AThink future. Switch to green.
Building Automation SystemsIndustrial Automation
User Manual
06/04 AWB2528-1480GB
MFD-TitanMulti-Function Display
-
8/6/2019 Manual MFD Ingles
2/450
All brand and product names are trademarks or registeredtrademarks of the owner concerned.
1st published 2003, edition date 06/032nd edition 06/2004See revision protocol in the About this manual chapter
Moeller GmbH, 53105 Bonn
Author: Dieter BauerfeindEditor: Heidrun RiegeTranslator: Terence Osborn
All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form(printed, photocopy, microfilm or any other process) orprocessed, duplicated or distributed by means of electronic
systems without written permission of Moeller GmbH, Bonn.
Subject to alteration without notice.
-
8/6/2019 Manual MFD Ingles
3/450
Before commencing the installation
Disconnect the power supply of the device.
Ensure that devices cannot be accidentally
restarted. Verify isolation from the supply.
Earth and short circuit.
Cover or enclose neighbouring units thatare live.
Follow the engineering instructions (AWA)of the device concerned.
Only suitably qualified personnel inaccordance with EN 50110-1/-2(VDE 0105 Part 100) may work on thisdevice/system.
Before installation and before touchingthe device ensure that you are free ofelectrostatic charge.
The functional earth (FE) must beconnected to the protective earth (PE) or
to the potential equalisation. The systeminstaller is responsible for implementingthis connection.
Connecting cables and signal lines shouldbe installed so that inductive or capacitive
Suitable safety harmeasures should bI/O interface so thaon the signal side undefined states indevices.
Ensure a reliable elow voltage for theuse power supply uIEC 60364-4-41 (VHD 384.4.41 S2.
Deviations of the mrated value must nlimits given in the s
this may cause maloperation.
Emergency stop deIEC/EN 60204-1 moperating modes odevices. Unlatching
devices must not c Devices that are de
housings or controoperated and contbeen installed with
Warning!Dangerous electrical voltage!
-
8/6/2019 Manual MFD Ingles
4/450
Measures should be taken to ensure theproper restart of programs interruptedafter a voltage dip or failure. This shouldnot cause dangerous operating states evenfor a short time. If necessary, emergency-
stop devices should be implemented.
Wherever faults in themay cause damage toexternal measures muensure a safe operatinof a fault or malfuncti
means of separate limmechanical interlocks
-
8/6/2019 Manual MFD Ingles
5/450
06/04 AWB2528-1480D
About This ManualDevice designationWriting conventionsList of revisions
1 MFD-TitanTarget readershipProper use
Improper use OverviewDevice overview MFD devices at a glance Type references for the MFD-MFD operation
Buttons Moving through menus and c Selecting main and system m MFD-Titan Status display Status display for local expan MFD-Titan advanced Status d
MFD-Titan LED display Menu structure Selecting or toggling betwee Cursor display Setting values
Contents
-
8/6/2019 Manual MFD Ingles
6/450
Contents 06/04 AW
Network cables and plugsConnecting the power supply Cable protection Connecting the inputs Connecting the AC inputs Connecting MFD-DC inputs Connecting the outputsConnecting relay outputs MFD-R.. EASY6..-..RE.. EASY2..-RE Connecting transistor outputs MFD-T.. EASY6..-DC-TE Connecting analog outputs Connecting servo valves Setpoint entry for a drive Connecting the NET network
Accessories Cable length and cross-sections Plugging and unplugging netwoConnecting the serial interfaceExpanding inputs/outputs Local expansion
Remote expansion
3 CommissioningSwitching on
-
8/6/2019 Manual MFD Ingles
7/450
Conten06/04 AWB2528-1480D
Configuring an easy-NET netwo Entering the network station Entering network stations Configuring an easy-NET net Changing the easy-NET netw
configuration Displaying the Status display Configuring the interface for thmode Setting up the COM-LINK Terminal mode Terminal mode
4 Wiring with MFD-TitanMFD-Titan operation Buttons for drawing circuit d
function block usage
Operating principles Usable relays and function bl Markers, analog operands Number formats Circuit diagram display Saving and loading programs
Working with contacts and rela Creating and modifying conn Inserting and deleting a rung Saving circuit diagrams Aborting circuit diagram entr
-
8/6/2019 Manual MFD Ingles
8/450
Contents 06/04 AW
Data block comparator Data block transfer Boolean operation Counters High-speed counters Frequency counters High-speed counters High-speed incremental encode Comparators Text output function block Data function block PID controller Signal smoothing filter GET, fetch a value from the netw Seven-day time switch Year time switch Value scaling Jumps
Master reset Numerical converters Operating hours counter PUT, send a value onto the netw Pulse width modulation Setting date/time
Set cycle time Timing relay Value limitation Example with timing relay and
counter function block
-
8/6/2019 Manual MFD Ingles
9/450
Conten06/04 AWB2528-1480D
Numerical value Example numerical value: Value entry Message text Button editor Select an operable screen ele Display backlight Screen change Password logout Set variable to fixed value Increment variable Decrement variable Changeover relay
6 easy-NET Network, COM-LINConnectionIntroduction to easy-NET
easy-NET network topologies, aand functions Loop through the unit wiring T connector and spur line Position and addressing of th
via easy-NET
Possible write and read authin the network Configuration of the easy-NET Station number Transmission speed
-
8/6/2019 Manual MFD Ingles
10/450
Contents 06/04 AW
Introduction to COM-LINK Topology Configuration of the COM-LINK
7 MFD Settings
Password protection Password setup Selecting the scope of the passw Activating the password Unlocking MFD Changing the menu language
Changing parameters Adjustable parameters for functSetting date, time and daylight savChanging between winter/summerActivating input delay (debounce) Deactivating debounce (input de
Activating and deactivating the P Activating the P buttons Deactivating the P buttons Startup behaviour Setting the startup behaviour Behaviour when the circuit diag
is deleted Behaviour during upload/downloto card or PC
Possible faults Card startup behaviour
-
8/6/2019 Manual MFD Ingles
11/450
Conten06/04 AWB2528-1480D
8 Inside MFDMFD Program cycle How MFD evaluates the high
CF, CH and CI Memory management of the
Delay times for inputs and out Delay times for the MFD inpuMonitoring of short-circuit/overwith EASY..-D.-T..Expanding MFD-Titan How is an expansion unit rec
Transfer behaviour Function monitoring of expanQA analog outputLoading and saving programs MFD without display and key Interface Memory card EASY-SOFT-PRO Device version
AppendixTechnical data
General CPU, real-time clock/timing r Transistor outputs Analog output easy-NET network
-
8/6/2019 Manual MFD Ingles
12/450
06/04 AW
-
8/6/2019 Manual MFD Ingles
13/450
06/04 AWB2528-1480GB
About This Manual
This manual describes the installatioprogramming (circuit diagram genercontrol relay.
A specialist knowledge of electrical for commissioning and creating circactive components such as motors ocontrolled, parts of the system can bput at risk if the MFD device is conn
incorrectly.
Device designation This manual uses the following abbrdifferent device models:
MFD-Titan MFD easy-AC for EASY618-AC-RC easy-DC for EASY6..-DC-.E
Writing conventions Symbols used in this manual have thX Indicates actions to be taken.
hAttention!W f th ibilit f li ht d
-
8/6/2019 Manual MFD Ingles
14/450
About This Manual 06
For greater clarity, the name of the currin the header of the left-hand page andcurrent section in the header of the righ
does not apply to pages at the start of pages at the end of a chapter.
List of revisions
h Indicates interesting tips and additio
Edition Page Topic New Ch
06/04 9 Device designation j
30 Section Setting values j
64 Section Temperature sensor,
brightness sensor, 20 mA sensor
j
73 Connection cable: j
74 Section Cable length and cross-sections
j
117 Initialise display j
131 Table 8 j132 Section Composition of the markers j
194 High-speed counters j
203 Figure 105 j
-
8/6/2019 Manual MFD Ingles
15/450
List of r06/04 AWB2528-1480GB
06/04 261 Section Time range
262 Section Variable setpoint values
265 Figure 101
266,267
Figure 135 and Figure 136
279 Chapter 5 j
365 Section Password incorrect or nolonger known
391 Section Memory management of theMFD-Titan
401 Section Memory card
406 Section EASY-SOFT-PRO
412 Graphic Dimensions of the MFD-80..
display/operating unit413 Graphic Dimensions of the MFD-CP8..
power supply/CPU module.
414 Climatic ambient conditions
414 Ambient mechanical conditions
415 Electromagnetic compatibility (EMC)415 Dielectric strength
416 Operating buttons, input current
Edition Page Topic New
-
8/6/2019 Manual MFD Ingles
16/450
06
-
8/6/2019 Manual MFD Ingles
17/450
06/04 AWB2528-1480GB
1 MFD-Titan
Target readership MFD must only be installed and wireelectricians or other persons familiar
electrical equipment.A specialist knowledge of electrical for commissioning and creating circcontrolling active components such cylinders, parts of the system can beput at risk if MFD is connected or pr
Proper use MFD is a programmable device that pclosed-loop and open-loop control fused to replace relay and contactor cused as an MFD device. MFD must b
before use.The display and operating unit of thIP65 and does not normally require protection. The rear MFD units are dunits and must be installed in an enor a service distribution board. Both signal terminals must be laid and coaccidental contact.
The installation must comply with reelectromagnetic compatibility (EMC
06/04 AWB
-
8/6/2019 Manual MFD Ingles
18/450
MFD-Titan 06/04 AWB
Overview MFD-Titan is an electronic HMI unit anthe following features:
Logic functions, Timing relay and counter functions, Time switch functions, Arithmetic functions, PID controllers, Operator and display functions.
MFD-Titan is a display, HMI, control and
With MFD-Titan you can create solutioapplications as well as for tasks in macconstruction. MFD-Titan is a modular a
The integral easy-NET network enables to eight easy-NET stations to form a sinEach easy-NET station can contain a pr
the design of systems using high-speeddecentralised intelligence.
In Terminal mode, the MFD can be usedin the network and display data from itwhether it is an easy800 or an MFD. Inmakes its keypad and display availablefor use.
Two devices, MFD with easy800 or MFsimply via the serial interfaces.
06/04 AWB2528 1480GB
-
8/6/2019 Manual MFD Ingles
19/450
Overvie06/04 AWB2528-1480GB
off-delayed, off-delayed with random switch on and off delayed, on and off delayed with random single pulse,
synchronous flashing, asynchronous flashing.
use up and down counters, count high-speed signals:
up and down counters with up
values, preset, frequency counters, high-speed counters, count incremental encoder valu
compare values, display graphics, texts, variables,
flashing values and graphics, chanand texts by pushbutton,
process additional inputs and out use 7-day and year time switches
count operating hours (operating communicate via the integrated e set up point-to-point communicat
interface,d l d l l h
i 06/04 AWB
-
8/6/2019 Manual MFD Ingles
20/450
MFD-Titan 06/04 AWB
track the flow of current in the circui load, save and password-protect circ
If you prefer to wire up MFD-Titan fromEASY-SOFT-PRO. EASY-SOFT-PRO allowtest your circuit diagram on the PC. All functions on the MFD device are createthe EASY-SOFT-PRO software. EASY-SOto print out your circuit diagram in DIN,
Device overview MFD devices at a glanceDisplay and operating unit
Figure 1: Overview of the display and ope
a DEL button
a
d
b
i efgh
c
D i06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
21/450
Device 06/04 AWB2528-1480GB
Power supply and CPU
Figure 2: Device overview of power su
a Power supplyb easy-NET terminalsc EASY-LINK terminal
d Interface for memory card, PC and pe Power supply / operating mode LEDf easy-NET LED
Inputs/outputs
a b
ef
d
ba
MFD Titan 06/04 AWB
-
8/6/2019 Manual MFD Ingles
22/450
MFD-Titan 06/04 AWB
Type references for the MFD-Titan
MFD operation Buttons
MFD - x xx x - x x - x x
Additional functions
EquipmentB = Operator buttonsME = Open-loop control, closedloop control, closed-loop contro
Device functionNumber = display and enclosureCP8 = Power supply and CPU raR = relay outputs, T = TransistorA = Analog outputNumber = Number of inputs and
Multi-function display
DEL: Delete object in circuit diagram
ALT: Special functions in circuit-diagra
Cursor buttons :Move cursorSelect menu itemsSet contact numbers, contacts and valu
*
DEL ALT
ESC
OK
MFD op06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
23/450
MFD op06/04 AWB2528 1480GB
Moving through menus and cho
and Show System menu
Go to next menu levelSelect menu item
Activate, modify, save your entryReturn to last menu levelCancel your entry since the last OK
Change menu itemChange valueChange place
Function of P buttons:
Input P1,Input P3,
InpuInpu
and Reset the MFD display
DEL ALT
OK
ESC
DEL ESC
MFD-Titan 06/04 AWB
-
8/6/2019 Manual MFD Ingles
24/450
MFD Titan
Selecting main and system menu
Status display
Date display
MFD-Titan Status display
R.2RS
MOS .2 6..
I .2..5.......P-
MO 02:00Q..34 . STOP
anDEL
OK ESC ESC
Current selectionflashes in
the MFD menu
1st menu levelMain menu
1st menu leveSystem men
PROGRAM...STOP RUNPARAMETERSSET CLOCK...
SECURITY...SYSTEM...MENU LANGUACONFIGURATO
I .2..5.......P-
MO 11:50Q..34.... STOP I .2..5....
MO 01.04.20Q..34....
ALT
MFD op06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
25/450
MFD op
Status display for local expansio
MFD-Titan advanced Status disp
Inputs AC expansExpansion or Weekda
Weekday/TimeOutputs
On: 1, 2, 3, 4/Off:RS = Expansion functioning correctl
R 1.........12RS AC P-MO 10:42S 1......8 STOP
Retention/debounce/easy-NET station
AC expansStartup beh
RE : Retention switched onI : Debounce switched onNT1 : easy-NET station with station addressCOM The COM connection is activeAC : AC expansion functioning correctlyDC : DC expansion functioning correctly
GW : Bus coupling module detectedGW flashes: Only easy200-easy detected. I/O expansion not detectedST : When the power supply is switched on, MFD switches to STOP mode
I 12...6.89..12RE I NT1 AC P-MO 14:42 TQ 12345678 RUN
MFD-Titan 06/04 AWB
-
8/6/2019 Manual MFD Ingles
26/450
ta
Table 1: Power supply/RUN-STOP mode
Table 2: easy-NET LED (easy-NET)
The front of the MFD-80.. device has a LED. These can be used in your visualizlight indicators.
The following applies to Terminal mode
Green LED
Table 3: Power supply/RUN-STOP mode
Red LED
bl l h
LED OFF No power supply
LED continuously lit Power supply prese
LED flashing Power supply prese
LED OFF easy-NET not operaconfiguration
LED continuously lit easy-NET is initialisbeen detected.
LED flashing easy-NET operating
LED OFF No power supply
LED continuously lit Power supply prese
LED flashing Power supply prese
MFD op06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
27/450
p
Menu structure
Main menu without password pX You access the main menu by pre
PROGRAM...DELETE PROGRAMCARD
Main menu
STOP: Ci
RUN: Po
Parameters
CIRCUIT DIAGRAMFUNCTION RELAYS
CIRCUIT DIAGRAMFUNCTION RELAYS
Parameter
display
PROGRAM... STOP RUNPARAMETERSSET CLOCK TERMINAL MODE..
MFD-Titan 06/04 AWB
-
8/6/2019 Manual MFD Ingles
28/450
Main menu
Parameters
Parameter display
SET CLOCKDST SETTING
DEVICE-CARDCARD-DEVICEDELETE CARD ?
PROGRAM...DELETE PROGRAMCARD...
DEVICE-CARDCARD-DEVICEDELETE CARD ?
DEVICE-CARDCARD-DEVICEDELETE CARD ?PROGRAM...
STOP RUN PARAMETERSSET CLOCK... TERMINAL MODE
PROGRAM... STOP RUN PARAMETERSSET CLOCK... TERMINAL MODE
SET CLOCKDST SETTING
Display for date and timsetting
HH:MM --:--DD.MM --.--YEAR ____
NONE MANUAL EU
PROGRAM... STOP RUN PARAMETERSSET CLOCK... TERMINAL MODE
MFD op06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
29/450
Main menu with password prote
MFD-Titan system menuX The System menu is accessed by s
DEL and ALT.
Password
Password entryUnlockingMFD
PASSWORD... STOP RUN PARAMETERSSET CLOCK...
Main menu
PASSWORD...RUN
CorrectentryStatus display
Four wrong e(if enabled)
PROGRAM
ENTER PASSWORD------
System menu
ACTIVATE PWCHANGE PW
Password entry
Change/deletepassword
SECURITY...SYSTEM...MENU LANGUAGECONFIGURATOR...
PasswordSetup
PASSWORD...RANGE...
ENTER PASSWORD------
PASSWORD...
MFD-Titan 06/04 AWB
-
8/6/2019 Manual MFD Ingles
30/450
MB -- -> MB -- C -- -> C --CH -- -> CH --
B: 200 CI -- -> CI --
DB -- -> DB --T -- -> T --
DEBOUNCE P BUTTONSRUN MODECARD MODE TERMINAL MODE
DISPLAY...RETENTION...INFORMATION...
System menu
SECURITY...SYSTEM...MENU LANGUAGECONFIGURATOR...
Retention only in STOPmode
DEBOUNCE P BUTTONS RUN MODE CARD MODE TERMINAL MODE
DISPLAY...RETENTION...INFORMATION...
DEBOUNCE P BUTTONSRUN MODECARD MODE TERMINAL MODEDISPLAY...RETENTION... INFORMATION...
DEBOUNCE P BUTTONSRUN MODE CARD MODE
TERMINAL MODEDISPLAY RETENTION...INFORMATION...
CONTRAST: 0LIGHTING: 75%
DEBOUNCE
P BUTTONSRUN MODECARD MODETERMINAL MODE DISPLAY...RETENTION...
MFD op06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
31/450
System menu
SECURITY...SYSTEM...MENU LANGUAGECONFIGURATOR...
SECURITY...SYSTEM...MENU LANGUAGECONFIGURATOR...
NET...COM...LINK...
NET PARAMETERS..STATIONS...CONFIGURE...
The other menus ofNET and COM areonly shown in STOPmode
Only one selection is p
ENGLISH DEUTSCH FRANCAISESPANOL ITALIANOPORTUGUES
NEDERLANDSSVENSKAPOLSKITURKCE
NET-ID : __ BAUDRATE: ____KBBUSDELAY: __
SEND IO: REMOTE RUNREMOTE IO
NET PARAMETERS...STATIONS...CONFIGURE...
MFD-Titan 06/04 AWB
-
8/6/2019 Manual MFD Ingles
32/450
1 1 2 03 04 0 5 06 07 08 0
System menu
NET PARAMETERS...STATIONS...CONFIGURATOR...
TinTs
s
NET PARAMETERS...STATIONS...CONFIGURATOR... CONFIGURE?
SAVE
CANCE
Fault scenario
with ID conflict.
Fault scenariowith networkfault.
C
P
ECC
E
MFD op06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
33/450
Selecting or toggling between m
BAUDRATE: 9600BCOM-LINKREMOTE MARKER...
System menu
NET...COM...CONFIGURE...
BAUDRATE:19200BCOM-LINK REMOTE MARKER...
Cursor
Select or switch
PROGRAM...STOPPARAMETERSSET CLOCK...
OK
MFD-Titan 06/04 AWB
-
8/6/2019 Manual MFD Ingles
34/450
Cursor display
Setting values
The cursor flashes.
