Ground fault location inAC & DC systems made easy
with BENDER EDS and RCMS systems
Secure Power
avoiding unwanted interruptions to operation
The increasing complexity of electrical installations places extreme-
ly high demands on the reliability of power supply systems. Even a
short power failure may be expensive due to production stoppage
and malfunction.
One decisive factor for the availability and operating safety of
electrical installations is the insulation resistance. Early detection,
fast localisation and elimination of insulation faults is the most
effective protection against interruption to operation and malfunc-
tion.
In distributed grounded & ungrounded systems, insulation fault location
is costly in terms of money and time. BENDER on-line insulation fault
and residual current location systems provide an innovative and
automatic solution to these problems. These comprehensive
solutions offer the user the benefits of increased system security
and safety, plus they provide significant reduction in time and cost.
• Time and cost reduction
- Automatic insulation fault or residual current location
during operation.
- Time saving thanks to exact location of the insulation fault.
- Effective support for preventive maintenance.
- No interruption to operation.
• Flexible in use
- Modular system for individual adaptation to the installati-
on.
- Flexible retrofitting and extension possibilities.
- Monitoring of up to 360 branches.
• Universal application
- EDS system for all AC/DC IT systems.
- RCMS system for all AC TN and TT systems.
- Portable location systems for small power systems and in
sub circuits.
- The EDS devices comply with IEC/EN61557-9 (draft).
Keeping everything under control - with PRC470
Provides a central control and display of the entire installation. All
monitoring parameters and important operating states are dis-
played in a text window, providing a complete overview of the
entire installation. The com-
munication between evalua-
tors and the central con-
trol/indicating device is via
a time and cost saving two-
wire
interface, which may be
easily extended.
sub distribution
infeed
main distribution
consumers
Error rate
Appl
icatio
n
x 1000
Advanced information
Insu
latio
n re
sista
nce
Time
Indication
Critical valuePersonal protectionInstallation protectionFire protection
Time gained thanks to early detection of insulation faults
An increasing number of sub circuits in an installation involves an increa-sing number of faults.
EDS470/EDS473 Ground fault location in ungrounded systems
When an insulation fault occurs in an ungrounded system, it will be
detected and indicated by the insulation monitoring device.
The ground fault location can be activated by the alarm contact
of the insulation monitor or manually. The test device PGH generates a
test signal for a defined period of time. Its amplitude and duration
are limited. This test signal flows via the location of the insulation fault
and through all measuring current transformers within the insula-
tion fault path. The EDS system scans all measuring current trans-
formers. The test signal is detected by the current transformers and
evaluated by the electronics of the EDS470-12/ EDS473-12. The
EDS with its LEDs and the PRC central controller, both provide fault
location path information.
The RCMS system operates on the principle of residual current
measurement. All conductors of the circuit to be monitored (except
the GND) are led through a current transformer. In a fault-free system
the resulting sum of all currents is equal to zero so that no voltage
is induced in the secondary winding of the measuring current
transformer. In the event of a fault current, the imbalance of the
current is sensed by the measuring current transformer and eva-
luated by the electronic circuitry.
A maximum of 12 measuring current transformers can be connec-
ted to one RCMS470-12 evaluator, i.e. 12 circuits can be monito-
red by one RCMS470-12. The RCMS470-12 scans all measuring
current transformers and indicates the faulty circuit via LED. All
RCMS units in a system work in parallel to minimise system evaluation.
The combination of an RCMS and PRC provides a central control
and display of the measuring results and a pre/main alarm war-
ning set up (10 mA-10 A), for each circuit. The use of current
transformers allows the RCMS system to be independent of both
the load current and the nominal voltage of the installation.
RF
IF
TN mit RCD
Iges
I1 I∆
Functional diagram EDS system
Functional diagram RCMS system
S
RCMS470 Ground fault current location in grounded systems
Ground fault location system EDS470
for ungrounded systems AC/DC 24...690V
•
Power supply circuits
• Systems with variable-speed drives
• Power supply systems with electricalinterference problems
T y p i c a l a p p l i c a t i o n
EDS470–12
Insulation fault evaluator which,together with the measuring cur-rent transformers, detects thePGH test signal and providesfault location indication.
