CONTACTORS
CONTACTORSKNL16, KNL18, KNL22, KNL30 KNL KNL6, KNL9, KNL12, Adaptable to various control requirements with ability of mounting from one to four additional auxiliary contacts. Versatile product capable of adaptation to different control requirements with capability of mounting from one to four additional auxiliary contacts (just for KNL6). Capability of incorporating RC suppressor to prevent voltage peaks at switch-off of control coil. Uniform marking of connection terminals in compliance with EN 50005 and EN 50011. Covered terminals - finger protection according to VDE 0106 and BGA 2. Capability of quick fitting to 35 mm wide mounting rail according to EN 60715. Open and funnel-shaped connection terminals - providing fast and simple connection. Combination head screws; standard or posidrive screwdrivers can be used. Specially shaped contact surfaces - high contact reliability even at low voltages (just for KNL6 and auxiliary contacts for KNL9 - KNL30). Uniform and easily exchangeable coils for the whole system. Mechanical interlock is possible for KNL9 - KNL30. Possibility of individual marking on a special plate - simple identification of a contactor in the circuit. Auxiliary contacts make or break which also serve as pushbuttons (just for KNL9 - KNL30). Uniform contactor width - 45 mm. Third terminal of coil. CONTACTOR RELAYSType Arrangement of contacts and terminal designation AC-15 Rated operational current Ie 400V 500V Conventional thermal current Ith
230V
690V
KNL6-22
KNL6-31
6A
4A
2A
1A
20A
KNL6-40
MOTOR CONTACTORSType KNL9-10 KNL12-10 KNL16-10 KNL-18-10 KNL9-01 KNL12-01 KNL16-01 KNL18-01 KNL9-22sp4 KNL12-22sp4 KNL16-22sp4 KNL22-00 KNL30-00R3 R5 7
Arrangement of contacts and terminal designation
Auxiliary contacts
AC-3 Rated power of threephase motors normal load Pm (kW) 230V 400V 500V 690V 2,2 3 4 4 2,2 3 4 4 2,2 3 4 5,5 7,5 4 5,5 7,5 9 4 5,5 7,5 9 4 5,5 7,5 11 15 5,5 5,5 7,5 9 5,5 5,5 7,5 9 5,5 5,5 7,5 11 15 5,5 7,5 7,5 9 5,5 7,5 7,5 9 5,5 7,5 7,5 11 15
Conventional thermal current Ith 25 32
25 32
R3 R6 8
25
-
35
Special versions of KNL9-10sp4, KNL12-10sp4 and KNL16-10sp4 are also available.
Standard AC control voltages: Volts 24 42 50/60 Hz B7 D7
48 E7 48 ED
110/125 F7 60 ND
220/240 M7 72 SD
380/415 Q7 110 FD
440 R7 125 GD
480/520 S7 220 MD
16 Volts
Standard DC control voltages: 12 24 JD BD
CONTACTORS
CONTACTORS KNLKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30CONTACTOR RELAYSStandards Approvals Climatic class open enclosedUi Ith Ue Ie Ue Ie Iv
GENERAL
VDE 0660, IEC/EN 60947-5-1 UL Damp heat, constant, acc. to IEC 60068-2-78 Damp heat, cyclic, acc. to IEC 60068-2-30 C g VA
Ambient temperature Weight Rated insulation voltage Conventional thermal current Ith = rated operating current Ie at AC-1 Rated operating current AC-15 Rated operating current DC-13
- 25 . . . + 55 - 25 . . . + 40 300 690 20 230 6 24 10 400 4 60 4 20 66 48 8 2,5 24 110/125 220/240 380/415 85 . . . 110 Mounting to vertical or horizontal level, permitted deviation 20 6000 10 x 106 see diagram 1 0,75 . . . 4 0,5 . . . 2,5 500 2 110 0,9 690 1 220 0,4
AUXILIARY CONTACTS
Short-circuit protection - max. current of fuse switch-on Coil consumption operation
V A V A A VA W VA W
Pc
Standard AC control voltages 50/60 Hz Operating range Operating position Maximum operating frequency Endurance Terminal capacity mehanical electrical rigid flexible
Uc
V
Uc
% op. c./h op. c.
