LVP5000 INSERT 1 ENG - automation-bulgaria.comautomation-bulgaria.com/img/mylvp5000...
Transcript of LVP5000 INSERT 1 ENG - automation-bulgaria.comautomation-bulgaria.com/img/mylvp5000...
LVP5000TM
System
Low Voltage Power Distribution System LVP5000 - the modular, reliable, flexible and economic solution
Your first class partner in up-to-date products and progress in electrical power
www.tempapano.com
Electrical Power Distribution for sophisticated low voltage applications with LVP5000™
LVP5000power supply
• Extendable cabinet system
• Unique patented busbar system type K-BAR
• Natural cooling system
• Best performance for even in high protection degree (IP 54)
Design verified by te
sts accord
ing to
IEC 61439-2
LVP5000TM
System
• All components fitted as Power Switch gear and Control gear
assembly PSC acc. to IEC61439-1/-2 (Design Verified)
• Main bus bar (K-BAR) located in the top and over the whole
length accessible without pre-drilled holes
• Protection degree up to IP54
• Partitioning up to Form 4b/type7
• Cable entry from top and/ or bottom
• End sections can be expanded as standard
• Clear segregation into functional areas
• Enclosure for combination or stand alone mounting
Enclosure:• Degree of protection IP32/IP44/IP54• Internal separation: up to Form 4b• Robust special formed frame system• Door opening angle ~100 degrees• Frame elements powder-spray painted• PSC (Desing Verified) complying connections for bus bar trunking system• PSC (Design Verified) complying connections for PROFIBUS communication• Finish in RAL 7035w, light grey / other colors on request• Painted parts: zinc - phosphate pre treated• All system variants can be combined• Mounting elements are zinc-plated• Cladding powder-spray painted
Steel thickness:• Frame 2.0 mm• Doors 1.5 mm• Top and bottom plates 1.5 mm• For non magnetic purposes (Aluminum) 2.0 – 3.0 mm • Side-, rear- plates 1.5 mm• Galvanized steel for segregation 1.5 mm
Busbar connections with new technology:• Special formed copper bars with significantly reduced heat loss power and accessibility without pre-drilled holes!
LVP5000TM
System
Type - PPower functionsIncomers, outgoers and bus- coupler sections for circuit- breakers from 630 to 5000 A
• Fixed mounting or withdrawable
• Connection with cable or bus bartrunking systems
Type - OOutgoing Circuit FunctionsSections for power outgoers and incomers with fixed compartments up to 630 A.
• Separated dropper bus bar trough
• Separated cable trough for cable connection
Application Outgoer Outgoer Outgoer Outgoer Outgoer Outgoer Outgoer Outgoer Outgoer Outgoer OutgoerRated Current "In" (A)
(related to the defined application( 16A 25A 32A 40A 50A 63A 80A 100A 125A 160A 200A
Enclosure Dimension (W x H x D)(mm) 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000 600x2000x1000
Enclosure Type (Catalogue type) FR062010 FR062010 FR062010 FR062010 FR062010 FR062010 FR062010 FR062010 FR062010 FR062010 FR062010
Outgoing Enclosure (wxhxd)(mm) up to FR082010 up to FR082010 up to FR082010 up to FR082010 up to FR082010 up to FR082010 up to FR082010 up to FR082010 up to FR082010 up to FR082010 up to FR082010
Application Outgoer/Incomer
Outgoer/Incomer
Outgoer/Incomer
Outgoer/Incomer
Outgoer/Incomer
Outgoer/Incomer
Outgoer/Incomer
Outgoer/Incomer
Outgoer/Incomer Incomer Incomer
Rated Current "In" (A) (related to the defined application( 250A 400A 630A 800A 1000A 1250A 1600A 2500A 3200A 4000A 5000A
Enclosure Dimension (W x H x D)(mm) 600x2000x1000 600x2000x1000 600x2000x1000 400x2000x1000 400x2000x1000 400x2000x1000 400x2000x1000 600x2000x1000 800x2000x1000 1000x2000x1000 1000x2000x1000
Enclosure Type (Catalogue type) FR062010 FR062010 FR062010 FR042010 FR042010 FR042010 FR042010 FR062010 FR082010 FR102010 FR102010
Outgoing Enclosure (wxhxd)(mm) up to FR082010 up to FR082010 up to FR082010 Included Included Included Included Included Included Included Included
Enclosure dimensions
LVP5000TM
System
Technical Data
General
Reference standards IEC 61439-2
Installation Indoor
Cable inlet Top/bottom
Access Front/rear
Degree of protection (IP) 20/32/44/54
Form 2b/3b/4b
Dimensions:
Height 2250
Width 400/600/800/1000/1200
Depth 800/1000
Panel coating Powder coating (standard)
Powder (SPO3) 60 μ - 80 μ
Framework Galvanized/Painted CRS steel
Panel color RAL 7035w(standard)
Electrical Data
Rated insulation voltage (Ui) 690 V AC
Rated operational voltage (Ue) 400 V AC
Rated frequency (F) 50/60 Hz
Rated impact withstand voltage (Uimp) 8 kV
Auxiliary circuit rated voltage 230 V AC max.
Surge category IV
Cooling System Natural
Degree of pollution 3
Rated current (ln) 5000 A
Horizontal busbar rating 4000 A
Vertical busbar rating up to 2000 A
Horizontal busbar:
Rated 1s short-term current (lcw) 50/85/100 kA
Rated peak current 105/187/220 kA
Vertical busbar:
Rated 1s short-term current (lcw) 30/50/85 kA
Rated peak current 63/105/178 kA
Rated conditional short-circuit current (lsc) 100 kA
Earthing system TT-IT-TNS-TNC
Power incoming and outgoing limits Up to 5000 A
HEAD OFFICE / FACTORY
Makine İhtisas Organize Sanayi Bölgesi 2.Cd. No:1
Demirciler Köyü 41455 Dilovası / Kocaeli - TURKEY
Tel : +90 262 642 63 40 / 8 lines
Fax : +90 262 642 63 48 / 49
e-mail: