Kwuit Power Plant Technical Specs_reduced

13
: *Technical Specifications for Shuaiba South Power & Water Production Station: *-Station installed capacity: (804 MW – 30X10 6 IMG/DAY) *-Station available capacity: (720 MW – 30 X 10 6 IMG/DAY) *-Type of power units: Steam turbines *-Number of Units: 6 Units (each unit has 120 MW as available capacity & 134 MW as installed Capacity which was reduced due to aging of the units) BOILERS *-Boilers type: Radiant, front firing, Pressurized Furnace -none reheat boiler, natural feed water circulation & forced draft *-Boilers Manufacturer: Boilers # 1 to 4 : BABCKOK WILCOX-GERMANY Boilers #5 & #6 : IHI-JAPAN *- Boiler outlet condition: 1250 psi – 950 0 F -1.2 Million pound/hr *- Boiler main Fuel Firing: Natural Gas & Gas Oil as Secondary fuel STEAM TURBINES *-Steam turbines type: Tandem compound 2- cylinders, double flow exhaust - none reheat *-Steam Turbines Manufacturer: TOSHIBA-JAPAN *- Number of HP- Turbine stages: 14 stages *- Number of LP- Turbine stages: 6 stages (double exhaust flow 2x6=12 stages in LP- cylinder) *- Condenser Pressure: 3.5 in Hg absolute *- Number of turbine extractions: 1 *- Turbine Extraction Condition: 30 psi –300 0 F *- Number of closed feed water heaters: none GENERATORS *-Generators Manufacturer: TOSHIBA-JAPAN *-Rated Apparent Power: 168 MVA *-Rated Active Power: 134 MW as installed capacity

description

presentation

Transcript of Kwuit Power Plant Technical Specs_reduced

Page 1: Kwuit Power Plant Technical Specs_reduced

������ ������� ��� �� ���� �� ����� �����

�������� ������� ����� ������ �������:

*Technical Specifications for Shuaiba South Power & Water Production Station:

*-Station installed capacity: (804 MW – 30X10 6 IMG/DAY)

*-Station available capacity: (720 MW – 30 X 10 6 IMG/DAY)

*-Type of power units: Steam turbines

*-Number of Units:

6 Units (each unit has 120 MW as available capacity & 134 MW as installed Capacity

which was reduced due to aging of the units)

BOILERS

*-Boilers type:

Radiant, front firing, Pressurized Furnace -none reheat boiler, natural feed water circulation

& forced draft

*-Boilers Manufacturer:

Boilers # 1 to 4 : BABCKOK WILCOX-GERMANY

Boilers #5 & #6 : IHI-JAPAN

*- Boiler outlet condition: 1250 psi – 950 0 F -1.2 Million pound/hr

*- Boiler main Fuel Firing: Natural Gas & Gas Oil as Secondary fuel

STEAM TURBINES

*-Steam turbines type:

Tandem compound 2- cylinders, double flow exhaust - none reheat

*-Steam Turbines Manufacturer: TOSHIBA-JAPAN

*- Number of HP- Turbine stages: 14 stages

*- Number of LP- Turbine stages: 6 stages (double exhaust flow 2x6=12 stages in LP-

cylinder)

*- Condenser Pressure: 3.5 in Hg absolute

*- Number of turbine extractions: 1

*- Turbine Extraction Condition: 30 psi –300 0 F

*- Number of closed feed water heaters: none

GENERATORS

*-Generators Manufacturer: TOSHIBA-JAPAN

*-Rated Apparent Power: 168 MVA

*-Rated Active Power: 134 MW as installed capacity

Page 2: Kwuit Power Plant Technical Specs_reduced

*-Rated Voltage at Generator Terminals: 15 KV

*-Rated Generator Output Current: 6466 A

*-Generator Cooling: H2- Cooling

*-Number of Generator water Coolers: 4

*-Generator Excitation: Rotary AC-Exciter

DISTILLERS PLANT

*- Type of Distiller units: Multi Stage Flash Evaporating (MSF)-low temperature operation.

*- Distillers Capacity: 5 X 10 6 IMG/DAY

*- Distillers Manufacturer:

Distiller’s #A1-A4: ALSTHOM-FRANCE

Distiller’s #A5 & A6: IHI-JAPAN

*- Number of Distillers Stages:

Distiller’s #A1-A4: 25 stages

Distiller’s #A5 & A6: 26 stages

*- Number of Heat Rejection (or Heat Recovery) Stages: 3

Distiller’s #A1-A4: stages (23, 24 &25)

Distiller’s #A5 & A6: stages (24, 25 & 26)

*- Brine Heater Steam Inlet Condition: 10 psi –1940 F (90

0 C)

*Commissioning Date of Power Units & Distillers in Shuaiba South Power & Water Production

Station:

Power units

Commissioning

Date Distillers

Commissioning

Date

Unit#1 07/06/1970 A1 01/11/1971

Unit#2 12/05/1971 A2 01/01/1972

Unit#3 22/07/1971 A3 14/02/1972

Unit#4 09/03/1972 A4 29/03/1972

Unit#5 04/03/1974 A5 26/06/1975

Unit#6 08/06/1974 A6 15/05/1975

Page 3: Kwuit Power Plant Technical Specs_reduced

)5( � ������� ������ ����� ������ �������:

*Technical Specifications for Doha East Power & Water Production Station:

*-Station installed capacity: (1158 MW – 42X10 6 IMG/DAY)

*-Station available capacity: (1158 MW – 42X 10 6 IMG/DAY)

*-Type of power units: Steam Turbines & Gas Turbines

*-Number of Steam Turbine Units: 7 Units (150 MW each)

*-Number of Gas Turbine Units: 6 Units (18 MW each)

BOILERS

*-Boilers type:

Two-pass front firing – Pressurized Furnace-none reheat boiler with steam drum, natural

feed water circulation& forced draft flow

*-Boilers Manufacturer:

Boilers # 1 to 4 : BABCKOK WILCOX

Boilers #5 to 7 : IHI-JAPAN

*- Boiler outlet condition: 90 bar – 510 0 C – 670 Ton/hr

*- Boiler main Fuel Firing: Heavy Oil-Crude Oil-Gas Oil & Natural Gas

STEAM TURBINES

*-Steam turbines type:

Tandem compound 2- cylinders, double flow exhaust - none reheat

*-Steam Turbines Manufacturer: TOSHIBA-JAPAN

*- Number of HP- Turbine stages: 13 stages

*- Number of LP- Turbine stages: 6 stages (double exhaust flow 2x6=12 stages in LP-

cylinder)

*- Condenser Pressure: 79.9 mbr absolute

*- Number of turbine extractions: 2

*- Number of closed feed water heaters: 2

GENERATORS

*-Generators Manufacturer: TOSHIBA-JAPAN

*-Rated Apparent power: 188 MVA

*-Rated Active power: 150 MW

*-Rated Voltage at Generator Terminals: 15 KV

*-Rated Generator output current: 7237 A

*-Generator Cooling: H2- Cooling

Page 4: Kwuit Power Plant Technical Specs_reduced

*-Number of Generator water Coolers: 4

*-Generator Excitation: Static excitation

DISTILLERS PLANT

*- Type of Distiller units: Multi Stage Flash Evaporating (MSF)-low temperature operation.

*- Distillers Capacity: 6 X 10 6 IMG/DAY

*- Distillers Manufacturer:

Distiller’s #A1-A7: IHI-JAPAN

*- Number of Distillers Stages: 26

*- Number of Heat Rejection (or Heat Recovery) Stages: 3

*- Brine Heater Steam Inlet Condition: 0.7 bar - (100 0 C)

GAS TURBINES

*-Gas Turbines Type: Open Cycle –single Shaft Gas Turbine

*-Gas Turbines Manufacturer: HITACHI-JAPAN

*-Number of Units: 6 Unit

*- Gas Turbine fuel: Natural Gas & Gas Oil

*-Number of Compressor Stages: 17 Stages

*-Number of Turbine Stages: 2 Stages

*-Combustors Type: Can Combustors

*-Number of Combustors: 10 Combustors

*-Gas Turbine Start Up Unit: Diesel Engine

GT-GENERATORS

*-Generators Manufacturer: HITACHI-JAPAN

*-Rated Apparent power (as per ISO-Standard): 30.313 MVA

*-Rated Active power (as per ISO-Standard): 24.250 MW

*-Available Active Power: 18 MW

*-Rated Voltage at Generator Terminals: 11.5 KV

*-Generator Cooling: air- Cooling

*-Generator Excitation: Static Excitation

Page 5: Kwuit Power Plant Technical Specs_reduced

*Commissioning Date of Power Units & Distillers in Doha East Power & Water Production

Station:

Steam

turbines

units

Commissioning

Date Distillers

Commissioning

Date

Unit#1 14/06/1977 A1 14/06/1978

Unit#2 13/10/1977 A2 17/07/1978

Unit#3 02/01/1978 A3 17/09/1978

Unit#4 13/03/1978 A4 13/02/1979

Unit#5 21/04/1979 A5 12/04/1979

Unit#6 03/08/1979 A6 07/06/1979

Unit#7 23/10/1979 A7 13/08/1979

Gas

turbines

units

Commissioning

Date

Unit#1 24/05/1981

Unit#2 26/05/1981

Unit#3 28/05/1981

Unit#4 30/05/1981

Unit#5 03/06/1981

Unit#6 04/06/1981

Page 6: Kwuit Power Plant Technical Specs_reduced

)6( � ������� ������ ����� ������ �������:

*Technical Specifications for Doha West Power & Water Production Station:

*-Station installed capacity: (2400 MW – 110.4X10 6 IMG/DAY)

*-Station available capacity: (2400 MW – 110.4 X 10 6 IMG/DAY)

*-Type of power units: Steam turbines

*-Number of Units: 8

BOILERS

*-Boilers type:

Open air instillation, front firing - reheat boiler with steam drum, natural feed water

circulation & forced draft flow

*-Boilers Manufacturer: DEUTSCHE BABCKOK –GERMANY

*- Boiler outlet condition: 146 bar, 540 0 C, 1102 Ton/hr

*-Boiler main Fuel Firing: Heavy Oil-Crude Oil-Gas Oil & Natural Gas

STEAM TURBINES

*-Steam turbines type:

Tandem compound 2- cylinders, double flow exhaust – Extraction, Condensing & reheat

*- Number of HP- Turbine stages: 10 stages

*- Number of IP- Turbine stages: 12 stages

*- Number of LP- Turbine stages: 6 stages (double exhaust flow 2x6=12 stages in LP-

cylinder)

*- Condenser Pressure: 70 mbar absolute

*- Number of turbine extractions: 6

*- Number of closed feed water heaters: 6

GENERATORS

*-Generators Manufacturer: MITSUBISHI-JAPAN

*-Rated Apparent power: 375 MVA

*-Rated Active power: 300 MW

*-Rated Voltage at Generator Terminals: 21 KV

*-Rated Generator output current: 10310 A

*-Generator Cooling: H2- Cooling

*-Number of Generator water Coolers: 2

*-Generator Excitation: Static Excitation System

DISTILLERS PLANT

*- Type of Distiller units: Multi Stage Flash Evaporating (MSF) - first 4 distillers are low

temperature operation & others are high temperature operation

*- Distillers Capacity:

Page 7: Kwuit Power Plant Technical Specs_reduced

Distillers D1A to D2B (low temperature operation): 6 X 10 6 IMG/DAY

Distillers D3A to D8B (high temperature operation): 7.2 X 10 6 IMG/DAY

*- Distillers Manufacturer:

Distiller’s #D1A-D2B: ANSALDO-ITALY

Distiller’s #D3A-D8B: SASAKURA-JAPAN

*- Number of Distillers Stages: 24

*- Number of Heat Rejection (or Heat Recovery) Stages: 3

*- Brine Heater Steam Inlet Condition:

Distillers D1A to D2B: 1.19 bar- 104 0 C

Distillers D3A to D8B: 2.015 bar to 1.886 bar- 120 to 118 0 C

*Commissioning Date of Power Units & Distillers in Doha West Power & Water Production

Station:

Power

units

Commissioning

Date Distillers

Commissioning

Date Distillers

Commissioning

Date

Unit#1 02/05/1983 D1A 27/10/1983 D5A 19/10/1984

Unit#2 25/06/1983 D1B 15/11/1983 D5B 31/08/1984

Unit#3 15/08/1983 D2A 26/06/1984 D6A 10/08/1984

Unit#4 31/08/1983 D2B 28/09/1984 D6B 23/07/1984

Unit#5 04/04/1984 D3A 30/06/1984 D7A 25/03/1985

Unit#6 26/04/1984 D3B 21/05/1984 D7B 02/02/1985

Unit#7 06/10/1984 D4A 25/03/1984 D8A 18/01/1985

Unit#8 02/12/1984 D4B 17/11/1983 D8B 15/12/1984

Page 8: Kwuit Power Plant Technical Specs_reduced

)7( � �������� �� �� ����� ������ �������:

