Load Flow With Capacitor

13
Location: Engineer: Study Case: LF 6.0.0 Page: 1 SN: 12345678 Filename: domafinal Project: ETAP Contract: Date: 07-04-2012 Revision: Base Config.: Normal Electrical Transient Analyzer Program Load Flow Analysis Number of Buses: Swing V-Control Load Total Number of Branches: XFMR2 Reactor Line/Cable Impedance Tie PD XFMR3 Total 1 0 23 24 0 0 0 23 0 0 23 Loading Category (1): Design Generation Category (1): Design Load Diversity Factor: None Maximum No. of Iteration: 99 System Frequency: 50 Hz Unit System: Metric Project Filename: domafinal Output Filename: C:\ETAP 600\domafinal\Untitled.lfr Precision of Solution: 0.0001000 Method of Solution: Newton-Raphson Method

Transcript of Load Flow With Capacitor

Page 1: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 1

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Electrical Transient Analyzer Program

Load Flow Analysis

Number of Buses:

Swing V-Control Load Total

Number of Branches:

XFMR2 Reactor Line/Cable Impedance Tie PDXFMR3 Total

1 0 23 24

0 0 0 23 0 0 23

Loading Category (1): Design

Generation Category (1): Design

Load Diversity Factor: None

Maximum No. of Iteration: 99

System Frequency: 50 Hz

Unit System: Metric

Project Filename: domafinal

Output Filename: C:\ETAP 600\domafinal\Untitled.lfr

Precision of Solution: 0.0001000

Method of Solution: Newton-Raphson Method

Page 2: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 2

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Adjustments

Transformer Impedance:

Reactor Impedance:

Adjustments

Apply

/Global

Individual

PercentTolerance

Overload Heater Resistance:

Transmission Line Length:

Cable Length:

Temperature Correction

Transmission Line Resistance:

Cable Resistance:

Apply

Adjustments

Individual

/Global Degree C

Individual

Individual

Individual

Individual

Yes

Yes

No

No

No

Yes

Yes

Page 3: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 3

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Bus Input Data

Sub-sys

GenericConstant IConstant ZConstant kVAInitial VoltageBus

MvarMWMvar MWMvar MWMvarMWAng. % Mag.kVID

Load

20.000Bus1 1 100.0 0.0

0.020 0.015 20.000Bus2 1 100.0 0.0

0.000 0.427 0.281 -0.100 20.000Bus3 1 100.0 0.0

0.215 0.083 20.000Bus4 1 100.0 0.0

0.000 0.640 0.464 -0.300 20.000Bus5 1 100.0 0.0

0.520 0.390 20.000Bus6 1 100.0 0.0

0.000 0.252 0.156 -0.200 20.000Bus7 1 100.0 0.0

0.000 0.893 0.554 -0.200 20.000Bus8 1 100.0 0.0

0.264 0.097 20.000Bus9 1 100.0 0.0

0.000 0.277 0.234 -0.200 20.000Bus10 1 100.0 0.0

0.157 0.074 20.000Bus11 1 100.0 0.0

20.000Bus12 1 100.0 0.0

0.323 0.201 20.000Bus13 1 100.0 0.0

0.156 0.055 20.000Bus14 1 100.0 0.0

0.085 0.053 20.000Bus15 1 100.0 0.0

0.000 0.322 0.233 -0.200 20.000Bus16 1 100.0 0.0

0.085 0.053 20.000Bus17 1 100.0 0.0

0.000 0.618 0.415 -0.300 20.000Bus18 1 100.0 0.0

20.000Bus19 1 100.0 0.0

0.370 0.229 20.000Bus20 1 100.0 0.0

0.123 0.045 20.000Bus21 1 100.0 0.0

0.277 0.086 20.000Bus22 1 100.0 0.0

0.000 0.933 0.613 -0.300 20.000Bus23 1 100.0 0.0

0.000 0.454 0.337 -0.300 20.000Bus24 1 100.0 0.0

-2.100 4.668 0.000 Total Number of Buses: 24 7.411 0.000 0.000 0.000 0.000

ID kV

Generation Bus

Sub-sysType

Voltage

% Mag. Angle MW Mvar Max Min

Generation Mvar Limits

% PF

Bus1 1 20.000 Swing 100.0 0.0

0.000 0.000

Page 4: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 4

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Line/Cable Input Data

ID Library Size T (°C)

Line/Cable

Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)

Adj. (m) #/Phase% Tol.

