An Asbestos Refurbishment/Demolition Survey (MA only) to the specific areas of
LSHTM TP1 & TP2 Project 15-17 Tavistock Place
London WC1H 9SH
Survey Carried Out On:
03 February 2018
Commissioned By:
William Pettit Kier Construction (London) 2 Langston Road Loughton Essex IG10 3SD
Date: 5 March 2018
Our Reference: J094568
Surveyed By: Danny Gurnham
Presented by: Pennington Choices Ltd Clan Works 1A Howard Road Bromley Kent BR1 3QJ t: 020 8290 5629 f: 020 8290 4443 e: [email protected] w: www.pennington.org.uk
Contents
Appendices
1.0 Executive Summary
2.0 Introduction
3.0 General Site Information
4.0 Conclusions and Actions
5.0 UKAS Accreditation
6.0 Regulations
Appendix 1 Plans
Appendix 2 Asbestos Register
Appendix 3 Asbestos Analysis Report
Appendix 4 Quality Assurance
Contents
Appendices
1.0 Executive Summary 3
2.0 Introduction 12
3.0 General Site Information 13
4.0 Conclusions and Actions 14
5.0 UKAS Accreditation 15
6.0 Regulations 16
Appendix 1 Plans
Appendix 2 Asbestos Register
Appendix 3 Asbestos Analysis Report
Appendix 4 Quality Assurance
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 2 of 16
Our Reference: J094568
1.0
Executive Summary
1.1
Introduction
Pennington Choices Ltd carried out a Refurbishment/Demolition Survey (MA only) to the specific areas of LSHTM TP1 & TP2 Project. The survey and this subsequent report has been produced in accordance with HSG264 – Asbestos: The Survey Guide, with the layout and content of the report being based on the specific guidance for survey reports contained in section 6 of HSG264. Please note the MA scores for the surface treatment of bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile have been given a score of 2 rather than 1 as suggested by HSG264.
This survey will report on the Material Assessment (MA).
1.2
Findings
Positive occurrences of asbestos containing materials were identified in the following areas:
Urgent Items (requiring immediate action on the part of the Client)
Please also refer to the section 4.0 and the Asbestos Register.
Location (Plan room references in brackets)
Result (asbestos type)
Action Sample Ref
There are currently no urgent items.
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 3 of 16
Our Reference: J094568
Other Items
Location Result (asbestos type)
Action Sample Ref
Ground (001) G40 Grey floor tiles and bitumen adhesive to concrete floor within plasterboard riser to rear right hand side wall (painted yellow)
Chrysotile Remove prior to refurbishment if likely to be disturbed
BH001940 (Sample 2)
Ground (001) G40 Bitumen adhesive to concrete floor beneath screed/carpet tiles
Chrysotile Remove prior to refurbishment if likely to be disturbed
BH001942 (Sample 4)
Ground (002) G41 Bitumen adhesive to concrete floor beneath screed/carpet tiles
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001942 (Ref Sample 4)
Ground (003) G42 Bitumen adhesive to concrete floor beneath carpet tiles/screed/ceramic tiles
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001942 (Ref Sample 4)
Ground (004) Corridor Bitumen adhesive to concrete beneath modern linoleum/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
BH001943 (Sample 5)
Ground (006) Student Room Bitumen adhesive to concrete beneath modern linoleum/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001943 (Ref Sample 5)
Ground (007) Student Room Bitumen adhesive to concrete beneath carpet/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001943 (Ref Sample 5)
Ground (008) Corridor Bitumen adhesive to concrete beneath modern linoleum/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001943 (Ref Sample 5)
Ground (008) Corridor Textured coating to concrete ceiling above suspended plasterboard ceiling
Chrysotile Remove prior to refurbishment if likely to be disturbed
BH001945 (Sample 6)
Ground (010) Office Bitumen adhesive to concrete beneath carpet/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001943 (Ref Sample 5)
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 4 of 16
Our Reference: J094568
Location Result (asbestos type)
Action Sample Ref
Ground (011) Landing Bitumen adhesive to concrete beneath modern linoleum/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001943 (Ref Sample 5)
Ground (012) Corridor Bitumen adhesive to concrete beneath modern linoleum/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001943 (Ref Sample 5)
Ground (013) Corridor Bitumen adhesive to concrete beneath modern linoleum/screed
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001943 (Ref Sample 5)
External (016) Main Warehouse Pitched corrugated roof sheets
Chrysotile Remove prior to refurbishment if likely to be disturbed
BH001951 (Sample 12)
External (017) Entrance Lobby Bitumen adhesive to concrete floor
Chrysotile Remove prior to refurbishment if likely to be disturbed
BH001949 (Sample 10)
External (018) Store Bitumen adhesive to concrete floor
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001949 (Ref Sample 10)
External (019) Store Bitumen adhesive to concrete floor beneath carpet tiles
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001949 (Ref Sample 10)
External (020) Lobby Bitumen adhesive to concrete floor beneath modern linoleum
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001949 (Ref Sample 10)
External (021) WC Bitumen adhesive to concrete floor beneath modern linoleum
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001949 (Ref Sample 10)
External (027) Tank Room Corrugated roof sheets
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001951 (Ref Sample 12)
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 5 of 16
Our Reference: J094568
Please also refer to the section 4.0 and the Asbestos Register.
