    SRI LANKA TELECOM

    TTEECCHHNNIICCAALL

    SSPPEECCIIFFIICCAATTIIOONNSS

    Surge Protection Devices (SPD)

    with Enclosure

  • 7/27/2019 L~0742~2013_[2] Specification

    2/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 1 of 1

    1. Requirement Introduction

    Surge Protection Device (SPD) connected in the mains power supply, needed to protect the

    electrical and electronic equipment, should be able to withstand maximum of 100 kA per mode

    (10/350sec).As per IEC 62305-1, LPL 1 (Lightning Protection Level) maximum expectedlightning current is 200 kA. As explained in IEC 62305,100 kA will be dissipated in earth and

    the balance 100 kA will reach the electrical supply lines. Power Line SPDs are to be connected at

    the mains incoming panel and in addition Distribution Boards which are more than 15 meters

    away from the incoming panel. DBs which is feeding power to critical and sophisticatedelectronic equipment. SPDs must be installed ignoring the cable distance. Suitable SPDs also tobe used in all Telecommunication, Signaling, automation and instrumentation equipment

    according to the Zonal concept explained in IEC 62305 for a perfect protection of complete

    electronic installations. All SPDs should be tested and ensure performance requirements

    according to IEC 61643

    2 Scope

  • 7/27/2019 L~0742~2013_[2] Specification

    3/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 2 of 1

    3.1.5. Offered equipment shall be capable of operating and delivering the expected

    performances without degrading the specified performances under the

    environmental conditions mentioned above.

    4. Technical requirement

    4.1. Mechanical Construction

    4.1.1. The entire surge carrying connections shall be of bolted connections.

    4.1.2. The mechanical Dimensions & weight shall be specified in schedule of

    requirement.4.1.3. Powder coating shall be applied for the Enclosure.

    4.1.4. Enclosure shall be design so that input power cable and output power cable

    separate with considerable distance to avoided surge interference to the output.

    4.1.5. Plastic Cable glands (Polyamide) shall be provided with the enclosure to fix the

    input and output cable. The class of the gland should be IP 67

    4 2 Ele t i l S e ifi ti

  • 7/27/2019 L~0742~2013_[2] Specification

    4/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 3 of 1

    5. Design Characteristics

    5.1. Option I5.1.1. The design characteristics of the power line protector shall be fully complied &

    tested for / with relevant international standards and specifications which is IEC

    61643 for providing required protection to sensitive telecommunication

    equipment.

    5.1.2. The offered protector shall be a modular design.

    5.1.3. The Surge protective device shall protect the system for both Common Mode and

    Transverse mode Surges, transients coming from Commercial Power lines.Protection modes shall be clearly specified.

    5.1.3.1. Line Neutral : Encapsulated/Non-exhausting Spark Gap

    5.1.3.2. Neutral Ground : Encapsulated/Non-exhausting Spark Gap

    5.1.4. Protector shall Type 1 (Class B ) protector which can be used between LPZ 0 and

    LPZ 1 (LPZ-Lightning Protection Zone) specified in international standard IEC

    62305-4

    5 1 5 Th it f th T 1(Cl B) SPD h ll b

  • 7/27/2019 L~0742~2013_[2] Specification

    5/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 4 of 1

    5.2. Option II

    5.2.1. The design characteristics of the power line protector shall be fully complied &

    tested for / with relevant international standards and specifications which is IEC61643 for providing required protection to sensitive telecommunication

    equipment.

    5.2.2. The offered protector shall be a modular design

    5.2.3. The Surge protective device shall protect the system for both Common mode and

    Transverse mode Surges, transients coming from Commercial Power lines.

    Protection modes shall be clearly specified.

