Main contentsGlobal Primary Products

Primary field of application 3• Typical network• Primary outdoor or indoor substations• Primary indoor substations

Market segments 7

Primary product concept 11

Primary product panorama 13• MV Indoor components• MV Outdoor components• MV Air Insulated Switchgear (AIS)• MV Gas Insulated Switchgear (GIS)• MV Switchgear Railway Application• MV Switchgear Control• Primary LoB’ Engineered Product Solutions• LV offering for packaging

Glossary 53• MV Switchgear• IEC 62271-200 • Circuit breaker (CB)• Disconnecting & isolating• Contactor • Earthing switch • Voltage Transformer (VT) • Current Transformer (CT) • IS Limiter • Monitoring devices for SmartGrid • Service conditions

Primary commercial contacts 63• Commercial Team (co-ordination/non-domestic markets)• Marketing Team

1

6

2

3

4

5

Page 4: Main Primary Products

2 FOR INTERNAL USE ONLY

Prim

ary f

ield

of a

pplic

atio

n

Page 5: Main Primary Products

3FOR INTERNAL USE ONLY

Typical network 4Primary outdoor or indoor substations 5Primary indoor substations 5

Global Primary Products Primary field of application

Contents

Page 6: Main Primary Products

4 FOR INTERNAL USE ONLY

Typical networkPrimary field of application

Medium Voltage products, systems & components to distribute & control power Primary distribution networks in a given country or area are defined by taking into account the following parameters:• Technical - economic analysis.• Supply to a diversity of customers: Utilities, Oil & Gas, Buildings, Mines & Metal.• History of the network.• Ability for the network to grow.• Increase quality and availability of Power supply.• Increase safety.• Environmental respect.• Standardization.

Transmission grid220 - 800 kV

DistributionMV substation

Distribution network66 … 170 kV

IndustryMV substation

Primary Distribution 1 - 52 kV

MV Process Control

Secondary distribution

LV Distribution & Control

PE

9020

7

PE

9022

6

PE

9033

3P

E90

227

PE

9022

8

PE

9022

4

PE

9022

5

Page 7: Main Primary Products

5FOR INTERNAL USE ONLY

Primary outdoor or indoor substationsPrimary indoor substations

Primary field of application

Outdoor substation

Indoor substation

Primary outdoor or indoor substations

PE

9033

1

PE

9033

2

Air InsulatedSwitchboard (PIX, MCset 17.5 kV...)

Gas insulatedSwitchboard (GMA/GHA, CBGS0...)

PE

9022

9P

E90

330

PE

9032

3P

E90

329

Primary indoor substations

DE

9018

6P

E90

281

Page 8: Main Primary Products

6 FOR INTERNAL USE ONLY

Mar

ket s

egm

ents

Page 9: Main Primary Products

7FOR INTERNAL USE ONLY

Global Primary Products Market segments

Contents

Product list by application type 8

Page 10: Main Primary Products

8 FOR INTERNAL USE ONLY

Market segments Product list by application type

* O&G: Oil & Gas segment; M&M: Mines & Metal segment; OEM: Original Equipment Manufacturer

PRIMARY product type Product platform Standards Market application Energy & Infrastructure Industry Name of the product IEC ANSI Utilities Power O&G* Marine Transp. MMM* Other Gen. Railways industriesMV Indoor componentsLoose CBs (SF6) FPX / LF / LFP ● ● ● ● ISF2 ● ● ● FP / SF ● ● ● ● ●Loose CBs (Vacuum) HVX ● ● ● ● ● Evolis ● ● ● ● ● ● ● VXC ● ● ● VAH ● ● ● ● ● ● ● BLV ● ● ● ●CBs with cradle/cassette PMX cradle (with ● ●(SF6+vacuum) HVX, FPX, CVX,…) NEX cradle (with Evolis) ● ● ●Loose contactor (SF6) GFA ● ● ● ● ● Rollarc ● ● ● ● ●Loose contactor (Vacuum) CBX, CVX, CLX, CPX ● ● ● ● ● ●MV Outdoor componentsDog house circuit breaker EOX ● ● ● ● EAX ● ● ● ●Dead Tank circuit breaker VOX ● ● ● ● ●Live tank circuit breaker GIE ● ● PCOB ● ●One & two Phase MV Switchgear (Railway application)Indoor circuit breaker VXA-VXB ● ●Indoor AIS PAD ● ●Indoor GIS WI / WI-G / CBGS-2 ● ●Pole-top switch disconnector SDR, NE, TILF ● ●Vacuum circuit breaker for 22CB ● ●LocomotivesPole-top circuit breaker CBR ● ●

Page 11: Main Primary Products

9FOR INTERNAL USE ONLY

Market segments Product list by application type

PRIMARY product type Product platform Standards Market application Energy & Infrastructure Industry Name of the product IEC ANSI Utilities Power O&G* Marine Transp. MMM* Other Gen. Railways industriesAIS - Air Insulated SwitchgearAIS SBB- mainly with circuit PIX ● ● ● ● ● ● ● ●breakers up to 24kV LSC2B-PM PIX MV ● ● ● PIX Compact ● ● ● ● ● PIX High ● ● ● ● ● ● MCset123 ● ● ● ● ● ● ● MCset4 ● ● ● ● NEX24 ● ● RoNEX ● ● ●AIS SBB- mainly with circuit VISAX / VISAX ● ● ● ● ●breakers up to 24kV LSC2B-PI Compact GenieEvo ● ● ● ● ●AIS DBB- mainly with circuit PIX (double busbar) ● ● ● ● ● ●breakers up to 24kV LSC2B-PM WBD (double busbar) ● ● ● ● ● ●AIS SBB- mainly with circuit PIB ● ● ●breakers up to 24kV LSC2A-PMAIS SBB- mainly with circuit PI ● ● ●breakers up to 24kV LSC2A-PIAIS – SBB mainly with circuit DNF7, PIX 36, AMS, ● ● ● ● ●breakers >30kV LSC2B-PM F400 ● ● ● ● Masterclad ● ● ● ● ●Motor Control Centre -Fixed type Alliance ● ● ● ● ●Motor Control Centre - PIX MCC ● ● ● ● ●Withdrawable type Motorpact Full Voltage ● ● ● ● ● ● ● Motorpact Reduced Voltage ● ● ● ● ● ● ● Motorpact S3 ● ● ● ● ● ● ● Motorpact Full Voltage 720A ● ● ● ● ● ●Switchgear ControlMotor starter GEMSTART 5.4 ● ● ● ● ●Intelligent Monitoring & Control GEMVIEW, ILIS, ● ● ● ● ● ●Control & Management GemControl ● ● ● ● ● ●GIS - Gas Insulated SwitchgearGIS - mainly with circuit breakers GMA ● ● ● ● ● ● ●up to 24 kVGIS - with circuit breakers GHA (WS-G) ● ● ● ● ● ●up to 36/40.5 kV WSA/WSB ● ● ● ● ● ●GIS - with circuit breakers CBGS-0 ● ● ● ● ● ●up to 36 kVGIS - with circuit breakers CBGS-2 ● ● ● up to 52 kV WIA/WIB ● ● ● ● ● ●

* O&G: Oil & Gas segment; M&M: Mines & Metal segment; OEM: Original Equipment Manufacturer

Page 12: Main Primary Products

10 FOR INTERNAL USE ONLY

Prim

ary p

rocu

ct co

ncep

t

Page 13: Main Primary Products

11FOR INTERNAL USE ONLY

Global Primary Products Primary product concept

AIS & Motor Starter GIS LT / DT Outdoor

Switchgears(Indoor

& Outdoor)

PackagesPower Houses / Trackside substations Innovative solutions

EngineeredProduct

Solutions

Vaccuum interrupters, mechanisms, actuators

Corecomponents

VCB Contactor VCB

Components

SF CB

PE

9031

3

PE

9032

6

PE

9032

5

PE

9031

7

PE

9025

2

PE

9025

1P

E90

234

PE

9032

7

PE

9032

8

PE

9027

9

PE

9028

1

PE

9025

8

PE

9026

5

PE

5656

0

PE

9024

6

PE

9026

6

PE

5799

4

PE

6024

7

PE

5719

1

Page 14: Main Primary Products

12 FOR INTERNAL USE ONLY

Prim

ary p

rocu

ct p

anor

ama

Page 15: Main Primary Products

13FOR INTERNAL USE ONLY

MV Indoor components Loose circuit breaker (SF6) 14Loose circuit breaker (Vacuum) 16Cradle / cassette with circuit breakers and other devices 18 Loose contactors (SF6) 19Loose contactors (Vacuum) 19 & 20

MV Outdoor componentsDog house circuit breaker 20Dead Tank circuit breaker 22Live tank circuit breaker 22

MV Air Insulated Switchgear (AIS)Single busbar mainly with circuit breakers up to 17.5 kV (LSC 2B - PM) 24Single busbar mainly with circuit breakers up to 24 kV (VISAX-Family) 28Double busbar mainly with circuit breakers up to 24 kV (LSC 2B - PM) 29Single busbar mainly with circuit breakers up to 24 kV (LSC 2A - PM) 31Single busbar mainly with circuit breakers up to 24 kV (LSC 2A - PI) 31Motorpact - Motor Control Center- Withdrawable type (LSC 2B - PM) 32PIX / Alliance - Motor Control Center - Fixed type (LSC 2A - PI) 34Mainly with circuit breakers > 30 up to 40.5 kV (LSC 2B - PM) 35ANSI - mainly with circuit breakers up to 27 kV 36

MV Gas Insulated Switchgear (GIS)Mainly with circuit breakers up to 24 kV 38Mainly with circuit breakers up to 36/40.5 kV 39Mainly with circuit breakers up to 52 kV 40

MV Switchgear Railway ApplicationIndoor circuit breaker 41Indoor AIS 41Indoor GIS 42Pole-top switch / disconnector 43Pole-top circuit breaker 44Indoor AIS DC Switchboard 44On Board Circuit Breaker (Locomotive) 44

MV Switchgear ControlMotor Control 45Switchgear Monitoring 49Intelligent Monitoring & Control - GEMVIEW 50Control and Management 50

Primary Engineered product SolutionWalk-in substations (Powerhouses) 51Mobile substations 51

Global Primary Products Primary product panorama

This Panorama doesn't contain products dedicated to only one home market of a unit, except products for which we believe that you might have sales opportunities in other countries.For more details, please refer to internal information systems, usual tools such as SMILE. At the end of this document a nominative list for more information.