Location Result (asbestos type)
Action Sample Ref
External (029) External Area Pitched corrugated roof sheets to Main Warehouse
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001951 (Ref Sample 12)
External (029) External Area Corrugated roof sheets to area (027)
Chrysotile Remove prior to refurbishment if likely to be disturbed
As BH001951 (Ref Sample 12)
Basement 1 (043) Store LG14 Beige floor tiles and bitumen adhesive to concrete floor beneath modern linoleum
Chrysotile Remove prior to refurbishment if likely to be disturbed
BH001998 (Sample 17)
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 6 of 16
Our Reference: J094568
Non asbestos items (no asbestos detected in sample)
Location (Plan room references in brackets) Result (asbestos type)
Sample Ref
Ground (001) G40 Bitumen adhesive residue to concrete ceiling above suspended plasterboard
No Asbestos Detected
BH001939 (Sample 1)
Ground (001) G40 Bitumen adhesive residues to brick walls behind foam lined plasterboard
No Asbestos Detected
BH001941 (Sample 3)
Ground (002) G41 Bitumen adhesive residue to concrete ceiling above suspended plasterboard
No asbestos detected in visually consistent material
As BH001939 (Ref Sample 1)
Ground (002) G41 Bitumen adhesive residues to brick walls behind foam lined plasterboard
No asbestos detected in visually consistent material
As BH001941 (Ref Sample 3)
Ground (003) G42 Bitumen adhesive residue to plasterboard lined concrete ceiling above suspended plasterboard
No asbestos detected in visually consistent material
As BH001939 (Ref Sample 1)
Ground (003) G42 Bitumen adhesive residues to brick walls behind foam lined plasterboard
No asbestos detected in visually consistent material
As BH001941 (Ref Sample 3)
Ground (005) Electrical Intake Room Boxing to steel column/lining sides of central beam
No asbestos detected in visually consistent material
As BH001947 (Ref Sample 8)
Ground (005) Electrical Intake Room High level boxing running along ceiling/wall to area (004)
No asbestos detected in visually consistent material
As BH001947 (Ref Sample 8)
Ground (005) Electrical Intake Room Bitumen adhesive residues to brick walls behind foam lined plasterboard
No asbestos detected in visually consistent material
As BH001941 (Ref Sample 3)
External (016) Main Warehouse Fascias to lower roof section of area (017) - (021)
No asbestos detected in visually consistent material
As BH001947 (Ref Sample 8)
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 7 of 16
Our Reference: J094568
Location (Plan room references in brackets) Result (asbestos type)
Sample Ref
External (016) Main Warehouse Door header panel to (017)
No asbestos detected in visually consistent material
As BH001947 (Ref Sample 8)
External (016) Main Warehouse Panels lining whole roof to area (017) - (021)
No asbestos detected in visually consistent material
As BH001947 (Ref Sample 8)
External (017) Entrance Lobby Bitumen adhesive to hardboard above suspended plasterboard ceiling
No Asbestos Detected
BH001946 (Sample 7)
External (017) Entrance Lobby Door header panel above access door
No Asbestos Detected
BH001947 (Sample 8)
External (017) Entrance Lobby Mastic to joints of high level ventilation trunking
No Asbestos Detected
BH001948 (Sample 9)
External (018) Store Bitumen adhesive to hardboard above suspended plasterboard ceiling
No asbestos detected in visually consistent material
As BH001946 (Ref Sample 7)
External (019) Store Bitumen adhesive to hardboard above suspended plasterboard ceiling
No asbestos detected in visually consistent material
As BH001946 (Ref Sample 7)
External (020) Lobby Bitumen adhesive to hardboard above suspended plasterboard ceiling
No asbestos detected in visually consistent material
As BH001946 (Ref Sample 7)
External (021) WC Bitumen adhesive to hardboard above suspended plasterboard ceiling
No asbestos detected in visually consistent material
As BH001946 (Ref Sample 7)
External (025) Store Bitumen adhesive to concrete beneath carpet tiles/modern linoleum
No Asbestos Detected
BH001950 (Sample 11)
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 8 of 16
Our Reference: J094568
Please also refer to the section 4.0 and the Asbestos Register.
Location (Plan room references in brackets) Result (asbestos type)
Sample Ref
External (027) Tank Room Felt lining brick base supporting tank
No Asbestos Detected
BH001952 (Sample 13)
First (028) Office Bitumen adhesive to concrete beneath carpet tiles/modern linoleum
No asbestos detected in visually consistent material
As BH001950 (Ref Sample 11)
External (029) External Area Fascias to area (027)
No asbestos detected in visually consistent material
As BH001947 (Ref Sample 8)
External (029) External Area Bituminous felt to flat roof of area (000)
No Asbestos Detected
BH001954 (Sample 14)
Ground (038) Reception G10 Bitumen adhesive to concrete floor beneath modern linoleum/screed
No Asbestos Detected
BH001996 (Sample 15)
Ground (041) Stairwell G15 Bitumen adhesive to concrete floor beneath modern linoleum/screed
No asbestos detected in visually consistent material
As BH001996 (Ref Sample 15)
Ground (041) Stairwell G15 Loose fill insulation behind decorative wood panels to external wall
No Asbestos Detected
BH001997 (Sample 16)
Ground (042) Corridor G16 Bitumen adhesive to concrete floor beneath modern linoleum/screed
No asbestos detected in visually consistent material
As BH001996 (Ref Sample 15)
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 9 of 16
Our Reference: J094568
Rooms/Areas inspected and not found to contain suspicious materials under the scope of this survey
Location (Plan room references in brackets)
Ground (009) Office
Basement 1 (014) Computer Room
Basement 1 (015) Corridor
External (023) Store
External (024) Store
External (026) WC
First (030) Offices 145 -148
First (031) Lobby 149
First (032) Corridor 132
First (033) Female WC 139
Second (034) Corridor 232
Second (035) Male WC 238
Third (036) Corridor 320
Third (037) Female WC 333
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 10 of 16
Our Reference: J094568
Please also refer to section 1.4, 3.0 and the Asbestos Register.