S
mm2
MOTOR CONTACTORSType KNL9 KNL12 KNL16 KNL18 KNL22 KNL30 Standards Approvals Climatic class Ambient temperature Weight Rated insulation voltage Conventional thermal current Rated power of threephase motors - normal load 230 V 400 V 500 V 690 V 230 V 400 V 500 V 690 V AC-3 AC-4 1 1) Rated operational current at: 24/110/220 V DC-1 21)
GENERAL
IEC/EN 60947-4-1, VDE 0660 UL, CSA Damp heat, constant, acc. to IEC 60068-2-78 Damp heat, cyclic, acc. to IEC 60068-2-30 -25 . . . +55 -25 . . . +45 300 320 690 25 25 32 35 3 5,5 5,5 7,5 1,1 2,2 2,2 2,2 4 4 7,5 9 7,5 9 7,5 9 1,5 1,5 3 3 3 3 3 3 see diagram 2 see diagram 3 15 / 6 / 4 18 / 12 / 8 20 / 15 / 10 A DC-2, DC-3 11)
open enclosedUi Ith
C g V A
25 2,2 4 5,5 5,5 0,75 1,5 1,5 1,5
35 7,5 15 15 15 4 6,5 6,5 6,5
AC-3
Pm
kW
AC-4
MAIN CONTACTS
Rated power of threephase motors - heavy load
Pm
kW
5,5 11 11 11 2,2 4 4 4
Electrical endurance of contacts
28 / 7 / 4 30 / 23 / 13 30 / 25 / 20 18 / 2 / 1 23 / 13 / 2 28 / 18 / 9 107 35 35 50 2,5 . . . 10 1,5 . . . 6 50
3 1)
12 / 2 / 0,75 15 / 8 / 1,5 18 / 12 / 6Iv
1)
numbers of poles in series
DC-4
2 1) 3 1) op. c. A mm2 25 25
DC-5 Mechanical endurance Short-circuit protection - max. fuse rating gL Terminal capacity
rigid flexible
S
0,75 . . . 4 0,5 . . . 2,5
17
CONTACTORS
CONTACTORSKNL16, KNL18, KNL22, KNL30 KNL KNL6, KNL9, KNL12,Type Rated insulation voltage KNL9 KNL12 690 20 6 4 2 1 10 4 0,9 0,4 20 0,75 . . . 4 0,5 . . . 2,5 66 48 8 2,5 Coil control voltage, dual voltage coil, dual-frequency coil 50/60 Hz Standard AC control voltages KNL16 KNL18 KNL22 KNL30
Ui Ith230 V 400 V 500 V 690 V 24 V 60 V 110 V 220 V rigid flexible switch-on
V A
AUXILIARY CONTACTS
Conventional thermal current Ith = rated operational current Ie at AC-1
AC-15 Rated operational current
Ie
A
DC-13 Rated operational current
Ie Iv S
A
Short-circuit protection - max. fuse rating gL Terminal capacity
A mm2 VA W VA W
Coil consumption operation
PC
MAGNETIC SYSTEM
UC
24 V 110/125 220/240
Range of control voltage Operating frequency - max. Operating position
UC
% op. c./h
380/415 85 ... 110 3000 Mounting on vertical or horizontal level, permitted deviation 20
AC-4 - 400 V
Operational power
18
CONTACTORS
CONTACTORS KNLKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30KNL6, KNL9, KNL12, KNL16, KNL18 KNL22, KNL30
ACCESSORIES
Two- and four-pole auxiliary contact modules (mounting on basic contactor) NDL1, NDL2, NDL3
Type NDL1 (for KNL6) NDL2 (for KNL9, KNL12,KNL16, KNL18) NDL3 (for KNL22, KNL30)
Version -20, -11, -02, -40, -31, -22, -13, -04 -11, -02, -22, -31, -13, -40, -04 -11, -02, -22, -31, -13
AC 15 Rated operational current Ie (A) 230 V 6 400 V 4 500 V 2 690 V 1
NDL1-20
NDL1-11
NDL1-02
NDL1-40
NDL1-31
NDL1-22
NDL1-13
NDL1-04
NDL2-11
NDL2-02
NDL2-22
NDL2-31
NDL2-13
NDL2-40
NDL2-04
NDL3-11
NDL3-02
NDL3-22
NDL3-31
NDL3-13