Page 16: Main Primary Products

14 FOR INTERNAL USE ONLY

Primary product panorama MV Indoor components

Loose circuit breaker (SF6)

LF overview • SF6 circuit breaker.• 12kV, 50kA, 3150A, 17.5kV, 40kA, 3150A.• For fixed or withdrawable air insulatedswitchgear.• Adapted to fit air-insulated switchgear MCset.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing units:SEA / FranceSET / Turkey

PE

5719

1

LF

FPX

FPX overview • SF6 circuit breaker.• Up to 12kV, 40kA, 4000A, 17.5 kV, 31.5 kA, 4000A, 24kV, 31.5kA, 3150A.• Designed for air-insulated switchgear and draw-out units.• Fitted with sealed for lifephase assemblies and highendurance spring mechanism.• Complies with IEC and other national standards.

Manufacturing units:STS / France

PE

9023

1

ISF2 overview • SF6 Furnace circuit breaker - Switchboard• 36kV, 40kA, 3150A.• For fixed or withdrawable air insulatedswitchgear.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing units:SET / Turkey

PE

9033

9

ISF2

FP overview • SF6 circuit breaker.• Up to 12kV, 50kA, 3150 A*, 24 kV, 40 kA, 3150A*, 40.5 kV, 31.5 kA, 3150A.• Excellent capacitive switching performance.• Wide choice of dimensions and arrangements.* 4000 A on request

Manufacturing units:STS / FranceSAS / China

PE

9023

3

FP

Page 17: Main Primary Products

15FOR INTERNAL USE ONLY

Primary product panoramaMV Indoor components MV Indoor components

SF1 overview • SF6 circuit breaker.• Up to 36kV, 25kA, 1250A.• For fixed or withdrawable air insulatedswitchgear.• Adapted to fit air insulated switchgear SM6, MCset4 & F400.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing unit:SET / Turkey

PE

9023

2

SF1

LFP overview • SF6 circuit breaker.• 12kV, 50kA, 5000A, 17.5kV, 31.5kA, 5000A.• For fixed open air type switchgear.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing units:SEA / FranceSET / Turkey

PE

9023

0

LFP

SF2 overview • SF6 circuit breaker.• 24kV, 40kA, 3150A, 36kV, 40kA, 3150A, 40.5kV, 31.5kA, 2500A.• For fixed or withdrawable air insulated switchgear.• Adapted to fit air-insulated switchgear MCset4 and F400.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing unit:SET / Turkey

SF2

PE

5650

1

Page 18: Main Primary Products

16 FOR INTERNAL USE ONLY

Primary product panorama MV Indoor components

Loose circuit breaker (Vacuum)

Evolis 17.5 kV overview • Vacuum circuit breaker.• Up to 17.5kV, 40kA, 2500A.• For fixed or withdrawable air insulated switchgear.• Adapted to fit air-insulated switchgear MCset, NEX and GenieEvo.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing unit:SEA / France

PE

5799

4

Evolis 17.5

Evolis 24 kV overview • Vacuum circuit breaker.• For 24kV, 31.5kA, 2500A.• For fixed or withdrawable air insulatedswitchgear.• Adapted to fit withdrawable air insulated switchgear NEX.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing unit:SEA / France

PE

5800

1

Evolis 24

Evolis 24 kV overview • Vacuum circuit breaker.• For 24kV, 25kA, 1250A.• For fixed air-insulated switchgear.• Adapted to fit air-insulated switchgear SM6.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing unit:SEA/France

PE

5808

6

Evolis 24

BLV

BLV overview • Vacuum circuit breaker.• Fixed type circuit breaker.• Up to 17.5kV, 40kA, 2500A,24kV, 31.5kA, 2500A.• 3-poles.• Vacuum switching.• Complies with IEC standards.

Manufacturing units:STS / FranceEMX / Mexico

PE

9024

0

Page 19: Main Primary Products

17FOR INTERNAL USE ONLY

Primary product panoramaMV Indoor components MV Indoor components

HVX overview • Vacuum circuit breaker.• Up to 12kV, 50kA, 3150A, 17.5kV, 50 kA, 3150A, 24kV, 31.5kA, 2500A.• For compact air-insulated switchgear adapted to fit in PIX switchgear.• For withdrawable, truckmounted and fixed-switchgear designs.• Conventional spring mechanism.• Reduced dimensions up to 12 kV, up to 25 kA, up to 1250 A. For use in PIX, IB,… or as loose component.• Complies with IEC standards, ANSI and other national standards.

Manufacturing units:AGS / GermanyABM / BrazilAVX / ChinaVDR / India

PE

9023

4

HVX

Evolis HP overview • Vacuum circuit breaker.• Up to 15kV 50kA 3150A.• For withdrawable air-insulated switchgear MCset.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing units:SEA / France

PE

5654

5

Evolis HP

HVX Compact overview • Vacuum circuit breaker.• Up to 17.5 kV, 31.5 kA, 2500 A.• For compact air-insulated switchgear, adapted to fit in PIX Compact switchgear.• For withdrawable, truckmounted and fixed-switchgear designs.• Conventional spring mechanism.• Complies with IEC standards.

Manufacturing units:AGS / GermanyABM / BrazilAVX / ChinaVDR / India

PE

9023

5

HVX Compact

HVX embedded pole overview • Vacuum circuit breaker.• Up to 12kV, 50kA, 3150A.• Up to 24kV, 31.5kA, 3150A.• For compact air-insulated switchgear adapted to fit in chinese cubicle KYN28.• OEM Market.• Conventional spring mechanism.• Complies with IEC, GB (chinese standard) and other national standards.

Manufacturing units:AVX / China

PE

9023

6

HVX embedded pole

Page 20: Main Primary Products

18 FOR INTERNAL USE ONLY

Primary product panorama MV Indoor components

Cradle / cassette with circuit breakers and other devices

VXC

VXC overview • Vacuum circuit breaker.• Up to 38kV.• Up to 40kA / 100kA pk.• Up to 4000A.• Arc furnace circuit breaker.• 3 poles.• High number of switching cycles.• Vacuum switching.• Complies with IEC standards.

Manufacturing unit:AGS / Germany

PE

9023

8

PMX cradle

PMX cradle overview • Cradle based on PIX & PIX Motor Control Center.• For FPX SF6 circuit breaker, HVX vacuum circuit breaker, CVX vacuum contactors, UTX, MTX.• Up to 24kV, 3150A, 40 kA.• 3-poles.• Complies with IEC standards.

Manufacturing units:STS / FranceABM / Brazil

PE

9024

1

VAH overview • Vacuum circuit breaker.• Up to 17.5kV.• Up to 63kA* / 160kA.• Up to 8000 A.• High performances.• High switching cycles.• 3-poles.• Vacuum switching.• Complies with IEC standards• *ANSI C37.013 Generator Switching 63kA, 4000 & 5000A

Manufacturing unit:AGS / Germany

PE

9023

9

VAH

HVX embedded pole overview • Vacuum circuit breaker.• Up to 40.5kV, 31.5kA, 2500A.• For compact air-insulated switchgear adapted to fit in PIX 36 kV, AMS and DNF7.• For withdrawable, truckmounted switchgear design.• Conventional spring mechanism.• Complies with IEC and other national standards.

Manufacturing units:AVX / China (40.5 kV)VDR / India (36 kV)

PE

9023

7

HVX embedded pole

Page 21: Main Primary Products

19FOR INTERNAL USE ONLY

Primary product panoramaMV Indoor components MV Indoor components

Loose contactors (SF6 )

Loose contactors (Vacuum)

GFA overview • SF6 contactor.• From 7.2 to 12kV.• SF6 technology.• Magnetic-holding version.• Mechanical latch-in control device version.• Designed for air-insulated switchgear.• Fixed or drawing-out units• Complies with IEC standards and other national standards

Manufacturing unit:STS / France

PE

9024

2

GFA

Rollarc overview • SF6 contactor.• Up to 12kV, 400A, AC4, 8kA (50kA in conjunction with fuses).• Magnetic holding and mechanical latch-in version. For fixed or withdrawable air insulatedswitchgear air insulated switchgear.• Adapted to fit air-insulated switchgear MCset.• Conventional spring mechanism..• Complies with IEC standards.

Manufacturing unit:SEA/France

PE

6024

7

Rollarc

CBX overview • Vacuum contactor.• Vacuum-switching technology• 12kV, 315A, AC4.• 7.2kV, 400A, AC4.• Up to 3 million operations.• Single-phase version.• Special version for capacitor banks.• Simple design for high reliability.• Low maintenance.• Complies with IEC standards.

Manufacturing units:STS / FranceSLW / IndiaAVX / China

PE

9024

3

CBX

CLX

CLX overview • Vacuum contactor.• Vacuum-switching technology.• 7.2kV, 400A, AC4.• Slim line version.• Long life.• Simple design for high reliability.• Low maintenance.• Complies with IEC standards.

Manufacturing unit:STS / France

PE

9024

5

NEX cradle overview • Cradle based on Nex cubicle.• For Evolis range.• Available as “ready to assemble kit” for up to 17kV and assembled version for 24kV.• Complies to IEC standards.

Manufacturing unit:SEA / France

PE

9034

0

NEX cradle

Page 22: Main Primary Products

20 FOR INTERNAL USE ONLY

Primary product panorama MV Indoor components

MV Outdoor components

Dog house circuit breaker (MV outdoor components)

EAX

CVX

CVX overview • Vacuum contactor and fuseholder as withdrawable unit.• CVX7 up to 7.2kV.• Operating current 400A (AC4 duty).• For cubicle width 400mm.• With DIN or BS fuses.• With contactor CBX inside.• 1,000,000 mechanical switching cycles.• Optional with aux. VT or mechanical latch.• Used in PIX.