Location (Plan room references in brackets)
Ground (039) First Aid Room G11
Ground (040) Office G12
1.3
No/Limited Access Areas (Whole Areas)
Due to the nature of the survey undertaken and for conditions found on site some parts of the building were not accessible by us or were only accessible on a limited basis, details of which are set out below
Please also refer to 1.4 and the Asbestos Register
Location No/Limited Access
External (022) Room
No access - as instructed by Kier
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 11 of 16
Our Reference: J094568
2.0
Introduction
2.1
Survey Scope
Pennington Choices Ltd was commissioned to carry out a refurbishment and demolition survey in accordance with HSG264, with the exception of MA surface treatment scores for selected bare materials. Refer to 1.1 for details. The purpose of this survey was to locate and describe, as far as reasonably practicable, all ACMs in the area where refurbishment work will take place. The survey included accessible areas within the scope of the survey only. The aim of the survey is to provide the client with information in order to be able to comply with the Control of Asbestos Regulations 2012. This survey report is not a management plan but can be used to assist in devising one. All efforts were made during the survey to identify and establish the presence (or absence) of asbestos based materials and their locations. However, asbestos may be concealed within the structural fabric of a building. This report should therefore only be seen as an overview of the current situation within the buildings requested for surveying.
2.2
Property Type
London School of Hygiene and tropical medicines
2.3
Recommendations
Recommendations have been provided on dealing with asbestos occurrences and are based on the Control of Asbestos Regulations 2012 and Approved Codes of Practice, Health and Safety at Work etc Act 1974, good management practices and known maintenance requirements.
2.4
Third Party Rights
This report is only for the use of the party to whom it is addressed and no responsibility is accepted to any other party for the whole or any parts of its contents and the Contracts (Rights of Third Parties) Act 1999 shall not apply. Neither the whole, nor a part of this report, or any reference thereto, may be included in any document or statement, nor published or reproduced in any way, without our prior approval in writing as to the form and context in which it will appear.
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 12 of 16
Our Reference: J094568
3.0
General Site Information
3.1
Areas included/excluded
specific areas.
Exclusions include any areas not detailed above.
A survey of the following HSG264 type(s) has been carried out as requested by the client: Refurbishment/Demolition Survey (MA only) to the ground floor areas, first floor office and computer room and corridor in the basement area. Surveys are carried out in accordance with our documented in-house procedure, which is accredited by UKAS as meeting the requirements of ISO17020.
3.2
Safety
The safety of the surveyors, staff, contractors and public has been of paramount importance during the course of the survey. All work has been carried out in accordance with the Health and Safety at Work etc Act 1974 and the Control of Asbestos Regulations 2012.
3.3
Areas of No or Limited Access
Due to the nature of the survey undertaken and for conditions found on site some parts of the building were not accessible by us or were only accessible on a limited basis, details of which are set out below:
General Areas No/Limited Access
Electrical components (fuse boxes, control panels, conduits, other): No Access
Within flues/chimneys: Not Applicable
Pipe gaskets/flue pipe seals/air duct seals/gaiters: Not Applicable
Under non asbestos insulations - pipe, eave: Not Applicable
Under upper roof covering: Not Applicable
Behind or through plaster skimmed material due to decorative damage: Limited Access
Within doors/firedoors: Not Applicable
Concealed spaces unknown to the surveyor: No Access
Known floor and/or wall voids e.g. wall cavities: Limited Access
Other: NA
Specific issues
Please refer to the Asbestos Register in Appendix 2 for specific access issues.
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 13 of 16
Our Reference: J094568
4.0
Conclusions and Actions
In this section, when removal is recommended, this should only be carried out by a licensed contractor under the supervision of a responsible agency in accordance with all current legislation, as detailed in Section 6.
It should be assumed that all electrical boxes contain asbestos components unless the equipment was inspected during the survey and none was found. If electrical work or other work that will disturb the electrical boxes were to be carried out, it would be prudent to isolate the supply and investigate the equipment once certified as safe. If asbestos is identified then it should be removed in accordance with current Health and Safety and Asbestos legislation.
Due to conditions found on site, certain areas could not be accessed. It should be assumed that all materials subsequently found in areas not accessible contain asbestos unless proven otherwise.
Where suspected asbestos materials form a duct cover, false ceiling, etc. or where these materials would require disturbing to gain access to an area, they have not been displaced, as any physical disturbance of these materials may have resulted in a release of airborne asbestos fibres which may pose a hazard to health.
If suspicious material is discovered during work or refurbishment then work should cease, and the suspicious material sampled and analysed for the presence of asbestos. If asbestos is identified then it should be removed in accordance with all current Health and Safety and Asbestos legislation.
It is recommended that all ACMs identified during this survey (refer to Asbestos Register - Appendix 2 - for details) be removed prior to work commencing if they are likely to be disturbed. It is recommended that removal be carried out by licensed contractors in the appropriate manner as dictated by current legislation and protocol.
Any ACMs that are to remain in situ should be made safe (encapsulated etc.) if necessary, labelled as containing asbestos and maintained as part of a management programme including regular inspections by a person competent to do so. This work should be carried out in accordance with the Control of Asbestos Regulations 2012.
Please also refer to the Asbestos Register in Appendix 2 for specific recommendations.
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 14 of 16
Our Reference: J094568
5.0
UKAS Accreditation
Pennington Choices Ltd is a UKAS (United Kingdom Accreditation Service) accredited laboratory. Strict controls on inspection bodies and laboratories are laid out and monitored by UKAS.
Testing
Pennington Choices Ltd meets the requirements of ISO 17025 for bulk sampling, bulk identification and air sampling and holds the UKAS accreditation number 0630 for testing.
Inspections
Pennington Choices Ltd is accredited as a Type ‘C’ inspection body meeting the requirements of ISO 17020 and holds the UKAS accreditation number 0179 for asbestos surveys.
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 15 of 16
Our Reference: J094568
6.0
Regulations
All work with asbestos containing materials is controlled under the Control of Asbestos Regulations 2012. The objective of these regulations is to minimise exposure to asbestos fibres.
Kier Construction (London) LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London
Pennington Choices Ltd - 3 February 2018 to 6 February 2018
Page 16 of 16
Our Reference: J094568
Appendix 1
Plans
The plans, while not to scale, provide you with an overview of the layout of the building and will help you to locate any asbestos containing materials that are referenced in the Asbestos Register (Appendix 2). Each room is provided a unique number. Each sample that we have taken also has a unique number. Both cross reference to the Asbestos Register. The plan is marked to show the areas or rooms where asbestos containing materials have been found. The ‘Key’ which follows this page provides further help in understanding the plans.
