MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

67
MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault Systems Chris Dolan Marina Electrical Equipment Pacific Coast Congress of Harbormasters and Port Managers April 15, 2021

Transcript of MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Page 1: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

MARINA ELECTRICAL SYSTEMS:Safe Design & Ground-Fault Systems

Chris DolanMarina Electrical Equipment

Pacific Coast Congress of Harbormasters and Port Managers

April 15, 2021

Page 2: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request.

This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner ofhandling, using, distributing, or dealing in any material or product.___________________________________________Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Page 3: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

This session will provide a review of the current ground-fault requirements per the National Electrical Code and general best practices for a marina electrical system. Electrical problems within a marina can be minimized or avoided if they are detected early and addressed immediately. The presentation will provide many examples of what owners, operators, and maintenance individuals should be looking for during routine marina inspections to minimize potential issues before they happen.

CourseDescription

Page 4: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Receptacle Selection?

• Many factors will help determine receptacle selection.

Page 5: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Recommended Receptacle Configurations – NEMA:

Page 6: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Recommended Receptacle Configurations – Megayachts:

Page 7: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Notes for Selecting Receptacles:

1. For sailboats use the minimum column.

2. For houseboats and fishing boats use the preferred column.

3. For a mix of sail & power pleasure craft use the satisfactory column.

4. The voltage rating for most 20 amp and 30 amp receptacles is 120V. Straight blade 20 amp receptacles must be GFCI protected.

5. The voltage rating for most 50 amp receptacles is 120/240V.

6. The voltage ratings for 100 or 200A amp, 4 wire receptacles are 120/240V or 480V.

7. The voltage ratings for 100 amp or 200A, 5 wire receptacle are 120/208V or 277/480V.

8. The 100 amp receptacles are IEC Pin & Sleeve configuration. 30 amp and 50 amp receptacles are twist-lock, while most 20 amp receptacles will be straight blade GFCIs.

Page 8: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

IMPORTANT NOTE – Avoid Using Adapters

• Most “Y-Adapter” cord sets are not listed products and do not provide the proper circuit protection for a safe electrical connection.

Page 9: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Listed ProductsWhat to Look for:

• Listed products go through stringent tests to ensure products meet certain safety guidelines.

Page 10: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Cords Sets and Splitters –Examples of Potential Danger:

• Overloading or overheating a receptacle can lead to melting, burning, arching, and potential fire.

Page 11: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Cords Sets and Splitters –Examples of Potential Danger:

• Overloading or overheating a receptacle can lead to melting, burning, arching, and potential fire.

Page 12: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Safety, Maintenance, and Electric Shock Drowning:

Page 13: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

In-Water Hazards and Electric Shock Drowning:

• Electric Shock Drowning occurs when faulty wiring on a boat or in a marina causes underwater metals to become energized.

• Examples of underwater metals that could become energized

• Boat props, dock frames, ladders, etc…

• This creates an electrical field in the water

• The magnitude and intensity of the electrical field is determined by how much current is being leaked into the water.

Page 14: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Electric Shock Drowning:

• A swimmer enters the electrical field and completes the electrical circuit to ground.

• The swimmer becomes a target for the electrical current leakage because the human body is a better conductor of electricity than fresh water

• Fresh water is close to 70 times more resistive than salt water. This makes electric current leakage in fresh water marinas a major concern.

• Depending on the amount of current in the water and a swimmers location relative to the electrical field, a person may experience effects ranging from a slight tingle, to complete loss of muscle control, to ventricular fibrillation.

Page 15: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Underwater Electrical Field:

50mA of Leakage

20mA of Leakage

5mA of Leakage

Page 16: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Electric Shock Medical Facts(Freshwater Environment):

• Current

• not Voltage

• Light Bulb

• 100 mA

Current Effects

1 mA to 8 mA Tingle, sensation of shock, not painful, muscle control not lost

8 mA to 15 mA Painful shock, muscle control not lost

15 mA to 20 mA Pain shock, muscle control is lost, paralysis / inability to swim occurs, labored breathing

50 mA to 100 mA Ventricular Fibrillation possible

100 mA to 200 mA Ventricular Fibrillation occurs

200+ mA Burn marks may appear, chest muscles clamp heart

Page 17: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Path of Least Resistance:

• Electricity will always look to return to its power source through the path of least resistance. Salt is a great conductor of electricity.

Salt Water Environment

Electricity is “transported” around the swimmer by the salt

Fresh Water Environment

The swimmer is the path of least resistance due to the salt

content of the human body

Page 18: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Electric Shock Drowning or Potential ESD:

• Often leaves no bodily clues to suggest anything but “simple drowning” due to alcohol intoxication or heart attack.

• No signs of burning due to the victim being submerged in water – no signs of electrocution.

• Often classified as electrical shock due to “evidence of great distress, multiple deaths…”

• Signs of a Potential Problem:

• Tingling sensation reported by anyone swimming in the marina.

• Excessive damage to metal boat parts in the water – props, etc…

Page 19: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Ground-Fault Regulation and Requirements:

Page 20: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Know Your Code:

States adopt versions of the National Electrical Code at different times. Make sure your constructions plans adhere to the codes your state (or municipality) have adopted.

Page 21: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Slide Title

Page 22: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Important Note on NEC Adoption / Implementation:

• Compliance with the most up to date NEC and NFPA codes are only required for new construction or modification that changes the fit, form, or function of a marina.

• Basic maintenance – changing a light bulb, receptacle, or circuit breaker does not require drastic upgrades to the entire electrical system.

• Some states or municipalities are requiring immediate compliance. Most are not. Check with the local AHJ for code requirements.

Page 23: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Relevant Codes:

• Testing / Inspection Requirements:

• Marinas:

• NEC and NFPA

• Vessels

• NEC 555.35B

• NFPA 4.8

• Needs to be documented

Page 24: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

National Electrical Code 555.35 – Ground-Fault Protection:

• 2020 National Electrical Code

• Receptacles – shall be ground-fault protected at 30mA or less. (555.35 (A)(1))

• Feeders and Branch Circuits – shall be ground-fault protected at 100mA or less. (555.35 (A)(3))

Diagram Courtesy of Gary Loftis

Page 25: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

National Electrical Code 555.35 – Ground-Fault Protection:

Diagram Courtesy of Gary Loftis

Page 26: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Typical Coordination:30mA Slip / 100mA Shore

Page 27: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

NEC 553Floating Buildings:

• The same code applies for floating buildings such as ship stores, bathrooms, and restaurants.

Page 28: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Inspection Requirements for Marinas (NFPA 303 5.20):

Inspection, Testing, and Maintenance of Electrical Wiring and Equipment:• Inspection of all:

• Electrical wiring including cable• Ground connections• Conduit and supports• Pedestals and utility centers• Distribution gear• Receptacles and circuit breakers

• Required annually• Needs to be documented

Page 29: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Inspection Requirements for Vessels (NEC 555.35 (B)):

Inspection, Testing, and Maintenance of Electrical Wiring and Equipment:• Where more than three receptacles supply shore power to boats, a leakage 

current measurement device shall be available and be used to determine leakage current from each boat that will utilize shore power.

• Every boat – full‐time, seasonal, and transient• Recommended annually• Needs to be documented

Page 30: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Inspection Requirements for Vessels (NFPA 303 - 4.8)

Ground‐Fault Testing for Marinas:• All vessels shall be tested for the presence of ac ground faults at the time of 

the initial connection to the marina electrical system…• Required annually• Vessel must display leakage under 30mA• Retroactive within 2‐years of adoption• Needs to be documented• Why?• How and Where?

Page 31: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Why?• Identify boats with potentially

dangerous electrical leakage problems before they connect to your marina electrical system.

• Typically ground-fault monitor tied to various receptacles and circuit breakers designed to evaluate the integrity of a boat’s electrical system.

• Visual displays help provide added piece of mind that a boat connecting to your marina is electrically safe.

Page 32: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – How and Where?