Full cursor /:
Move cursor with ,
in circuit diagram also with Value M/M
Change position with Change values with
Flashing values/menus are shown in gr
HH:MM '4:23DD.MM 05.05YEAR 2003
HH:MM 14:23DD.MM 05.05YEAR 2003
Change value
Select cursor positionChange value at posi
Store entries
Retain previous value
ValuesPositions
Value at
HH:MM 14:23DD.MM 03.10YEAR 2002
OK
ESC
06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
35/450
2 Installation
The MFD must only be installed andelectricians or other persons familiarelectrical equipment.
The MFD is installed in the following Mounting, Wiring up the inputs, Wiring up the outputs, Wiring up the NET network (if req
Setting up the serial interface (if r Connecting the power supply.
Danger of electric shock!Never carry out electrical work onpower supply is switched on.
Always follow the safety rules:
Switch off and isolate, Ensure that the device is no lon Secure against reclosing, Short-circuit and ground, Cover adjacent live parts.
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
36/450
For ease of wiring, leave a gap of at leaMFD terminals and the wall or adjacen
Figure 4: Clearances to the MFD
Fitting the protective membraneFor special applications such as in the foperating unit must be protected againsliquids etc.
For this use the specially designed protFit the protective membrane before mooperating unit.
h When using the MFD with expansionexpansion concerned before mountin
30
30
30
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
37/450
Figure 5: Fitting the protective membr
a Protective membraneb Display/operating unit
X Place the protective membrane ovunit.
Caution!Ensure that the membrane fits snudisplay/operating unit.
Otherwise a proper seal cannot be
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
38/450
Figure 6: Correct position of the protectiv
Mounting the protective coverThe protective cover is provided for usiaggressive environments. This protects
operating unit against mechanical damProtection to IP65 is maintained.
The protective cover can be opened so unit can be used.
The protective cover can be closed withprovide protection against unauthorise
Before mounting the display/operating ucover.
h If the protective membrane has to be
and the operating unit have to be remmembrane and refit the device.
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
39/450
Figure 7: Removing the front frame
X Remove the front frame as shown
The protective cover can be mountepositions. Choose the position that application at hand and your require
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
40/450
Figure 9: Mounting the protective cover
XMount the protective cover as shown
Sealing the protective cover
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
41/450
Mounting the display/operatingmounting
Figure 11: Drill holes for the MFD
X Drill and punch out two 22.5 mmdiameter is the same as is normalcircuit devices.
30
22.5
h Observe the following technical re
The hole spacing is 30 mm. The maximum thickness of the f
the power supply/CPU module 6 mm.
The maximum thickness of the fan expansion unit with a top-ha
power supply/CPU module mus4 mm.
Leave enough space at the sideCPU module, and if necessary, t
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
42/450
Figure 12: Mounting the display/operating
The protective membrane or the protecfitted.
X Fit the display/operating unit in the p
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
43/450
Figure 13: Screw fastening the display/o
X Screw fasten the display/operatin
The tightening torque must be betw
2x
h Ensure that the correct torque is utorque is too low or high, this ma
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
44/450
Removing the display/operating unmountingX Unscrew the fixing element and remo
operating unit.
Mounting the power supply/CPU m
If you wish to add expansion units to thmodule, the top-hat rail must be fitted
Fitting the top-hat railEnsure that the cutout of the top-hat rathe fixing shafts according to the specif
Figure 15: Top-hat rail with cutout
120
216
60
30g0.2
h The two fixing shafts of the display/odesigned for a 2 space unit expansio
If you wish to fit wider expansion unmust be supported at a third support
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
45/450
Attach the expansion unit before fitt
Figure 16: Fitting the top-hat rail
X Fit the top-hat rail in the groove uthe power supply/CPU module an
X Turn the top-hat rail towards the X Let the top-hat rail snap into posiX Press the power supply/CPU modu
Caution!The fixing shafts of the display/opefor mounting the expansion unitscontactors must not be mounted
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
46/450
Figure 17: Fitting the CPU with and withou
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
47/450
Mounting the inputs/outputs onCPU module
Figure 18: Plugging in the I/O module
h The inputs/outputs can be mountemounting the power supply/CPU mshaft.
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
48/450
Removing the inputs/outputs
Figure 20: Releasing the I/O module
X Press the two catches together.X Pull one side out of the catch.
X Pull the other side out of the second
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
49/450
Removing the power supply/CPUThe power supply/CPU module can without the I/O module.
Figure 22: Releasing the fixing shaft
Use a screwdriver with a 100 x 3.5 m
X Insert the screwdriver into the lug X Lever out the slide catch.X Pull out the power supply/CPU mo
shafts.
Mounting on top-hat railThe power supply/CPU module can b
h If there is another fixing point for from the one for the display/opera
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
50/450
Figure 23: Removing the spring
X Remove the spring with a screwdrive
Mounti06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
51/450
X Hook the MFD to the top edge of hinge into place while pressing dolightly on both the device and the tsnaps over the lower edge of the
The MFD will clip into place automa
X Check that the device is seated fir
The device is mounted vertically on away.
Screw mountingFor screw mounting on a mounting must be used that can be fixed to thfixing brackets are available as an asupply/CPU module can be screwedwithout the display/operating unit.
Figure 25: Inserting a fixing bracket
CLICK!
h Three fixing brackets are sufficienfi i i t
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
52/450
Figure 26: Screw mounting for the MFD
EASY2..-..: easy600:
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
53/450
Connecting the expansionunit
Figure 28: Connecting expansion units
Terminals Tool for cage clamp terminals
Slot-head screwdriver, width 3.5 x
Connection cross-sections of theterminal cables
Solid: 0.2 to 4 mm2 (AWG 24 -12 Flexible with ferrule: 0.2 to 2.5 m
(AWG 24-12)
Tool for slot-head screws for ea
Slot-head screwdriver, width 3.5 xtorque 0.6 Nm.
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
54/450
Network cables and plugs If possible use the prefabricated EASY-80 cm).
Other cable lengths can be made usingcable, the EASY-NT-RJ45 plug and the crimping tool.
AWG 24, 0.2 mm2 are the largest crimThe first and last stations in the networwith an EASY-NT-R bus termination res
Connecting the powersupply
h The required connection data for botdevice types with 24 V DC and MFD-standard voltages of 100 V to 240 VChapter Technical data, Page 409
The MFD-Titan devices run a system after the power supply has been switor STOP mode will be activated afteron the default setting.
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
55/450
MFD-AC power supply
Figure 29: AC power supply on the MFD
N NL0.6x 3.5x 100
L
N
> 1 A
Ue = 115/230 V h 50/60 Hz(85 264 V h)
Ie = 70 mA 115 V35 mA 230 V
Attention!A short current surge will be produ
for the first time. Do not switch onsince these may burn or melt.
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
56/450
EASY-AC-.E expansion units
Figure 30: Power supply on the AC expans
NL
N
F1
L
115/230
E+ E- R1 ... R12
Attention!A short current surge will be producefor the first time. Do not switch on eacontacts since these may burn or me
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
57/450
MFD DC power supply
Figure 31: Power supply on the MFD
The MFD power supply/CPU modulepower supply to itself, the display, telectronics, the easy-LINK, and optio
L01
> 1 A
L01+ L02+
+24V 0V 0V
h The MFD device power supply/CPagainst reverse polarity. Ensure thterminals to ensure that the MFD
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
58/450
EASY-DC-.E DC expansion units
Figure 32: Power supply on the DC expans
Cable protection
With easy-AC, easy-DC and the MFD p
module, provide cable protection (F1) f
L01-
F1
L01+
E+ E- R1 ... R12
h easy DC is protected against polaritythat easy works correctly, ensure thaterminal is correct.
h When easy or the MFD is switched onpower supply circuit behaves like a c
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
59/450
Connecting the inputs easy or MFD inputs switch electroniconnected a contact via an input teras a contact in your MFD circuit diag
Figure 33: Connecting the inputs
Connect contacts such as pushbuttoto easy or MFD input terminals.
Connecting the AC inputs
+24 V
S1
0 VI1
I1
L
N
Caution!Connect up the AC inputs in accorequirements of the VDE, IEC, UL
phase conductor that provides theOtherwise easy will not detect the be damaged or destroyed by over
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
60/450
MFD-AC basic unit
Figure 34: Connecting the inputs
N
> 1 A
L
I1 I3 I4 I7 I8
1 > 79 V0 < 40 V
264 VI1 I12 0.5
I2 I5 I6 I9 I10 I11L N N
I1 I12 0.2
0.6x 3.5x 100
Ue = 115/230 V h 50/60 Hz(85 264 V h)
Ie = 150 mA
Warning!The AC inputs must only be used witdevices. Other devices may be destro
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
61/450
AC expansion device
Figure 35: Inputs on the EASY-AC-.E
Connect the inputs, for example, to switches or relay/contactor contacts
Input signal voltage range OFF signal: 0 to 40 V ON signal: 79 to 264 V
Input current
I1 to I12 0.5 mA/0.2 mA at 230 V R1 to R12
0.5 mA/0.25 mA at 230 V/115 V
L1
N
RR8R7R6R5R4R3R2R1E+ E
115/230 V h
F1
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
62/450
Ensure that the diode is pointing towardin the circuit diagram, otherwise easy wstate.
Figure 36: easy-AC with a diode on the inp
Two-wire proximity switches have a resi0 state. If this residual current is toomay detect a 1 signal.
If inputs with a higher input current areadditional input circuit must be used.
L1
N
RR9R8R7R6R5R4R3R2R1E+ E
115/230 V h
F1
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
63/450
Increasing the input currentThe following input circuit can be usinterference and also when using twswitches:
Figure 37: Increasing the input current
A resistor can be connected in seriesin order to restrict the inrush curren
L1
N
R8R7R6R5R4R3R2R1E+ E
115/230 V h
F1
100 nF/275 V h
h When using a 100 nF capacitor, tinput increases by 80 (66.6) ms a
L1
N
F1
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
64/450
Complete devices for increasing the inpavailable under the type reference EAS
Figure 39: easy600 with EASY256-HCI
Connecting MFD-DC inputs
Use input terminals I1 to I12 to connecactuators, switches or 3 or 4-wire proxi
the high residual current, do not use 2-switches.
