma ing the warrant claim.

This warrant shall not cover an de ect in an otherwise covered Product resulting directl or indirectl rom (and the occurrence o an o the ollowing shall void an otherwise applicable warrant claim) (i) ailure to install, operate or maintain the product in accordance with the Installation and Operation Manual that was included with the Product when it was sold and all other applicable Thermaco instructions and procedures, including, without limitation, use o mechanical crust brea ing devices, use with grinding augers, use in e cess o rated ow, use in e cess o rated grease capacit , use to remove emulsified ats and oils or use that ails to compl with applicable laws, regulations or codes (ii) damage in transit, handling or installation (iii) modifications, adjustments, repairs, or alterations made b persons other than Thermaco representatives or certified plumbers (iv) an change in the original installation or change to the original use o the Product or (v) other causes not arising out o de ects in wor manship or materials. Thermaco shall not be responsible or damage to products resulting rom ultraviolet light e posure, oating o tan , vault ooding, sewer line bac -up, pumping or li t station ailure, ambient water ow, ree ing, or other sources o water damage. This warrant does not cover e uipment or parts not manu actured b Thermaco. riginal user s costs relating to an service, adjustment, removal, repair, pac ing, or otherwise incurred with respect to the de ect prior to submission or warrant are the responsibilit o the original user. No distributor, sales person or other person is authori ed to ma e an warrant statements on behal o Thermaco regarding Thermaco products other than as set orth in this warrant . This statement o warrant supersedes and replaces an uote, brochure, or other statement or document with respect to warrant o the Product.

C PT AS P SS S T T A , T AC A S N P S NTATI NS, A AN-TI S G A ANT S, IT P SS I P I , INC ING, IT T I ITATI N, AS T

C ANTA I IT ITN SS A PA TIC A P P S , T N T T AC A N G P C AS S PA TIC A I NTS N S, IT SP CT T

G N ATI N T INCI NTA S ATING T S T P CT.

The sole and e clusive remed with respect to this warrant or an other claim relating to de ects or an other condition or use o Products, however caused, and whether such claim is based upon warrant , contract, tort, strict liabilit or an other theor , is I IT to the repair or replacement o the a ected Product, component, or parts, in each case e cluding labor or an other cost to remove or install the Product or, at Thermaco s sole option, re und o the original purchase price. IN N NT S A T AC IA , T IN C NT ACT,

A ANT , T T (INC ING N G IG NC ), ST ICT IA I IT , IN NIT AN T GA T , INCI NTA C NS NTIA A AG S AN T SS C ST A SI I A T P . N N CI C STANC S I T AGG GAT IA I IT T AC AN CA S ACTI N AT T T P CT C C T N T P C AS P IC C I T AC T P CTS. This arrant is made onl or the benefit o the original user and is void upon an trans er o ownership or changes in installation. Note o not Pressure/ dro-static test our Products.