Single-pole auxiliary contact for side mounting + push button NPL1, NPL2
Type NPL1 (just for KNL9, KNL12, KNL16, KNL18) NPL2 (just for KNL22, KNL30)
Version -10, -01 -10, -01 6
AC-15 Rated operational current Ie (A) 230 V 400 V 4 500 V 2 690 V 1
NPL1-10
NPL1-01
NPL2-10
NPL2-01
RC suppressor
19
CONTACTORS
CONTACTORSKNL16, KNL18, KNL22, KNL30 KNL KNL6, KNL9, KNL12,Type Control voltage range Ue (V) RC1 24 48 RC2 48 250 RC3 250 380 RC4 380 500
Mechanical interlock MBL
Distance spacer DZ
Identification plate NTConnection diagram
Thermal overload relay TRB14/KNLTHERMAL OVERLOAD RELAY Type AC-15 Rated operational current Ie (A) 230 V TRB14 / KNL 3A 400 V 2A 500 V 1A 0,15 - 0,25 0,24 - 0,4 2,4 - 4,0 15 - 25 Relay setting range (A) 0,38 - 0,63 3,8 - 6,3 0,6 - 1,0 6,0 - 10,0 0,96 - 1,6 9,6 - 16,0 1,5 - 2,5
24 - 40 (just for KNL22, KNL30)
ORDERING DATA Type designation and height of control voltages should be given when ordering.
KNL16-10 -
M7
control voltage (see page 16), frequency type
20
CONTACTORS
CONTACTORS KNLG KNL6G, KNL9G, KNL12G, KNL16G, KNL22G, KNL30GKNLG contactors are for DC control voltage. Application KNL6G contactors relays are applied for switching control, signal and measuring circuits. KNL9G - KNL30G motor contactors are used for switching motors. Of course, both can be used for switching other ohmic, inductive and capacitive consumers. Protection class is IP20, which means that contactors must be mounted in dry and clean ambient. If the ambient is damp or dusty, they must be mounted in a suitable box. Contactors can be built in electric distribution panels on 35 mm mounting rails (in compliance with EN 60 715) or they are fixed with screws on a vertical level (permitted deviation 20).TECHNICAL DATA
Type Standards Rated insulation voltage Conventional thermal current Back-up fuse gL max. rating Ambient temperature open in box Coil consumption in rush holding Range of control voltage Range of activity Maximum operating frequency Mechanical endurance Terminal capacity single standed fine standed
KNL6G
KNL9G
KNL12G
KNL16G
KNL22G
KNL30G
IEC/EN 60947-4-1, IEC/EN 60947-5-1
Ui Ith
V A A C 20 20 25 25 25 25
690 25 25 -25 +60 -25 +40 35 50 35 50
Pc
W
110 3
Uc Uc
V % op. c./h op. c. mm2 0,75 4 0,5 2,5
24 240 85 110 3000 5 x 106 2,5 10 1,5 6
AUXILIARY CONTACTSUeAC15 - Rated operational current V A V A 230 6 24 10 400 4 60 4 500 2 110 0,9 690 1 220 0,4
Ie Ue
DC13 - Rated operational current
Ie
21
CONTACTORS
CONTACTORS KNLG KNL22G, KNL30G KNL6G, KNL9G, KNL12G, KNL16G,MOTOR CONTACTORS KNL9G - KNL30GType AC-3-Rated power of three-phase motors - normal load 230 V 400 V 500 V 690 V AC-4- Rated power of three-phase motors - heavy load 230 V 400 V 500 V 690 V kW kW KNL9G 2,2 4 5,5 5,5 0,75 1,5 1,5 1,5 KNL12G 3 5,5 5,5 7,5 1,1 2,2 2,2 2,2 KNL16G 4 7,5 7,5 7,5 1,5 3 3 3 KNL22G 5,5 11 11 11 2,2 4 4 4 KNL30G 7,5 15 15 15 4 6,5 6,5 6,5