Input signal voltage range
L1
N
R9R8R7R6R5R4R3R2R1E+ E
115/230 V h
F1
h The increased capacitance increases approx. 40 ms.
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
65/450
Figure 40: MFD-DC
L01
> 1 A
L01+
I1 I3 I4 I7
L02+
I2 I5 I6+24V 0V 0V
h The digital inputs must have the s
power supply of the MFD.
L01 +
L01
F1
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
66/450
Connecting analog inputsInputs I7, I8, I11 and I12 can also be usevoltages ranging from 0 V to 10 V.
The following applies:
I7 = IA01
I8 = IA02 I11 = IA03 I12 = IA04
The resolution is 10-bit = 0 to 1023.
X Use shielded twisted pair cables to pwith the analog signals.
X For short cable lengths, ground the susing a large contact area. If the cab30 m or so, grounding at both ends cequalisation currents between the twand thus in the interference of analogonly ground the cable at one end.
X Do not lay signal lines parallel to pow
Caution!Analog signals are more sensitive to digital signals. Consequently, more cwhen laying and connecting the signswitching states may occur if they arcorrectly.
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
67/450
The following circuits contain exampanalog value processing.
Setpoint potentiometer
Figure 42: Setpoint potentiometer with
Use a potentiometer with a resistan1 kO, 0.25 W.
h Ensure that the reference potentiathe 0 V of the power supply unit fpotentiometers and sensors show
0 V terminal of the MFD power fe
L01
> 1 A
L01+
I1 I3 I4 I7
L02+
I2 I5 I6
1.
1
+24V 0V 0V
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
68/450
Temperature sensor, brightness se
Figure 43: Temperature sensor, brightness 20 mA sensor
4 to 20 mA (0 to 20 mA) sensors can bwithout any problem using an external
The following values apply:
4 mA = 1.9 V 10 mA = 4.8 V
20 mA = 9.5 V(according to U = RxI= 478 Ox 10
L01
> 1 A
L01+
I1 I3 I4 I7
L02+
I2 I5 I6+24V 0V 0V
+24 V H
0 V
Out0...10 V
35...55 C
a
500 O
4...20 mA
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
69/450
Connecting high-speed countersgeneratorsHigh-speed counter signals on the Mcounted correctly on inputs I1 to I4 cycle time.
Figure 44: High-speed counter, frequen
L01
> 1 A
L01+
I1 I3 I4
L02+
I2 I5 I6+24V 0V 0V
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
70/450
Connecting incremental encodersInputs I1, I2 and I3, I4 on the MFD-Titafor the high-speed counting of an increindependently of the cycle time. The incmust generate two 24 V DC square wavphase shift between them.
Figure 45: Connecting incremental encoder
Connecting the outputs The Q... outputs function inside MFD a
L01
> 1 A
L01+
I1 I3 I4 I7 I8
L02+
A B
I2 I5 I6+24V 0V 0V
Q1
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
71/450
The relay or transistor outputs are usas fluorescent tubes, filament bulbsmotors. Check the technical threshobefore installing such devices (seeadata, from Page 409).
Connecting relay outputs MFD-R..
Figure 47: MFD-R.. relay outputs
0 VH, N
L1, L2, L3 (115/250 V h)+24 V H
Q1
1 2
f 8 A/B 16
f 10 000 000
Q2
1 2
... ... ...
Q3
1 2
M
Q4
1 2
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
72/450
EASY6..-..RE..
Figure 48: EASY6..-..-RE.. relay outputs
EASY2..-RE
0 VH, N
F 8 A/B 16
L1, L2, L3 (115/230 V h)+ 24 VH
212
1 2 2 2 2 2 21 1 1 1 1
10 000 000S6S5S4S3S2S1
+ 24 V HV
0 VH, N
F 8 A/B 16
L1, L2, L3 (115/230 Vh)
1 2 21
10 000 000S2S1 24
11
23
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
73/450
Connecting transistoroutputs
MFD-T..
Figure 50: MFD-T.. transistor outputs
EASY6..-DC-TE
0 V Q1 Q2 Q3 Q4
F 10 A
Q24 VQ
(20.4 28.8 VH)+ 24 V H 24 V
0 VH
S1 S2 S3 S4 S5 S6 S7
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
74/450
Parallel connection:Up to four outputs can be connected inincrease the power. The output currentcase to a maximum of 2 A.
If inductive loads are not suppressed, thSeveral inductive loads should not be ssimultaneously to avoid overheating thworst possible case. If in the event of an+24 V DC power supply is to be switchcontact, and if this would mean switchin
controlled output with an inductive loaprovide suppressor circuits for these loadiagrams).
Caution!Outputs may only be connected in pa(Q1 to Q4 or Q5 to Q8, S1 to S4 or Sand Q3 or Q5, Q7 and Q8. Outputs cmust be switched at the same time.
Caution!
Please note the following when switcloads:Suppressed inductive loads cause lesentire electrical system. For optimumsuppressor circuits are best connecteproximity of the inductive load.
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
75/450
Behaviour with short-circuit/oveShould a short circuit or overload ocoutput, this output will switch off. Thup to maximum temperature after thelapsed. This time depends on the amthe current involved. If the fault conoutput will keep switching off and ocorrected or until the power supply (aSection Monitoring of short-cEASY..-D.-T.., Page 395).
Connecting analogoutputs MFD-RA.. and MFD-TA.. each have a0 V to 10 V DC, 10 bit resolution (0output allows you to control servo vcontrolling elements.
Caution!Analog signals are more sensitivedigital signals. Consequently, morwhen laying and connecting the sswitching states may occur if theycorrectly.
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
76/450
Connecting servo valves
Figure 53: Connecting servo valves
Setpoint entry for a drive
L01
> 1 A
L01+
I1 I3 I4 I7 I8 I9 I10
L02+
A B
I2 I5 I6+24V 0V 0V
L01
> 1 A
L01+ L02+
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
77/450
Connecting the NETnetwork MFD-Titan with network connectionused for creating the NET network.
be connected to this network. Furthfound in the Chapter easy-NET NetConnection, Page 335.
Accessories
Connection plug:8-pole RJ45, EASY-NT-RJ45
Connection assignment of the R
device
Figure 55: RJ45 socket
Connection cable:4-wire, twisted pair;achapter TPage 428
A 1 ECAN_HA 2 ECAN_LB 3 GND (Gr
1
2
3
4
5
6
7
8
Installation 06/04 AWB
Table 5: Prefabricated cables RJ45 plug
-
8/6/2019 Manual MFD Ingles
78/450
Table 5: Prefabricated cables, RJ45 plug
Material for self-manufactured cab100 m 4x 0.18 mm2: EASY-NT-CAB
Required crimping tool for RJ45 plug: E
Bus termination resistorThe first and last stations in the networwith a bus termination resistor.
Value: 124 O Termination connector: EASY-NT-R
Cable length and cross-sections
For correct operation of the network thesections and cable resistances must corfollowing table.
Cable length Type designation
cm
30 EASY-NT-30
80 EASY-NT-80
150 EASY-NT-150
Cable length Cable resistance Cross-sec
m mO/m mm2
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
79/450
Calculating the cable length witresistanceIf the resistance of the cable per uni
(resistance per unit lengthR
in O/mresistance RL must not exceed the fodepends on the selected baud rates
lmax = maximum cable length in mRL = Total cable resistance in OR = Cable resistance per unit length
Calculating cross-section with kThe minimum cross-section is determmaximum extent of the network.
h With cables >500 m it may be feaoptic run.
Baud rate Cable resistance
KBaud O
10 to 125 F 30
250 F 25
5001000
F 12
lmax =RL
R
Installation 06/04 AWB
Calculating length with known cab
-
8/6/2019 Manual MFD Ingles
80/450
Calculating length with known cabThe maximum cable lengths are calculaconductor cross-section
lmax = cable length in mS = minimum cable cross-section in mmrcu = resistivity of copper, if not otherwise
Plugging and unplugging network
MFD-Titan is provided with two RJ45 n
The socket 1 in the first station is for thresistor. For other stations, socket 1 is the incoming cable. Socket 2 is used foor for the bus termination resistor on the
in the network.
lmax =Sx 12.4rcu
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
81/450
Figure 57: Bus termination resistorsa First station on the NET networkb Bus termination resistorc L t t ti th NET t k
1 1
2 21 2
1 2
I 1 - 12
Q 1 - 6
3 3 AS-Interface
+
8 8
I 1 - 12
Q 1 - 8
R 1 - 12
S 1 - 6
R 1 - 12
S 1 - 8a
b
c
b
Installation 06/04 AWB
-
8/6/2019 Manual MFD Ingles
82/450
Figure 58: Plugging and unplugging cables
Connecting the serialinterface
The MFD power supply/CPU module is pfunction interface. This can be used to scommunication between different devialso used for connecting EASY-SOFT-PR
The following device configurations are MFD with MFD, MFD with easy800 (from device vers
The serial interface must be implementcables.
The standard MFD-800-CAB cable is 2
12
3
h The MFD-800-CAB cable must not be
Connec06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
83/450
Figure 59: Fitting/removing the interfac
X Remove the interface cover or othinterface.
X Fit the connectors in the devices.
06/04 AWB
-
8/6/2019 Manual MFD Ingles
84/450
Figure 60: Fitting the connection plug
a
h It must be ensured in all circumstanceith th ki POW Sid i fitt d i
Expand06/04 AWB2528-1480GB
-
8/6/2019 Manual MFD Ingles
85/450
Figure 61: Point-to-point serial interface
Expanding inputs/outputs You can add expansion units to all MLINK connection in order to increaseand outputs:
POW-Side
Expandable easybasic units
Expansion units
MFD-CP8-.. EASY618-..-RE 12 AC 6 rela
EASY620-..-TE 12 DC 8 tran
EASY202-RE 2 relay o
S i l i it f
Installation 06/04 AWB
X Connect the easy expansion unit via
-
8/6/2019 Manual MFD Ingles
86/450
plug connector.