#
#
Appendix 2
Asbestos Register
The sheets that follow this page constitute the Asbestos Register. Each room or area referenced in the plan (Appendix 1) has a sheet. Where no suspected asbestos was found under the scope of this survey this is recorded, together with general notes detailing stand-out items noted in the area in question e.g. MMMF pipe lagging present. Where asbestos has been identified, is presumed or is referenced to a sample this is recorded with the material risk assessment and recommended actions.
#
#
Building: N/A Floor Level: Ground Room Name: (001) G40
Component: Bitumen adhesive residue to concrete ceiling above suspended plasterboard
Sample Reference Asbestos Type Material Surface Treatment Score
BH001939 (Sample 1)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/foam lined plasterboard/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 1 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (001) G40
Component: Grey floor tiles and bitumen adhesive to concrete floor within plasterboard riser to rear right hand side wall (painted yellow)
Sample Reference Asbestos Type Material Surface Treatment Score
BH001940 (Sample 2)
Chrysotile (1) Floor Tile + Bitumen Backing (1)
0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 <1m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/foam lined plasterboard/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 2 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (001) G40
Component: Bitumen adhesive residues to brick walls behind foam lined plasterboard
Sample Reference Asbestos Type Material Surface Treatment Score
BH001941 (Sample 3)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/foam lined plasterboard/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 3 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (001) G40
Component: Bitumen adhesive to concrete floor beneath screed/carpet tiles
Sample Reference Asbestos Type Material Surface Treatment Score
BH001942 (Sample 4)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 >50m² (3) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/foam lined plasterboard/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 4 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (002) G41
Component: Bitumen adhesive residue to concrete ceiling above suspended plasterboard
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001939 (Ref Sample 1)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/foam lined plasterboard/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 5 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (002) G41
Component: Bitumen adhesive residues to brick walls behind foam lined plasterboard
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001941 (Ref Sample 3)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/foam lined plasterboard/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 6 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (002) G41
Component: Bitumen adhesive to concrete floor beneath screed/carpet tiles
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001942 (Ref Sample 4)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 >70m² (3) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/foam lined plasterboard/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 7 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (003) G42
Component: Bitumen adhesive residue to plasterboard lined concrete ceiling above suspended plasterboard
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001939 (Ref Sample 1)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete lined with plasterboard above suspended plasterboard ceiling W - brick/foam lined plasterboard/ceramic tiled/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 8 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (003) G42
Component: Bitumen adhesive residues to brick walls behind foam lined plasterboard
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001941 (Ref Sample 3)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete lined with plasterboard above suspended plasterboard ceiling W - brick/foam lined plasterboard/ceramic tiled/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 9 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (003) G42
Component: Bitumen adhesive to concrete floor beneath carpet tiles/screed/ceramic tiles
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001942 (Ref Sample 4)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 40m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete lined with plasterboard above suspended plasterboard ceiling W - brick/foam lined plasterboard/ceramic tiled/plaster F - bitumen adhesive to concrete beneath screed/carpet tiles Metal framed skylights MMMF insulation to metal pipework and ventilation trunking visible from access points made in suspended plasterboard ceiling Accessed within low level wood boxing to concrete/steel frame No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 10 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (004) Corridor
Component: Bitumen adhesive to concrete beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
BH001943 (Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 25m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - pitched metal sheets above suspended plasterboard ceiling W - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum/screed Metal framed glazing Wood/glass access doors MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 11 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (005) Electrical Intake Room
Component: Boxing to steel column/lining sides of central beam
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001947 (Ref Sample 8)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - pitched metal sheets above suspended plasterboard ceiling W - brick/blockwork/foam lined plasterboard F - concrete Wood access doors - wood door header MMMF insulation to metal pipework and ventilation trunking No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 12 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (005) Electrical Intake Room
Component: High level boxing running along ceiling/wall to area (004)
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001947 (Ref Sample 8)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - pitched metal sheets above suspended plasterboard ceiling W - brick/blockwork/foam lined plasterboard F - concrete Wood access doors - wood door header MMMF insulation to metal pipework and ventilation trunking No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 13 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (005) Electrical Intake Room
Component: Bitumen adhesive residues to brick walls behind foam lined plasterboard
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001941 (Ref Sample 3)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - pitched metal sheets above suspended plasterboard ceiling W - brick/blockwork/foam lined plasterboard F - concrete Wood access doors - wood door header MMMF insulation to metal pipework and ventilation trunking No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 14 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (006) Student Room
Component: Bitumen adhesive to concrete beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001943 (Ref Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 20m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - bitumen adhesive to concrete beneath modern linoleum/screed Metal framed glazing Wood/glass access doors MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live Modern fitted kitchen
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 15 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (007) Student Room
Component: Bitumen adhesive to concrete beneath carpet/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001943 (Ref Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 25m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - bitumen adhesive to concrete beneath carpet tiles/screed Wood/glass access door Rubber stairnosing
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 16 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (008) Corridor
Component: Bitumen adhesive to concrete beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001943 (Ref Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 20m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum/screed Metal framed glazing Wood/glass access doors MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 17 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (008) Corridor
Component: Textured coating to concrete ceiling above suspended plasterboard ceiling
Sample Reference Asbestos Type Material Surface Treatment Score
BH001945 (Sample 6)
Chrysotile (1) Textured Coating (1) 1
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (4) 1 20m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum/screed Metal framed glazing Wood/glass access doors MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 18 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (009) Office