*Technical Specifications for Azzour South Power & Water Production Station:

*-Station installed capacity: (2511MW –115.2X10 6 IMG/DAY)

*-Station available capacity: (2511MW – 115.2 X 10 6 IMG/DAY)

*-Type of power units: Steam Turbines & Gas Turbines

*-Number of Steam Turbine Units: 8 Units (300 MW each)

*-Number of Gas Turbine Units: 4 Units (27.75 MW each)

BOILERS

*-Boilers type:

Tangential firing - reheat boiler with steam drum, natural feed water circulation & forced

draft

Boilers Manufacturer:

All Boilers design is MITSUBISHI

*- Boiler outlet condition: 146 bar – 540 0 C -1101.6 Ton/hr

*- Boiler main Fuel Firing: Heavy Oil-Crude Oil-Gas Oil & Natural Gas *-Burner Type: Tangential Tilting Corner Firing

STEAM TURBINES

*-Steam turbines type:

Tandem compound 2- cylinders, double flow exhaust – with reheat

*- Number of HP- Turbine stages: 7stages

*- Number of IP- turbine stages: 7 stages

*- Number of LP- Turbine stages: 6 stages (double exhaust flow 2x6=12 stages in LP-

cylinder)

*- Condenser Pressure: 63 mbar absolute

*- Number of turbine extractions: 6

*- Number of closed feed water heaters: 6

GENERATORS

*-Generators Manufacturer: TOSHIBA-JAPAN

*-Rated Apparent power: 375 MVA

*-Rated Active power: 300 MW

*-Rated Voltage at Generator Terminals: 17 KV

*-Rated Generator output current: 12736 A

*-Generator Cooling: H2- Cooling & water cooling inside stator windings

*-Number of Generator water Coolers: 4

*-Generator Excitation: Static Excitation system

Page 9: Kwuit Power Plant Technical Specs_reduced

DISTILLERS PLANT

*- Type of Distiller units: Multi Stage Flash Evaporating (MSF)-high temperature operation

*- Distillers Capacity: 7.2 X 10 6 IMG/DAY

*- Distillers Manufacturer:

Distiller’s D1-D12: MITSUBISHI-JAPAN

Distiller’s D13-D16: DOSAN-SOUTH KOREA

*- Number of Distillers Stages:

Distiller’s D1 to D12: 24 stages

Distiller’s D13 to D14: 26 stages

*- Number of Heat Rejection (or Heat Recovery) Stages: 3

*- Brine Heater Steam Inlet Condition: 2 bar – 110 0 C

GAS TURBINES

*-Gas Turbines Type: Open Cycle –single Shaft Gas Turbine

*-Gas Turbines Manufacturer: MITSUBISHI-JAPAN

*-Number of Units: 4 Unit

*- Gas Turbine fuel: Natural Gas & Gas Oil

*-Number of Compressor Stages: 18 Stages

*-Number of Turbine Stages: 3 stages

*-Number of Combustors: 8 Combustors

*-Combustors Type: Can Combustors

*-Gas Turbine Start Up Unit: Diesel Engine

GT-GENERATORS

*-Generators Manufacturer: MITSUBISHI-JAPAN

*-Rated Apparent power: 38.8 MVA

*-Rated Active power: 27.5 MW

*-Rated Voltage at Generator Terminals: 13.8 KV

*-Rated Generator output current: 1232 A

*-Generator Cooling: air- Cooling

*-Generator Excitation: Brushless Excitation System

*Commissioning Date of Power Units & Distillers in Az-zour South Power & Water Production

Station:

