Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral...
Transcript of Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral...
![Page 1: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/1.jpg)
1
FLORIDA
Loop Current Balanceand
Setting Electrical NeutralDC Machines – AC Method
Rick Scherer, PETechnical Training Advisor
June 11, 2015
![Page 2: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/2.jpg)
2
Loop Current Balance
•Why is it important?
Mechanical Reliability
Mechanical Torque Balance
Electrical Dynamic / TransientResponse
•What is an acceptable tolerance?
OEM’s Recommend <10%
•How do we correct loop imbalance?
Let’s Explore……
![Page 3: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/3.jpg)
3
Electrical-Mechanical Relationships
• Speed of DC Motor is proportional to:
Armature Voltage (Va)(CEMF)
• Speed of DC Motor is “inversely” to:
Shunt Field Current (1/If)
• Torque of DC Motor is proportional to:
Armature Current (Ia)
• Torque of DC Motor is proportional to:
Shunt Field Current (If)
![Page 4: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/4.jpg)
4
PrimeMover
Resistance = .01W
Ward Leonard LoopFundamental Construction
ACSynchronous
Motor
CEMF
EMF = K x if
Speed = K xCEMF
i f
![Page 5: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/5.jpg)
5
Typical 2 Loop Configuration
Loop 1
ArmatureCurrent
Flow
Loop 2
ArmatureCurrent
Flow
Each Motor and each Generatorrepresents a variable DC VoltageSource
![Page 6: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/6.jpg)
6
Equivalent Circuit
8 Variables
G1 G2
M1
M2
G3 G4
M3
M4
Loop 1 Loop 2
Balance motor shunt field flux (i.e. field amps)
How might we reduce the variables?
Electrical neutral influences motor CEMF performance
![Page 7: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/7.jpg)
7
Equivalent Circuit
G1 G2
M1
M2
G3 G4
M3
M4
Loop 1 Loop 2
How might we furtherreduce the variables?
4 Variables
Electrical neutral influencesgenerator EMF performance
![Page 8: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/8.jpg)
8
DrawingCompliments ofDCS
Let’s Explore aMethod to Set
Electrical Neutral
![Page 9: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/9.jpg)
9
What is Electrical Neutral ?
Of the following definitions, which BESTdescribes Electrical Neutral?
1. Point of Optimum Commutation / Film
2. Point of Zero Induced Voltage in Armature Coil
3. Point of Optimum Performance
Answer:
Point of Zero Induced Voltage in ArmatureCoil
![Page 10: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/10.jpg)
10
DC Motors:
–Typically DC Motors are set to PreciseElectrical Neutral
• This provided for balanced reversing performance
DC Generators:
–Typically, Intentionally set ¼ - ¾ CommutatorBar (Segment) Against Rotation
• DC Generators Operate one Direction of RotationOnly
• Boost commutating field strength resulting inimproved commutation
DC Motors – vs – DC Generators
![Page 11: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/11.jpg)
11
•PVN (Pencil Volt Neutral)
•DC “Kick” or “Flash” Method
•Bi-Directional Speed Matching
•Generators, Voltage Drop at Stall
•AC Null Method
•Brush Potential Method
•Tram Markings / Mechanical Method
•Cover the Spark Method ☺
•AC Curve Method
Various Methods of SettingElectrical Neutral
![Page 12: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/12.jpg)
12
The Question?
Considering all factors, whichmethod of setting the electricalneutral on a DC Machine is best foryour application?
Let us explore the AC Plot method,theory and safety……then youdecide!
![Page 13: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/13.jpg)
13
AC Plotting Method
•Safe – electrical exposure is 120 VAC viaGFCI
•Safe – no flash hazard while testing
•No moving parts
•Very accurate
•Repeatable / Dependable
•Easy to learn, easy to implement
•> 15 Minutes for experienced techniciansfollowing test set up
•Let’s explore this method……
![Page 14: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/14.jpg)
14
DC Machine Simplified Drawing
![Page 15: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/15.jpg)
15
Single Ø Transformer ModelDC Machine Equivalent Circuit
Transformer Primary:
Typical 6 pole DC Machine: 200 +/- turns / pole , approximately 1200 total turns
Transformer Secondary:
Each commutator bar represents a tap of a single turn secondary winding
Iron core
Secondary voltage: Vs = Vp * Ns/Np Vs = 120V * 1/1200 ~ 100mV
![Page 16: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/16.jpg)
16
ALL:
Electrical, Mechanical, Hydraulic and Stored
Energy sources must be properly disabled,
locked, blocked and tagged, per your company
policy…..
Lock / Tag / Try
• Let’s explore the testing procedure….