Manufacturing units:STS / FranceAVX / China

PE

9024

6

• Vacuum contactor and fuseholder as withdrawable unit.• CVX12 up to 12 kV.• Operating current up to 315 A (AC4 duty)• For cubicle width 650mm in PIX and 800 mm in PIX High.• With DIN or BS fuses.• With contactor CBX inside.• 1,000,000 mechanical switching cycles.• Optional mechanical latch.

Manufacturing units:STS / FranceAVX / China

PE

9024

6

CVX

EAX overview • Dog house circuit breaker.• Up to 38kV, 40kA, 2000 A.• Designed for air-insulated switchgear and draw-out units.• Fitted with sealed for lifephase assemblies and highendurance spring mechanism.• Complies with IEC Standards, ANSI and other national standards.

Manufacturing unit:EMX / Mexico

Customization unit:ACM / Colombia

PE

9024

8

CPX overview • Vacuum contactor.• Vacuum-switching technology• 3.6kV, 400A, AC4.• Ease of installation.• Long life.• Simple design for high reliability.• Low maintenance.• Complies with IEC standards.

Manufacturing unit:STS / France

PE

9024

4

CPX

Page 23: Main Primary Products

21FOR INTERNAL USE ONLY

Primary product panoramaMV Indoor components

MV Outdoor componentsMV Outdoor components

EOX overview • Dog house circuit breaker.• Up to 15.5kV, 31.5kA 2000 A, 27kV, 31.5kA, 2000 A (ANSI).• Reliable design.• Extremely compact design - small footprint.• Proven vacuum technology.• Application for the most aggressive environments (stainless steel).• Complies with ANSI standards.

Manufacturing unit:EMX / Mexico

Customization units:MVC / CanadaACM / Colombia

PE

9024

7

EOX

EVR overview • V Free Standing Medium Voltage Vacuum Station Breaker.• 15kV, 600 to 1200A, 110kV BIL, 12.5 to 25kA.• Evolis Vacuum Breaker Unit. Fixed Mounted in High Voltage Compartment.• Uses Same RI Mechanism as FVR Type Station Breaker.• Seismic Zone Four per UBC.

Manufacturing unit:West Chester / USA

PE

9024

9

EVR

FVR Station Breaker overview • Free standing medium voltage vacuum station breaker.• 15kV, 600 to 4000A, 110kV BIL, 12.5 to 40kA.• 27kV, 1200 & 2000A, 125kV BIL, 12.5 to 25kA.• 38kV, 1200 & 2000A, 150kV BIL, 12.5 to 31.5kA.• 38kV, 1200A, 200kV BIL, 25kA.• Arc Resistant Class B. Enclosure for breakers rated 2000A and below per EEMAC and IEC.• No fans required for 3000A rated breaker.• Seismic zone 4 per UBC.

Manufacturing unit:West Chester / USA

PE

9025

0

FVR Station Breaker

EOX MAGnetic overview • Dog house circuit breaker.• Up to 15.5kV, 25kA, 2000A.• Reliable design.• Extremely compact design - small footprint.• Proven vacuum technology.• Application for the most aggressive environments (stainless steel).• Using a magnetic actuator.• Manual emergency tripping.• Complies with ANSI standards.

Manufacturing unit:EMX / Mexico

Customization unit:MVC / Canada

PE

9024

7

EOX MAGnetic

Page 24: Main Primary Products

22 FOR INTERNAL USE ONLY

Primary product panorama MV Outdoor components

Dead Tank circuit breaker

Live tank circuit breakerGIE overview • Outdoor SF6 circuit-breaker.• Up to 40.5kV.• Rated short circuit current up to 31.5 kA.• Complies with IEC standards.• Application: public and industry distribution

PE

9015

5

GIE

PCOB overview • Live tank circuit breaker.• 15 & 36kV, 25kA, 2000A.• High-speed auto-reclosing at maximum breaking capacity.• Circuit breakers are type tested to IEC and IS.• Very cost effective due to minimal maintenance.• Simple, time-saving installation.• Live Tank.• Complies with IEC standards / Indian standards (IS).

Manufacturing unit:VDR / India

Customization units:ABM / BrazilACM / Colombia

Manufacturing unit:STEzzANO / Italy

PE

9025

2

PCOB

VOX overview • Vacuum contactor.• Up to 38kV, 40kA, 2000A.• IEC and ANSI ratings available.• Maintenance free vacuum switching.• SF6 insulation in a stainless steel sealed-for-life corrosion free tank.• Large accommodation for bushing current transformer.• Suitable for high-speed autorecloserswitching duty.• - 65° C test available• Complies with IEC, ANSI, EATS, GOST standards.

Manufacturing unit:STS / France

Customization units:MVC / CanadaEMX / MexicoMRA / AustraliaACM / Colombia

PE

9025

1

VOX

Page 25: Main Primary Products

23FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

Type Voltage LSC Standard Isc Busbar Busbar Switching Fixed / system current medium withdrawableUp to 24 kV SwitchgearsPIX Compact 17.5 kV 2B-PM IEC 31.5 kA Single 2500 A Vacuum CB / Withdrawable Vacuum contactor PIX Standard 17.5 kV 2B-PM IEC 40 kA Single 4000 A Vacuum and SF6 Withdrawable CB / contactor 24 kV 2B-PM IEC 31.5 kA Single 2500 A Vacuum Withdrawable and SF6 CBPIX High 17.5 kV 2B-PM IEC 50 kA Single 5000 A Vacuum CB Withdrawable PIX MV 12 kV 2B-PM IEC 25 kA Single 1250 A Vacuum CB Withdrawable MCset123 17.5 kV 2B-PM IEC 50 kA Single 4000 A Vacuum and SF6 Withdrawable CB / contactorMCset 4 24KV 2B-PM IEC 31,5 KA Single 3150 A SF6 CB Withdrawable NEX 24 24KV 2B-PM IEC 25 KA Single 2000 A Vacuum CB Withdrawable RoNEX 17,5 KV 2B-PM IEC 40 KA Single 2500 A Vacuum Withdrawable and SF6 CB VISAX 24 kV 2B-PI 2A-PI IEC 25 kA Single 2500 A Vacuum CB Withdrawable VISAX Compact 12 kV 2A-PM IEC 25 kA Single 2000 A Vacuum CB FixedGenieEvo 13,8 KV 2A-PM IEC 25 KA Single 2500 A Vacuum CB Fixed / demountable PIB 12 kV 2A-PM IEC 25 kA Single 1250 A Vacuum CB Withdrawable 24 kV 2A-PM IEC 20 kA Single 1250 A Vacuum CB WithdrawablePI 12 kV 2A-PI IEC 25 kA Single 1250 A Vacuum CB Withdrawable 24 kV 2A-PI IEC 20 kA Single 1250 A Vacuum CB Withdrawable Motor starterPIX MCC 7.2 kV 2B-PM IEC 50 kA Single 5000 A Vacuum contactor Withdrawable Alliance 12 kV 2A-PI IEC 25 kA Single 1250 A Vacuum and SF6 Fixed CB / contactor Motorpact 7.2 KV 2A-PM IEC/ NEMA 50KA Single 3150 A Vacuum contactor WithdrawableFull Voltage Motorpact 7.2 KV 2A-PM IEC/ NEMA 50KA Single 3150 A Vacuum contactor WithdrawableReduced Voltage Motorpact 7.2 KV 2A-PM IEC/ NEMA 50KA Single 3150 A Vacuum contactor WithdrawableSequential Smart Start (S3) Motorpact 7.2 KV 2A-PM IEC/ NEMA 50KA Single 3150 A Vacuum contactor WithdrawableFull Voltage 720A (NEMA) Double busbarPIX DBB 17.5 kV 2B-PM IEC 31.5 kA Double 3150 A Vacuum CB Withdrawable WBD 12 kV 2B-PM IEC 31.5 kA Double 3150 A Vacuum CB Withdrawable PAUD 24 kV 2B-PM IEC 25 kA Double 2000 A Vacuum CB Fixed 36 and 40.5 kV switchgearPIX 36 36 kV 2B-PM IEC 25 kA Single 2000 A Vacuum Withdrawable and SF6 CBDNF7 / AMS 40.5 kV 2B-PM IEC GB 31.5 kA Single 3150 A Vacuum Withdrawable and SF6 CBF400 40.5KV 2B-PM IEC 40 KA Single 2500 A SF6 CB Withdrawable ANSI SwitchgearPIX A 27 kV 2B-PM ANSI, CSA, UL 50 kA Single 3000 A Vacuum CB, Withdrawable two highMasterclad 27 KV 2B-PM ANSI 50 KA Single 3000 A Vacuum CB Withdrawable

Page 26: Main Primary Products

24 FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

Single busbar mainly with circuit breakers up to17.5 kV (LSC 2B - PM)MCset 123 overview • Air Insulated Switchgear.• LSC2B-PM.• The MCset 123 rating version with 3 metallic compartments.• Up to 17.5kV, 50kA, 4000A.• Robust construction.• Compact design.• No ventilation openings on the front of the cubicle.• Single busbar (SBB).• Withdrawable vacuum circuit breaker: Evolis or SF6 circuit breaker : LF• Withdrawable vacuum contactor: CTV1 or SF6 contactor: Rollarc.• Can be combined with MOTORPACT for contactor applications.• Internal arc classification AFL(R) 50 kA 1s• Complies with IEC standards.

Manufacturing units:EMT / FranceSET / TurkeyCikarang / IndonesiazEG/Hungary

Customization units:SBMV / China - Saoudy Arabia - Egypt - Italy - Grinon/Spain - Sumaré/Brazil -Mexico - Argentina -Chile

DE

9018

6

MCset 123

MCset 4 overview • Air Insulated Switchgear.• LSC2B-PM.• The MCset 4 has with 3 metallic compartments.• 24kV, 31.5kA, 2500A.• Robust construction.• Compact design.• Single busbar.• Withdrawable SF6 circuit breaker : SF1/SF2.• Internal arc classification AFL(R) 25kA/1s-31.5 kA/ 0.5s.• Complies with IEC standards.