    5.2.3.1. Line Neutral : MOV with built in thermal fuse5.2.3.2. Neutral Ground : Encapsulated/Non-exhausting Spark Gap

    5.2.4. Protector shall Type1+2 (Class B+C ) protector which can be used between LPZ 0

    (Lightning Protection Zone) and LPZ 2 specified in international standard IEC

    62305-4

    5.2.5. The capacity of the Type 1 + 2 (Class B + C) SPD shall be,

    5.2.5.1. Impulse current (Iimp) between Line to Neutral shall be 7 kA at 10/350 s

    i l

  • 7/27/2019 L~0742~2013_[2] Specification

    6/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 5 of 1

    5.2.11. Provisions shall be made for extension of alarm condition mentioned on clause

    5.2.9 to a distant location via potential free contact.

    5.3. Option III

    5.3.1. The design characteristics of the power line protector shall be fully complied &

    tested for / with relevant international standards and specifications which is IEC

    61643 for providing required protection to sensitive telecommunication

    equipment.

    5.3.2. The offered protector shall be a modular design

    5.3.3. The Surge protective device shall protect the system for both Common Mode andTransverse mode Surges, transients coming from Commercial Power lines.

    Protection modes shall be clearly specified.

    5.3.3.1. Line Neutral : MOV with built in thermal fuse

    5.3.3.2. Neutral Ground : Encapsulated/Non-exhausting Spark Gap

    5.3.4. Protector shall Type 2 (Class C ) protector which can be used between LPZ 1

    (Lightning Protection Zone) and LPZ 2 specified in international standard IEC

    62305 4

  • 7/27/2019 L~0742~2013_[2] Specification

    7/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 6 of 1

    5.3.10. The offered protector shall not induce fire hazard either in an event of diverting

    any power line surges or in an event of sustaining over voltage.

    5.3.11. Provisions shall be made for extension of alarm condition mentioned on clause5.3.9 to a distant location via potential free contact.

    6. Standards

    Offered manufacture or (and) product shall complied to the following standards

    6.1. ISO 9001-2008 & ISO 14001 - 2009

    6.2. UL listed

    6.3. IEC 62305 & 61643EN

    7. Installation Materials

    The installation materials needed for installation of the protective device shall be supplied

    with the protective device.

    8. Spare parts

    8 1 S li h ll t th l f ll t f f i t f t l t t

  • 7/27/2019 L~0742~2013_[2] Specification

    8/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 7 of 1

    10.3. One set of each above literature (comprehensive technical hand book) should be

    provided with the bidding documents, for the evaluation purpose of the Technical

    Evaluation Committee.

    11. Training

    11.1. Supplier shall arrange the local training for technical officers of SLT from foreign or

    local qualified trainer.

    11.2. Supplier shall provide the details of the resource person for such training along with

    the bids.

    11.3. The training program shall include11.3.1. IEC 62305

    11.3.2. Physics of lightening

    11.3.3. Characteristics of protectors and parameters

    11.3.4. Protection of telecommunication systems against lightening

    11.3.5. EMC: how these effects on systems and possible ways of avoiding damages

    11.3.6. Characteristics of offered arresters theoretical data sheets

    11.3.7. Correct installation and maintenance methods11 3 8 E thi & I t f th d h i l thi

  • 7/27/2019 L~0742~2013_[2] Specification

    9/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 8 of 1

    Technical Description

    Complied(C)/

    Not complied(NC) Remarks

    1 Requirement Introduction

    2 Scope

    2.1 This specification covers for Type I, II & III (Class B, C

    & D) Surge Protection Devices (SPD). Bidders shall quote

    for the tender accordingly for the given specifications /

    options only.2.2 Whole unit shall be design as one unit within single metal

    / Self-extinguishing high quality Polycarbonate enclosure

    and shall be able to mount to wall without any

    modification to the enclosure.

    3 Environmental & Operating Conditions

    3.1 The equipment shall be constructed in such a manner to

    t ti f t il i t i l diti t ith t d

  • 7/27/2019 L~0742~2013_[2] Specification

    10/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 9 of 1

    Technical Description

    Complied(C)/

    Not complied

    (NC)

    Remarks

    4.1.4 Enclosure shall be design so that input power cable and

    output power cable separate with considerable distance to

    avoided surge interference to the output.

