Metal Cubicle Heater Sizing Guideline.xls

4
METAL CUBICLE HEATER SIZING GUIDELINE Location of enclosure 1 Enclosure Position 5 Height 2.28 m Width 0.80 m Depth 0.80 m Temperature differential required 5.00 Surface area exposed to air 5.99 Material of cubicle 2 Heating Power, if any 0 w Required Heating Power 134.82 w 4.5 Indoor 1 Outdoor 2 Single enclosure free on all side 7.45 Single enclosure, wall mounted 6.72 First or last enclosure in free standing row 6.72 First or last enclosure in wall mounted row 5.99 Middle enclosure in free standing row 5.99 Middle enclosure in wall mounted row 5.26 Middle enclosure in wall mounted row with covered t 4.82 Steel sheet, painted 5.5 Steel sheet, stainless 4.5 Aluminium 12 Aluminium, double-walled 4.5 Polyester/Plasric/Insulated Stainless 3.5 o K m 2

description

Metal Cubicle Electrical Heater Sizing

Transcript of Metal Cubicle Heater Sizing Guideline.xls

Page 1: Metal Cubicle Heater Sizing Guideline.xls

METAL CUBICLE HEATER SIZING GUIDELINE

Location of enclosure 1

Enclosure Position 5

Height 2.28 m

Width 0.80 m

Depth 0.80 m

Temperature differential required 5.00

Surface area exposed to air 5.99

Material of cubicle 2

Heating Power, if any 0 w

Required Heating Power 134.82 w 4.5

Indoor 1

Outdoor 2

Single enclosure free on all side 7.45

Single enclosure, wall mounted 6.72

First or last enclosure in free standing row 6.72

First or last enclosure in wall mounted row 5.99

Middle enclosure in free standing row 5.99

Middle enclosure in wall mounted row 5.26

Middle enclosure in wall mounted row with covered top 4.82

Steel sheet, painted 5.5

Steel sheet, stainless 4.5

Aluminium 12

Aluminium, double-walled 4.5

Polyester/Plasric/Insulated Stainless 3.5

oK

m2

E13
Temperature differential between internal and external of cubicle (increase of temperature required inside the cubicle)
E19
Components in the cubicle that generate heat, if any. Negligible if quantity is small.