Length

YR X

Line1 3250.0 1 0.192970 0.144000 75 0.0

Line2 300.0 1 0.176034 0.236121 75 0.0

Line3 5.0 1 0.283300 0.380000 75 0.0

Line4 208.0 1 0.283300 0.120000 75 0.0

Line5 1000.0 1 0.283300 0.380000 75 0.0

Line6 500.0 1 0.283300 0.120000 75 0.0

Line7 600.0 1 0.283300 0.120000 75 0.0

Line8 450.0 1 0.459610 0.235560 75 0.0

Line9 400.0 1 0.680000 0.380000 75 0.0

Line10 1000.0 1 0.680000 0.380000 75 0.0

Line11 500.0 1 0.680000 0.380000 75 0.0

Line12 400.0 1 0.680000 0.380000 75 0.0

Line13 800.0 1 0.680000 0.380000 75 0.0

Line14 200.0 1 0.680000 0.380000 75 0.0

Line15 700.0 1 0.422532 0.236121 75 0.0

Line16 100.0 1 0.680000 0.380000 75 0.0

Line17 90.0 1 0.680000 0.380000 75 0.0

Line18 500.0 1 0.680000 0.380000 75 0.0

Line19 800.0 1 0.680000 0.380000 75 0.0

Line20 950.0 1 0.680000 0.380000 75 0.0

Line21 250.0 1 0.680000 0.380000 75 0.0

Line22 302.0 1 0.680000 0.380000 75 0.0

Line23 500.0 1 0.680000 0.380000 75 0.0

Line / Cable resistances are listed at the specified temperatures.

Page 5: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 5

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Branch Connections

ID From Bus To Bus R X ZType

CKT/Branch % Impedance, Pos. Seq., 100 MVA BaseConnected Bus ID

Y

Line1 Bus1 15.68 11.70 19.56Bus2Line

Line2 Bus2 1.32 1.77 2.21Bus3Line

Line3 Bus3 0.04 0.05 0.06Bus4Line

Line4 Bus4 1.47 0.62 1.60Bus5Line

Line5 Bus5 7.08 9.50 11.85Bus6Line

Line6 Bus6 3.54 1.50 3.85Bus7Line

Line7 Bus7 4.25 1.80 4.62Bus8Line

Line8 Bus8 5.17 2.65 5.81Bus9Line

Line9 Bus9 6.80 3.80 7.79Bus10Line

Line10 Bus9 17.00 9.50 19.47Bus11Line

Line11 Bus11 8.50 4.75 9.74Bus12Line

Line12 Bus12 6.80 3.80 7.79Bus13Line

Line13 Bus14 13.60 7.60 15.58Bus12Line

Line14 Bus15 3.40 1.90 3.89Bus14Line

Line15 Bus16 7.39 4.13 8.47Bus15Line

Line16 Bus17 1.70 0.95 1.95Bus16Line

Line17 Bus18 1.53 0.86 1.75Bus17Line

Line18 Bus19 8.50 4.75 9.74Bus18Line

Line19 Bus19 13.60 7.60 15.58Bus20Line

Line20 Bus21 16.15 9.03 18.50Bus20Line

Line21 Bus22 4.25 2.38 4.87Bus21Line

Line22 Bus19 5.13 2.87 5.88Bus23Line

Line23 Bus23 8.50 4.75 9.74Bus24Line

Page 6: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 6

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

LOAD FLOW REPORT

Bus

ID kV

Voltage

Ang.% Mag.

