    MiCOM C264 LBUS

    Configuration

    PCLPCLPCLPCL

    PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2

    CS&P Support TeamCS&P Support TeamCS&P Support TeamCS&P Support Team

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    2/18

    Schneider Electric 2- CS&P – C264 LBUS Configuration – E01

    • Content

    LBUS Direct Implementation

    Use of Library

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    3/18

    Schneider Electric 3- CS&P – C264 LBUS Configuration – E01

    • Content

    LBUS Direct Implementation

    Use of Library

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    4/18

    Schneider Electric 4- CS&P – C264 LBUS Configuration – E01

    • Add / Configure a LBUS (1)1) LBUS can be added at MiCOM C264 Level => Protocol Oriented

    Number of retries :number of time C264 will try to poll IED

    Synchronization cycle :periodic synchro. frames 

    2) LBUS attributes (example given with T103, cf. C264 AP chapter)

    Acknowledgement time-out :IED response time-out

    Downgraded cycle :when IED not responding, periodic retry 

    Inter frame

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    5/18

    Schneider Electric 5- CS&P – C264 LBUS Configuration – E01

    • Add / Configure a LBUS (2)3) Connect LBUS to communication port

    4) Configure C264 communication

    Communication parametersNote that COM3 and COM4 should have sametransmission speed 

    For COM3 and COM4 => Tx carrier management set to Switched 

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    6/18

    Schneider Electric 6- CS&P – C264 LBUS Configuration – E01

    • Add / Configure an IED (1)1) IED can be added at LBUS Level

    IED @ on LBUS

    2) IED attributes (example given with T103, cf. C264 AP chapter)

    Automatic disturbance available for SMT +local name for COMTRADE file display in

    viewing tool (WaveWin, …)N/A for DNP3 

    No space in the name of the directory

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    7/18

    Schneider Electric 7- CS&P – C264 LBUS Configuration – E01

    • Add / Configure an IED (2)3) IED Should be connected to a Acq Profile

    IED main protective function codehere T103 FTYPE = 160 (OC) 

    4) Acq Profile attributes (example given with T103, cf. C264 AP chapter)4.1) General Tab

    1) Add the IED Acq Profile under LBUS 2) Complete relation “has for acq profile” 

    between IED and acq profile 

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    8/18

    Schneider Electric 8- CS&P – C264 LBUS Configuration – E01

    • Add / Configure an IED (3)

    GI period :- 0 => GI at connection only - advised = 3600s (1h) 

    4) Acq Profile attributes (example given with T103, cf. C264 AP chapter)4.2) Acquisition Tab

    Nominal values per setting group

    MV reduction coefficient :- 1.2 or 2.4 (cf. IED documentation) 

    - MV = red_coeff x transmitted val x nominal val.

    5) Under Acq Profile => disturbance channels

    AI channel : Channel number as per IED setting 

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    9/18

    Schneider Electric 9- CS&P – C264 LBUS Configuration – E01

    • Add / Configure IED Mapping (1)1) Add DP (DataPoints) addresses

    IED Mapping :set of SPS, DPS, MPS, MV, SPC, DPC, …

    managed by IED (cf. IED documentation) 

    To add a DP address :

    1) select kind of DP Mapping 2) Through Objects Entry Window, add an address 

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    10/18

    Schneider Electric 10- CS&P – C264 LBUS Configuration – E01

    • Add / Configure IED Mapping (2)

    2.2) DPS address

    SPS address :as per IED documentation, here ASDU, FTYP

    and INF (as per IEC-60870-5-103 standardpublic or IED private) 

    DPS address :as per IED documentation, here ASDU, FTYP

    and INF (as per IED private) 

    Contact = relevant status

    2) Configure DP addresses (example given with T103)2.1) SPS address

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    11/18

    Schneider Electric 11- CS&P – C264 LBUS Configuration – E01

    • Add / Configure IED Mapping (3)

    2.4) MV address

    SPC address :as per IED documentation, here ASDU, FTYP

    and INF (as per IEC-60870-5-103 standardpublic or IED private) 

    MV address :as per IED documentation, here ASDU, FTYP,

    INF and index=rank in ASDU (as per IEC-60870- 5-103 standard public or IED private) 

    DE/SBO regarding LBUS protocol

    2) Configure DP addresses (example given with T103)2.3) SPC address

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    12/18

    Schneider Electric 12- CS&P – C264 LBUS Configuration – E01

    • Add / Configure IED Mapping (4)3) Link DP with the relevant address (example given with T103)

    => Relation “has for IED address” 

    Under datapoint :DP link with relevant address on the IED 

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    13/18

    Schneider Electric 13- CS&P – C264 LBUS Configuration – E01

    • Miscellaneous (1)1) IED System information

    IED SPS Com :

    Gives connection status between C264 and IED(animated at PACiS OI Level) 

    IED SPS Synchro :Gives IED synchronization status 

    + IED RDRE Ready :SPS indicates when IED disturbance file is ready at C264 level 

    Note : “ext IEC Mapping” added by “SBUS automatic addressing”,

    but not in template 

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    14/18

    Schneider Electric 14- CS&P – C264 LBUS Configuration – E01

    • Miscellaneous (2)2) Modbus LBUS

    Standard attributes :

    same as T103 (nb of retries, response timeout,…) 

    Synchronization :None/AREVA (for AREVA Modbus) 

    Modbus IED acq. Profile :definition of Modbus type (MiCOM S20 = AREVA Modbus) 

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    15/18

    Schneider Electric 15- CS&P – C264 LBUS Configuration – E01

    • Miscellaneous (3)3) Reminder

    Limits

    up to 4 communication links (LBUS+TBUS serial or ethernet) 

    up to 4 LBUS 

    up to 2 TBUS 

    Connections

    BIU port 1 => RS232/RS485 

    BIU port 2 => RS232/RS485/RS422 

    CPU port 3 => RS232 

    CPU port 4 => RS232 

    Jumpers on BIU board

    ECU201 => RS485/RS422ECU200 => Fiber Optics

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    16/18

    Schneider Electric 16- CS&P – C264 LBUS Configuration – E01

    • Content

    LBUS Direct Implementation

    Use of Library

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    17/18

    Schneider Electric 17- CS&P – C264 LBUS Configuration – E01

    • Why using a template?1) Direct implementation :=> configure IED general info=> add mapping (DP addresses)=> add DP and link

    Repeat for each IED and then test resulting configuration

    => JOB INTENSIVE

    2) Template instantiations :=> DP and links already done=> only configure IED name and @=> repeatable

    => all DP already tested OK => IED integration

    => SAVE TIME

  • 8/20/2019 L2 V4 08 C264 LBUS Configuration E 01

    18/18

    Schneider Electric 18- CS&P – C264 LBUS Configuration – E01

    • List of integrated IED and relevant

    templates1) Integrated IED :=> PACiS version + IED version=> integration report

    => relevant template

    2) List of integrated IED :=> LN database “Products and System Info”