Figure 62: Connecting local expansion unit
MFD-CP8.. EASY6.EASY6.EASY2
EASY-LINK
The following electrical separation isbetween the power supply/CPU moduand the expansion unit (separation aconnection of expansion unit)
Simple isolation 400 V AC (+10 % Safe isolation 240 V AC (+10 %)
Units may be destroyed if the value 4
exceeded, and may cause the malfunsystem or machine!
h MFD l /CPU d l d
Expand06/04 AWB2528-1480GB
Remote expansion
-
8/6/2019 Manual MFD Ingles
87/450
Remote expansion units can be instaaway from the basic unit.
Warning!The two-wire or multiple-wire cab
must adhere to the insulation voltis stipulated for the installation envfault (ground fault, short-circuit) mdestruction of the units or injury t
A cable such as NYM-0 with a rateUe = 300/500 V AC is normally su
E+ E
E+ E
MFD-CP..EA
Ue = 300/500 V
EASY200-
06/04 AWB
-
8/6/2019 Manual MFD Ingles
88/450
06/04 AWB2528-1480GB
3 Commissioning
-
8/6/2019 Manual MFD Ingles
89/450
Switching on Before startup check whether the pooutputs, the serial interface and the eproperly connected:
24 V DC version: Terminal +24 V: +24 V voltage Terminal 0 V: 0 V voltage Terminals I1 to I12, R1 to R12:
Actuation via +24 V 230 V AC version
Terminal L: Phase conductor L Terminal N: Neutral conductor Terminals R1 to R12:
Actuation via phase conductor If you have already integrated devic
any parts of the system connected tprevent access and ensure that no-oexample, motors start up unexpecte
Setting the menu
language
When you switch on MFD for the firs
to select the menu language.
X Use the cursor buttons or to required.ENGLISH
Commissioning 06/04 AWB
X Press OK to confirm your choice and
-
8/6/2019 Manual MFD Ingles
90/450
menu.easy will then switch to the Status disp
MFD operating modes MFD operating modes - RUN, STOP anIn RUN mode the MFD continuously prprogram until you select STOP, disconnor switch to TERMINAL MODE. The proand the MFD settings are retained in thfailure. All you will have to do is reset tafter the back-up time has elapsed. Cironly possible in STOP mode.
h You can change the language settingwish, seeaSection Changing thePage 366.
If you do not set the language, MFD wevery time you switch on and wait folanguage.
Caution!In RUN mode, the MFD will immediasaved in the unit when the power su
This will not happen if STOP or TERMas startup mode. In RUN mode outpuaccording to the switch logic involve
Creatindiagram
06/04 AWB2528-1480GB
Creating your first circuitdi The following single line diagram tah h i i fi i i d
-
8/6/2019 Manual MFD Ingles
91/450
Creating your first circuitdiagram The following single line diagram tathrough wiring up your first circuit dwill learn all the rules, quickly enablyour own projects.
As with conventional wiring, you usthe MFD diagram. With MFD, howev
to connect up components individuabuttons, the MFD circuit diagram prrequired. All you have to do is then sensors, lamps or contactors you wi
Figure 64: Lamp controller with relays
H1
L01-
S1
S2
L01+
F1
K1
K1
Commissioning 06/04 AWB
In the following example, MFD carries operforms the tasks of the circuit diagra
-
8/6/2019 Manual MFD Ingles
92/450
performs the tasks of the circuit diagra
H1
L01
S1 S2
L01+
L01
F1
I 01----I 02- -- Q 01
+24V 0V 0V I1 I3I2
Q11 2
DEL
ESC
ALT
OK
*
Creatindiagram
06/04 AWB2528-1480GB
Starting point Status display
Wh i h MFD i
-
8/6/2019 Manual MFD Ingles
93/450
When you switch on MFD, it opens immediately to show the switching soutputs. It also indicates whether thea program. Note: If another display screen is shown.
X Press OK to switch to the main m
Press OK to switch to the next menumove one level back.
In this case MFD must be in STOP m
X Press OK 2 x to enter the circuit menu items PROGRAMhPRyou will create the circuit diagram
I ............I P-
MO 02:00Q........ STOP
h The examples were written withounits. If an expansion unit is connewill first show the status of the bastatus of the expansion unit beforselection menu.
PROGRAM...STOP RUNPARAMETERSSET CLOCK...
h OK has two other functions: Press OK to save modified setti In the circuit diagram, you can
and modify contacts and relay c
CIRCUIT DIAGRAMFUNCTION RELAYS
Commissioning 06/04 AWB
Circuit diagram display
Th i it di di l i tl
-
8/6/2019 Manual MFD Ingles
94/450
The circuit diagram display is currently flashes at the top left, which is where yoyour diagram.
The location of the cursor is indicated inRung (line), C: = Contact or coil (contac
available in bytes. Start value 7944, withalready generated.
The MFD-Titan circuit diagram supportcoil in series. The MFD-Titan display cadiagram contact fields.
Use the cursor buttons to mthe invisible circuit diagram grid.
The first four columns are contact fieldsa coil field. Each line is a rung. MFD authe contact to the power supply.
Figure 66: Circuit diagram with inputs I1, I2
X Now try to wire up the following MF
Switches S1 and S2 are at the input. I 0
L: 1 C:1 B:7944
------L: 1 C:1 B:7944
Ml
L
m
I 01----I 02--...- Q 01
L: 1 C:1 B:7944
Creatindiagram
06/04 AWB2528-1480GB
From the first contact to the ou
With MFD you work from the input
-
8/6/2019 Manual MFD Ingles
95/450
With MFD, you work from the inputinput contact is I 01.
X Press OK.MFD proposes the first contact I 0
I flashes and can be changed, for epushbutton input using the cursor bHowever, nothing needs to be chan
X Press OK 2 x, to move the cursosecond contact field.
You could also move the cursor to tusing the cursor button.
X Press OK.Again, MFD inserts a contact I 01Change the contact number to I 02
S2 can be connected to input terminX Press OK so that the cursor jumps
press cursor button or to cha
X Press OK to move the cursor to thYou do not need a third relay contacthe contacts directly up to the coil fi
I 01
L: 1 C:1 B:7944
I 01
L: 1 C:1 B:7944
I 01 I 02
L: 1 C:2 B:7944
h You can press DEL to delete a conposition.
-I 02
Commissioning 06/04 AWB
Wiring
MFD displays a small arrow l in the cir
-
8/6/2019 Manual MFD Ingles
96/450
MFD displays a small arrow l in the circreating the wiring.
Press ALT to activate the wiring arrow cursor buttons to move it.
The wiring arrow works between contayou move the arrow onto a contact or rback to the cursor and can be reactivatrequired.
X Press ALT to wire the cursor from I 0field.
The cursor changes into a flashing wiriautomatically jumps to the next possib
X Press the cursor button . Contact I 0
h ALT also has two other functions depposition:
In the left contact field, you can prnew empty rung.
The contact under the cursor can b
a make and break contact by press
--l----L: 1 C:1 B:7944
MlL
m
h MFD automatically wires adjacent cothe coil.
-I 02 l
Creatindiagram
06/04 AWB2528-1480GB
X Press the cursor button again.
-
8/6/2019 Manual MFD Ingles
97/450
The cursor will move to the coil field
X Press OK.MFD inserts the relay coil Q 01. Th and the output relay Q 01 are cor
be changed.Your first working MFD circuit diagr
Figure 67: Your first circuit diagram
= visible area
X Press ESC to leave the circuit diagThe SAVE menu appears.
Figure 68: SAVE menu
= visible area
X Press the OK button.
-------- Q 01
L: 1 C:1 B:7944
I 01----I 02-----------------
L: 1 C:1 B:7944
I 01----I 02-----------------
SAVE
Commissioning 06/04 AWB
Testing the circuit diagram
X Switch to the main menu and select t
-
8/6/2019 Manual MFD Ingles
98/450
X Switch to the main menu and select toption.
With a tick at RUN or STOP you switchoperating modes.
MFD runs in the mode indicated by the
X Press the OK button. MFD will chang
The Status display shows the current mswitching states of the inputs and outp
X Change to the Status display and preactuator S1.
The contacts for inputs I1 and I2 are acpicks up. This is indicated on the numbdisplayed.
Power flow displayMFD allows you to check rungs in RUNthat you can check your circuit diagrampower flow display while it is being pro
X Change to the Circuit diagram displa
pushbutton actuator S1.The relay picks up. MFD shows the pow
PROGRAM...STOP RUNPARAMETERSSET CLOCK...
h The mode assigned the tick is always
I 12..........I P-
MO 14:42Q 1....... RUN
Creatindiagram
06/04 AWB2528-1480GB
X Press pushbutton actuator S2, tha
a break contact.
-
8/6/2019 Manual MFD Ingles
99/450
The rung is interrupted and relay Q1
Figure 70: Power flow display: Input I1 relay Q1 has dropped out
= visible area
X Press ESC to return to the Status
Power flow display with Zoom fMFD enables you to check the follow
all four contacts plus one coil in s and 3 rungs
X Change to the Circuit diagram disbutton. Press pushbutton actuato
I 01====I 02----------------
L: 1 C:1 RUN
h With MFD you can test parts of a cis entirely completed.
MFD simply ignores any incompleworking and only runs the finishe
==========
Commissioning 06/04 AWB
X Press pushbutton actuator S2, that ha
a break contact.
-
8/6/2019 Manual MFD Ingles
100/450
The rung is interrupted and relay Q1 dr
Use the cursor buttons to mcontacts or coil.
X Press the cursor button .