SAFETY - First and Always
![Page 17: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/17.jpg)
17
Step # 1
VERIFY and CORRECTas necessary to obtain
EqualizedCircumferentialSpacing (Span)
TOLERANCE:
1/32”
(0.8 mm)
Equal Circumferential Spacing
Symmetry / Symmetry / Symmetry
![Page 18: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/18.jpg)
18
Measuring CircumferentialSpacing “Span”
Tolerance 1/32” MaximumDifference between all Arms
Maintenance PracticesSetting Span in the Field
![Page 19: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/19.jpg)
19
Step # 2
VERIFY and CORRECTas necessary to obtain
proper
Brush Box Elevation
TOLERANCE:
.070” to .080”
(1.8 mm to 2.0mm)
Brush Holder Elevation
Symmetry / Symmetry / Symmetry
![Page 20: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/20.jpg)
20
Test Procedure Outline:
1. Determine the total number of commutator bars
2. Identify the total number of poles
3. Calculate the Span and Throw (see following example)
4. Number the commutator bars (see following illustrations)
5. Lift all the brushes to isolate the armature from thearmature circuit components
6. Apply a GFCI protected, 120 VAC - 1Ø (F1 to F4)
7. Measure and record at the commutator, theinduced AC voltage into the Armature
8. Plot the results and adjust brush yoke accordingly
Proceed Only after verifying Span and Brush Box Elevation, Subsequent Adjustments
![Page 21: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/21.jpg)
21
Convenient Location for which to apply
GFCI Protected 120 Vac
Photo:
Complements ofDCS
Don Pattersonoffers the Ghost atno additionalcharge!
![Page 22: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/22.jpg)
22
Span Calculation
1. Throw = Commutator Bars ÷ Number of Poles
2. Span = Throw + 1
Total number of commutator bars: 288
Total number of main field coils:6
Throw: (288 ÷ 6) 48
Span: 48 + 11 and 49
Practical Example:
![Page 23: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/23.jpg)
23
Numbering the Commutator Bars
21 43 5
12:00 Position Brush
![Page 24: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/24.jpg)
24
“As Found” Neutral Setting
21
“As Found” Position
12:00 Position Brush
543
![Page 25: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/25.jpg)
25
Data Acquisition Procedure
Test Results:
1-49 = .094V or 94mV2-50 = .050V or 50mV3-51 = .006V or 6mV4-52 = .038V or 38mV5-53 = .081V or 81mV
Commutator Bars = 288Main Shunt Field Poles = 6Throw = 48Span = 1 and 49
![Page 26: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/26.jpg)
26
Document:
A. Equipment I.D.
B. Machine I.D.
C. Date
D. Technician
Plot Step 1
![Page 27: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/27.jpg)
27
Plot Step 2
Document:
Actual measuredinducedvoltage
![Page 28: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/28.jpg)
28
Plot Step 3
Scaling:
Determine verticalscaling basedupon highestinduced voltage
![Page 29: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/29.jpg)
29
Plot Step 4
Data:
Place the first of fivepoints on theproperly scaledgraph
![Page 30: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/30.jpg)
30
Plot Step 5
Data:
Place the second offive points on theproperly scaledgraph
![Page 31: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/31.jpg)
31
Plot Step 6
Data:
Place the fourth andfifth points on theproperly scaledgraph
![Page 32: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/32.jpg)
32
Plot Step 7
Data:
Using a straightedge, draw a linethrough the fourdata points
![Page 33: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/33.jpg)
33
Plot Step 8
Quality Control:
The fifth data pointwill now fall directlyon the line to serveas quality assurancethe recorded data isvalid
![Page 34: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/34.jpg)
34
Plot Step 9
ElectricalNeutral:
Precise ElectricalNeutral is now definedas the point at whichthe drawn lineintersects the zeroinduced voltage axisNow it is necessary totransfer this graphicalrepresentation ontothe actual commutatorsurface
![Page 35: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/35.jpg)
35
Graphically
“As Found”
VS.
“Precise”
Or
“Hard”
Neutral
![Page 36: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/36.jpg)
36
“As Found” Neutral Setting
21
“As Found” Position
12:00 Position Brush
543
![Page 37: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/37.jpg)
37
“Desired” Neutral Setting
21
12:00 Position Brush
543
“Desired” Position
![Page 38: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/38.jpg)
38
“Final” Electrical Neutral
51 2 3 4
“Final” and “Precise”Electrical Neutral Setting
![Page 39: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/39.jpg)
39
What if….Throw is not a whole number ?
• A few DC Machines have armaturewindings that result in a throw that is not awhole number, i.e. not evenly divisible
• In this situation it is necessary to obtain twosets of data and subsequently plot two lines(see following Data Sheet)
– 1 plus throw less ½
– 1 plus throw plus ½
• Electrical neutral will be ½ the distancebetween the two parallel plotted lines
• Q/A, if plotted correctly, the two lines will beperfectly parallel to each other
![Page 40: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/40.jpg)
40
Data Sheet for
Multiple Data
Two Sets of Dataare Necessary:
The data sheet allowsfor 2 sets of data
![Page 41: Loop Current Balance - Mining Electrical FLORIDA Loop Current Balance and Setting Electrical Neutral DC Machines – AC Method Rick Scherer, PE Technical Training Advisor June 11,](https://reader034.fdocuments.us/reader034/viewer/2022051800/5acfe7287f8b9a1d328d998e/html5/thumbnails/41.jpg)
41
Conclusion…
• Extremely accurate, combined with Q/C
• Safe…eliminates PVN and the inherent danger ofworking on generator while rotating
• Serves both Generators and Motors
• Safe…energized with GFCI protected 120 Vac
• Eliminates brush seating as potential error
• Fast…performed with minimal down time
• Does not require un-coupling the motor
• Very effective procedure in correcting loop currentimbalances
The AC Plotting Method for Setting Electrical Neutral is: