Line ProtectionRoy Moxley – Siemens USA
siemens.com/digitalgridUnrestricted © Siemens AG 2017
![Page 2: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/2.jpg)
What is a Railroad’s Biggest Asset ?
• Rolling Stock
• Share-holders
• Relationships
• Shipping Contracts
• Employees (Engineers)
• Tracks and Right of Way
![Page 3: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/3.jpg)
What is a Railroad’s Biggest Asset ?
• Rolling Stock
• Share-holders
• Relationships
• Shipping Contracts
• Employees (Engineers)
• Tracks and Right of Way
![Page 4: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/4.jpg)
Transmission Lines are the Power System’s Largest Asset
![Page 5: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/5.jpg)
Exposed to Weather
Self-Sustaining Arc
Clear Quickly to Avoid Permanent Damage
![Page 6: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/6.jpg)
How Do We Detect and Isolate Faults on Transmission Lines ?
• Overcurrent
• Distance
• Differential
• Travelling Wave (?)
![Page 7: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/7.jpg)
Overcurrent I>PU
1000 A
Advantages:•Simple•Reliable•Easy to Set
![Page 8: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/8.jpg)
Overcurrent
900 A
Advantages:•Simple•Reliable•Easy to Set
Disadvantages:•Possible Overtripping•Non-Directional•Depends on Source Connected
![Page 9: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/9.jpg)
Overcurrent
900 A
Advantages:•Simple•Reliable•Easy to Set
Disadvantages:•Possible Overtripping•Non-Directional•Depends on Source
Solutions:•Add Communications•Add Directional Polarizing•Change to Distance Protection
![Page 10: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/10.jpg)
Distance IZ - V
3 Ω
Advantages:•Not Dependent on Source Current•Fixed Reach•Inherently Directional
![Page 11: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/11.jpg)
Distance
3 Ω
Disadvantages:•Requires Potential•Limited Resistance Coverage•Impacted by Load Current and Power Swings•Reach is Not Perfect
![Page 12: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/12.jpg)
Distance
3 Ω
Solutions:
• Monitor Loss of Potential• Use Reactance Element to Increase Resistance Coverage (limited)•Apply Power Swing Block / Trip and Load Cutout•Add Communications
![Page 13: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/13.jpg)
Differential Iin ≠ Iout
Advantages:• Sensitive• Not Influenced by Load or Power Swings• Provides Unit Protection, Doesn’t Over Reach
Iin Iout
![Page 14: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/14.jpg)
Differential
Disadvantages:• 100% Communication Dependent• CT Saturation Must be Accounted For• No Inherent Backup
Iin Iout
![Page 15: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/15.jpg)
Differential
Solutions:• Monitor Communications• Detect and Account for CT Saturation• Provide Backup With No Communications or on Different Channel
Iin Iout
![Page 16: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/16.jpg)
Traveling Wave
Advantages:• Sensitive• Minimal Settings• Fast• Precise Fault Location
![Page 17: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/17.jpg)
Traveling Wave
Disadvantages:• 100% Dependent on Communications• 100% Dependent on Clocks• Difficult to Test• No Inherent Backup• Checkered Past
Solutions:
Yet to Determine
![Page 18: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/18.jpg)
Every System Has Strengths and Weaknesses
![Page 19: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/19.jpg)
Communications is King
Overcomes Weakness
Enhances Strengths
![Page 20: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/20.jpg)
Two Basic Communication Schemes
Permissive:Permits a Trip Under Proper Conditions
I See a Fault I See a Fault too
I See a Fault I don’t Not see a Fault
Blocking:Prevents a Trip on External Fault
![Page 21: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/21.jpg)
Permissive
I See a Fault I See a Fault too
![Page 22: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/22.jpg)
Permissive
I See a Fault
?
What If the Remote End Doesn’t See the Fault ?What if the Signal Doesn’t get Through ?
![Page 23: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/23.jpg)
BlockingI See a Fault
![Page 24: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/24.jpg)
BlockingI See a Fault
What Happens if Block Signal is Late?
What Happens if Overreaching Zone sees past Blocking Zone?
![Page 25: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/25.jpg)
Hybrid SchemeI See a Fault
Weak InfeedI See No Fault
![Page 26: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/26.jpg)
Power Systems are Almost Never Simple
CA
DB
Line 1
Line 2
Which Breaker Would Trip First?
What Happens to the Fault Currents Then?
![Page 27: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/27.jpg)
Power Systems are Almost Never Simple
CA
DB
Line 1
Line 2
Changed from forward to reverse Changed from reverse to forward
Timing Becomes Everything !
![Page 28: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/28.jpg)
Three (or More) Terminals Save Money
BA
C
Blocking or Permissive ?