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - concrete beneath carpet tiles/screed Wood framed sash windows - wood sill Wood/glass access door MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 19 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (010) Office
Component: Bitumen adhesive to concrete beneath carpet/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001943 (Ref Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 10m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - bitumen adhesive to concrete beneath carpet tiles/screed Wood framed sash windows - wood sill Wood/glass access door MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 20 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (011) Landing
Component: Bitumen adhesive to concrete beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001943 (Ref Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 12m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum/screed Metal framed glazing Wood/glass access doors MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 21 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (012) Corridor
Component: Bitumen adhesive to concrete beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001943 (Ref Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 20m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete/plasterboard above suspended perforated metal sheets W - painted brick F - bitumen adhesive to concrete beneath modern linoleum/screed Metal framed glazing Wood/glass access doors MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live Accessed behind wood cladding/plasterboard to metal panel walls
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 22 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (013) Corridor
Component: Bitumen adhesive to concrete beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001943 (Ref Sample 5)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 12m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - plasterboard/plaster W - brick/plasterboard/plaster F - bitumen adhesive to concrete beneath modern linoleum/screed Wood/glass access doors No access above/behind plasterboard ceiling/walls - as instructed by client
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 23 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Basement 1 Room Name: (014) Computer Room
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - concrete/render F - screed to concrete beneath carpet tiles Wood/glass access door MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 24 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Basement 1 Room Name: (015) Corridor
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - plasterboard/plaster W - brick/block/plasterboard/plaster F - concrete beneath modern linoleum/screed Wood/glass access doors MMMF insulation to metal pipework and ventilation trunking visible from access points in suspended plasterboard ceiling No access within ventilation units or electrics - live
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 25 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (016) Main Warehouse
Component: Pitched corrugated roof sheets
Sample Reference Asbestos Type Material Surface Treatment Score
BH001951 (Sample 12)
Chrysotile (1) Cement (1) 1
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (4) 1 >150m² (3) 1
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - pitched corrugated sheets W - painted brick/blockwork F - concrete Steel columns/beams Metal framed glazing Metal rolling shutter Metal guttering trays Metal rainwater goods Sporadic perspex roof sheets Accessed area section off with wood hoarding
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 26 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (016) Main Warehouse
Component: Fascias to lower roof section of area (017) - (021)
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001947 (Ref Sample 8)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - pitched corrugated sheets W - painted brick/blockwork F - concrete Steel columns/beams Metal framed glazing Metal rolling shutter Metal guttering trays Metal rainwater goods Sporadic perspex roof sheets Accessed area section off with wood hoarding
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 27 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (016) Main Warehouse
Component: Door header panel to (017)
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001947 (Ref Sample 8)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - pitched corrugated sheets W - painted brick/blockwork F - concrete Steel columns/beams Metal framed glazing Metal rolling shutter Metal guttering trays Metal rainwater goods Sporadic perspex roof sheets Accessed area section off with wood hoarding
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 28 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (016) Main Warehouse
Component: Panels lining whole roof to area (017) - (021)
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001947 (Ref Sample 8)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - pitched corrugated sheets W - painted brick/blockwork F - concrete Steel columns/beams Metal framed glazing Metal rolling shutter Metal guttering trays Metal rainwater goods Sporadic perspex roof sheets Accessed area section off with wood hoarding
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 29 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (017) Entrance Lobby
Component: Bitumen adhesive to hardboard above suspended plasterboard ceiling
Sample Reference Asbestos Type Material Surface Treatment Score
BH001946 (Sample 7)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete Wood/glass access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 30 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (017) Entrance Lobby
Component: Door header panel above access door
Sample Reference Asbestos Type Material Surface Treatment Score
BH001947 (Sample 8)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete Wood/glass access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 31 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (017) Entrance Lobby
Component: Mastic to joints of high level ventilation trunking
Sample Reference Asbestos Type Material Surface Treatment Score
BH001948 (Sample 9)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete Wood/glass access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 32 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (017) Entrance Lobby
Component: Bitumen adhesive to concrete floor
Sample Reference Asbestos Type Material Surface Treatment Score
BH001949 (Sample 10)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 3 6m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete Wood/glass access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 33 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (018) Store
Component: Bitumen adhesive to hardboard above suspended plasterboard ceiling
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001946 (Ref Sample 7)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 34 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (018) Store
Component: Bitumen adhesive to concrete floor
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001949 (Ref Sample 10)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 3 3m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 35 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (019) Store
Component: Bitumen adhesive to hardboard above suspended plasterboard ceiling
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001946 (Ref Sample 7)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete beneath carpet tiles Wood access door - wood door header
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 36 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (019) Store
Component: Bitumen adhesive to concrete floor beneath carpet tiles
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001949 (Ref Sample 10)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 3 4m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete beneath carpet tiles Wood access door - wood door header
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 37 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (020) Lobby
Component: Bitumen adhesive to hardboard above suspended plasterboard ceiling
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001946 (Ref Sample 7)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum Wood access door - wood door header
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 38 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (020) Lobby
Component: Bitumen adhesive to concrete floor beneath modern linoleum
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001949 (Ref Sample 10)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 3 2m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum Wood access door - wood door header
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 39 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (021) WC
Component: Bitumen adhesive to hardboard above suspended plasterboard ceiling
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001946 (Ref Sample 7)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 40 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (021) WC