    4.1.5 Plastic Cable glands (Polyamide) shall be provided with

    the enclosure to fix the input and output cable. The class

    of the gland should be IP 67

    4.2 Electrical Specification4.2.1 All component of the panel shall be compatible to the

    following characteristics of the main supply.

    4.2.1.1 Nominal Voltage: 400V (line to line) 20.0%; 3, 4

    wire. TT System

    4.2.1.2 Nominal Voltage: 230V (line to Neutral)

    4.2.1.3 Frequency: 50Hz 2 Hz.

    4 2 1 4 E i ti di t ib ti t i TT t h

  • 7/27/2019 L~0742~2013_[2] Specification

    11/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 10 of 1

    Technical Description

    Complied(C)/

    Not complied

    (NC)

    Remarks

    be fully complied & tested for / with relevant international

    standards and specifications which is IEC 61643 for

    providing required protection to sensitive

    telecommunication equipment.

    5.1.2 The offered protector shall be a modular design.

    5.1.3 The Surge protective device shall protect the system for

    both Common Mode and Transverse mode Surges,transients coming from Commercial Power lines.

    Protection modes shall be clearly specified.

    5.1.3.1 Line Neutral :Encapsulated/Non-exhausting Spark Gap

    5.1.3.2 Neutral Ground :Encapsulated/Non-exhausting Spark

    Gap

    5.1.4 Protector shall Type 1 (Class B ) protector which can be

    d b t LPZ 0 d LPZ 1 (LPZ Li ht i

  • 7/27/2019 L~0742~2013_[2] Specification

    12/21

  • 7/27/2019 L~0742~2013_[2] Specification

    13/21

  • 7/27/2019 L~0742~2013_[2] Specification

    14/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 13 of 1

    Technical Description

    Complied(C)/

    Not complied

    (NC)

    Remarks

    5.3.3.2 Neutral Ground : Encapsulated/Non-exhausting Spark

    Gap

    5.3.4 Protector shall Type 2 (Class C ) protector which can be

    used between LPZ 1 (Lightning Protection Zone) and LPZ

    2 specified in international standard IEC 62305-4

    5.3.5 The capacity of the Type 2 (Class C) SPD shall be,

    5.3.5.1 Nominal current (In) between Line to Neutral shall be 20kA at 8/20 s

    5.3.5.2 Maximum discharge current (Imax)between Line to Neutral

    shall be 40 kA at 8/20 s

    5.3.5.3 Nominal current (In) between Neutral to Ground shall be

    50 kA at 8/20 s

    5.3.5.4 Maximum discharge current between Neutral to Ground

    h ld b 50 kA t 8/20

  • 7/27/2019 L~0742~2013_[2] Specification

    15/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 14 of 1

    Technical Description

    Complied(C)/

    Not complied

    (NC)

    Remarks

    6 Standards

    6.1 ISO 9001-2008 & ISO 14001 - 2009

    6.2 UL listed

    6.3 IEC 62305 & 61643EN

    7 Installation Materials

    8 Spare parts

    8.1 Supplier shall guarantee the supply of all types of sparesof equipment for at least ten (10) years from the date of

    purchase of equipment.

    8.2 List of spares and annual price variation for each spare

    part for ten (10) years period shall be provided with the

    submission

    9 Samples

    10 D i lit t h d b k & d t ti

  • 7/27/2019 L~0742~2013_[2] Specification

    16/21

    Clause by Clause compliance sheet

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 15 of 1

    Technical Description

    Complied(C)/

    Not complied

    (NC)