Manufacturing units:MGL / FranceCikarang / IndonesiaBard city /Egypt

PE

5656

0

MCset 4

Page 27: Main Primary Products

25FOR INTERNAL USE ONLY

Primary product panoramaMV Air Insulated Switchgear (AIS) MV Air Insulated Switchgear (AIS)

PIX overview • Air Insulated Switchgear.• The UNIVERSAL MV indoor switchgear with 3 metallic compartments.• Up to 24kV, 40kA, 4000A.• Single busbar (SBB) and duplex (DBB).• Vacuum and SF6 breaking technology.• Available with contactor on withdrawable truck/ combined with PIX MCC.• Marine version.• Rear/top/bottom entry available.• Compact design.• Back to wall installation (rear access optional).• Internal arc classification AFL(R) 40 kA 1s.• Complies with IEC standards.• IS limiter option.

Manufacturing units:ATM / Turkey AIN / Indonesia ABM / Brazil EMX / Mexico ARU / Russia AMA / Malaysia APK / Pakistan SAS / China ACM / Colombia AHM / Hungary

Customization units:AMT / France ASP / SpainMGS / SwedenMRA / Australia MSE / UK MVC / Canada MSO / Austria AGS / Germany - EIB / Belgium SEM /Switzerland

PE

9025

3

PIX

NEX overview • Air Insulated Switchgear.• Dedicated offer for transfer to partner• MV indoor switchgear with 3 metallic compartments.• Up to 24kV, 40kA, 3150A.• Single busbar.• Vacuum breaking technology.• Rear/bottom entry available.• Internal arc classification AFL R 25kA 0.5s.• Complies with IEC / China GB standard.• Proactive interlocking system.• Cradle structure for high CB interchangeability• Special design for technical transfer to facilitate partner manufacturing.

Schneider Electric LAC (for 24 kV): Indonesia -Columbia - Brazil

Partners:China - Iran - Greece - India - Estonia - South Africa - Russia - Thaïland

PE

5623

4

NEX

Page 28: Main Primary Products

26 FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

EAX

PIX High overview • Air Insulated Switchgear.• The PIX high rating version with 4 metallic compartments.• Up to 17.5kV, 50kA, 5000A.• Robust Construction.• Compact design.• No ventilation openings on the front of the cubicle.• Back to wall installation.• Single busbar (SBB).• Vacuum circuit breaker HVX.• Can be combined with PIXMCC for contactor applications.• Can be combined with CVX 12 for contactor applications.• Internal arc classification AFL(R) 50 kA 1s.• Complies with IEC standards.• IS limiter option.

Manufacturing units:AGS / GermanySAS / China

Customization units:ATM / Turkey AIN / Indonesia ABM / Brazil EMX / Mexico ARU / Russia AMA / Malaysia AMT / France ACM / Colombia AHM / Hungary ASP / SpainMGS / Sweden MRA / Australia MSE / UKMSO / Austria SEM / Switzerland EIB / Belgium

PE

9025

5

PIX High

PIX Compact overview • Air Insulated Switchgear.• The compact MV indoor switchgear with 3 metallic compartments.• Up to 17.5kV, 31.5kA, 2500A.• Single busbar (SBB).• Vacuum breaking technology.• Compact design.• Back to wall installation.• Internal arc classification AFL(R) 31.5 kA / 1s.• Complies with IEC standards.

Manufacturing units:ATM / Turkey AIN / Indonesia ABM / BrazilEMX / Mexico ARU / Russia AMA / Malaysia APK / Pakistan SAS / China ACM / Colombia AHM / Hungary

Customization units:AMT / FranceASP / Spain MGS / Sweden MRA / Australia MSE / UK MVC / Canada MSO / Austria AGS / Germany EIB / Belgium SEM /Switzerland

PE

9025

4

PIX Compact

Page 29: Main Primary Products

27FOR INTERNAL USE ONLY

Primary product panoramaMV Air Insulated Switchgear (AIS) MV Air Insulated Switchgear (AIS)

RoNEX overview • Air Insulated Switchgear.• Rolling on floor type.• MV indoor switchgear with 3 metallic compartments.• Up to 17.5kV, 40kA, 2500A.• Single busbar.• Vacuum and SF6 breaking technology.• Top/bottom entry available.• Internal arc classification A FLR 31.5kA 0.5s• Complies with IEC / Egypt /Russia GOST standard.• Proactive interlocking system.• Cassette structure for high CB interchangeability.• In line with Egypt and Gulf countries requirements

Schneider Electric LAC / Egypt

Partners:UAE

PE

9025

7

RoNEX

PIX MV overview • Air Insulated Switchgear.• 4 metallic compartments.• Up to 12kV, 25kA, 1250A.• Compact design.• Single busbar (SBB).• Vacuum circuit breaker HVX.• Internal arc classification AFLR 25kA 0.1s• Complies with IEC standards and IS requirements.• In line with Indian Market requirements.

Manufacturing unit:VDR / India

PE

9025

6

PIX MV

Page 30: Main Primary Products

28 FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

Single busbar mainly with circuit breakers up to 24 kV (VISAX-Family)GenieEvo overview • Air Insulated Switchgear.• Up to 13.8kV, 25kA 3s, 2500A.• Vacuum fixed de-mountable circuit breaker.• Screened encapsulated disconnector.• Solid insulated busbar.• LSC2A-PM.• Internal Arc classification AF(LR) 25kA.• Rear cable box.• Fully interlocked front cable test access.• Can be combined with Motorpact.• Complies with IEC and BS standards.

Manufacturing unit:Leeds / UK

Customization unit:Leeds / UK

Partners:South Africa (LV customization)

PE

9020

8

GenieEvo

VISAX overview • Air Insulated Switchgear.• Up to 24kV, 25kA, 2500A.• Vacuum-isolating circuit breaker BLV.• Functional components mounted in line.• Internal arc classification AFL 25 kA 1s.• LSC 2B-PI (standard version).• LSC 2A-PI available (UKversion: VISAX-S).• Complies with IEC standards.

Manufacturing unit:AHM / HungaryAMA / Malaysia

Customization unit:ASP / SpainMGS / SwedenMSE / UKMVC / CanadaAMT / France

PE

9025

8

VISAX

Page 31: Main Primary Products

29FOR INTERNAL USE ONLY

Primary product panoramaMV Air Insulated Switchgear (AIS) MV Air Insulated Switchgear (AIS)

Double busbar mainly with circuit breakers up to 24 kV (LSC 2B - PM)

VISAX Compact overview • Air Insulated Switchgear.• Up to 12kV, 25kA, 1250A/2000A, 75kV, BIL (95kV under development).• Fixed pattern design.• Vacuum-circuit breaker BLV.• 3 position isolator/earth switch.• Functional components mounted in line.• Rear cable box.• Internal arc classification AFL 25 kA 1s.• LSC 2A-PM.• Complies with IEC standards.

Manufacturing unit:AHM /Hungary

Customization unit:MSE / UK

PE

9025

9

VISAX Compact

PAUD overview • Air Insulated Switchgear.• Up to 24kV, 25kA, 2000A.• 25kA, IAC AFLR.• Fixed vacuum circuit breaker or load break switch.• Indoor installation.• Complies with IEC standards.

Manufacturing unit:MSO / Austria

PE

9026

3

PAUD

SESA29870
Droite
Page 32: Main Primary Products

30 FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

WBD overview • Air Insulated Switchgear.• Up to 12kV, 31.5kA, 2500A (3150A busbar).• 31.5 kA, IAC AFLR.• Withdrawable vacuum circuit breaker.• Indoor installation.• Extension without busbar outage.• Complies with IEC standards.

Manufacturing unit:MSO / Austria

Customization unit:MSE / UK

PE

9026

2

WBD

PIX Double busbar overview • Air Insulated Switchgear.• Up to 17.5 kV.• Up to 31.5 kA.• Internal arc classification AFLR 25 kA 1s.• Up to 3150 A.• With withdrawable vacuum circuit breaker HVX.• Indoor installation.• Extension without busbar outage.• Complies with IEC standards.

Manufacturing unit:EIB / Belgium

PE

9026

0

PIX Double busbar

Page 33: Main Primary Products

31FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

Single busbar mainly with circuit breakers up to 24 kV (LSC 2A - PM)

Single busbar mainly with circuit breakers up to 24 kV (LSC 2A - PI)

PIB

PI

PIB overview • Air Insulated Switchgear.• 12 kV up to 1250A, 25kA-3s.• 24 kV up to 1250A, 20kA-3s.• Metal-enclosed 2 metallic compartments.• With withdrawable vacuum C.B. HVX• Optional with fused circuit switcher• Long periods of operation without maintenance.• Internal arc classification AFL.• Complies with IEC standards.

Manufacturing unit:AGS / Germany

PE

9026

1

PI overview • An economical circuit breaker and switch disconnector switchgear.• 12kV up to 1250A, 25kA-1s.• 24kV up to 1250A, 20kA-1s.• Air-insulated, metal-enclosed.• With withdrawable vacuum C.B. HVX.• With switch disconnector.• With contactors up to 12 kV.• Compatible with PN 600.• Long periods of operation without maintenance.• Internal arc classification AFL.• Complies with IEC standards.

Manufacturing unit:AGS / Germany

PE

9026

4

Page 34: Main Primary Products

32 FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

Motor Control Center- Withdrawable type (LSC 2B - PM)Motorpact Full Voltage overview • Air Insulated Switchgear.• Direct on line motor starting applications.• LSC2A-IM.• Motorpact - 3 metallic compartments.• Up to 7.2kV, 50kA 4s, 3150A, (3800 kW).• 400 A IEC - 450 A NEMA.• Robust construction.• Compact design.• No ventilation openings.• Single busbar.• Withdrawable vacuum contactor.• Can be combined with MCset, MasterClad, PIX…if CB required.• Internal arc classification AFL(R) 50 kA.• Complies with IEC, NEMA, UL, GOST, IACS standards.

Configurations• DOL.• Reversing.• 2 speed 1 winding.• 2 speed 2 winding.

Manufacturing unit:Smyrna / USA

Customization units:Sumaré / BrazilEMT/ FranceCikarang / IndonesiaKSA / Chile

Marine Partners:South Korea

NEMA Partner:KSA

PE

9026

6

Motorpact Full Voltage

Motorpact Full Voltage 720A(NEMA) overview • Air Insulated Switchgear.• Direct on line motor starting applications.• LSC2A-IM.• Motorpact - 3 metallic compartments.• Up to 7.2kV, 50kA 4s, 3150A.• 720 A continuous (5600 kW).• Robust construction.• Compact design.• No ventilation openings• Single busbar.• Withdrawable vacuum contactor.• Can be combined with MasterClad for CBapplications.• Internal arc classification AFL(R) 50 kA.• Complies with IEC, NEMA, UL standards.

Configuration• Direct On Line (DOL).

Manufacturing unit:Smyrna / USA

PE

9026

7

Motorpact Full Voltage 720A (NEMA)

Page 35: Main Primary Products

33FOR INTERNAL USE ONLY

Primary product panoramaMV Air Insulated Switchgear (AIS) MV Air Insulated Switchgear (AIS)

Motorpact Sequential SmartStart • Air Insulated Switchgear.• Reduced voltage “Multiple” motor starting solution.• LSC2A-IM.• Motorpact - 3 metallic compartments.• Up to 7.2kV, 50kA 4s, 3150A.• 400 A continuous (3800 kW).• Robust construction.• Compact design.• No ventilation openings.• Double busbar – start and run.• Withdrawable Vacuum contactor.• Can be combined with MCset, MasterClad, PIX…if CB required.• Internal arc classification AFL(R) 50 kA.• Complies with IEC, NEMA, UL, GOST, IACS standards.

Configurations• S3 - Sequential Smart Start.• RS3 – Redundant Sequential Smart Start.

Manufacturing unit:Smyrna / USA

Customization unit:Cikarang / Indonesia

Marine Partners:South Korea

PE

9026

8

Motorpact Sequential Smart Start

Motorpact Reduced Voltage • Air Insulated Switchgear.• Reduced voltage motor starting applications.• LSC2A-IM.• Motorpact - 3 metallic compartments.• Up to 7.2kV, 50kA 4s, 3150A.• 400 A continuous (3800 kW).• Robust construction.• Compact design.• No ventilation openings.• Single busbar.• Withdrawable vacuum contactor.• Can be combined with MCset, MasterClad, PIX…if CB required.• Internal arc classification AFL(R) 50 kA.• Complies with IEC, NEMA, UL, GOST, IACS standards.

Configurations• Reduced voltage Soft Starter (RVSS).• Stand Alone RVSS.• Reduced Voltage Autotransformer (RVAT).

Manufacturing unit:Smyrna / USA

Customization units:EMT/ FranceCikarang / Indonesia

Marine Partners:South Korea

PE

9026

9

Motorpact Reduced Voltage

Page 36: Main Primary Products

34 FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

PIX Motor Control Center (MCC) overview • Motor Control Center.• Up to 7.2 kV, 400A, 40kA and 50kA, busbar current 4000A.• Internal arc containment up to 40 kA and 50kA for 1 second.• Direct “line up” with PIX or PIX High circuit breaker cubicles.• Same operation as in PIX family.• CVX: withdrawable vacuum contactor and fuse holder.• With DIN or BS fuses.• 1,000,000 mechanical switching cycles.• Internal arc classification AFLR• Ratings up to:- Motors 2,700 kW.- Transformers 3,100 kW.- Capacitor banks 1,700 kW.• Controlled and protected by GEMSTART 5.4.• Complies with IEC standards

Manufacturing unit:AGS / GermanySAS / ChinaAIN / IndonesiaABM/ BrazilEMX / MexicoATM / Turkey

PE

9026

5

PIX Motor Control Center (MCC)

Motor Control Center - Fixed type (LSC 2A - PI)

Alliance overview • Motor Control Center.• Up to 12 kV, 1250 A, 25 kA/1s.• Especially suitable for industrial application, water treatment and public lighting.• Vacuum or SF6 contactors, circuit breakers.• Air-insulated fixed type MCC.• Complies with IEC standards.

Manufacturing unit:AMT / France

PE

9027

0

Alliance

Page 37: Main Primary Products

35FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

Mainly with circuit breakers > 30 up to 40.5 kV (LSC2B - PM)DNF7 / AMS overview • Air Insulated Switchgear.• Up to 40.5 kV / 36 kV.• Up to 31.5 kA.• Up to 3150 A*.• With withdrawable SF6 and vacuum circuit breaker.• Cassette type or floor rolling.• Indoor.• Type tests in both Chinese and European laboratories.• Complies with IEC standards and GB standards.• IAC 31.5 kA 1s AFLR• IP4X in standard

* 3150 A with forced cooling

Manufacturing unit:SAS / ChinaAVX / China

Manufacturing units (roll out)ATM / TurkeyACM / ColombiaABM / BrazilARU / Russia

Customization unit:AMT / FranceMVC / CanadaMRA / Australia

PE

9027

2

DNF7 / AMS

F400 overview • Air Insulated Switchgear.• LSC2B-PM.• The F400 rating version with 3 metallic compartments.• Up to 40.5 kV, 31.5 kA, 2500A.• Robust construction.• Compact design.• Single busbar.• Withdrawable SF6 circuit breaker: SF1/SF2.• Internal arc classification AFLR: 25kA/1s - 31.5kA/0.5s - 40 kA/0.15s.• Complies with IEC standards.

Manufacturing unit:MGL / FranceSET / Turkey

Customization unit:Ryad / KSA

PE

9027

1

F400

PIX 36 overview • Air Insulated Switchgear.• Up to 36 kV.• Up to 25 kA.• Up to 2000 A.• IAC 25 kA -1s.• With withdrawable vacuum circuit breaker HVX overmoulded / SF6 circuit breaker FP.• Indoor.• Internal arc classification AFL.• Complies with IEC standards.• Mainly for Indian and OMAN markets.

Manufacturing unit:MVI / India

PE

9027

3

PIX 36

Page 38: Main Primary Products

36 FOR INTERNAL USE ONLY

Primary product panorama MV Air Insulated Switchgear (AIS)

ANSI - mainly with circuit breakers up to 27 kV

MasterClad overview • Air Insulated Switchgear.• Meets IEEE/ANSI C37.20.2 Metal-Clad Switchgear.• Indoor or Outdoor enclosures.• Sheltered aisles.• Prefabricated houses.• Arc Resistant Type 2b C37.20.7.• 3000A 15kV 50kA (being extended to 63kA in 2011).• 2750A 27kV 40kA.• 1200A – 3000A withdrawable VCBs.• 4000A VCB being introduced in 2011.• Arc Terminator – active arc flash mitigation. Market differentiator.• Direct connections (throat) to Cast, Liquid or Dry transformers.

Manufacturing units:Smyrna / TNRoio Gomez / Mexico

Customization units:EEIC / KSABrossard / CANRojo Gomez / MEX

PE

9027

6

MasterClad

PIX A overview • Air Insulated Switchgear.• MV indoor switchgear with 6 metallic compartments.• Up to 27kV, 50kA, 3000A.• Single busbar (SBB) and two high configuration (2 CBs per cubicle).• Vacuum breaking technology.• Internal arc resistance.• Rear/top/bottom entry.• Compact design.• Complies with ANSI, CSA, UL standards.

Manufacturing unit:EMX / Mexico

Customization units:MVC / CanadaABM / BrazilACM / Colombia

PE

9027

5

PIX A

Page 39: Main Primary Products

37FOR INTERNAL USE ONLY

Primary product panorama MV Gas Insulated Switchgear (GIS)

Type Voltage BIL Isc Busbar Busbar Switching medium Number of gas system current compartmentsGMA 24 kV 125 kV 25 kA Single 1250 A Vacuum CB oneGMA 24 kV 125 kV 20 kA Double 1250 A Vacuum CB twoWSA 36 kV 170 kV 31.5 kA Single 3000 A Vacuum CB twoWSB 36 kV 170 kV 31.5 kA Double 2500 A Vacuum CB threeGHA 36 kV 170 kV 40 kA Single 2500 A Vacuum CB twoGHA 40.5 kV 185 kV 31.5 kA Single 2500 A Vacuum CB twoGHA 36 kV 170 kV 40 kA Double 2500 A Vacuum CB threeGHA 40.5 kV 185 kV 31.5 kA Double 2500 A Vacuum CB threeWIA 52 kV 250 kV 40 kA Single 2500 A Vacuum CB twoWIB 52 kV 250 kV 40 kA Double 2500 A Vacuum CB threeCBGS-0 24 KV 125 KV 31,5 KA Single 1600 A SF6 CB threeCBGS-0 36 KV 170 KV 31,5 KA Single 1250 A SF6 CB threeCBGS-2 52 KV 250 KV 25 KA Single 2000 A SF6 CB threeCBGS-2 52 KV 250 KV 25 KA Double 2000 A SF6 CB three

Page 40: Main Primary Products

38 FOR INTERNAL USE ONLY

Primary product panorama MV Gas Insulated Switchgear (GIS)

Mainly with circuit breakers up to 24kVCBGS-0 overview • Gas Insulated Switchgear.• The CBGS-0 has 3 compartments.• Up to 36kV, 31.5kA/3s, 1250A at 36kV, 1600A at 24kV, Busbar 2000 A.• Solid insulated busbar.• Compact design.• Single busbar.• Fixed SF6 circuit breaker.• Internal arc classification AFLR: 31.5kA/1s.• Complies with IEC standards.

For higher ratings up to 24kV, please refer to GHA

GMA overview • Gas Insulated Switchgear.• Up to 24kV, 2500A, 31.5kA (3s).• Circuit breakers are equipped with vacuum interrupters.• Circuit breaker, switch disconnector or switchdisconnector-fuse-combination can be selected.• Up to four feeders (function units) in one expandable module.• Compact height 2100mm.• Double busbar as back-to-back solution (height 2100 mm).• Complies with IEC standards GOST and China National standard (CNS).• Internal arc classification AFL(R).

Manufacturing unit:MESA / Spain

Manufacturing unit:AGS / Germany

PE

9028

1P

E90

278

CBGS-0

GMA

Page 41: Main Primary Products

39FOR INTERNAL USE ONLY

Primary product panorama MV Gas Insulated Switchgear (GIS)

Mainly with circuit breakers up to 36/40.5kVGHA (WS-G in China) overview • Gas Insulated Switchgear.• Up to 40.5kV, 2500A, 40kA (3s) with natural cooling.• With vacuum circuit breaker.• Modular design of switchgear panels, single or double busbar.• No gas handling during erection, extension work and panel replacement.• Innovative fault-tolerant busbar link “B-link”.• Intelligent Gas Density System (IDIS).• Complies with IEC standards, GOST and China National standard (CNS).• Internal arc classification AFL (R).

