Latest Developments in Foundation Fieldbus Safety Instrumented Functions(FF-
SIF) SIF)
October 25, 2009
Hamad S. Balhareth Saudi Aramco
Outline
� FF-SIF History and Background.
� Why FF-SIF?
� Existing ESD Architecture.
� Future FF-SIF Architecture.
© 1999 – 2007 Fieldbus Foundation2
� Future FF-SIF Architecture.
� FF-SIF Reliability.
� FF-SIF Project at Saudi Aramco Facility.
� What Will We Measure?
� Questions…
History & Background
� FF BOD approved FF-SIF Specification Development Project – Oct. 2002.
� FF-SIF Spec’s developed in cooperation with End-users, Control System Manufacturers, and Safety Experts.
© 1999 – 2007 Fieldbus Foundation3
Safety Experts.
� TUV granted protocol type approval – End of 2005.
� FF-SIF Spec’s final release – 2009.
� End-user demo’s and Rollout Team Suppliers
SIF Rollout Team Suppliers
Logic Solver
DO
D I
Manual TripLevel
SIF
HIMAHoneywellInvensys - TriconexYokogawaEmerson
ABBE+H
Discrete I/O
Logic SolverEngineering Workstation
Asset Management BPCS
Others
© 1999 – 2007 Fieldbus Foundation4
TripLevel
FlowValve
Pres
Temp
LCP*
H1BIFFIEmersonMetsoMasoneilanTopWorxWestlock/Tyco
E+HEmersonHoneywellInvensysMagnetrolSmarYokogawa
Cooper Crouse-HindsMoore IndustriesMTLP+F
* Local Control Panel
Demonstration SitesShell Global Solutions – AmsterdamSaudi Aramco - DhahranChevron – Richmond, CABP – Gelsenkirchen, Germany
OthersFieldbus DiagnosticsSoftingTÜV
• Device Self-Diagnostics
• Identify dangerous failures in real-time
• Provide valve partial stroke
Improved Safety Improved Operability
• Trip on demand only
• New/improved device self diagnostics
Why Why FFFF--SIFSIF??Why Why FFFF--SIFSIF??
© 1999 – 2007 Fieldbus Foundation6
and full stroke testing
• Reduce burden of manual proof testing
Reduced Cost
diagnostics
• Reduce safety system nuisance trips
• Multi-drop architecture
• Installation flexibility
• Asset management tools
Opex
Existing Existing ESDESD ArchitectureArchitecture
Operation Engineering
Sensors, Logic Solver, and Final elements make up each ESD loop.
1. Today, sensors and valves are hardwired with no continuous two-way communications…no direct way to see diagnostics within ESD logic solver.
2. Data has to be mapped from ESD to DCS (OPC, Modbus)
3. Different tools for ESD than
© 1999 – 2007 Fieldbus Foundation7
Logic Solver
3. Different tools for ESD than DCS.
4. Life-cycle cost is $$$
Diagnostics require 3rd partysoftware
Future FFFuture FF--SIFSIF ArchitectureArchitecture
Operation Engineering Asset Management
Future architecture will be a hybrid solution consisting of both conventional and FF-SIF I/O to a Safety Logic Solver/Host.
Diagnostics
© 1999 – 2007 Fieldbus Foundation8
Self Testing
Logic Solver
Flexible Wiring
Reduced ESD I/O
FF communications will make benefits available today with regulatory control systems possible in the future for safety applications.
Diagnosticsavailable to ESD
FF-SIF Project at Saudi Aramco Facility
� Trial location - Juaimyah Gas Plant
� ESD Logic Solver – Trident (FF compliant).
� ESD Valves – Metso & Ledeen/Cameron
� Valve Accessories – Mestso VG9000F and Emerson DVC6000f (with their LCPs).
© 1999 – 2007 Fieldbus Foundation11
DVC6000f (with their LCPs).
� Permissive to Open Valve – Rosemount FF Dp.
� Hardwired DO from Old Triconex to Trident.
What will we measure?What will we measure?
Operability Valve Self-Diagnostics at the LCP and SLS
Communications error detection
User defined valve action on loss of communications
© 1999 – 2007 Fieldbus Foundation12
User defined valve action on loss of communications
Trip on ESD Demand only “Stay Put“ option
Improved Functional Testing? Use of differential pressure measurement during PST
Full Stroke test results captured during unplanned trip