    Remarks

    11.3.3 Characteristics of protectors and parameters

    11.3.4 Protection of telecommunication systems against

    lightening

    11.3.5 EMC: how these effects on systems and possible ways of

    avoiding damages

    11.3.6 Characteristics of offered arresters theoretical data sheets

    11.3.7 Correct installation and maintenance methods

    11.3.8 Earthing & Improvements of earth and chemical earthing

    11.3.9 Related Surge Protection and earthing standards

    11.3.10 Installation Practices of the offered product

    11.3.11 Periodical Maintenance Practices of the offered product

    11.4 Supplier shall provide the details of the training schedule

    and the place within two weeks period after issuing Letter

    of Intent (LI)

  • 7/27/2019 L~0742~2013_[2] Specification

    17/21

    Schedule of Requirement

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 15/08/2013Revision No : 02

    Date of Revision : 15/08/2013

    Page : Page 1 of 1

    ITEM DESCRIPTION

    NO

    1 Manufacture details

    1.1 Brand/Trade Name

    1.2 Country of Origin

    1.3 Country of Manufacture / Assemble

    1.4 Name of Manufacturer

    1.5 Factory Address

  • 7/27/2019 L~0742~2013_[2] Specification

    18/21

    Drawings

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 18/08/2013Revision No : 02

    Date of Revision : 18/08/2013

    Page : Page 1 of 1

    SPD

    1

    P

    D

    2

    L

    N

    F2

    F1

    Connection dia ram for SPD for 1 hase network

  • 7/27/2019 L~0742~2013_[2] Specification

    19/21

    Drawings

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 18/08/2013

    Revision No : 02

    Date of Revision : 18/08/2013

    Page : Page 2 of 1

    IncomingACB/MCCB/SFU

    Backupfuse/MPCB/MCBforSurgeArrester

    RYB

    andN

    Busbarorlooping

    aftertheincomer

    EarthBusbarinthepanel

    SurgeArrestertoconnectbetweenLineandNeutral

    SPD

    toconnectbetweenNeutralandEarth

    .

    SPD

    1

    R

    Y

    B

    N

    F4 F5 F6

    F1

    F2

    F3

    SPD

    2

    SPD

    3

    Connection dia ram for SPD for 3 hase 4 wire

  • 7/27/2019 L~0742~2013_[2] Specification

    20/21

    Previous Local Experience

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 18/08/2013

    Revi si on No : 02

    Date of Revision : 18/08/2013

    Page : Page 1 of 1

    1

    . .

    Name & Signature of the Tenderer Date Official Frank

    Client Name & address TypeCapacity Qty

    Contact person Contact No.Cost of thecontract

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 7/27/2019 L~0742~2013_[2] Specification

    21/21

    Price Schedule

    Three Phase Surge Protection Devices (SPD) with Enclosure

    No: PACS SPC 706

    Issue No : 002

    Date of Issue : 18/08/2013

    Revi si on No : 02

    Date of Revision : 18/08/2013

    Page : Page 1 of 1

    1

    (A) FOR LOCAL SUPPLIERS

    Description Qty Unit Price (Rs.)[Excluding Taxes]

    Total Cost (Rs.)[Excluding Taxes]

    Total VAT(Rs.)

    Total OtherTaxes (Rs.)

    Grand Total (Rs.)[Including Taxes]

    1 Three Phase Surge Protection Devices (SPD)

    with Enclosure

    2 Others (Please Specify)

    (B) FOR FOREIGN SUPPLIERS

    Description Qty Country of Origin FOB Unit PriceTotal FOB

    Cost

    Total

    Insurance

    Total Freight Total CIF Cost

    1 Three Phase Surge Protection Devices (SPD)

    with Enclosure

    2 Others (Please Specify)

    I / We agree to supply, install & commission the above mentioned items as per quoted price to Sri Lanka Telecom as per the

    Clause No 32 of General Conditions of tender.

    . ..

    Name & Signature of the Tenderer Date Official Frank

    Note :

    Part (A) for local suppliers and Part (B) for foreign suppliers only

    All details shall be filled and submitted with the offer. Incomplete offers will be rejected.

    All applicable taxes should be clearly indicated in this form.

    Any other charges should be clearly included