Manufacturing units:AGS / GermanySAS / China

PE

9027

9

GHA (WS-G in China)

WS (WSA – WSB) overview • Gas Insulated Switchgear.• Up to 36kV, 2500A, 31.5kA (3s).• With vacuum circuit breaker.• Modular design of switchgear panels, single or double busbar.• All live parts are hermetically enclosed and gas.• Complies with IEC standards, GOST and China National standard (CNS).• Internal arc classification AFL.

Manufacturing unit:AGS / Germany

PE

9027

7

WS (WSA – WSB)

Page 42: Main Primary Products

40 FOR INTERNAL USE ONLY

Primary product panorama MV Gas Insulated Switchgear (GIS)

Mainly with circuit breakers up to 52 kVCBGS-2 overview • Gas Insulated Switchgear.• The CBGS-2 has 3 compartments.• Up to 52kV, 25kA/3s, 2000A, 250 kV BIL.• Monophasic or biphasic applications at 27.5 kV for railways.• Compact design.• Single busbar or double busbar.• Fixed SF6 circuit breaker.• Internal arc classification AFLR : 25kA/1s.• Complies with IEC standards.

WI (WIA – WIB) overview • Gas Insulated Switchgear.• Up to 52kV, 2500A, 40kA (3s), 250kV BIL.• 60kV on request.• Only 600 mm wide for high performance up to 52 kV.• Vacuum circuit breaker.• Modular design of switchgear panels - single or double busbar.• Three-pole encapsulation technique derived from high voltage technology.• All live parts are hermetically enclosed and gas-insulated.• Panels can be extended without switching off the busbar.• Complies with IEC, ANSI, GOST and China National standard (CNS).

Manufacturing unit:MESA / Spain

Manufacturing unit:AGS / Germany

PE

9028

2P

E90

283

CBGS-2

WI (WIA – WIB)

Page 43: Main Primary Products

41FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Railway Application

Indoor circuit breaker

Indoor AIS

VXA-VXB overview • Vacuum circuit breaker.• Up to 27.5kV.• Up to 40kA / 100 kA.• Up to 2500A.• 16.7/50/60Hz.• For railways applications.• 1 or 2 poles.• Complies with IEC standards.

PAD overview • Air Insulated Switchgear.• Indoor metal-clad switchgear for railway power supply.• Up to 17.5kV, 16 2/3Hz.• Indoor installation.• With vacuum breaking technology.• Complies with IEC standards.

Manufacturing unit:AGS / Germany

Manufacturing unit:MSO / Austria

PE

9028

4P

E90

285

VXA-VXB

PAD

Page 44: Main Primary Products

42 FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Railway Application

Indoor GISGHA Rail (WI-G in China) overview • Gas Insulated Switchgear.• Up to ± 27.5kV, 2500A, 31.5kA.• Up to 220/325kV BIL.• 1- or 2-pole version.• Modular design of switchgear panels.• Vacuum circuit breaker.• Complies with IEC and GB standards (China).• For deliveries to Chinese rail.

WI overview • Gas Insulated Switchgear.• Only 600 mm wide for high performance.• Up to 52/55kV (± 27.5kV), 2500A, 40kA (3s).• Up to 250kV BIL.• 1- or 2-pole version.• Modular design of switchgear panels.• Vacuum circuit breaker.• Complies with IEC standards.

Manufacturing units:SAS / ChinaAGS / Germany

Manufacturing unit:AGS / Germany

PE

9028

6P

E90

287

GHA Rail (WI-G in China)

WI

Page 45: Main Primary Products

43FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Railway Application

Pole-top switch / disconnectorNE overview • Outdoor DC switches.• Switches for DC traction lines.• Up to 3.8kV, 2000A, 25kA.• Short time rating: up to 5000 A for 3 min.• Single-pole.• Earthing switch version, type NE-T also available.• Complies with IEC standards.

Manufacturing unit:EIB / Belgium

PE

9028

9

NE

TILF overview • Outdoor DC switches.• Switches for DC traction lines.• Up to 3.8kV, 3150A, 25kA.• Short time rating: up to 5000A for 3 min.• Single-pole.• Complies with IEC standards.

Manufacturing unit:EIB / Belgium

PE

9029

0

TILF

SDR overview • Load Switch for Railway Networks.• Railway networks at 25kV-50Hz.• 12.5kA, 1600A.• Outdoor.• Maintenance free.• Vacuum interrupter.• Magnetic actuator.• SF6 gas insulation.• Sealed tank IP67.• No static or dynamic gaskets.• Complies with IEC standards IEC 60265-1, classes E3, M2.

Manufacturing unit:STS / France

PE

9028

8

SDR

Page 46: Main Primary Products

44 FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Railway Application

Pole-top circuit breakerCBR overview • Vacuum Circuit breaker for Railway Networks.• Railway networks at 27.5kV- 50Hz , 25kA, 2000 A.• Outdoor.• Maintenance free.• Vacuum interrupter.• Magnetic actuator.• SF6 gas insulation.• Sealed tank IP67.• No static or dynamic gaskets.• Complies with IEC standards IEC 60265-1, classes E3, M2.

Manufacturing unit:STS / France

PE

9028

8

CBR

PIX DC

Indoor AIS DC switchboard

PIX DC overview • DC switchboard fitted with High speed circuit breaker (available first quarter 2010).• Light railway segment (tram and metro system).• Up to 1500V DC, 4000 A.• DC panel based on PIX standard panel with a width of 650mm.• High speed circuit breaker, disconnector and rectifier panels.• Rated short-circuit current (peak value): 125kA.• Complies with EN 50123 or IEC 61992.

Manufacturing unit:ATM / Turkey

PE

9029

1

On Board Circuit Breaker (Locomotive)

22 CB overview • Vacuum Circuit Breaker for Locomotives and Electric Multiple Units (EMU).• Railway networks at 25kV AC single phase, 50Hz, 16kA, 1000A.• Outdoor on Locomotive top.• Minimum maintenance.• Vacuum interrupter.• Pneumatic Mechanism.• Solid insulation (sealed for life vacuum interrupter).• External Protection IP67.• Complies with IEC standards.

Manufacturing unit:VDR / India

PE

9029

2

22 CB

Page 47: Main Primary Products

45FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Control

Motor ControlGEMSTART 5.4 overview Motor Control - GEMSTART 5.4for MV & LV motor starters:• Monitoring• Control• Protection• Measurement• Serial communications

• Economical solution for MV Motor Starter, available with PIX Motor Control Center.• Memory module (PAMM).• Optional RTD module or 4 additional inputs.• Communication interface for MODBUS or Profibus.• Remote or local configuration.

GEMSTART 5 Hand Held Programmer • Secure configuration.• Mechanical key protected.• Unique to AREVA.• O&G approved.• Avoids the use of Laptop !• Reset & Control capability.• Work at convenient height.• Power supplied from GEMSTART 5.

Customization units:Available to all Primary LoB units for inclusion in own build switchgear

Not available to sell or forward to other OEM’s or asloose equipment

PE

9029

3P

E90

294

PE

9029

5

GEMSTART 5

Page 48: Main Primary Products

46 FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Control

Current Transformers (CT) overview • Insulation class A.• Covering and insulation realized by vacuum casting EPOXY resin with excellent electrical characteristics, high mechanical strength and high ageing resistance.• Manufactured and tested according to IEC 60044-1.• Specific country standards can be supplied (IEEE, NBR, NFC, GOST…).• Insulation voltage levels from 7,2 kV up to 40,5 kV.• Rated primary currents up to 4000 A.• Short-time thermal current up to 60kA x 1 s.• Available types both for indoor and outdoor installations.• For metering or protection purpose.• PX accuracy class can be respected in accordance to the relay formula.• CT types available with primary winding (wounded or bar type) or without primarywinding (toroid or window type).• Ratio change (tapping) on primary or secondary side according to CT types.• Outdoor current transformers treated by application of silicon on the sand blasted surface of the resin.• Lack of emissions of any harmful substances in case of fire.

Standard installation:• Compartmented cubicles (SM6, MCset, NEX, F400..).• Metal clad cubicles (GMset).• Large motor terminals.• Capacitor banks.

Special installations:• Explosive gaseous atmosphere environments (Eex).• Corrosive atmosphere environments.• Outstanding behaviour in tropical climates.

Manufacturing plants:CAIRO MONTENOTTE /Italy

PE

9029

6P

E90

297

PE

9029

8

Page 49: Main Primary Products

47FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Control

Voltage Transformers (VT) overview • E Insulation class A.• Covering and insulation realized by vacuum casting EPOXY resin with excellent electrical characteristics, high mechanical strength and high ageing resistance.• Manufactured and tested according to IEC 60044-1.• Specific country standards can be supplied (IEEE, NBR, NFC, GOST…).• Available types for connection between phases or between phase and earth.• Insulation voltage levels from 7,2 kV up to 40,5 kV.• Voltage factor 1,9Um x 8h (phase-earth) or 1,2 Um continuously (phase-phase)• Rated primary voltage up to 35:√3 kV (phase-earth) or 35 kV (phase-phase)• Suitable for applications in earthed or insulated neutral systems• Available types both for indoor and outdoor installations.• For metering or protection purpose.• Available types with metal screened surface according to application.• Outdoor voltage transformers treated by application of silicon on the sand blasted surface of the resin.• Lack of emissions of any harmful substances in case of fire.

Standard installation:• Compartmented cubicles (SM6, MCset, NEX, F400..).• Metal clad cubicles (GMset).• Large motor terminals.• Capacitor banks.

Special installations:• Explosive gaseous atmosphere environments (Eex).• Corrosive atmosphere environments.• Outstanding behaviour in tropical climates.