The cursor moves to the second contac
X Press the ALT button. The display chastatus with contact and/or coil desig
Figure 72: Power flow display: Input I1 is c
relay Q1 has dropped out= visible area
==#-------- #
L: 001 I 01
==#-------- #
L: 002 I 02
I 01====I 02-------------------
L: 1 C:2 RUN
Creatindiagram
06/04 AWB2528-1480GB
Deleting the circuit diagram
X Switch the MFD to STOP mode.
-
8/6/2019 Manual MFD Ingles
101/450
X Use PROGRAM to switch from next menu level.X Select DELETE PROGRAM
The MFD will display the prompt DE
X Press OK to delete the program oX Press ESC to return to the Status
Fast circuit diagram entry
You can create a circuit diagram in s
option is to enter the elements in theall the elements together. The otherenhanced operator guidance of the circuit diagram in one go, from the fthe last coil.
If you use the first option, you will ha
elements in order to create and condiagram.
The second faster option is what yo
h MFD must be in STOP mode in ordmodify the circuit diagram.
PROGRAM...DELETE PROGRAM
Commissioning 06/04 AWB
Configuring an easy-NETnetwork
If you want to work with the easy-NET communicate with several stations, the
fi d fi
-
8/6/2019 Manual MFD Ingles
102/450
configured first.
Proceed as follows:
X Connect all network stations. easy-Neasy-NET socket 1L.
X The first station 1 (socket 1L) and th(socket 2e) must be provided with a resistor a.
X Connect all stations to the power sup
Figure 73: Example topology with two easy
a Network termination resistor
2
1
1
2
I1 I12
Q1 Q6
R1 R12
S1 S8
a
a
Configunetwor
06/04 AWB2528-1480GB
h The following tasks are only poss
-
8/6/2019 Manual MFD Ingles
103/450
Entering the network station nu
X Simultaneously press the DEL andshows the Status display.
The System menu appears
Select the CONFIGURATOR menu op
X Press the OK button.
The NET menu appears.
X Press the OK button.
The NET PARAMETERS menu app
X
Press theOK
button.
X Press the OK button and select theand . In this case the station nu
X Press the OK button.
X Exit the NET PARAMETERS menu
SECURITY...SYSTEM...MENU LANGUAGECONFIGURATOR...
NET..COM...LINK....
NETPARAMETERS...
STATIONS...CONFIGURE
NET-ID : 00 BAUDRATE: 125KBBUSDELAY: 00SEND IO REMOTE RUN
REMOTE IO
NET-ID : 01 BAUDRATE: 125KB
Commissioning 06/04 AWB
Entering network stations
Only the network station at physical locb h l
-
8/6/2019 Manual MFD Ingles
104/450
number 1 has a station list.
X Use the and cursor buttons to smenu and press the OK button.
X Proceed to the station with physical X Select the required physical location
cursor buttons. Press the OK button.X Use cursor buttons and to selec
X Press the OK button.At physical location 2, the station has baddress 2.
X Press ESC to return to the STATIONS
h The left-hand column is the physical loassign a physical location to unused Physical location 1 is permanently asnumber 1.
1 1 2 03 04 0
1 1 2 23 0
4 0
Configunetwor
06/04 AWB2528-1480GB
Configuring an easy-NET netwo
The easy-NET network can only be co
-
8/6/2019 Manual MFD Ingles
105/450
Requirement:All stations are correctly connected termination resistors have been con
All stations have a power supply andPOW LED is permanently lit. The NE
X Proceed to the CONFIGURE menu
button.
You will be asked to acknowledge wconfigure the system.
X Press the OK button.
The message on the left appears:
All NET LEDs on the stations which numbers higher than 1 (2 to 8) switeasy-NET.
As soon as the configuration has becompleted, the NET LEDs on all statinetwork is ready for operation.
h If the connected stations are confautomatically switch to the STOP
NET
PARAMETERS...STATIONS...CONFIGURE
CONFIGURE?
CONFIGURATIONINPROGRESS.
Commissioning 06/04 AWB
Changing the easy-NET network co
The configuration of the easy-NET netwat any time at station 1 physical locati
-
8/6/2019 Manual MFD Ingles
106/450
at any time at station 1, physical locati
X The NET parameters are modified as inputting parameters for the first tim
Station addresses in the STATIONS men
follows:X Go to the physical location which is tX Press the OK button.
X Select the required station number wcursor buttons and confirm your inpu
X Configure all easy-NET stations againCONFIGURATION menu.
h Existing station numbers can only be
non-assigned station numbers. If all assigned, all station numbers which must be set to zero. Thereafter, all stareassigned. (MFD-Titan sets all statiowhich are assigned a physical locatiozero.)
hFurther information concerning the etopic can be found in Chapter easy-LINK Serial Connection, Page 335.
Configunetwor
06/04 AWB2528-1480GB
Displaying the Status display of
On every device with a display, you cthe inputs and outputs of each netw
-
8/6/2019 Manual MFD Ingles
107/450
the inputs and outputs of each netw
X Change to the Status display and
The cursor changes to the display of tand flashes. The station number is dinputs and outputs.
X Change to the number of the requand cursor buttons.
X Press the OK button.
X If you want to view the state of tha local expansion, press the OK b
If you press the ESC button again odisplay of the input and output state
terminated.
1I12..........I NT1 P-
MO 06:421Q1....... RUN
3I12.....7....I NT3 P-
MO 06:42
3Q1.3..6.. RUN
3R12.....7....I NT3 DC P-
MO 06:453S1.3..6.. RUN
h The station showing the status onits own data from the network.
Example: NT3 flashes on station 3
3I.., 3R.., 3Q.. and 3S.. cannot beIf the NT3 display is not flashing, are shown.
Commissioning 06/04 AWB
Configuring the interfacefor the COM-LINK mode
If you wish to set up point-to-point comanother station, this can be done usinginterface or easy-NET. The MFD must b
-
8/6/2019 Manual MFD Ingles
108/450
interface or easy NET. The MFD must bdisplay and operating unit. The connecconfigured for this purpose (Page 350aIntroduction to COM-LINK).
Proceed as follows:
X Connect both stations together.Only use original connection cables. ThPOW-Side must be plugged into an MFDinterface electronics of the connection
X Connect both stations to the power s
h Ensure that the other station supportmode.
POW-Side
Configuthe COM
06/04 AWB2528-1480GB
to configure the stations which ha
supply.XGo to the MFD device that is the ac
-
8/6/2019 Manual MFD Ingles
109/450
serial interface.
Setting up the COM-LINK
X Simultaneously press the DEL andshows the Status display.The System menu appears
h The following tasks are only poss
Caution!The MFD device can either run as
NET or as a station in a COM-LINswitch an MFD device running as COM-LINK. If this is done on easyentire easy-NET network will be deno further data transfer.
Solution:
X Deactivate the COM-LINK.X Re-enter the easy-NET address.X Switch the power supply off anX Reconfigure the easy-NET on st
SECURITY...
Commissioning 06/04 AWB
The menu BAUDRATE: 9600B will app
rates are for 9600 or 19200 baud. Seleyour connection will support. Baud rate
BAUDRATE: 9600B
COM-LINKREMOTE MARKER...
-
8/6/2019 Manual MFD Ingles
110/450
X Press the OK button.
Select 19200 baud as the baud rate.
X Press the or button.X Press the OK button.
Switch on the COM connection.
X Press the button.X Press the OK button.
The tick on the COM-LINK menu item iLINK has been selected.
No tick means that COM-LINK has not
h Select 19200 baud as the baud rate. Bgive rise to electromagnetic interferebaud as the baud rate. If this is not sconnection cable must be laid in a di
BAUDRATE:19200BCOM-LINKREMOTE MARKER...
hThe COM-LINK must only be switchestation. Two devices with COM-LINKcannot communicate with each othe
BAUDRATE:19200BCOM-LINK REMOTE MARKER...
Configuthe COM
06/04 AWB2528-1480GB
X Press the OK button.
The data is physically located in the remote station
READ:
1MD00 1MD00WRITE:1MD00 1MD00
-
8/6/2019 Manual MFD Ingles
111/450
remote station.
The following marker ranges can be
1MD1 to 1MD20
1MD00 1MD00
h The active station reads and writemarkers of the remote station. At
remote station has read and writemarker range.
Ensure that both stations do not hsame markers simultaneously. Thwill be the one that is retained.
Example:READ 1MD2h1MD2
WRITE 1MD3h1MD3
The MFD device accesses the mark1xx... These markers correspond to
and MD3 in the remote station.These marker double words conta
MD2, MW3, MW4, MB5; MB6, M
MD3, MW5, MW6, MB9, MB19, MM96
Commissioning 06/04 AWB
X Use the button to enter the upper
range.X Use the button to select the value
READ:
1MD11 1MD14WRITE:1MD00 1MD00
-
8/6/2019 Manual MFD Ingles
112/450
X Confirm the entry with the OK butto
X Use the button to enter the WRITE
Enter the WRITE range.
X Press ESC to leave the entry menu.
The COM-LINK has now been set. No C
required at the remote station.
X Press ESC to return to the Status dis
The entry in the second COM line indicconnection is active.
1MD00 1MD00
READ:1MD11 1MD14
WRITE:1MD00 1MD00
READ:1MD11 1MD14
WRITE:1MD00 1MD00
READ:1MD11 1MD14
WRITE:1MD15 1MD17
BAUDRATE:19200BCOM-LINK REMOTE MARKER...
I 12.4.67.....I COM P-
FR 02:02 STQ........ STOP
Termina06/04 AWB2528-1480GB
Terminal mode Terminal mode
The MFD device also supports the Toperating mode. This allows you to
-
8/6/2019 Manual MFD Ingles
113/450
operating mode. This allows you to devices. This is especially useful if thein an inaccessible place. Terminal mshow the menus and displays of dev
their own display or operating unit. used both with the serial interface aserial interface enables you to accessuse the easy-NET network, all other addressed.