![Page 29: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/29.jpg)
Sensitivity
On Short Lines Ground Resistance Can Be Higher than Line Impedence
But What Can Happen if we Just Increase Resistive Reach?
18 Ω
3 Ω
![Page 30: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/30.jpg)
Load Flow and Sensitivity
Load Trajectory
![Page 31: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/31.jpg)
For Sensitivity; Ground Overcurrent or Differential
18 Ω
3 Ω
DiffI
ResI
trip
area
restraint
area
1 2 3
N
iiII
0Diff
N
iiII
0Res
![Page 32: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/32.jpg)
Differential Relays Have to Accommodate CT saturation
relay measures a distorted current signal (red curve)
relay calculates the fundamental frequency component (blue curve)
deviation between both curves (green area) is a criteria for signal distortion
relay determines restrained current depending this signal deviation
![Page 33: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/33.jpg)
Restraining on Errors
AI
AI
BI
BI IRe
IImeach I is the summation of:Ii = ICT-Err.+ ISignal-Err.+ISync-Err.
DiffI
BI
AI
AI BII
Res_minRes III
min_Re sI Trip if differential current exceeds sum of measurement errors added by safety margin IRes_min
![Page 34: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/34.jpg)
Protection / Communication topology
I2I1 R2R1
R5
I5
R6
I6
R3
I3
Standard application for two terminal line: Two terminal line with redundant communication channel Three terminal line with communication chain
topology
R4
I4
For terminal line - communication ring topology – transformer in the protected area
Six terminal line – ring topology
![Page 35: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/35.jpg)
Special Conditions - Transformers in Zone
Wind Farm
Inrush ? 2nd Harmonic Restraint
Ratio and Angle Correction for differential
Reach for Distance Relay
Will the relay see through the transformer for ground faults?
![Page 36: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/36.jpg)
Special Conditions – Tapped Loads and Infeed
Tapped Loads
2Ω 3Ω
Distance Without Infeed =
Distance With Infeed =
10,000 A
10,000 A
![Page 37: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/37.jpg)
Special Conditions – Tapped Loads and Infeed
Tapped Loads
2Ω 3Ω
Distance Without Infeed =
Distance With Infeed =
10,000 A
10,000 A
5Ω
8Ω
![Page 38: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/38.jpg)
Special Conditions Combined
Wind Farm
Tapped Loads
Major Industrials
Photo VoltaicDifferential – Multi-terminalDistance – Blocking SchemeDistance (no-Comms) – Sequential Tripping
![Page 39: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/39.jpg)
Relay 1
Relay 6
Relay 2
Relay 5
Relay 3
Relay 4
Information sent to all Relays by Transmitting “Partial Summation”
Addressed Data Sent Until All Terminals Have All the Data
I1
I5
I4
I3
I2
I6
I2 +I3+I4+I5+I6
I2 +I1
Hot Standby
I6
I5 +I6
I4 +I5+I6
I3+I4 +I5+I6
I1I3+I2 +I1
I4+I3+I2 +I1
I5+I4+I3+I2 +I1
![Page 40: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/40.jpg)
Relay 1
Relay 6
Relay 2
Relay 5
Relay 3
Relay 4
Set Reach to Inside Line With Maximum Infeed – But What About Faults Beyond That ?
![Page 41: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/41.jpg)
Relay 1
Relay 6
Relay 2
Relay 5
Relay 3
Relay 4
Sequential Tripping Clears Strongest Source First – Best Stability Response
Note: Shape shows reach, not characteristic of the relay
![Page 42: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/42.jpg)
Phu My
Industrial
Area
New Plant 720 MW total from Three Units
Real-World Application
![Page 43: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/43.jpg)
Things Don’t Always End Up How You Expect !!
Who Me ?
![Page 44: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/44.jpg)
Initial Plans Were Pretty Standard500 kV Station
![Page 45: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/45.jpg)
GT 1 GT 2 ST 3
Everything Wasn’t Ready On Time –Changes Connections
220 kV Station
450 MVA
500 / 220 kV
450 MVA
500 / 220 kV
![Page 46: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/46.jpg)
Initial Communications Layout
![Page 47: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/47.jpg)
GT 1 GT 2 ST 3
As Installed Communications Layout
![Page 48: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/48.jpg)
It’s OK
![Page 49: Line Protection - na.eventscloud.com · Protection / Communication topology I1 I2 R1 R2 R5 I5 R6 I6 R3 I3 Standard application for two terminal line:Two terminal line with redundant](https://reader033.fdocuments.us/reader033/viewer/2022042023/5e7b079fda82da69726e11c2/html5/thumbnails/49.jpg)