PE

9029

9

Manufacturing plants:CAIRO MONTENOTTE /Italy

PE

9030

0P

E90

301

Page 50: Main Primary Products

48 FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Control

Low Power Current Transformers (LPCT) overview • For Medium Voltage applications.• Insulation class A.• Covering and insulation realized by vacuum casting EPOXY resin with excellent electrical characteristics, high mechanical strength and high ageing resistance.• Manufactured and tested according to IEC 60044-8.• Insulation voltage level 24 kV.• Rated extended primary current up to 1250 A.• Rated nominal secondary voltage 22,5 mV.• For metering or protection purpose.• Lack of emissions of any harmful substances in the case of fire.

• For Low Voltage applications.• Manufactured and tested according to IEC 60044-8.• Insulation voltage level 0,72 kV.• Rated extended primary current up to 2500 A.• Rated nominal secondary voltage 22,5 mV.• For metering or protection purpose.

Standard installation:Compartmented cubicles (SM6).

Secondary connector:RJ45 – 8pts for direct connection to protection relay.

Accuracy:Accuracy is guaranteed for connection with SEPAM and all devices with impedance ≥ 2 kΩ.

Manufacturing plant:CAIRO MONTENOTTE /Italy

PE

9030

2P

E90

303

Page 51: Main Primary Products

49FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Control

Switchgear MonitoringInternal arc Monitoring overview Switchgear Monitoring – ILISIntelligent Light Information System• Arc Detection & Quenching• Rapid Disconnection• Up to 4 independent loops• Self Testing / Test function• LED Display• Alarm Contacts• Multi direction diffused sensors• Multiple sensors per channel• Economical solution for MV.• GIS or AIS applications.• Fibre Optic Sensors.• 4 compartments per column.• Up to 5 columns.• 6 to 250ms detection time.• Fibre length 1.5, 3, 5,10 m.

Customization units:Available to all Primary LoB units for inclusion in own build switchgear

Not available to sell orforward to other OEM’s or asloose equipment

PE

9030

4

Page 52: Main Primary Products

50 FOR INTERNAL USE ONLY

Primary product panorama MV Switchgear Control

Intelligent Monitoring & Control - GEMVIEW

GEMVIEW screenshots

GEMVIEW overview Intelligent Control & Monitoring System• Modular PLC based Control System to international O&G standards.• Switchgear single line diagram and real time status, simple and graphical monitoring and control at the switchboard level.• Provides external interface to a client's DCS with client connection to a single or dualredundant PLC system.• Economical solution for MV & LV Switchboards for all functions and relay typesincluding MICOM, GEMSTART and non-AREVA.• Expandable architecture for large projects.• 200 plus protocol library.• Easy windows look and feel.• Structured top down menus.• Multi-level alarms.• Long Term trending.• Maintenance flags.• Control Logic for Interlocking.

Customization units:Available to Primary LoB units for use in packaged offers for the O&G Industry

PE

9030

8P

E90

343

PE

9030

7P

E90

306

Control and ManagementGemControl SMART Switchgear Controller overview• Suitable for AIS or GIS equipments.• Pre defined configuration sets.• Direct Circuit Breaker Control.• No interposing relays required.• MultiVoltage Inputs.• Modular expansion for additional motors.• Robust Hardware.• High reliability Integrated PLC functions.• Flexible and friendly Gemcontrol Suite.• Unique to SE Primary MV products.

Customization units:Available to all Primary LoB units for use on own switchboards

Page 53: Main Primary Products

51FOR INTERNAL USE ONLY

Primary product panorama

Walk-in substations (Powerhouse / Power zone)

Mobile substations

Overview Containerized Substation - comprising:• MV switchboard (AIS, GIS).• LV switchboard.• Monitoring, Control.• Protection, Measurement.• Pre-engineered solution.• Pre-assembled at works.• Pre-commissioned in factory.• Up to 52 kV.• Increased reliability owing to full assembly/quality control in the factory.• Reduced erection and commissioning time/cost.• Reduced cost and reduced time to network connection.

NOMAD overview Mobile Substation – type NOMAD comprising:• MV switchboard (AIS, GIS).• LV switchboard.• Transformer.• Monitoring, Control.• Protection, Measurement.• Pre-engineered solution.• Pre-assembled at works.• Pre-commissioned in factory.• Up to 52 kV.• Increased reliability owing to full assembly/quality control in the factory.• Reduced erection and commissioning time/cost.• Reduced cost and reduced time to network connection.

Targeted market segments• Railways.• Utilities.• Oil & Gas.• Mining.• Wind.

Targeted market segments• Utilities.• Emergency temporary supply.

Manufacturing unit:ABM / BrazilACM/ ColombiaAGS / GermanyARU / RussiaASP / SpainEIB / BelgiumEMX / MexicoMRA / AustraliaMVC / CanadaAMT / FranceMSE / UKMUS / USAMSO / AustriaAIN / IndonesiaSD / USA

Manufacturing unit:MRA / Australia

PE

9031

6

PE

9031

5P

E90

313

PE

9031

4

PE

9031

7Primary Engineered Product Solutions

Page 54: Main Primary Products

52 FOR INTERNAL USE ONLY

Glo

ssar

y

Page 55: Main Primary Products

53FOR INTERNAL USE ONLY

MV Switchgear 54IEC 62271-200Latest requirements for MV switchgear 55 Loss of Service Continuity Category LSC 55Internal Arc Classification (IEC) 57IAC according to ANSI 57

Circuit breaker (CB) 58Disconnecting & isolating Contactor 58Earthing switch 58Voltage Transformer (VT) 59Current Transformer (CT) 59IS Limiter 59Monitoring devices for SmartGrids Gas Insulated Switchgear (GIS)Thermal monitoring – IR Monitoring System vs windows 60 Internal arc protection device 60

Service conditionsProtection Degree (IP) 61Ambient temperature 61Effects of altitude on Air Insulated Switchgear 61

Global Primary Products Glossary

Page 56: Main Primary Products

54 FOR INTERNAL USE ONLY

Glossary MV Switchgear

Medium Voltage Switchgear• Metal-enclosure containing:Circuit-breakers, contactor, contactor with fuses, earthing switch, switchdisconnectors, monitoring and control.• Typically, the incoming, coupling and cable feeders are equipped with a circuit breaker.• The auxiliary transformer can be protected by three fuses combined with a switchdisconnector.• Installed close to the consumer, mainly indoor or in prefabricated housings.

Page 57: Main Primary Products

55FOR INTERNAL USE ONLY

Glossary IEC 62271-200

New Target for IEC 62271-200

Latest requirements for MV switchgear

Loss of Service Continuity Category LSC

New IEC 62271-200Up to now IEC 60298

LSC Category If an accessible Construction details compartment (e.g. for (examples) C.B.) in a feeder will be opened, ...

LSC 1 … other switchgear … no partition walls must be switched off, minimum one other or the a relevant busbar section

LSC 2 LSC 2A … all other feeders Partition walls are still stay under + min. 1 isolating voltage (stay live) distance + min. 2 compart- ments in each feeder

LSC 2B … all other, including Partition walls the cable compartment of, + min. 2 isolating the open feeder, stay distance under voltage (stay live) + min.3 compart- ments in each feeder

Protection against environmental influence touch proof andArc protection („optional“)

Metal-enclosed:• Metal-clad• Clad• Partly metal-clad

SAFETY

LOSS OFSErVICECONTINuITY (LSC)

MAINTENANCECAPABILITY

Safe access to compartments, if neighbour compartment still live

Page 58: Main Primary Products

56 FOR INTERNAL USE ONLY

Glossary IEC 62271-200

Example of Loss of Service continuity: LSC 2B PM Air-insulated C.B. feeder with 3 compartments -Example product PIX M

Example of Loss of Service continuity: LSC 2A PI Air-insulated C.B. feeder with temporary slide-in isolating plate - Example product PI

All compartments are separated by metallic walls/shutters = partition class PM

All feeders are separated by metallic partition walls and for maintenance there is a temporary slide-in isolating plate = partition class PI

3 separate compartments per feeder 1. Busbar compartment: no access2. C.B. compartment3. Cable compartmentAll compartment walls metallic.

One common compartment per feeder 1. Place for a slide-in isolation plate2. Busbar compartment: No access with silde-in3. Switching device and cable compartment

PE

9032

3

23

1

3

2

1

Page 59: Main Primary Products

57FOR INTERNAL USE ONLY

Glossary IEC 62271-200

Accessibility A (authorised personnel) and B (member of public) has to be added together with switchboard sides of access.

Example: Qualification IAC A FL 25 kA 1sInternal Arc ClassificationA: Accessibility AF: at the front side andL: at both sides accessible 25 kA1 secondF = FrontL = Lateralr = rear

Internal Arc Classification (IEC)

IAC according to ANSI

Rea

r

Fron

t

Lateral

Lateral

SWITCHBOARD

Extract of IEEE Std C37.20.7-2007: Guide for Testing Metal-Enclosed Switchgear Rated Up to 38kV for Internal Arcing FaultsA distinction is made between two levels of accessibility to switchgear assemblies. These levels correspond directly to the indicator placement:• Type 1 - Switchgear with arc-resistant designs or features at the freely accessible front of the equipment only. Indicators are to be fitted on a mounting rack in a vertical and, a horizontal plane at the front of the switchgear to be tested.• Type 2 - Switchgear with arc-resistant designs or features at the freely accessible exterior (front, back, and sides) of the equipment only. Indicators are to be fitted on a mounting rack in a vertical and a horizontal plane at the front, back and at the sides of the switchgear to be tested.

Accessibility: Type (either Type 1 or 2) and adding the suffix for the specific performance features.• Suffix A (“basic” design).• Suffix B (equipment where normal operation of the equipment involves opening the door or cover of compartments specifically identified as low-voltage control or instrumentation compartments). Suffix “B” testing requires the placement of indicators directly in front of the low-voltage control or instrument compartment(s) adjacent to the compartment inwhich the arc is initiated with the compartment cover/door(s) removed to evaluate the entrance of ionized gases into those compartments.• Suffix C (equipment where isolation from the effects of an internal arcing fault is desired between all adjacent compartments within a switchgear assembly). Suffix “C” testing requires the placement of indicators within the interior compartments adjacent to the compartment in which the arc is initiated to evaluate the entrance of ionized gases into those compartments.

The preferred rated arcing duration is 0.5 s.