Generation

MW Mvar

Load

MW Mvar

Load Flow

MW Mvar AmpID % PF

XFMR

% Tap

Bus1* 20.000 0.0 100.000 2.955 7.704 Bus2 7.704 2.955 238.2 93.40 0

Bus2 20.000 -0.3 98.447 0.015 0.020 Bus1 -7.597 -2.875 238.2 93.50 0

Bus3 7.577 2.860 237.5 93.6

Bus3 20.000 -0.3 98.294 0.184 0.427 Bus2 -7.568 -2.848 237.5 93.60 0

Bus4 7.141 2.664 223.8 93.7

Bus4 20.000 -0.3 98.291 0.083 0.215 Bus3 -7.141 -2.663 223.8 93.70 0

Bus5 6.926 2.580 217.1 93.7

Bus5 20.000 -0.3 98.170 0.175 0.640 Bus4 -6.917 -2.577 217.1 93.70 0

Bus6 6.277 2.402 197.6 93.4

Bus6 20.000 -0.6 97.486 0.390 0.520 Bus5 -6.244 -2.357 197.6 93.60 0

Bus7 5.724 1.967 179.2 94.6

Bus7 20.000 -0.6 97.248 -0.033 0.252 Bus6 -5.710 -1.962 179.2 94.60 0

Bus8 5.458 1.995 172.5 93.9

Bus8 20.000 -0.6 96.972 0.366 0.893 Bus7 -5.443 -1.988 172.5 93.90 0

Bus9 4.550 1.622 143.8 94.2

Bus9 20.000 -0.6 96.685 0.097 0.264 Bus8 -4.537 -1.616 143.8 94.20 0

Bus10 0.277 0.047 8.4 98.6

Bus11 3.996 1.472 127.2 93.8

Bus10 20.000 -0.6 96.664 0.047 0.277 Bus9 -0.277 -0.047 8.4 98.60 0

Bus11 20.000 -0.7 95.838 0.074 0.157 Bus9 -3.963 -1.453 127.2 93.90 0

Bus12 3.806 1.379 121.9 94.0

Bus12 20.000 -0.7 95.432 Bus11 -3.791 -1.371 121.9 94.00 0 0 0

Bus13 0.323 0.201 11.5 84.9

Bus14 3.468 1.170 110.7 94.8

Bus13 20.000 -0.7 95.401 0.201 0.323 Bus12 -0.323 -0.201 11.5 84.90 0

Bus14 20.000 -0.8 94.845 0.055 0.156 Bus12 -3.448 -1.158 110.7 94.80 0

Bus15 3.292 1.103 105.7 94.8

Bus15 20.000 -0.8 94.705 0.053 0.085 Bus14 -3.288 -1.101 105.7 94.80 0

Bus16 3.203 1.048 102.7 95.0

Bus16 20.000 -0.8 94.409 0.055 0.322 Bus15 -3.193 -1.043 102.7 95.10 0

Bus17 2.871 0.988 92.8 94.6

Bus17 20.000 -0.9 94.348 0.053 0.085 Bus16 -2.869 -0.987 92.8 94.60 0

Bus18 2.784 0.934 89.9 94.8

Bus18 20.000 -0.9 94.294 0.148 0.618 Bus17 -2.783 -0.933 89.9 94.80 0

Bus19 2.165 0.785 70.5 94.0

Bus19 20.000 -0.9 94.059 Bus18 -2.160 -0.782 70.5 94.00 0 0 0

Page 7: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 7

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Bus

ID kV

Voltage

Ang.% Mag.

Generation

MW Mvar

Load

MW Mvar

Load Flow

MW Mvar AmpID % PF

XFMR

% Tap

Bus20 0.771 0.361 26.1 90.6

Bus23 1.388 0.421 44.5 95.7

Bus20 20.000 -0.9 93.919 0.229 0.370 Bus19 -0.770 -0.360 26.1 90.60 0

Bus21 0.400 0.131 12.9 95.0

Bus21 20.000 -0.9 93.837 0.045 0.123 Bus20 -0.400 -0.131 12.9 95.00 0

Bus22 0.277 0.086 8.9 95.5

Bus22 20.000 -0.9 93.822 0.086 0.277 Bus21 -0.277 -0.086 8.9 95.50 0

Bus23 20.000 -0.9 93.971 0.348 0.933 Bus19 -1.387 -0.421 44.5 95.70 0

Bus24 0.454 0.072 14.1 98.8

Bus24 20.000 -0.9 93.926 0.072 0.454 Bus23 -0.454 -0.072 14.1 98.80 0

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)