Monitors:• Types:

• Single‐Channel• Multi‐Channel• Integral CT• Digital Displays

• Locations:• Portable• Permanent

• Fuel Piers• Greeting Docks

Page 33: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Typical Procedure

1. Turn off all breakers on the power pedestal and testing device.2. Turn off all circuits on the vessel.3. Plug the power cord or cords into the testing device and then into the

pedestal.4. Energize the power outlet supply and then the testing device.5. Energize the VGFCU (main and branch breakers) – See Notice.6. Energize all of the circuits on the vessel one at a time and document

the ground-fault reading.7. If the readings do not exceed 30mA, the vessel is code compliant.8. If the readings exceed 30mA, the vessel is not code compliant and

should be barred from plugging in until repairs have been made and the vessel has been retested.

Page 34: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Portable Testing Devices:

Portable

Operating Instructions

Circuit Breakers

Receptacles

Alarms

Test Buttons

Portable Testing Device

Page 35: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Portable Testing Devices:

Cart Style Monitors

Page 36: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Portable Testing Devices:

Cord‐Set Style Module

Page 37: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Permanent Testing Devices:

Permanent Testing Pedestals:• Isolated from main marina• Available attendant

• Fuel Dock• Dockmaster’s Office• Greeting Dock

• Signage – Testing Purposes Only• Ideal for transient facilities• Trained attendant(s)• Document arrival time, testing 

times, and readings

Page 38: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Importance of Documentation:

Current Effects

15 mA to 20 mA

Pain shock, muscle contraction

Page 39: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Testing – Importance of Documentation:

Page 40: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

NEC 555.24Required Signage:

“555.24 Signage. Permanent safety signs shall be installed to give notice of electrical shock hazard risks to persons using or swimming near a boat docks or marina and shall comply with all of the following:

(2) The signs shall be clearly visible from all approaches to a marina or boatyard facility.

(3) The signs shall state ‘WARNING – POTENTIAL SHOCK HAZARD –ELECTRICAL CURRENTS MAY BE PRESENT IN WATER.’”

Page 41: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

NEC 555.24Required Signage:

Photo from JADELearning (www.jadelearning.com)

Page 42: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

General Electrical Safety Rules:

• Do not allow swimming in your marina.

• Post signs prohibiting swimming in the marina.

Page 43: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

General Electrical Safety Rules:

• Electrical work should only be completed by certified electricians.

• Marina work should comply with all NEC and NFPA codes.

• Routine maintenance and inspections should be performed at least annually per NFPA 5.20 “Maintenance of Electrical Wiring and Equipment.”

• Document inspections and maintenance for liability purposes.

• Boat owners should have all electrical work completed by ABYC certified electricians.

• Boat owners should also document inspections and maintenance for liability purposes.

Page 44: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

What to Look for While Walking Around the Facility

Page 45: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsExposed Conductors / Damaged Cables

Page 46: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsExposed Conductors Near Gas Lines

Page 47: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsSubmerged Connections

Page 48: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsHomemade Cord Sets / Use of Splitters

Page 49: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsHomemade Cord Sets / Use of Splitters

Page 50: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

“Customer Renovations”

Page 51: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsLoose or Broken Fittings

Page 52: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsEquipment in Poor Location / Overloaded Access Points

Page 53: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsPoor Cable or Cord Management

Page 54: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsGear in Illegal Locations – Below Datum Plane

Page 55: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsGear in Illegal Locations – No Circuit Breakers

Page 56: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsDamaged Gear / Pedestals

Page 57: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsPoorly Placed Equipment – Use Barriers

Page 58: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsDuct Tape on Anything Electrical

Page 59: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsGeneral Maintenance

Page 60: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsGarden Hose Conduit / Snakes for Ground Wires

Page 61: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsAggressive Boaters

Page 62: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsAggressive Drivers

Page 63: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Signs of Potential ProblemsRUN!!!!!!!!!!!!

Page 64: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Good References and Documents to Own

• NFPA 303 – Fire Protection Standards for Marinas and Boatyards – 2021 Edition

• National Electrical Code Handbook 2020 – Article 555 Marinas and Boatyards

• ACSE 50 – Planning and Design Guidelines for Small Craft Harbors

• AMI

• American Boat and Yacht Council

• Electrical Safety Foundation Intl.

•Local Electrical Authorities

Page 65: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

AMI – Best Management Practices for Marina Electrical Safety

Page 66: MARINA ELECTRICAL SYSTEMS: Safe Design & Ground-Fault …

Thank You