Manual LX10.2 V1.2 EN - emri.nl
Transcript of Manual LX10.2 V1.2 EN - emri.nl
LX10.2 Voltage regulator for generators
Instruction Manual V1.2
Product version V1.1.0.0
Manual V1.2 Page 2 of 20
Warnings And Commissioning information
Revision history
The manual does not cover all technical details of the product. Specifications may be modified by the manufacturer without notice. For further information, the manufacturer should be contacted.
Manual V1.2 Page 3 of 20
Table of contents
General description The LX10.2 is designed for use in brushless generators and can be used as a cost effective universal replacement for a great variety original manufacturers AVR’s. The LX10.2 can be used for parallel operation with other generators that also control voltage droop by means of Quadrature Droop Compensation (QDC). Parallel operation is possible with an additional droop CT, which can be 0.5 or 1A secondary. Installation, maintenance and adjustment don’t require special application software. The AVR is protected from the environment by a PUR coating.
Manual V1.2 Page 4 of 20
Absolute maximum rating
Manual V1.2 Page 5 of 20
Protections
Manual V1.2 Page 6 of 20
Modes of control I
Sensing voltage
Sensing voltage
Generator voltage
Generator voltage
Manual V1.2 Page 7 of 20
Modes of control II
Sensing voltage
Sensing voltage
Sensing voltage
+
Sensing voltage
+
Manual V1.2 Page 8 of 20
Modes of control III
Sensing voltage
Sensing voltage
Max. excitation voltage
(AVR supply voltage
x √2 )
Max. excitation voltage
(AVR supply voltage
x √2 )
AVR supply
Manual V1.2 Page 9 of 20
Commissioning set up
Underspeed commissioning set up
Start (AVR Active / Generator running ! )
Underspeed protection
Done
Threshold underspeed
UnderspeedSlowly
Until led on
Setpoint underspeed
UnderspeedVery slowly
Until led off
Led not red flickering!
Nominal speed
GM
Note:
It is recommended to turn
the potentiometer a little
further clockwise,
to allow for short
frequency dips.
Indication setpoints
Manual V1.2 Page 10 of 20
Quick reference I
AFD ModeMinimum Rfield
FormulaMinimum field resistance
Factory settings
Sensing voltageUnderspeed frequencyUnderspeed slopeDroopStability P-actionStability I-actionMax. outDipswitch 1Dipswitch 2Dipswitch 3Dipswitch 4Dipswitch 5Dipswitch 6Dipswitch 7Dipswitch 8
: 400V : 45Hz: Trip slope: 100%: 50%: 50 %: 100 %: On: Off: Off: On: Off: Off: Off: Off
Link: J3-J4, EX-EX
AVR field current.
Max. rating: Intermitted 12A < 10s.
Max. rating: Field forcing 20A < 1s.
Max. out Droop Underspeed Stability Voltage
(Page 6)(Page 6)(Page 6)(Page 8)
Underspeed
Coarse
Fine
- +
- +
Range 230V sensing
+/- 185 .. 290V
Range 400V sensing
+/- 315 .. 505V
+ -0% 100%0% 100% - + - +
I-action
(Integral time)
P-action
(Proportional gain)
Dipswitch
ON
1234
dip
5678
400V sensing voltage.
Phase loss protection disabled.
Remote adjust enabled.
DIP Off On
S-T internally shorted.1
2
3
4
5
6
7
8
Underspeed trip disabled.
Underspeed F/V curve disabled.
Buildup speed 2 sec.
Normal Integral time.
Underspeed voltage level +/- 27.5% of Unom.
Phase loss protection enabled.
230V sensing voltage.
Underspeed trip enabled.
Buildup speed 5 sec.
Increased Integral time.
Do not place or remove link!
Inputs are for EMRI AFD.
AFD is an option unitfor dual AVR applications.
For more information
see manual AFD.
Underspeed F/V curve enabled.
Underspeed voltage level +/- 17.5% of Unom.
(Page 5..8)
Trip @
Higher – RPM - Lower
+/- 62Hz +/- 27Hz
Manual V1.2 Page 11 of 20
Quick reference II
Exciter
0 .. 10Adc
Check Formula
Minimum
Field Resistance
(Page 4, 10)
Max. rating: Intermitted 12A < 10s.