Page 60: Main Primary Products

58 FOR INTERNAL USE ONLY

Glossary Circuit breaker (CB) - Disconnecting & isolating - Contactor - Earthing switch

• Breaking and making fault currents.• It opens automatically on detection of a fault.• Manual or electrical operation.• Fixed or withdrawable in AIS solution; fixed in GIS.• A circuit breaker is used for protection of large size distribution transformer or as general protection of each feeder.

Circuit Breaker (CB)

• Disconnection of the main circuit is achieved either by the use of a disconnecting switch e.g. GIS Switchgear or VISAX Compact, or by physically racking out the circuit breaker truck e.g. PIX. In both cases the disconnection also provides circuit isolation as defined by the IEC standard.• Independent of the method of disconnection, isolation is always achieved ‘off load’ and is interlocked with the circuit breaker.

Disconnecting & isolating

• Mainly dedicated to start and protect a MV motor.• Breaking and making low fault currents without fuse.• Automatically opens on under voltage faults (Electrically held version).• When combined with fuses, replaces the HVX VCB in PIX cubicles.

Contactor

• Fault making capability.• It is manually or electrically operated. They are used to earth devices or line sections during maintenance and repair in order to ensure the operator safety.

Earthing switch

Page 61: Main Primary Products

59FOR INTERNAL USE ONLY

Glossary Voltage Transformer (VT) Current Transformer (CT) - IS Limiter

• Voltage Transformers are included on either circuits (incomers or feeders) or busbars to provide a voltage source relating to the supply. This voltage is typically used for metering and protection (i.e. Voltmeters, kW Meters and under voltage protection). Depending on the application the class is chosen i.e. Class 1 giving 1% accuracy. The typical ratings are 10-30 VA.• Control Voltage Transformers are used in fused contactors to provide a control supply to the contactor and control circuit, thus making the complete circuit independent of external supplies. These transformers are usually rated for 250VA.

Voltage Transformer (VT)

Current Transformers are used within the switchgear and are selected to provide either protection or metering/indication functions:• Protection – the most common functions are over-current and earth fault, usually defined with accuracy classes of 5P10, 5P20, 10P10 or 10P20.e.g. 5P10 gives 5% accuracy at 10 times nominal current.• Metering/Indication – functions include local ammeters/ kW meters, etc, and tariff metering with accuracies up to 0.5% typically.e.g. Class 0.2 equals 0.2% accuracy.

Current Transformer (CT)

An IS limiter is a ‘one shot’ fault current limiting device, which can be installed into medium voltage switchgear (another equipment). The purpose of these devices is to very quickly detect when a current is flowing which could be greater than the capabilities of the connectedequipment, and then interrupt the current, thereby ensuring the connected equipment is not subject to peak and short time currents which are greater then they can withstand.

The IS limiter is made up of a sensing circuit, a main current carry conductor, a parallel fuse and a small pyrotechnic device which when triggered open-circuit’s the main current carrying conductor.The current then flows through the fuse which operates to open circuit the network.

A typical example of an application of an IS limiter would be on an existing network which is extended to introduce addition supply sources, such as generation. The new equipment has a higher fault rating than the existing equipment and the potential fault level of the new network is also higher than the existing system. The IS limiter is used to connect the two networks together. Under normal conditions power can flow between the two networks. Under a fault condition on the existing network the Is limiter would operate before the fault current on the existing network exceeds the networks capabilities.

IS Limiter

Example of current waveform during IS limiter operation

Page 62: Main Primary Products

60 FOR INTERNAL USE ONLY

Glossary Monitoring devices for SmartGrids

Thermal monitoring – Ir Monitoring System vs windows

Internal arc protection device

Many industrial customers have insurance against lost of production due to failure of equipment. To minimize potential failure the insurance companies require that the equipment is properly maintained and monitored to predict any possible failure. Thermo graphic imagining is one way to predict if the equipment is operating correctly. Of course customers also use IR monitoring as part of their regular maintenance, as any failure is very disruptive.

For many years’ customers MV and LV switchgear has had facilities to gain access to the various connections so that thermal imaging cameras can be 'pointed' at them and the temperature measured.In the past this has been achieved by removable covers and mesh screens, or for MV, IR 'windows' were fitted using special crystal glass to allow the transmission of IR. These windows were located in the switchgear panels at appropriate points to view the various connections.

Recently we have introduced electronic IR monitoring devices into our switchgear (EXERTHERM). This has a number of advantages over the traditional approach - they can be mounted inside the switchgear panel and therefore can be used to access connections not normally visible. They do not require the operator to approach the equipment (very important for safety), the integrity of the switchgear cubicle is maintained therefore IAC is not compromised. And importantly for maintenance, the devices can offer continuous monitoring.

Thermal diagnosis: monitoring – alarm – fault location.It is based on the principle of measuring circuit temperaturesat Medium-Voltage (MV) potential, without insulation-related risk(due to the use of optical fibres).By measuring the temperature of live circuits, it ensures:• continuous monitoring of the temperature rise in power circuitsat busbar and cable connections,• tripping of a pre-alarm, followed by an alarm, by activatingdry contact outputs (remote operation via the monitoring system),• location of the zone and circuit concerned.

Today thermal monitoring is requested more and more. In Canada we are advised that IR monitoring is becoming a 'standard'. Many large industry and O&G companies now request this either on specific projects or as part of their Switchgear standard specifications.

Modern MV Switchgear is of course fully Internal Arc Classified to prevent an Arc in one compartment from travelling to adjacent compartments - propagating the fault . Of course an internal arc failure is still very disruptive and will cause severe damage within the compartmentwhere it occurs. It will also have substantial pollution effects on adjacent equipment. Although the arc will always be contained and will not spread outside the faulty compartment, the arc products must be dissipated in a safe manner. Even IAC rated switchgear will migrate large quantities ofcombustion products into most adjacent switchgear compartments and possibly to other equipment within the same Switchroom.

By using the ILIS/VAMP light detection system, arc faults can be detected and disconnected in less than 100ms (severe faults within 25ms). This considerably reduces the volume and pressure of the arc combustion products and minimizes the impact of an arc fault.

Page 63: Main Primary Products

61FOR INTERNAL USE ONLY

Glossary Service conditions

Protection Degree (IP)

Ambient temperature

Effects of altitude on Air Insulated Switchgear

Protection degree is defined according to IEC 62 271-1.

under certain conditions a de-rating factor shall be applied to e.g. rated current. refer to technical documentation and support.

According to IEC standards, current carrying capacities of indoor switchgear refer to ambient temperatures of 40°C maximum, with an average of 35°C for period of 24h. In case of more severe conditions a de-rating factor shall be applied to the rated current of the apparatus.

The rated dielectric values are guaranteed at sea level and under normal atmospheric conditions (IEC 60071-2, pressure 1013 h Pa, temperature 20 °C, relative humidity 11 g/m3). Despite the fact that the degree of air insulation decreases progressively as the altitude increases, the ratedvalues are guaranteed up to 1000 metres above sea level.Above 1000 m, a correction factor must be taken into account to calculate the level of insulation which could be guaranteed.For information refer to the graph below for correction factor vs. altitude.

This applies as well to the air insulated fuse compartment in Gas Insulated Switchgear (GIS).

Example IP41: Protections against bodies with Ø ≥ 1mm and ingress of vertical dripping water

Example: for an altitude of 2500 m, the insulation value should be divided by 1.2.

IP First significant number Second significant number (protection against (protection against water) foreign bodies)0 No protection No protection1 Protection against bodies Ingress of vertical dripping with Ø ≥ 50mm water2 Protection against bodies Dripping water with with Ø ≥ 12.5mm an angle of 15°3 Protection against bodies Dripping water with with Ø ≥ 2.5mm with an angle of 60°4 Protection against bodies Spray from all direction with Ø ≥ 1mm5 Deposit of dust Jets from all direction6 Entry of dust Flood7 - Immersion of limited duration8 - Immersion of unlimited duration

Page 64: Main Primary Products

62 FOR INTERNAL USE ONLY

Prim

ary L

oB' c

omm

ercia

l con

tact

s

Page 65: Main Primary Products

63FOR INTERNAL USE ONLY

PrimaryLoB Product Primary commercial contacts

Commercial Team (co-ordination/non-domestic markets)• Sales Support & BD Director Eric HENNEQUIN• Central & East. Europe, China, India Americas, Near & Middle East Shubhronil ROY• Eastern Asia-Pacific, Large Projects Europe, Africa Franck PELLAT• Eastern Europe Nedialko LATINOV• Africa Nader GHABBOUR• Gulf Countries Krishna KUMAR• Eastern Asia Lawrence FOONG• Projects & Solutions Xavier-Franck BRAUD

• Marketing DirectorGMA, GHA, Local Offer GIS Frank WROBEL• Primary Communication Manager Martine MAITRE• PIX, DNF7 range, Contactors Sylvain IBANEZ• PIX High, MCC, VISAX, GenieEvo Martin CHALLES• MCset 4 24kV, F400, CBGS0, Local Offer GIS Jean ZADEM• MCset 123 17.5 kV Joseph MARZOCCA• NEX KeFeng HOU• Motorpact Tony NARUSEVICIUS• Switchgear Control & Smart Grid Paul BROWN• Current/ Voltage Transformers Cristiano BARBERIS• Evolis, SF6 breaker, local offer CB Mahesh ANANDA-KUMAR• HVX-O, VEP (China) Becky ZHOU• Circuit Breaker Outdoor (DT, LT) Vivek SARWATE

Marketing Team

Page 66: Main Primary Products

64 FOR INTERNAL USE ONLY

Page 67: Main Primary Products

65FOR INTERNAL USE ONLY

Page 68: Main Primary Products

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

This document has been printed on ecological paper.

Publishing: SYNTHESE ECA, Schneider Electric.Photos: Schneider Electric

02/2011

© S

chne

ider

Ele

ctric

Indu

strie

s S

AS

- A

ll rig

hts

rese

rved

EnergyMain Primary ProductsPanorama February 2011

Schneider Electric Industries SAS35, rue Joseph Monier CS30323F - 92505 Rueil-Malmaison cedex (France)

RCS Nanterre 954 503 439Capital social 896 313 776 €www.schneider-electric.com

NOT FOR CUSTOMER USE - THE INFORMATION HEREIN IS FOR INTERNAL USE ONLY