MiCOM C264 LBUS
Configuration
PCLPCLPCLPCL
PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2
CS&P Support TeamCS&P Support TeamCS&P Support TeamCS&P Support Team
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
2/18
Schneider Electric 2- CS&P – C264 LBUS Configuration – E01
• Content
LBUS Direct Implementation
Use of Library
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
3/18
Schneider Electric 3- CS&P – C264 LBUS Configuration – E01
• Content
LBUS Direct Implementation
Use of Library
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
4/18
Schneider Electric 4- CS&P – C264 LBUS Configuration – E01
• Add / Configure a LBUS (1)1) LBUS can be added at MiCOM C264 Level => Protocol Oriented
Number of retries :number of time C264 will try to poll IED
Synchronization cycle :periodic synchro. frames
2) LBUS attributes (example given with T103, cf. C264 AP chapter)
Acknowledgement time-out :IED response time-out
Downgraded cycle :when IED not responding, periodic retry
Inter frame
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
5/18
Schneider Electric 5- CS&P – C264 LBUS Configuration – E01
• Add / Configure a LBUS (2)3) Connect LBUS to communication port
4) Configure C264 communication
Communication parametersNote that COM3 and COM4 should have sametransmission speed
For COM3 and COM4 => Tx carrier management set to Switched
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
6/18
Schneider Electric 6- CS&P – C264 LBUS Configuration – E01
• Add / Configure an IED (1)1) IED can be added at LBUS Level
IED @ on LBUS
2) IED attributes (example given with T103, cf. C264 AP chapter)
Automatic disturbance available for SMT +local name for COMTRADE file display in
viewing tool (WaveWin, …)N/A for DNP3
No space in the name of the directory
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
7/18
Schneider Electric 7- CS&P – C264 LBUS Configuration – E01
• Add / Configure an IED (2)3) IED Should be connected to a Acq Profile
IED main protective function codehere T103 FTYPE = 160 (OC)
4) Acq Profile attributes (example given with T103, cf. C264 AP chapter)4.1) General Tab
1) Add the IED Acq Profile under LBUS 2) Complete relation “has for acq profile”
between IED and acq profile
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
8/18
Schneider Electric 8- CS&P – C264 LBUS Configuration – E01
• Add / Configure an IED (3)
GI period :- 0 => GI at connection only - advised = 3600s (1h)
4) Acq Profile attributes (example given with T103, cf. C264 AP chapter)4.2) Acquisition Tab
Nominal values per setting group
MV reduction coefficient :- 1.2 or 2.4 (cf. IED documentation)
- MV = red_coeff x transmitted val x nominal val.
5) Under Acq Profile => disturbance channels
AI channel : Channel number as per IED setting
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
9/18
Schneider Electric 9- CS&P – C264 LBUS Configuration – E01
• Add / Configure IED Mapping (1)1) Add DP (DataPoints) addresses
IED Mapping :set of SPS, DPS, MPS, MV, SPC, DPC, …
managed by IED (cf. IED documentation)
To add a DP address :
1) select kind of DP Mapping 2) Through Objects Entry Window, add an address
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
10/18
Schneider Electric 10- CS&P – C264 LBUS Configuration – E01
• Add / Configure IED Mapping (2)
2.2) DPS address
SPS address :as per IED documentation, here ASDU, FTYP
and INF (as per IEC-60870-5-103 standardpublic or IED private)
DPS address :as per IED documentation, here ASDU, FTYP
and INF (as per IED private)
Contact = relevant status
2) Configure DP addresses (example given with T103)2.1) SPS address
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
11/18
Schneider Electric 11- CS&P – C264 LBUS Configuration – E01
• Add / Configure IED Mapping (3)
2.4) MV address
SPC address :as per IED documentation, here ASDU, FTYP
and INF (as per IEC-60870-5-103 standardpublic or IED private)
MV address :as per IED documentation, here ASDU, FTYP,
INF and index=rank in ASDU (as per IEC-60870- 5-103 standard public or IED private)
DE/SBO regarding LBUS protocol
2) Configure DP addresses (example given with T103)2.3) SPC address
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
12/18
Schneider Electric 12- CS&P – C264 LBUS Configuration – E01
• Add / Configure IED Mapping (4)3) Link DP with the relevant address (example given with T103)
=> Relation “has for IED address”
Under datapoint :DP link with relevant address on the IED
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
13/18
Schneider Electric 13- CS&P – C264 LBUS Configuration – E01
• Miscellaneous (1)1) IED System information
IED SPS Com :
Gives connection status between C264 and IED(animated at PACiS OI Level)
IED SPS Synchro :Gives IED synchronization status
+ IED RDRE Ready :SPS indicates when IED disturbance file is ready at C264 level
Note : “ext IEC Mapping” added by “SBUS automatic addressing”,
but not in template
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
14/18
Schneider Electric 14- CS&P – C264 LBUS Configuration – E01
• Miscellaneous (2)2) Modbus LBUS
Standard attributes :
same as T103 (nb of retries, response timeout,…)
Synchronization :None/AREVA (for AREVA Modbus)
Modbus IED acq. Profile :definition of Modbus type (MiCOM S20 = AREVA Modbus)
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
15/18
Schneider Electric 15- CS&P – C264 LBUS Configuration – E01
• Miscellaneous (3)3) Reminder
Limits
up to 4 communication links (LBUS+TBUS serial or ethernet)
up to 4 LBUS
up to 2 TBUS
Connections
BIU port 1 => RS232/RS485
BIU port 2 => RS232/RS485/RS422
CPU port 3 => RS232
CPU port 4 => RS232
Jumpers on BIU board
ECU201 => RS485/RS422ECU200 => Fiber Optics
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
16/18
Schneider Electric 16- CS&P – C264 LBUS Configuration – E01
• Content
LBUS Direct Implementation
Use of Library
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
17/18
Schneider Electric 17- CS&P – C264 LBUS Configuration – E01
• Why using a template?1) Direct implementation :=> configure IED general info=> add mapping (DP addresses)=> add DP and link
Repeat for each IED and then test resulting configuration
=> JOB INTENSIVE
2) Template instantiations :=> DP and links already done=> only configure IED name and @=> repeatable
=> all DP already tested OK => IED integration
=> SAVE TIME
-
8/20/2019 L2 V4 08 C264 LBUS Configuration E 01
18/18
Schneider Electric 18- CS&P – C264 LBUS Configuration – E01
• List of integrated IED and relevant
templates1) Integrated IED :=> PACiS version + IED version=> integration report
=> relevant template
2) List of integrated IED :=> LN database “Products and System Info”