Exciter Field
AVR supply
Transformer
Max. rating: 20..300Vac
PMG
Max. rating: 20..300Vac
Stator
Max. rating: 20..300Vac
Auxilary windings
Max. rating: 20..300Vac
LH1 LH2 LH3 LH4 EX EX
Link
Link
Link
- +
Sensing
U-V-W
clockwise
(Page 12..15)
W
V
U
N
230V
Remote adjust
1kΩ
-
+
Max. value : 10K Max. : -10V..+10V
S T
Isolated supply
(-10V .. +10V)
Rx (10kΩ ..100kΩ)
Dipswitch 1 off Dipswitch 1 off
S T
0..10kΩ
Rx
Current selection
Input X1-X2CT 0.5A(Droopkit)
Input X1-X2CT 1A
(Droopcat)
J1 J2J1 J2
J1-J2 : Open J1-J2 : Link
Current sensing
J1 J2J1 J2
J1-J2 : Open J1-J2 : Link
V phase
0.5A
V phase
1A
X1 X2 X1 X2
400V
Manual V1.2 Page 12 of 20
Wiring diagram I
AVR with PMG
Manual V1.2 Page 13 of 20
Wiring diagram II
AVR with auxilary windings (self excited)
Manual V1.2 Page 14 of 20
Wiring diagram III
AVR with transformer (self excited)
Manual V1.2 Page 15 of 20
Wiring diagram IV
AVR with generator phase supply (self excited)
Manual V1.2 Page 16 of 20
Tips and Suggestions I
Manual V1.2 Page 17 of 20
Tips and Suggestions II
Field flash with isolated battery (AVR)
Manual V1.2 Page 18 of 20
Tips and Suggestions III
Field flash with isolated battery (Exciter field)
Manual V1.2 Page 19 of 20
General installation information Absolute Maximum Ratings - The Absolute Maximum Ratings are those limits for the device that, if exceeded, will likely damage the device. Exceeding the
absolute maximum ratings voids any warranty and/or guarantee. Mounting
Mounting of the product should be done in such a way that: - the absolute maximum ambient temperature rating of the product will never be exceeded. - maximum cooling (direction of cooling ribs and direction of airflow) is achieved. - Mounting no humid air can flow through the product or condensation occurs. - dust or other materials or residue will not remain in or on the product. - the maximum vibration is not exceeded. - personal contact with persons is impossible. Wiring - Diameter size of the wiring should be enough to carry the expected current. Wire insulation should be enough to withstand
the expected operating voltages and temperatures. - To improve EMC emission and immunity, care should be taken for the lay out of the wiring. This in respect to all wiring in the
installation. - Keep current carrying wires as short as possible. - Keep wires carrying a total sum of zero Ampere close to each other, or in one single cable, E.g. U, V, W, or X (+) and XX (-),
or Phase and neutral, or S and T. - Avoid current carrying conductors next to sensing or control wiring. Especially current controlled by SCR’s or PWM controlled
transistors. - If sensitive sensing signal cables need to be laid across distance along other cabling, shielded cable is preferred. Keep the
shield as long as possible and the wiring outside the shield as short as possible. Do not solder or shrink the shield to a regular wire. Connect the original shield to ground at one side with an as large as possible contact surface.
Additional installation information - When the product is supplied by means of a transformer, it should never be an auto-transformer. Auto-transformers react as
voltage sweep up coil and may cause high voltage peaks. - Standard fit capacitors or over-voltage suppressers across X (+) and XX (-), or exciter field terminals inside the generator
should be removed. - When the product is supplied by means of a transformer, it should be able to carry at least the maximum expected current.
Advisable is, to have a transformer which can carry twice the maximum expected current. Inductive loads make voltage sacks and peeks into the secondary voltage of a transformer, from which the device may malfunction.
- It is not recommended to apply switches in dc outputs. It is preferred to use switches in the ac supply inputs of devices. In case it is unavoidable to have switches in the dc output of a device, action must be taken to avoid over voltage damage to the device due to contact arcing. Use a voltage suppressor across the output.
- It is not recommended to apply switches or fuses in the sensing lines. Defects can cause high voltage situations due to over-excitation.
- When using a step down transformer in medium or high voltage generators, the transformer should be three phase (if three phase sensing), and the transformer should be suitable for acting as a sensing transformer. If the transformer is unloaded, connect a resistor to avoid voltage waveform distortion.
- The phase relation from the generator to the AVR is important. Also when voltage transformers and/ or current transformers are installed.
- When using a step down or insulation transformer in the droop circuit, phase relation from the generator to the AVR is important.