The following topologies are permis
hTerminal mode is a separate opermode. It only functions when a prothis mode to be active, the MFD m
h All connected devices must also s
Commissioning 06/04 AWB
Terminal mode using the point-to-
interface
-
8/6/2019 Manual MFD Ingles
114/450
Figure 75: Terminal mode using the point-t
POW-Side
Termina06/04 AWB2528-1480GB
Terminal mode using the easy-N
1 1
R 1 121 2
I 1 12
-
8/6/2019 Manual MFD Ingles
115/450
Figure 76: Terminal mode using the eas
In the above topology, the physical to the station number. The MFD devimiddle of the network line Termina
2 51 2
1 2
I 1 - 12
Q 1 - 6
3 7
4 3
I 1 - 12
Q 1 - 8
R 1 - 12
MFD
S 1 - 8
I 1 - 12
Q 1 - 6
Commissioning 06/04 AWB
1 1
MFD
-
8/6/2019 Manual MFD Ingles
116/450
Figure 77: Terminal mode in easy-NET with
The above topology allows two MFD deasy-NET Terminal mode. Each MFD deother devices in Terminal mode.
2 2
1 2
3 3
4 4
I 1 - 12
Q 1 - 8
1 2I 1 - 12
Q 1 - 6
MFD
MFD
Termina06/04 AWB2528-1480GB
1I 1 - 12
-
8/6/2019 Manual MFD Ingles
117/450
Figure 78: Terminal mode in easy-NET ainterfaces
The above topology is a combination
POW-Side
2
3
4
I 1 - 12
Q 1 - 8
I 1 - 12
Q 1 - 6
Q 1 - 6
MFD
POW-Side
Commissioning 06/04 AWB
Caution!
Data collision!
In order to ensure proper operat
-
8/6/2019 Manual MFD Ingles
118/450
Proceed as follows:
Your easy-NET or your serial interface mcorrectly.
X Press the OK button from the Status The first menu will appear.
X Press the button.
This will display the TERMINAL MODE
In order to ensure proper operatconditions must be observed.
The following applies:
If there is more than one MFD deviceeach MFD device must access a differ
A device running in Terminal mode mtwo devices communicating with eacmode.
If a PC with EASY-SOFT (-PRO) or anserial interface is in active communicNET station, this station must not be atime in Terminal mode via the easy-N
PROGRAM... STOP RUNPARAMETERSSET CLOCK...
Termina06/04 AWB2528-1480GB
Select the second station. This statio
and respond to the operating unit.STATION ID: 0
START MODE
-
8/6/2019 Manual MFD Ingles
119/450
X Press the OK button.
Select your station.
X Press the or button.X Press the OK button.
Select the START MODE menu optio
X Press the button.X
Press the OK button.In this case the easy-NET station 2 i
h Station ID:
0 = Station on the serial interface
1 = Station 1 easy-NET2 = Station 2 easy-NET3 = Station 3 easy-NET4 = Station 4 easy-NET5 = Station 5 easy-NET6 = Station 6 easy-NET
7 = Station 7 easy-NET8 = Station 8 easy-NET
STATION ID: 0START MODE
STATION ID: 0START MODE
STATION ID: 2
Commissioning 06/04 AWB
hIf the text Connection establishmendisplayed for longer than 10 s, the coselected device is faulty. Press ESC toRectify the fault Try to re-establish t
-
8/6/2019 Manual MFD Ingles
120/450
The following applies if the device to bemode and is displaying a screen:
This screen is not displayed in Termina
MFD message: The remote device is in
X Press the ALT and ESC button simultThis will call up the Status display.
The easy-NET station 2 controls the disdevice.
Rectify the fault. Try to re establish t
The remote
device is in
Graphic mode
I 1..4..789... *I NT2 P-
TU 06.05.2003Q 1..45678 RUN
h The activation of Terminal mode is in
flashing star at the top right of the S
Caution!In Terminal mode, you can operate apositioned far from your actual locatthat you would also require "locally"
It is not always possible to obtain a vlocally. Use of this operating modeany changes to device settings shoul
ith th t t ti
Termina06/04 AWB2528-1480GB
hIn Terminal mode, the MFD deviceoperating unit available to the condata for the display and the statuvia the connection. This ensures th
-
8/6/2019 Manual MFD Ingles
121/450
Close Terminal mode.Press the * button to close the Term
X Press the * button.
This returns you back to your local d
X Press the ESC button twice.
The Status display of the MFD devic
The flashing star at the top right of
via the connection. This ensures thconnected device is not destroyedcommunication fault.
STATION ID: 2START MODE
h The * button cannot be assigned tto use Terminal mode in your applito change from the visualization tOtherwise the Terminal mode me
STATION ID: 2START MODE
I ..345..89...I P-
06/04 AWB
-
8/6/2019 Manual MFD Ingles
122/450
06/04 AWB2528-1480GB
4 Wiring with MFD-T
This chapter describes all the functioMFD Titan
-
8/6/2019 Manual MFD Ingles
123/450
MFD-Titan.
MFD-Titan operation Buttons for drawing circuit diagblock usage
Delete rung, contact, relay or emptydiagram
Toggle between break and make co
Connect contacts and relaysAdd rungs
Change valuesCursor up, downChange positionCursor left, right
Cursor buttons set as P buttons:
Input P1,Input P3,
InpuInpu
Undo setting from previous OKExit current display or menu
Change, add contact/relaySave setting
Terminal mode on/off
DEL
ALT
ESC
OK
Wiring with MFD-Titan 06/04 AWB
Operating principles
The cursor buttons in the MFD-Titan circthree functions. The current mode is indappearance of the flashing cursor.
-
8/6/2019 Manual MFD Ingles
124/450
pp g
Move Entering
Connect
In Move mode you can use to around the circuit diagram in order to sor relay coil.
Use OK to switch to Entry mode so thachange a value at the current cursor poESC in Entry mode, MFD-Titan will undchanges.
Press ALT to switch to Connect mode forelays. Press ALT again to return to Mo
Press ESC to leave the circuit diagram display.
Opening the parameter display fori h il
I 01
l
h MFD-Titan performs many of these cautomatically. For example, MFD-Titcursor to Move mode if no further en
are possible at the selected cursor po
MFD-Ti06/04 AWB2528-1480GB
Program
A program is a sequence of commanexecutes cyclically in RUN mode. Anconsists of the necessary settings foCOM-LINK password system settin
-
8/6/2019 Manual MFD Ingles
125/450
COM-LINK, password, system settinand/or function blocks and/or the vi
The circuit diagram is that part of th
contacts are connected together. In switched on and off in accordance wthe coil function specified.
Function blocksFunction blocks are program elemen
functions. Example: timing relays, tifunction blocks. Function blocks are or without contacts and coils as reqfunction blocks are processed accordiagram and the results are updated
Examples:
Timing relay = function block with cTime switch = function block with c
Visualization screensVisualisation screens are the sectioncontaining the display and operator
RelaysRelays are switching devices which simulated in MFD-Titan. They actuat
d h d d f
Wiring with MFD-Titan 06/04 AWB
Coils
Coils are the actuating mechanisms of rthe results of the wiring are sent to theon or off accordingly. Coils can have sefunctions
-
8/6/2019 Manual MFD Ingles
126/450
functions.
Table 6: Usable contacts
MFD-Titan works with different contactin any order in the contact fields of the
Table 7: Contacts
Contact MFD-Titan
Make contact, open in releaseposition
I, Q, M, A, Other conta
Break contact, closed in releaseposition
i, q, m, a, Other conta
Contact Make contact Break contact
Inputs
Inputs of a network station* = Station address 1 to 8
*I *i
COM slave inputs 1I 1i
MFD-Titan input terminal I i
Cursor button P p
Network station expansion inputi l
*R *
MFD-Ti06/04 AWB2528-1480GB
Diagnostics inputs
Expansion network station status* Station address 1 to 8
*I *i
Contact Make contact Break contac
-
8/6/2019 Manual MFD Ingles
127/450
* = Station address 1 to 8
Network station short-circuit/overload* = Station address 1 to 8
*I *i
COM slave expansion unit status 1I 1i
COM slave short-circuit/overload 1I 1i
Expansion status I i
Short-circuit/overload I i
Short-circuit/overload in expansionnetwork station* = Station address 1 to 8
*R *
Short-circuit/overload in COM slaveexpansion
1R 1
Short circuit/overload with expansion R
Outputs
Deactivate backlight of the MFDdisplay
LE LE
Red LED of MFD display LE LE
Green LED of MFD display LE LE
MFD-Titan output MFD networkstation* = Station address 1 to 8
*Q *q
Wiring with MFD-Titan 06/04 AWB
Other contacts
Markers M m
m
Contact Make contact Break contact
-
8/6/2019 Manual MFD Ingles
128/450
COM slave marker (REMOTEMARKER)
1M 1m
Jump label:
Diagnostics messages ID ID
COM slave diagnostics messages 1ID 1iD
Function blocks
Analog value comparator function
block
A X Q1 A X Q1
Function blocksAnalog value comparatorValue overflow (CARRY)
A X CY a X CY
Arithmetic value overflow (CARRY)function block
AR X CY a X CY
Zero arithmetic value (zero) functionblock
AR X ZE a X ZE
Data block comparator functionblock, error: number of elementsexceeded
BC X E1 BC X E1
Data block comparator functionblock, error: range overlap
BC X E2 BC X E2
Data block comparator functionbl k i lid ff
BC X E3 BC X E3
MFD-Ti06/04 AWB2528-1480GB
Data block transfer function block,error: range overlap
BT X E2 BT X E2
Data block transfer function block BT X E3 BT X E3
Contact Make contact Break contac
-
8/6/2019 Manual MFD Ingles
129/450
Data block transfer function block,error: invalid offset
BT X E3 BT X E3
Boolean operation function block,
value zero
BV X ZE BV X ZE
Counter function block, uppersetpoint value exceeded (Overflow)
C X OF c X OF
Counter function block, lowersetpoint value undershot(Fall below)
C X FB c X FB
Counter function block, actualvalue equal to zero
C X ZE c X ZE
Counter function block, actual valuehas exceeded counter range (CARRY)
C X CY c X CY
Frequency counter function block,
upper setpoint value exceeded(Overflow)
CF X OF CF X OF
Frequency counter function block,lower setpoint value undershot(Fall below)
CF X FB CF X FB
Frequency counter function block,
actual value equal to zero
CF X ZE CF X ZE
High-speed counter function block,upper setpoint value exceeded
CH X OF CH X OF
Wiring with MFD-Titan 06/04 AWB
Incremental encoder counter functionblock, upper setpoint value exceeded(Overflow)
CI X OF CI X OF
Contact Make contact Break contact
-
8/6/2019 Manual MFD Ingles
130/450
Incremental encoder counter functionblock, lower setpoint value undershot
(Fall below)
CI X FB CI X FB
Incremental encoder counter functionblock, actual value equal to zero
CI X ZE CI X ZE
Incremental encoder counter functionblock, actual value has exceededcounter range (CARRY)
CI X CY CI X CY
Comparator function block,less than
CP X LT CP X LT
Comparator function block,equal to
CP X EQ CP X EQ
Comparator function block,greater than
CP X GT CP X GT
Text output function block D X Q1 X Q1
Data function block DB X Q1 DB X Q1
PID controller, value range ofmanipulated variable exceeded
DC X LI DC X LI
Receive a variable from a station (Get) GT X Q1 GT X Q1
MFD-Ti06/04 AWB2528-1480GB
Operating hours counter, valueoverflow (CARRY)
OT X CY OT X CY
Send a variable to the network, PT X Q1 PT X Q1
Contact Make contact Break contac
-
8/6/2019 Manual MFD Ingles
131/450
Send a variable to the network,enable active Put
PT X Q1 PT X Q1
Pulse width modulation, error
minimum on or off time exceeded
PW X E1 PW X E1
Send date and time via the network(easy-NET) function block
SC X Q1 SC X Q1
Timing relay function block T X Q1 T X Q1
Wiring with MFD-Titan 06/04 AWB
Usable relays and function blocks
MFD-Titan provides various relay typesblocks and their coils for wiring in a cir
Relay/function block MFD-Titan Number C
-
8/6/2019 Manual MFD Ingles
132/450
ydisplay
OutputsMFD-Titan output relays, networkstations (only network master)* = Station address 2 to 8
*Q 0108 j
MFD-Titan output relay Q 0108 j
MFD-Titan output relay expansion,network stations (only networkmaster)* = Station address 2 to 8
*S 0108 j
MFD-Titan expansion output relay S 0108 j
Bit outputs
* = Station address 1 to 8
*SN 0132 j
General coils
Markers M 0196 j
COM slave marker(REMOTE MARKER)
1M 0196 j
Jump label: 01
32 j
Function blocks
Analog value comparator function A 01 32
MFD-Ti06/04 AWB2528-1480GB
Counter function block, direction C X D_ X=0132
Counter function block, set counter C X SE X=0132
Relay/function block MFD-Titan
display
Number
-
8/6/2019 Manual MFD Ingles
133/450
Counter function block, set countervalue (Preset)
C X SE X 0132
Counter function block, reset countervalue
C X RE X=0132
Frequency counter function block,activate counter (enable)
CF X EN X=0104
High-speed counter function block,direction
CH X D_ X=0104
High-speed counter function block,activate counter (enable) CH X EN X=0104
High-speed counter function block,set counter value (Preset)
CH X SE X=0104
High-speed counter function block,reset counter value
CH X RE X=0104
Incremental encoder counter functionblock, set counter value (Preset)
CI X SE X=0102
Incremental encoder counter functionblock, activate counter (enable)
CI X EN X=0102
Incremental encoder counter function
block, reset counter value
CI X RE X=0102
Comparator function block CP X=0132
Activate text output function block D X EN X=01 32
Wiring with MFD-Titan 06/04 AWB
Get from network station functionblock
GT X=0132
Relay/function block MFD-Titan
display
Number C
-
8/6/2019 Manual MFD Ingles
134/450
Seven-day time switch HW X=0132
Year time switch function block HY X=0132
Activate value scaling function block LS X EN X=0132 j
Master reset function block MR X T_ X=0132 j
Activate numerical converter functionblock
NC X EN X=01 32 j
Function block operating hourscounter, enable
OT X EN X=0104 j
Operating hours counter functionblock, reset
OT X RE X=0104 j
Send to the network (easy-NET)function block, trigger
PT X T_ X=0132 j
Activate pulse width modulationfunction block PW X EN X=0102j
Send time to the network (easy-NET)function block, trigger
SC X T_ X=01 j
Activate set cycle time function block ST X EN X=01
Timing relay function block,trigger control coil (enable)T X EN X=01
32 j
Timing relay function block, stop T X ST X=0132 j
MFD-Ti06/04 AWB2528-1480GB
The options for setting output and m
with the description of each coil funThe function block coil functions andwith the description of each function
-
8/6/2019 Manual MFD Ingles
135/450
Markers, analog operands
Specific markers are available for acor inputs/outputs.
Table 8: Markers
When using the COM communicatiothe following data accesses on the s
i h f ll i
Markers
Analogoperand
MFD-Titandisplay
Number Valurang
Marker 32 bit MD 0196 32 b
Marker 16 bit MW 0196 16 b
Marker 8 bit MB 0196 8 bitMarker 1 bit M 196 1 bit
Analog inputsbasic unit
IA X X=0104 10 b
Analog output QA X X=01 10 b
Wiring with MFD-Titan06/04 AWB
Markers
Analogoperand
MFD-Titan
display
Number Value
range
M k 32 bit 1MD 01 20 32 bit
-
8/6/2019 Manual MFD Ingles
136/450
The following rules apply if you want tooperands (contacts) from the markers M
Table 9: Composition of the markers
Marker 32 bit 1MD 0120 32 bit
Marker 16 bit 1MW 0140 16 bit
Marker 8 bit 1MB 0180 8 bit
Marker 1 bit 1M 196 1 bit
Analog inputsbasic unit
1IA X X=0104 10 bit
Analog output 1QA X X=01 10 bit
Applies to
MD, MW,MB, M
Left = most
significant bit,byte, word
32 bit MD1
16 bit MW2 MW1
8 bit MB4 MB3 MB2
1 bit M32 to M25 M24 to M17 M16 to M9
32 bit MD2
MFD-Ti06/04 AWB2528-1480GB
16 bit MW8 MW7
Applies to
MD, MW,MB, M
Left = most
significant bit,byte, word
-
8/6/2019 Manual MFD Ingles
137/450
8 bit MB16 MB15 MB14
32 bit MD5
16 bit MW10 MW9
8 bit MB20 MB19 MB18
32 bit MD23
16 bit MW46 MW45
8 bit MB92 MB91 MB90
32 bit MD24
16 bit MW48 MW478 bit MB96 MB95 MB94
32 bit MD25
16 bit MW50 MW49
32 bit MD26
16 bit MW52 MW51
Wiring with MFD-Titan06/04 AWB
Marker double words always contain alseveral write accesses to MD, MW, MB are made, it is the last write operation
h You should only write the markers on
-
8/6/2019 Manual MFD Ingles
138/450
also applies if you are writing markers screen.
MFD-Ti06/04 AWB2528-1480GB
Number formats
MFD makes computations with a sigThe value range is:2147483648 to +2147483647
With 31 bit l th 32 d bit i t
-
8/6/2019 Manual MFD Ingles
139/450
With a 31 bit value, the 32nd bit is t
Bit 32 = state 0 means a positive
Example:000000000000000000000100000412hex =1042dec
Bit 32 = 1 means a negative numbe
Example:11111111111111111101110010bin = FFFFDCAEhex = 9042dec
Circuit diagram display
In the MFD-Titan circuit diagram, conare connected up from left to right - coil. The circuit diagram is created o
containing contact fields, coil fields wired up with connections.
h The marker byte (MB) and markerformats are unsigned.
Wiring with MFD-Titan06/04 AWB
I 01----I 02----CP01GT------Q 01----HY01Q1k''''''' '''''''''''' ''''''' ''''''' '''''L: 1 C:1 B:____
Contact fields (1 to 4)
Rung
Status line
-
8/6/2019 Manual MFD Ingles
140/450
Connections are used to produce thbetween relay contacts and the coils.across several rungs. Each point of inconnection.
The number of free bytes is displayedrecognise how much memory is avadiagram and function blocks.
MFD-Titan circuit diagram displayFor greater legibility, the circuit diagramMFD-Titan shows two contacts per rung
a coil in series. A total of 16 charactersrungs plus the status line can be displa
L 1 C 1 B ____
Connections
Status line
Number of rung
Number offield in therung
Amount of freememory in bytes
I 01----I 02---
Q 01----HY01Q1k
L: 1 C:1 B:7840
MFD-Ti06/04 AWB2528-1480GB
Saving and loading programs
MFD-Titan provides you with two wdiagrams externally:
Saving to a memory card. Saving on a PC with EASY-SOFT-P
-
8/6/2019 Manual MFD Ingles
141/450
g
Once they have been saved, programMFD-Titan, edited and run.
All program data is saved in MFD-Tipower failure the data will be retainis overwritten or deleted.
Memory card
Each memory card contains a circuitinserted into the MFD-Titan interfac
The MFD-Titan behaves in the followaccordance with the type and settin
Requirement:
A valid circuit diagram must be storVariants with display:
XGo to the CARD menu and load ththe unit in STOP mode via CARD r
CARD MODE settingapage 376.
Variants without display:If the circuit diagram on the card is
Wiring with MFD-Titan06/04 AWB
Working with contacts
and relays
In MFD-Titan circuit diagrams, the swit
relays of conventional circuit diagrams using input contacts and relay coils.
Conventional circuit MFD-Titan circ
MFD-Titan con
-
8/6/2019 Manual MFD Ingles
142/450
MFD-Titan circuit diagram:
First specify which input a