• Up to 12 measuring current transformers inputs.• Alarm LED for each measuring current transformer.• Voltage-free common alarm contact.• RS485 interface.• Response value 5 mA.
Type Supply voltage US Art. No.
EDS470-12 AC230V B95012002
PGH471
Generates a defined test current signal.
• Manual or automatic testing possible.• LED to indicate the test cycle.• The operating range of the nominal voltage can be exten-ded with the coupling device AGE470.• RS485 interface.• Selectable test current 25/10 mA.
Type Supply voltage US Art. No.
PGH471 AC230V B95018004
PRC470
For central indication and con-trol of all EDS470-12 evalua-tors via RS485 interface.
• Text display –clear indication of all essential parameters, alarm messages and simplifies set-to-work.
• Fast detection of faulty circuits.• Centralised testing function.• Easy to operate via functional keys.• RS485 interface for up to 30 EDS470-12.• Up to 360 branches can be monitored.
Type Supply voltage US Art. No.
PRC470 AC230V B95012001
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 GND IN1 IN2 IN3 IN4 O1+ O1- O2+ O2-
A B 21 22 2411
PRC470
12 14
ALARM RS485RS485
PRC470 V1.1Bender, Grünberg
DATA 1+
DATA 1-
TX 1+
TX 1-
RX 1+
RX 1-
11
(RS-485)(RS-422)
DATA 0+
DATA 0-
RX 0+
RX 0-
TX 0+
TX 0-
(RS-485)(RS-422)
(R) +Vs
(B) GND
10
RS
-422/RS
-485R
EP
EATE
RS
W2
BA
UD
RATE
1O
N1200
2O
N2400
3O
N4800
4O
N9600
5O
N19200
6O
N38400
7O
N57600
8O
N115200
A1 A2 11 14 L1 L2 L3
A B GND IN1 IN2 E
10
RS485STARTSTOPON 25mA A3 A2 A1 A0
PGH471
SLAVE ADDRESS + 110
GENERATOR
SLAVE
MASTER10mA
IN3
46810204060∞
A1 A2 L1 L2 AK
PT 21 22 24
ALARMTESTRESET
KE
11 12 14
LT1 LT2M+ M-
2
+ -ON
201
kΩ
x1 kOhmx10 kOhm~
A-ISOMETER®Serie 470
kΩMONITOR
SMO480
A B 124 121 114 111 104 101 94 91 84 81 74 71 64
A1 A2 11 14 21 24 31 34 41 44 51 54 61 64
A3 A1TESTFAULT
TESTON/OFF
RS485
PSA3
352
MES
SZAN
GE
/ CL
AMP
ON
PRO
BE
Date
nbla
tt /
Data
shee
t : T
GH1
320
Durc
hmes
ser /
Dia
met
er :
52 m
m
Art.-
Nr.
/ Ar
t.-no
. : B
980
695
max
. 1 A
600
V C
AT II
I
1000
mA
/ 0,
1 m
A ~
EDS470 System
Insulation fault location system EDS473for IT systems AC/DC 24...230V
• Control systems
• Programmable controllers
• Diode-decoupled DC-powerplants distribution systems
• Hospitals, operating theatres
EDS473–12
Evaluator which with the mea-suring current transformersdetects the PGH test signal andprovides fault location indicati-on.
• Up to 12 measuring current transformers inputs.• Alarm LED for each measuring current transformer.• Voltage-free common alarm contact.• RS485 interface.• Response value 0.5mA.
Type Supply voltage US Art. No.
EDS470-12 AC230V B95012019
PGH473
Generates a defined test cur-rent signal which meets therequirements of most controlcircuits.
• Manual or automatic testing possible.• LED to indicate the test cycle.• RS485 interface.• Selectable test current 2.5/1m.
Type Supply voltage US Art. No.
PGH473 AC230V B95018009
PRC470
For central indication andcontrol of all EDS473-12 eva-luators via RS485 interface.
• Text display- clear indication of all essential parameters, alarm messages and simplifies set-to-work.
• Fast detection of faulty circuits.• Centralised testing function.• Easy to operate via functional keys.• RS485 interface for up to 30 EDS470-12.• Up to 360 branches can be monitored.