- CT’s wiring, connected to the AVR should never be grounded. - Always disconnect electronic products, circuits and people before checking the insulation resistance (Megger check). - Due to differences in generators impedance’s, EMC behavior is not predictable. Therefore the commissioner / installer should
be aware of proper and correct installation. - Large, highly inductive, exciter stator windings can cause destructive high voltage peaks. Adding a resistor from 10 to 20
times the exciter stator field resistance reduces voltage spikes. If necessary filter can be fitted additionally. (e.g. snubber, RC-network)
- Upon problems during commissioning, faulty behavior or defects in the generator, consult the fault finding manual at our web site
- Some advises may be overdone or seem extraordinary, but since the electrical rules are the same everywhere, these advises are given.
Manual V1.2 Page 20 of 20
Contact
EMRI Electronics B.V. Manufacturer Morsestraat 10 6716 AH, Ede, Netherlands Tel: +31 (0)318 620 427 Website: www.emri.nl E-mail: [email protected]
ICELAND, Hafnarfjordur Rafeining ehf Tel: +354 565 3049 Fax: +354 565 3048 Website: www.rafeining.is
E-mail: [email protected]
POLAND, Gdynia An-Elec Sp. z o.o. Tel: +48 58 668 44 00 Fax: +48 58 668 44 66 Website: http://an-elec.pl E-mail: [email protected]
INDIA, Faridabad
Power Solutions Tel: +91 9868907903 Fax:: +91 129 2431216 Website: www.psolindia.com E-mail: [email protected]
SOUTH AFRICA, Roodepoort
Yneldo Electronics Tel: +27(0)117637053 Fax: +27(0)117634212 Website: www.yneldo.com E-mail: [email protected]
POLAND, Szczecin-Mierzyn
Marel Serwis Tel: +48 91 48 58 388 Fax: +48 91 48 79 948 Website: www.marel.szczecin.pl E-mail: [email protected]
CHILE, Santiago Lucio Vicencio y CIA.LTDA Tel: +1-281-334-2904 Fax:: +1-832-221-5642 Website: www.luciovicencio.cl E-mail: [email protected]
NORWAY, Bergen Frydenbø Electric A/S Tel: +47 55 34 91 00 Fax: +47 55 34 91 10 Website: www.frydenbo.no
E-mail: [email protected]
SINGAPORE, Singapore Cyclect Electrical Engineering Tel: +65 6868 6013 Fax: +65 6863 6260 Website: www.cyclect.com.sg E-mail: [email protected]
THAILAND, Bang Lamung Semtec Maritime/Genetech Co.Ltd Tel: +66 38301262 Fax: +1-832-221-5642 Website: semtecmaritime.com/ Email: [email protected]
UNITED ARAB EMIRATES, Sharjah KDU Technical Services Tel: +971-6-5575480 Fax: +971-6-5575490 Website: www.kdutech.ae E-mail: [email protected]
SWEDEN, Kungälv Elektrisk Drivteknik EDT AB Tel: +46-705-28 20 60 Tel: +46-709-50 47 90 Website: www.edtab.se E-mail: [email protected]
GREECE, Piraeus Stavros Kassidiaris S.A. Tel: +30 210 4636000 Fax: +30 210 4624471 Website: www.kassidiaris.gr E-mail: [email protected]
CANARY ISLANDS, Las Palmas
Zamakona Yards Tel: +34 928467521 Fax: +34 928461233 Website: www.zamakonayards.com/ E-mail: [email protected]
UNITED KINGDOM, Stockton on Tees
MJR Controls Tel: +44 1642 762 151 Fax: +44 1642 762 502 Website: www.mjrcontrols.com Email: [email protected]
UNITED STATES, Kemah - Texas
Ramtec Marine Systems LLC Tel: +1-281-334-2904 Fax: +1-832-221-5642 Website: www.ramtec-marine.com Email: [email protected]
REPUBLIC OF PANAMA, Panama
PASRAS S.A. Tel: +507 3140095 Fax: +507 3140094 Website: www.pasras.com E-mail: [email protected]
ROMANIA, Constanta SAMTEC SRL Tel: +40 241 517 047 Fax: +40 241 517 047 Website: www.samtec.ro E-mail: [email protected]
UNITED KINGDOM, Cheadle Hulme
TGS Total Generator Solutions Ltd Tel: +44161 8188720 Fax: +447754677963 Website: http://totalgeneratorsolutions.com Email: [email protected]
POLAND, Szczecin MARCONTREL Tel: +48 91 4 888 474 Fax: +48 91 4 888 475 Website: www.marcontrel.com E-mail: [email protected]
TURKEY, Izmir INTEGRAL Tel: +90 (555) 211 55 75 Email: [email protected]