Component: Bitumen adhesive to concrete floor beneath modern linoleum
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001949 (Ref Sample 10)
Chrysotile (1) Bitumen (1) 0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 3 2m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - bitumen adhesive to hardboard above suspended plasterboard (MMMF insulation filling void) w - brick/plaster F - bitumen adhesive to concrete beneath modern linoleum Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 41 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (022) Room
Component: No Access
Sample Reference Asbestos Type Material Surface Treatment Score
Inaccessible (Presumed)
Presumed Asbestos
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- Further Inspection Required. -
Further Recommendations: None
General Notes: No access - as instructed by Kier
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 42 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (023) Store
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - painted concrete W - painted blockwork F - concrete beneath carpet tiles/hardboard Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 43 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (024) Store
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - painted concrete W - painted blockwork F - concrete Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 44 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (025) Store
Component: Bitumen adhesive to concrete beneath carpet tiles/modern linoleum
Sample Reference Asbestos Type Material Surface Treatment Score
BH001950 (Sample 11)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - painted concrete above modern suspended ceiling tiles W - painted block/brickwork F - bitumen adhesive to concrete beneath carpet tiles/modern linoleum Wood/glass access door Wood framed windows Electrical cables within wood boxing
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 45 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (026) WC
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - painted concrete W - painted brickwork/ceramic tiled F - concrete beneath quarry tiles Wood access door - glass door header panel Metal framed windows Plastic cisterns
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 46 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (027) Tank Room
Component: Corrugated roof sheets
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001951 (Ref Sample 12)
Chrysotile (1) Cement (1) 2
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Low (5) 1 6m² (1) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - corrugated roof sheets W - brickwork F - concrete Metal tank on brick base Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 47 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (027) Tank Room
Component: Felt lining brick base supporting tank
Sample Reference Asbestos Type Material Surface Treatment Score
BH001952 (Sample 13)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - corrugated roof sheets W - brickwork F - concrete Metal tank on brick base Wood access door
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 48 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: First Room Name: (028) Office
Component: Bitumen adhesive to concrete beneath carpet tiles/modern linoleum
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001950 (Ref Sample 11)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - wood above modern suspended ceiling tiles/plasterboard W - painted brickwork F - bitumen adhesive to concrete beneath carpet tiles/modern linoleum Wood/glass access door Wood framed windows - wood sills Modern electrics unit
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 49 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (029) External Area
Component: Pitched corrugated roof sheets to Main Warehouse
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001951 (Ref Sample 12)
Chrysotile (1) Cement (1) 1
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (4) 1 >150m² (3) 0
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: Brick built warehouse attached to brick built offices that have had recent refurbishments Warehouse: Perspex and metal windows Metal rolling shutter Pitched corrugated cement sheets to roof Main offices: Large brick built building clad with wood panel fixed to metal sheets Metal framed windows Metal rainwater goods No visible damp proof course to external brickwork 2x large spiral staircase constructed of steel and timber
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 50 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (029) External Area
Component: Corrugated roof sheets to area (027)
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001951 (Ref Sample 12)
Chrysotile (1) Cement (1) 2
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Low (5) 1 6m² (1) 0
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: Brick built warehouse attached to brick built offices that have had recent refurbishments Warehouse: Perspex and metal windows Metal rolling shutter Pitched corrugated cement sheets to roof Main offices: Large brick built building clad with wood panel fixed to metal sheets Metal framed windows Metal rainwater goods No visible damp proof course to external brickwork 2x large spiral staircase constructed of steel and timber
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 51 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (029) External Area
Component: Fascias to area (027)
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001947 (Ref Sample 8)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: Brick built warehouse attached to brick built offices that have had recent refurbishments Warehouse: Perspex and metal windows Metal rolling shutter Pitched corrugated cement sheets to roof Main offices: Large brick built building clad with wood panel fixed to metal sheets Metal framed windows Metal rainwater goods No visible damp proof course to external brickwork 2x large spiral staircase constructed of steel and timber
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 52 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: External Room Name: (029) External Area
Component: Bituminous felt to flat roof of area (000)
Sample Reference Asbestos Type Material Surface Treatment Score
BH001954 (Sample 14)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: Brick built warehouse attached to brick built offices that have had recent refurbishments Warehouse: Perspex and metal windows Metal rolling shutter Pitched corrugated cement sheets to roof Main offices: Large brick built building clad with wood panel fixed to metal sheets Metal framed windows Metal rainwater goods No visible damp proof course to external brickwork 2x large spiral staircase constructed of steel and timber
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 53 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: First Room Name: (030) Offices 145 -148
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - wooden pitched roof above suspended plasterboard ceiling W - brick/plasterboard/plaster F - hardboard beneath carpet tiles Wood/glass access doors Metal framed windows - wood sills Modern electrics Rubber stair nosing to steps Visible above suspended plasterboard ceiling - - Wooden pitched roof - Modern metal ventillation trunking with modern mastics - Modern electrics Accessed within plasterboard risers/boxing via access hatch - foam insulated pipework Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 54 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: First Room Name: (031) Lobby 149
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - pitched wooden roof above lath and plaster W - brick/plasterboard/chip paper F - hardboard to concrete Wood/glass access doors Wood steps
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 55 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: First Room Name: (032) Corridor 132
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - concrete beneath modern linoleum Wood/glass access doors Metal framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 56 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: First Room Name: (033) Female WC 139
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster/ceramic tiles F - concrete beneath ceramic tiles Wood access door Metal framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics Ceramic cisterns Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 57 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Second Room Name: (034) Corridor 232
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - concrete beneath modern linoleum Wood/glass access doors Metal framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics - MMMF insulation to pipework Accesed within wood/plasterboard riser - foam insulated pipework Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 58 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Second Room Name: (035) Male WC 238