Page 10: Kwuit Power Plant Technical Specs_reduced

Power

units

Commissioning

Date Distillers

Commissioning

Date Distillers

Commissioning

Date

Unit#1 14/11/1987 D1 08/08/1988 D9 12/08/1998

Unit#2 19/12/1987 D2 08/05/1988 D10 15/07/1998

Unit#3 14/03/1988 D3 30/03/1988 D11 25/05/1998

Unit#4 05/04/1988 D4 04/02/1988 D12 23/02/1998

Unit#5 28/08/1988 D5 18/04/1989 D13 23/12/2001

Unit#6 15/09/1988 D6 10/01/1989 D14 15/11/2001

Unit#7 30/09/1989 D7 18/11/1988 D15 25/09/2001

Unit#8 16/10/1989 D8 01/10/1988 D16 10/08/2001

Gas Turbine Units

Commissioning

Date

Unit#1 25/11/1987

Unit#2 30/11/1987

Unit#3 20/08/1988

Unit#4 15/06/1988

Page 11: Kwuit Power Plant Technical Specs_reduced

)8( ������ ����� ������ ������� :

*Technical Specifications for Sabiah Power Production Station:

*-Station installed capacity: (2400 MW)

*-Station available capacity: (2400 MW)

*-Type of power units: Steam Turbines

BOILERS

*-Boilers type:

Two-pass front firing Radiant reheat boiler with steam drum, natural feed water circulation

& forced draft flow

*- Boilers Manufacturer: MITSUBISHI-JAPAN

*- Boiler outlet condition: 145 bar – 540 0 C - 975.6 Ton/hr

*- Boiler main Fuel Firing: Heavy Oil, Crude Oil, Gas Oil & Natural Gas

STEAM TURBINES

*-Steam turbines type:

Tandem compound 2- cylinders, double flow exhaust – Single reheat, Regeneration &

Condensing

*- Steam Turbine Manufacturer: MITSUBISHI-JAPAN

*- Number of HP- Turbine stages: 10 stage

*- Number of IP- Turbine stages: 12 stage

*- Number of LP- Turbine stages: 6 stages (double flow exhaust 2x6=12 stages in LP-

cylinder)

*- Condenser Pressure: 80 mbar absolute

*- Number of turbine extractions: 6

*- Number of closed feed water heaters: 6

GENERATORS

*-Generators Manufacturer: MITSUBISHI-JAPAN

*-Rated Apparent power: 353 MVA

*-Rated Active power: 300 MW

*-Rated Voltage at Generator Terminals: 20 KV

*-Rated Generator output current: 10190 A

*-Generator Cooling: H2- Cooling

*-Number of Generator water Coolers: 4

*-Generator Excitation: Static Excitation System

*Commissioning Date of Power Units in Sabiah Power Production Station:

Page 12: Kwuit Power Plant Technical Specs_reduced

Power Units

Commissioning

Date

Unit#1 09/02/1998

Unit#2 21/09/1998

Unit#3 06/05/1999

Unit#4 26/04/1999

Unit#5 24/07/1999

Unit#6 01/05/2000

Unit#7 07/03/2000

Unit#8 01/04/2000

Page 13: Kwuit Power Plant Technical Specs_reduced

)9( � !������ �� ��� ������"#� �� �� ����� ������ �������:

*Technical Specifications for Azzour Gas Turbines Power Station:

*-Station installed capacity: (1000 MW)

*-Station available capacity: (1000MW)

*-Type of power units: Gas Turbines

*-Number of Units: 8 Units (125 MW each)

GAS TURBINES

*-Gas Turbines Type: Open Cycle –single Shaft Gas Turbine

*-Gas Turbines Manufacturer: SIEMENS-GERMANY

*-Gas Turbines Model Number: V94.2

*- Gas Turbine fuel: Natural Gas & Gas Oil

*-Number of Compressor Stages: 16 Stages

*-Number of Turbine Stages: 4 Stages

*-Combustors Type: Silo-Reversed Flow Type Combustors

*-Number of Combustors: 2 Combustors

*-Gas Turbine Start Up Unit: Static Frequency Converter

GT-GENERATORS

*-Generators Manufacturer: SIEMENS-GERMANY

*-Rated Apparent power: 147 MVA

*-Rated Active power: 125 MW

*-Rated Voltage at Generator Terminals: 15.7 KV

*-Rated Generator output current: 5389 A

*-Generator Cooling: air- Cooling

*-Number of Generator water Coolers: 4

*-Generator Excitation: Static Excitation System

*Commissioning Date of Power Units in Azzour Gas Turbines Power Station:

Commissioning

Dtae

Units Commissioning

Dtae

Units

5#Unit 1#Unit

6#Unit 2#Unit

7#Unit 3#Unit

8#Unit 4#Unit