# Indicates a bus with a load mismatch of more than 0.1 MVA

Page 8: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 8

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Bus Loading Summary Report

ID

Bus

kV

Directly Connected Load

MW Mvar MVA % PF AmpRated Amp LoadingMW Mvar MW Mvar

Constant kVA Constant Z Constant IPercent

Generic

MW Mvar

Total Bus Load

Bus1 20.000 8.251 238.2 93.4 0 0 0 0 0 0 0 0

Bus2 20.000 8.123 238.2 93.5 0.020 0.015 0 0 0 0 0 0

Bus3 20.000 8.121 238.5 93.2 0.427 0.281 0 -0.097 0 0 0 0

Bus4 20.000 7.621 223.8 93.7 0.215 0.083 0 0 0 0 0 0

Bus5 20.000 7.487 220.2 92.4 0.640 0.464 0 -0.289 0 0 0 0

Bus6 20.000 6.674 197.6 93.6 0.520 0.390 0 0 0 0 0 0

Bus7 20.000 6.102 181.1 93.6 0.252 0.156 0 -0.189 0 0 0 0

Bus8 20.000 5.862 174.5 92.9 0.893 0.554 0 -0.188 0 0 0 0

Bus9 20.000 4.817 143.8 94.2 0.264 0.097 0 0 0 0 0 0

Bus10 20.000 0.363 10.8 76.4 0.277 0.234 0 -0.187 0 0 0 0

Bus11 20.000 4.221 127.2 93.9 0.157 0.074 0 0 0 0 0 0

Bus12 20.000 4.031 121.9 94.0 0 0 0 0 0 0 0 0

Bus13 20.000 0.380 11.5 84.9 0.323 0.201 0 0 0 0 0 0

Bus14 20.000 3.638 110.7 94.8 0.156 0.055 0 0 0 0 0 0

Bus15 20.000 3.467 105.7 94.8 0.085 0.053 0 0 0 0 0 0

Bus16 20.000 3.419 104.5 93.4 0.322 0.233 0 -0.178 0 0 0 0

Bus17 20.000 3.034 92.8 94.6 0.085 0.053 0 0 0 0 0 0

Bus18 20.000 3.031 92.8 91.8 0.618 0.415 0 -0.267 0 0 0 0

Bus19 20.000 2.297 70.5 94.0 0 0 0 0 0 0 0 0

Bus20 20.000 0.850 26.1 90.6 0.370 0.229 0 0 0 0 0 0

Bus21 20.000 0.421 12.9 95.0 0.123 0.045 0 0 0 0 0 0

Bus22 20.000 0.290 8.9 95.5 0.277 0.086 0 0 0 0 0 0

Bus23 20.000 1.547 47.5 89.7 0.933 0.613 0 -0.265 0 0 0 0

Bus24 20.000 0.565 17.4 80.3 0.454 0.337 0 -0.265 0 0 0 0

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).

# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).

Page 9: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 9

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Branch Loading Summary Report

ID Type

Loading

Amp %

Capability

(MVA) MVA %

Loading (output)

CKT / Branch Cable & ReactorTransformer

Loading (input)

%MVA

Ampacity

(Amp)

* Indicates a branch with operating load exceeding the branch capability.

Page 10: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 10

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Branch Losses Summary Report