TypeSupply voltage US Art. No.PRC470 AC230V B95012001
T y p i c a l a p p l i c a t i o n
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
A B R1 R2 l K12 K11 K10 11 12 14
onoff
RS485TEST
RESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1EDS470
I∆s
SLAVE ADDRESS
MONITOR
A1 A2 GND IN1 IN2 IN3 IN4 O1+ O1- O2+ O2-
A B 21 22 2411
PRC470
12 14
ALARM RS485RS485
PRC470 V1.1Bender, Grünberg
DATA 1+
DATA 1-
TX 1+
TX 1-
RX 1+
RX 1-
11
(RS-485)(RS-422)
DATA 0+
DATA 0-
RX 0+
RX 0-
TX 0+
TX 0-
(RS-485)(RS-422)
(R) +Vs
(B) GND
10
RS
-422/RS
-485R
EP
EATE
RS
W2
BA
UD
RATE
1O
N1200
2O
N2400
3O
N4800
4O
N9600
5O
N19200
6O
N38400
7O
N57600
8O
N115200
A1 A2 11 14 L1 L2 L3
A B GND IN1 IN2 E
10
RS485STARTSTOPON 25mA A3 A2 A1 A0
PGH471
SLAVE ADDRESS + 110
GENERATOR
SLAVE
MASTER10mA
IN3
46810204060∞
A1 A2 L1 L2 AK
PT 21 22 24
ALARMTESTRESET
KE
11 12 14
LT1 LT2M+ M-
2
+ -ON
201
kΩ
x1 kOhmx10 kOhm~
A-ISOMETER®Serie 470
kΩMONITOR
SMO480
A B 124 121 114 111 104 101 94 91 84 81 74 71 64
A1 A2 11 14 21 24 31 34 41 44 51 54 61 64
A3 A1TESTFAULT
TESTON/OFF
RS485
PSA3
352
MES
SZAN
GE
/ CL
AMP
ON
PRO
BE
Date
nbla
tt /
Data
shee
t : T
GH1
320
Durc
hmes
ser /
Dia
met
er :
52 m
m
Art.-
Nr.
/ Ar
t.-no
. : B
980
695
max
. 1 A
600
V C
AT II
I
1000
mA
/ 0,
1 m
A ~
EDS473 System
Ground fault location system RCMS470 for grounded & high-resistance grounded systems
• Industrial systems
• Power plants
• Traffic engineering
• Electronic data processing systems
• Building services managementsystems
RCMS470–12
Residual current monitor, func-tions with the measuring cur-rent transformers, detects resi-dual current and indicates thefaulty circuit.
• Up to 12 measuring current transformers inputs. • Alarm LED for each measuring current transformer.• Voltage-free common alarm contact.• RS485 interface.• Wide response range 10mA-10A.
Type Supply voltage US Art. No.
RCMS470–12 AC230V B94052001
PRC470
Central indication and controlof all RCMS470-12 evaluatorsvia RS485 interface.
• Text display- clear indication of all essential parameters, alarm messages and simplifies set-to-work.
• Fast detection of faulty circuits.• Remote setting of the RCMS470-12 response values.• Easy to operate via functional keys.• RS485 interface.• Up to 360 branches can be monitored.
Type Supply voltage US Art. No.
PRC470 AC230V B95012001
T y p i c a l a p p l i c a t i o n
A1 A2 11 12 14
0 1t/s
ALARMONTEST
RESET
21 22 24T/R
1 10x mA10 30 10
030
050
0x1
0x1
- / R
es
RCM Serie 470 MONITOR10 50 100%
T/R
M+ M- (k) (l)
A1 A2 11 12 14
0 1t/s
ALARMONTEST
RESET
21 22 24T/R
1 10x mA10 30 10
030
050
0x1
0x1
- / R
es
RCM Serie 470 MONITOR10 50 100%
T/R
M+ M- (k) (l)
A1 A2 11 12 14
0 1t/s
ALARMONTEST
RESET
21 22 24T/R
1 10x mA10 30 10
030
050
0x1
0x1
- / R
es
RCM Serie 470 MONITOR10 50 100%
T/R
M+ M- (k) (l)
A1 A2 11 12 14
0 1t/s
ALARMONTEST
RESET
21 22 24T/R
1 10x mA10 30 10
030
050
0x1
0x1
- / R
es
RCM Serie 470 MONITOR10 50 100%
T/R
M+ M- (k) (l)
RCMS470 MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
10
TESTRESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1
SLAVE ADDRESS
Y:
RS485
1 A500300100503010Y/mAD0D1D2
MASTER:
SLAVE
D2 D1 D0 R/- MASTER
A B R1 R2 l K12 K11 K10 11 12 14
A1 A2 GND IN1 IN2 IN3 IN4 O1+ O1- O2+ O2-
A B 21 22 2411
PRC470
12 14
ALARM RS485RS485
RCMS470 MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
10
TESTRESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1
SLAVE ADDRESS
Y:
RS485
1 A500300100503010Y/mAD0D1D2
MASTER:
SLAVE
D2 D1 D0 R/- MASTER
A B R1 R2 l K12 K11 K10 11 12 14
BMT1000
Supervisor
localindication
centralindication
RS485
RCMS470-12 RCMS470-12
PRC470
RCM475 RCM475 RCM475 RCM475
Monitoring concept with RCMS470 systemand local RCM470 devices
RCMS470 system
A1 A2 GND IN1 IN2 IN3 IN4 O1+ O1- O2+ O2-
A B 21 22 2411
PRC470
12 14
ALARM RS485RS485
PRC470 V1.1Bender, Grünberg
SMO480
A B 124 121 114 111 104 101 94 91 84 81 74 71 64
A1 A2 11 14 21 24 31 34 41 44 51 54 61 64
A3 A1TESTFAULT
TESTON/OFF
RS485
DATA 1+
DATA 1-
TX 1+
TX 1-
RX 1+
RX 1-
11
(RS-485)(RS-422)
DATA 0+
DATA 0-
RX 0+
RX 0-
TX 0+
TX 0-
(RS-485)(RS-422)
(R) +Vs
(B) GND
10
RS
-422/RS
-485R
EP
EATE
RS
W2
BA
UD
RATE
1O
N1200
2O
N2400
3O
N4800
4O
N9600
5O
N19200
6O
N38400
7O
N57600
8O
N115200
RCMS470 MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
10
TESTRESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1
SLAVE ADDRESS
Y:
RS485
1 A500300100503010Y/mAD0D1D2
MASTER:
SLAVE
D2 D1 D0 R/- MASTER
A B R1 R2 l K12 K11 K10 11 12 14
RCMS470 MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
10
TESTRESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1
SLAVE ADDRESS
Y:
RS485
1 A500300100503010Y/mAD0D1D2
MASTER:
SLAVE
D2 D1 D0 R/- MASTER
A B R1 R2 l K12 K11 K10 11 12 14
RCMS470 MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
10
TESTRESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1
SLAVE ADDRESS
Y:
RS485
1 A500300100503010Y/mAD0D1D2
MASTER:
SLAVE
D2 D1 D0 R/- MASTER
A B R1 R2 l K12 K11 K10 11 12 14
RCMS470 MONITOR
A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9
10
TESTRESETFAULTALARMON A4 A3 A2 A1 A0
K12K11K10K9K8K7K6K5K4K3K2K1
SLAVE ADDRESS
Y:
RS485
1 A500300100503010Y/mAD0D1D2
MASTER:
SLAVE
D2 D1 D0 R/- MASTER
A B R1 R2 l K12 K11 K10 11 12 14
PSA3
352
MES
SZAN
GE
/ CL
AMP
ON
PRO
BE
Date
nbla
tt /
Data
shee
t : T
GH1
320
Durc
hmes
ser /
Dia
met
er :
52 m
m
Art.-
Nr.