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster/ceramic tiles F - concrete beneath ceramic tiles Wood access door Metal framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics Ceramic cisterns Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 59 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Third Room Name: (036) Corridor 320
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - concrete beneath modern linoleum Wood/glass access doors Metal framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics - MMMF insulation to pipework Accesed within wood/plasterboard riser - foam insulated pipework Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 60 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Third Room Name: (037) Female WC 333
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster/ceramic tiles F - concrete beneath ceramic tiles Wood access door Metal framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics Ceramic cisterns Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 61 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (038) Reception G10
Component: Bitumen adhesive to concrete floor beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
BH001996 (Sample 15)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - concrete beneath modern linoleum Wood/glass access doors Metal framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics - MMMF insulation to pipework Limited access to ceilings/walls/floor - due to area still being constantly occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 62 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (039) First Aid Room G11
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster/ceramic tiled F - concrete beneath ceramic tiles Wood/glass access doors Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics - MMMF insulation to pipework Limited access to ceilings/walls/floor - due to area still being occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 63 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (040) Office G12
Component: No suspected materials noted to be present in this area under scope of survey
Sample Reference Asbestos Type Material Surface Treatment Score
No suspect materials
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - brick/plasterboard/plaster F - thick screed beneath carpet tiles Wood/glass access doors Wood framed windows - wood sill Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics - MMMF insulation to pipework Limited access to ceilings/walls/floor - due to area still being constantly occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 64 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (041) Stairwell G15
Component: Bitumen adhesive to concrete floor beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001996 (Ref Sample 15)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - plasterboard to underside of ceiling W - brick/plasterboard/plaster F - bitumen adhesive to concrete beneath screed/modern linoleum Wood/glass access doors Metal framed windows - wood sill Metal staircase - rubber stair nosing Limited access to ceilings/walls/floor - due to area still being constantly occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 65 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (041) Stairwell G15
Component: Loose fill insulation behind decorative wood panels to external wall
Sample Reference Asbestos Type Material Surface Treatment Score
BH001997 (Sample 16)
No Asbestos Detected
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - plasterboard to underside of ceiling W - brick/plasterboard/plaster F - bitumen adhesive to concrete beneath screed/modern linoleum Wood/glass access doors Metal framed windows - wood sill Metal staircase - rubber stair nosing Limited access to ceilings/walls/floor - due to area still being constantly occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 66 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Ground Room Name: (042) Corridor G16
Component: Bitumen adhesive to concrete floor beneath modern linoleum/screed
Sample Reference Asbestos Type Material Surface Treatment Score
As BH001996 (Ref Sample 15)
No asbestos detected in visually consistent
material
Extent of damage Material Assessment* Accessibility Extent/amount Location
Recommendations
Who What When
- No further action required -
Further Recommendations: None
General Notes: C - concrete above suspended metal ceiling tiles W - brick/plasterboard/plaster F - bitumen adhesive to concrete beneath screed/modern linoleum Wood/glass access doors Accessed behind decorative wood panels to external wall - plasterboard/wiring behind Metal framed windows - wood sill Visible above suspended metal ceiling tiles - - Modern metal ventillation trunking with modern mastics - Modern electrics - MMMF insulation to pipework Limited access to ceilings/walls/floor - due to area still being constantly occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 67 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
Building: N/A Floor Level: Basement 1 Room Name: (043) Store LG14
Component: Beige floor tiles and bitumen adhesive to concrete floor beneath modern linoleum
Sample Reference Asbestos Type Material Surface Treatment Score
BH001998 (Sample 17)
Chrysotile (1) Floor Tile + Bitumen Backing (1)
0
Extent of damage Material Assessment* Accessibility Extent/amount Location
Low Damage (1) Very Low (3) 1 14m² (2) 2
Recommendations
Who What When
Licensed contractor Remove Prior to refurbishment if likely to be disturbed
Further Recommendations: None
General Notes: C - concrete above suspended plasterboard ceiling W - painted blockwork F - beige floor tiles and bitumen adhesive to concrete beneath modern linoleum Wood access door Visible above suspended plasterboard ceiling - - Modern metal ventillation trunking with modern mastics - Modern electrics - MMMF insulation to pipework Limited access to ceilings/walls/floor - due to area still being constantly occupied and personal belongings
Asbestos Register Site Address: LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London Ref No.
J094568 Date Of Issue 05/03/2018
Page 68 of 69
*Sample taken in the original survey. **Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HSG264.
All efforts were made during the survey to identify and establish the presence (or absence) of asbestos based materials and their locations within an unfamiliar building and accessible areas. However, asbestos may be concealed within the structural fabric of a building, which only major refurbishment or full demolition will bring to light and this is beyond the scope of this building survey. Therefore, PC cannot guarantee that all asbestos materials have been identified and survey results are definitive.
This register should therefore only be seen as an overview of the current situation within the areas surveyed. The survey was a refurbishment & demolition survey (HSG264). Further investigation of suspicious materials should be undertaken if discovered. All extents detailed within this report are approximations and removal contractors should not rely on these extents for costing purposes.
**Material Assessment (HSG264, 2012) Description refers to materials potential to release asbestos fibres - with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by HGS264.
Asbestos Type Chrysotile (1); Amphibole asbestos excluding crocidolite (2); Crocidolite content (3).
Extent of Damage (Good) None (0); (Low) Scratches, broken edges (1); (Medium) Significant breakage, exposed fibres (2); (High) High damage, visible debris (3).
Surface Treatment Composite materials, floor tiles, bitumen etc (0); Enclosed sprays/lagging, encapsulated AIB, encapsulated asbestos cement, encapsulated textured coating, encapsulated gaskets, encapsulated paper and encapsulated woven/textile (1); Unsealed AIB, encapsulated lagging/sprays, bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile (2); Unsealed lagging/sprays (3).
Priority assessment scores for the following items are included as a courtesy to the client and are not accredited by UKAS. The responsibility for carrying out full and complete priority assessments lies with the client. Refer to Algorithm table for explanations of scores.
Accessibility Usually inaccessible or unlikely to be disturbed (0); Occasionally likely to be disturbed (1); Easily disturbed (2); Routinely disturbed (3).
Location Outdoors (0); Large rooms or well ventilated areas (1); Rooms up to 100m2 (2); Confined spaces (3).
Extent/Amount Small amounts or items (eg strings, gaskets) (0); =10m2 or =10m pipe run (1); >10m2 to =50m2 or >10m to =50m pipe run (2); >50m2 or >50m pipe run (3)
Where visually consistent material is referenced to an analysed 'No Asbestos Found' sample, this is a visual assessment only. Therefore, further sampling must be requested if further confirmation is required.
This register is not complete without being accompanied by the full report. All written components must be read prior to making any assessments based upon the surveyors' findings. All positive incidents of asbestos are recommended to be labelled if to be left in place and not removed during refurbishment works. If it is not the Duty Holder’s policy to label ACMs then the ACMs should be managed according to the management plan which the Duty Holder has in place.
Asbestos Register Page 69 of 69
Reference information and disclaimer
**Material Assessment (HSG264, 2012) - Description refers to materials potential to release asbestos fibres – in accordance, with the exception of surface treatment scores for bare cement, bare textured coating, bare gaskets, bare paper and bare woven/textile which we score as 2 rather than 1 as suggested by
HSG264.
Appendix 3
Asbestos Analysis Report J094568
The pages in this appendix contain the laboratory analysis reports of any samples that were taken during the course of this survey. It is a requirement of HSG264 that this certificate is included in the report.
#
#
Location of Analysis Laboratory: Clan Works, Bromley, BR1 3QJ
Asbestos Analysis Report
Report No : J094568 Sample Batch 1-17
Client : Kier Construction (London) Client Ref: Email instruction to JN
Location : LSHTM TP1 & TP2 Project, 15-17 Tavistock Place, London, WC1H 9SH
Samples Taken : 3 February 2018 Report Issued: 13 February 2018
Sample No. Source Result Material (see Note(3))
Sample 1 Ground (001) G40 Bitumen adhesive residue to concrete ceiling above suspended plasterboard
No Asbestos Detected
Bitumen
Sample 2 Ground (001) G40 Grey floor tiles and bitumen adhesive to concrete floor within plasterboard riser to rear right hand side wall (painted yellow)
Chrysotile Floor Tile + Bitumen Backing (Chrysotile present in both floor tile and bitumen backing)
Sample 3 Ground (001) G40 Bitumen adhesive residues to brick walls behind foam lined plasterboard
No Asbestos Detected
Bitumen
Sample 4 Ground (001) G40 Bitumen adhesive to concrete floor beneath screed/carpet tiles
Chrysotile Bitumen
Sample 5 Ground (004) Corridor Bitumen adhesive to concrete beneath modern linoleum/screed
Chrysotile Bitumen
Sample 6 Ground (008) Corridor Textured coating to concrete ceiling above suspended plasterboard ceiling
Chrysotile Textured Coating
Sample 12 External (016) Main Warehouse Pitched corrugated roof sheets
Chrysotile Cement
Sample 7 External (017) Entrance Lobby Bitumen adhesive to hardboard above suspended plasterboard ceiling
No Asbestos Detected
Bitumen
Pennington Choices Ltd
Clan Works, 1A Howard Road, Bromley, Kent, BR1 3QJ Tel: 020 8290 5629 Fax: 020 8290 4443
Email: [email protected] Web: www.pennington.org.uk
J094568 Asbestos Analysis Report Template/Version 42/ 9 Aug 2016 Page 1 of 3
Sample No. Source Result Material (see Note(3))
Sample 8 External (017) Entrance Lobby Door header panel above access door
No Asbestos Detected
Board
Sample 9 External (017) Entrance Lobby Mastic to joints of high level ventilation trunking
No Asbestos Detected
Mastic
Sample 10 External (017) Entrance Lobby Bitumen adhesive to concrete floor
Chrysotile Bitumen
Sample 11 External (025) Store Bitumen adhesive to concrete beneath carpet tiles/modern linoleum
No Asbestos Detected
Bitumen
Sample 13 External (027) Tank Room Felt lining brick base supporting tank
No Asbestos Detected
Bitumen
Sample 14 External (029) External Area Bituminous felt to flat roof of area (000)
No Asbestos Detected
Bitumen
Sample 15 Ground (038) Reception G10 Bitumen adhesive to concrete floor beneath modern linoleum/screed
No Asbestos Detected
Bitumen
Sample 16 Ground (041) Stairwell G15 Loose fill insulation behind decorative wood panels to external wall
No Asbestos Detected
Non Insulation
Sample 17 Basement 1 (043) Store LG14 Beige floor tiles and bitumen adhesive to concrete floor beneath modern linoleum
Chrysotile Floor Tile + Bitumen Backing (Chrysotile present in both floor tile and bitumen backing)
Pennington Choices Ltd
Clan Works, 1A Howard Road, Bromley, Kent, BR1 3QJ Tel: 020 8290 5629 Fax: 020 8290 4443
Email: [email protected] Web: www.pennington.org.uk
J094568 Asbestos Analysis Report Template/Version 42/ 9 Aug 2016 Page 2 of 3
Test Method:
Polarised light microscopy; Dispersion staining, in accordance with HSG248
Note (1):
PC laboratory analysis of samples and sampling procedures are in compliance with ISO 17025 and our UKAS accreditation.
Note (2):
Where PC staff have not taken samples (indicated by "Samples Received" or "Samples Collected"), results given are based on information supplied by the client taking the samples. PC is not responsible for any errors/misinterpretations of analytical results due to inappropriate sampling strategies or techniques.
Note (3):
Observations and interpretations expressed (i.e. nature of fibres other than asbestos or description of material) are outside the scope of our UKAS accreditation.
Types of Asbestos
Amosite - Brown Asbestos
Chrysotile - White Asbestos
Crocidolite - Blue Asbestos
ANALYST:
Dorothy Dewan Mariana Camargo
Pennington Choices Ltd
Clan Works, 1A Howard Road, Bromley, Kent, BR1 3QJ Tel: 020 8290 5629 Fax: 020 8290 4443
Email: [email protected] Web: www.pennington.org.uk
J094568 Asbestos Analysis Report Template/Version 42/ 9 Aug 2016 Page 3 of 3
Appendix 4
Quality Audit
Prior to this report being issued it will have been reviewed by a number of people as part of our documented quality management systems. The following page confirms that this was undertaken and by whom.
#
#
Report Number J094568
LSHTM TP1 & TP2 Project 15-17 Tavistock Place
London WC1H 9SH
Report Author: Sam Clouter
Date: 5 March 2018
Report Reviewer: John James
Date: 7 March 2018
Lead Surveyor: Danny Gurnham
Date: 7 March 2018
This survey was carried out in accordance with our UKAS accreditation and ISO 17020.