ID MW Mvar MW Mvar kW kvar From To

CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage% Drop

Vd

in Vmag

7.704 2.955 -7.597 -2.875 106.7 79.6 100.0 98.4 1.55Line1

7.577 2.860 -7.568 -2.848 8.9 12.0 98.4 98.3 0.15Line2

7.141 2.664 -7.141 -2.663 0.2 0.3 98.3 98.3 0.00Line3

6.926 2.580 -6.917 -2.577 8.3 3.5 98.3 98.2 0.12Line4

6.277 2.402 -6.244 -2.357 33.2 44.5 98.2 97.5 0.68Line5

5.724 1.967 -5.710 -1.962 13.7 5.8 97.5 97.2 0.24Line6

5.458 1.995 -5.443 -1.988 15.2 6.4 97.2 97.0 0.28Line7

4.550 1.622 -4.537 -1.616 12.8 6.6 97.0 96.7 0.29Line8

0.277 0.047 -0.277 -0.047 0.1 0.0 96.7 96.7 0.02Line9

3.996 1.472 -3.963 -1.453 33.0 18.4 96.7 95.8 0.85Line10

3.806 1.379 -3.791 -1.371 15.2 8.5 95.8 95.4 0.41Line11

0.323 0.201 -0.323 -0.201 0.1 0.1 95.4 95.4 0.03Line12

3.468 1.170 -3.448 -1.158 20.0 11.2 95.4 94.8 0.59Line13

3.292 1.103 -3.288 -1.101 4.6 2.5 94.8 94.7 0.14Line14

3.203 1.048 -3.193 -1.043 9.4 5.2 94.7 94.4 0.30Line15

2.871 0.988 -2.869 -0.987 1.8 1.0 94.4 94.3 0.06Line16

2.784 0.934 -2.783 -0.933 1.5 0.8 94.3 94.3 0.05Line17

2.165 0.785 -2.160 -0.782 5.1 2.8 94.3 94.1 0.23Line18

0.771 0.361 -0.770 -0.360 1.1 0.6 94.1 93.9 0.14Line19

1.388 0.421 -1.387 -0.421 1.2 0.7 94.1 94.0 0.09Line22

0.400 0.131 -0.400 -0.131 0.3 0.2 93.9 93.8 0.08Line20

0.277 0.086 -0.277 -0.086 0.0 0.0 93.8 93.8 0.01Line21

0.454 0.072 -0.454 -0.072 0.2 0.1 94.0 93.9 0.04Line23

292.5 211.0

Page 11: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 11

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Alert Summary Report

Cable 95.0 100.0

Bus

MarginalCritical

95.0 100.0

Loading

% Alert Settings

95.0 100.0

95.0 100.0

95.0 100.0

Line

Transformer

Reactor

Panel

95.0 100.0

95.0 98.0

102.0 105.0

95.0 100.0

95.0 100.0

95.0 100.0

100.0

Generator Excitation

Bus Voltage

UnderExcited (Q Min.)

OverExcited (Q Max.)

UnderVoltage

OverVoltage

Protective Device

Generator

Critical Report

Device ID Type Rating/LimitCondition Unit Operating % Operating Phase Type

20.000 kV 18.969 94.8 3-PhaseUnder VoltageBus14 Bus

Bus15 20.000 kV 18.941 94.7 3-PhaseUnder VoltageBus

Bus16 20.000 kV 18.882 94.4 3-PhaseUnder VoltageBus

Bus17 20.000 kV 18.870 94.3 3-PhaseUnder VoltageBus

Bus18 20.000 kV 18.859 94.3 3-PhaseUnder VoltageBus

Bus19 20.000 kV 18.812 94.1 3-PhaseUnder VoltageBus

Bus20 20.000 kV 18.784 93.9 3-PhaseUnder VoltageBus

Bus21 20.000 kV 18.767 93.8 3-PhaseUnder VoltageBus

Bus22 20.000 kV 18.764 93.8 3-PhaseUnder VoltageBus

Bus23 20.000 kV 18.794 94.0 3-PhaseUnder VoltageBus

Bus24 20.000 kV 18.785 93.9 3-PhaseUnder VoltageBus

Marginal Report

Device ID Type Rating/LimitCondition Unit Operating % Operating Phase Type

20.000 kV 19.333 96.7 3-PhaseUnder VoltageBus10 Bus

Page 12: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 12

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

Marginal Report

Device ID Type Rating/LimitCondition Unit Operating % Operating Phase Type

20.000 kV 19.168 95.8 3-PhaseUnder VoltageBus11 Bus

Bus12 20.000 kV 19.086 95.4 3-PhaseUnder VoltageBus

Bus13 20.000 kV 19.080 95.4 3-PhaseUnder VoltageBus

Bus6 20.000 kV 19.497 97.5 3-PhaseUnder VoltageBus

Bus7 20.000 kV 19.450 97.2 3-PhaseUnder VoltageBus

Bus8 20.000 kV 19.394 97.0 3-PhaseUnder VoltageBus

Bus9 20.000 kV 19.337 96.7 3-PhaseUnder VoltageBus

Page 13: Load Flow With Capacitor

Location:

Engineer:Study Case: LF

6.0.0

Page: 13

SN: 12345678

Filename: domafinal

Project: ETAP

Contract:

Date: 07-04-2012

Revision: Base

Config.: Normal

0.000 0.000 0.000

0.000 0.000 0.000

Lagging 0.00 1.924

Total Generic Load:

Total Constant I Load:

0.000 0.000

0.211 0.293

Number of Iterations: 3

System Mismatch:

Apparent Losses:

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

Lagging 84.61 8.759

Lagging

Lagging

-1.924 0.000

4.668 7.411

93.37 8.251 2.955 7.704

0.000 0.000 0.000

93.37 8.251 2.955 7.704

% PFMVAMvarMW

Total Static Load:

Total Motor Load:

Total Demand:

Source (Non-Swing Buses):

Source (Swing Buses):