/ Ar
t.-no
. : B
980
695
max
. 1 A
600
V C
AT II
I
1000
mA
/ 0,
1 m
A ~
Portable systems
• For small power systems, tem-porary insulation fault or resi-dual current location
• As supplement to RCMS470,EDS470 and EDS473 systems
A p p l i c a t i o n
Overview of portable systems
EDS EDS EDS EDSPortable systems 3060 3065 3360 3365
Insulation fault (IT system) x x x x
Response value (test current) 5mA 5mA 0.5mA 0.5mA
Residual current TN system 10mA-10A 10mA-10A 10mA-1A 10mA-1A
Test device - PGH185 - PGH183
Evaluator EDS165 EDS165 EDS165-3 EDS165-3
Measuring clampsPSA3020 ø 20 mm x x - -PSA3052 ø 52 mm x x - -PSA3320 ø 20 mm - - x xPSA3352 ø 52 mm - - x xPSA3165 ø 100 mm optional optional - -
Insulation fault location systems for IT systems and
IT systems with integrated residual current measu-
rement for all earthed systems (TN/TT systems)
Portable insulation fault location systems comprising a test device, an evaluator, various measuring clamps and accessories, in a robust carrying case.
• Easy to operate with a clear text display on the EDS165 evaluator
• Measuring clamps with an internal diameter of 20/52 mm, alternatively 100 mm.
EDS3065 • For IT systems AC 24-500V/ DC 24-360V.• Test signal evaluator EDS165: 5mA.• Residual current measurement: 10mA-10A.
EDS3060 • The same as EDS 3065, but without testdevice, for EDS470 systems.
EDS3365 • For IT systems AC 24-230V/ DC 24-230V. • PGH test signal: 2.5mA/ 1mA.• Response value evaluator
EDS165-3:0.5mA.• Residual current measurement: 10mA-1A.
EDS3360 • The same as EDS3365, but without test device, for EDS473 systems.
TypeSupply voltage US Art. No.
EDS3065 AC 230V B91082004
EDS3060 AC 230V B91082006
EDS3365 AC 230V B91082011
EDS3360 AC 230V B91082013
Bender Inc.700 Fox ChaseCoatesville, PA 19320 - USATel : 610-594-8595 Fax : 610-383-7100In ter ne t : h t tp : / /ww w.bender . o r gE-mai l : i n fo@bender .o rg
Right to modifications reserved
GPW
· 21
02/0
799/
3000
SMO signal converter
The SMO480-12 connects to the RS485 interface and converts EDS470/RCMS470fault location indications to relay outputs.
Type Supply voltage US Art. No.SMO480–12 AC230V B95012011
FTC1500
For the connection of the BenderMeasuring Interface (BMS) bus tostandard field bus systemsJBUS/MODBUS, suitable for instal-lation into distribution panels,96x96mm, or for DIN rail mounting
Type Supply voltage US Art. No.FTC1500 AC230V B95012012
DI-1
Repeater for RS485 interface with electrical isolation. To extend the bus length by 4000 ft. (1200 m) and/orto extend the number of connected nodes by 32.
Type Supply voltage US Art. No.DI-1 DC10-30V B95012015
Coupling device AGE470
To extend the operating rangeof the nominal voltage of theEDS470 system in 1 ph/3ph ITsystems to AC500-690 V/DC360-690V
Type Nominal voltage UN Art. No.AGE470 AC500-690/DC440-690V B98018002
Measuring current transformers WR series
rectangular type,particulary suited for bus bar systems
Type W x H (mm)Art.No. EDS470 EDS473 RCMS470WR 70 x 175S 70 x 175 B911738 x xWR 115 x 305S 115 x 305 B911739 x xWR 150 x 350S 150 x 350 B911740 x x
Measuring current transformers WR series
split-core type,particulary for retrofitting
Type W x H (mm) Art.No. EDS470 EDS473 RCMS470WS50x80S 50 x 80 B911741 x xWS80x80S 80 x 80 B911742 x xWS80x120 80 x 120 B911743 x xWS80x160S 80 x 160 B911755 x xWS50x80S/8000 50 x 80 B911757 x
Measuring current transformerscircular type, for normal application
Type ø mm Art. No. EDS470 EDS473 RCMS470W0-S15 15 B911753 x xW1-S35 35 B911731 x xW2-S70 70 B911732 x xW3-S105 105 B911733 x xW4-S140 140 B911734 x xW5-S210 210 B911735 x xW6-S35/8000 35 B911756 x
System ExtensionsAccessories