CONNECTION DIAGRAMSKNL6G-10, KNL9G-10+NPL1 KNL12G-10+NPL1 KNL16G-10+NPL1 KNL6G-10 + NDL1-21 KNL9G-10 + NDL2-21 KNL12G-10 + NDL2-21 KNL16G-10 + NDL2-21 KNL6G-01 KNL9G-01 + NPL1 KNL12G-01 + NPL1 KNL16G-01 + NPL1
KNL6G-01 + NDL1-12 KNL9G-01 + NDL2-12 KNL12G-01 + NDL2-12 KNL16G-01 + NDL2-12
KNL22G-00 + NPL2 KNL30G-00 + NPL2
KNL22G-00 + NDL3-03 KNL30G-00 + NDL3-03
Contactors in combination with NDL may have number of auxiliary contacts: -30, -21, -12, -03, -10, -01
DIMENSIONS KNL6G + NDL - KNL16G + NDL KNL22G + NDL, KNL30G + NDL
KNL6G + NPL - KNL16G + NPL
KNL22G + NPL, KNL30G + NPL
22
CONTACTORS
CONTACTORS KNL KNL40, KNL65
TEHNICAL DATA MOTOR CONTACTORS
GENERAL
Type Standards Mechanical endurance Ambient temperature Rated insulation voltage Ui Short-circuit protection - max. fuse rating gLAC-1 Rated thermal current Ith
KNL40 operations open enclosed C 8 x 106 -5 +55 -5 +40
KNL65
IEC/EN 60947-4-1, IEC/EN 60947-5-1 VDE 0660
V A A400 V 690 V
690 63 60 40/18,5 34/9 80 80 65/28 42/14
MAIN CONTACTS
Rated operating current IeAC-3/AC-4
A
Rated motor powers 230 V 400 V 690 V Terminal capacity Rated thermal current Ithrigid flexible
kW
11 18,5 30 25 2510 6 4 2 1 4 0,25 0,1 11 1 2,5 1 2,5 12 520
18,5 30 37 25 25
mm2 A 230 V 400 V 500 V 690 V 24 V 110 V 220 V
AUXILIARY CONTACTS
AC-15 Rated operating current Ie
A
DC-13 Rated operating curent Ie
A
Contact arrangement Terminal capacity Rated control voltage Uc Standard control voltages Uc Range of control voltage in rush Coil consumption holding VA VA W rigid flexible min. max. mm2 V V
MAGNETIC SYSTEM
24, 110/115, 220/240, 380/400 (50/60Hz) 85 110 200 20 6 - 10
a
23
CONTACTORS
CONTACTORS KNL KNL40, KNL65ACCESSORIES
Two- and four-pole auxiliary contact modules NDL5 (mounting on basic contactor)
Type NDL5
Contacts arrangement -11, -02, -22, -31, -13 6
AC 15 Rated operational current Ie (A) 230 V 400 V 4 500 V 2 690 V 1
NDL5-11
NDL5-02
NDL5-22
NDL5-31
NDL5-13
Mechanical interlock MBL40
Thermal overload relay BR43
Type BR43
AC 15 Rated operational current Ie 50/60 Hz 230 V 4A 400 V 2A
Relay setting range (A) 14,5 - 21 21 - 30 30 - 43 43 - 63
ORDERING DATA Type designation and control voltage of contactors should be given when ordering.
KNL40/65 -
11
- 220/230 - 50/60 frequency control voltage arrangment of contacts type
24
CONTACTORS
CONTACTORSKNL110 KNL KNL80, KNL90,
Type OPERATING CONDITIONS Ambient temperature Operating position Fixing Correspondance to standards POLE CHARACTERISTICS Rated insulation voltage
KNL80 operation storage normal allowable
KNL90
KNL110
C
-50 to +70 -60 to +80 on vertical plane 30 Screw or DIN rail 35 mm and 75 mm (EN 60 715) IEC/EN 60947-4-1 690 125 80 38 480 160 80 1200 1050 800 0,6 9,4 3,8 125 95 43 760 160 100 1200 1200 1050 800 0,6 9,4 5,4 lug clamp 2 12,3 12 M6 4-5 0,8 - 1 2 6 - 50 IP20 125 110 50 880 160 125 1200 1050 800 0,6 9,4 7,3
Ui
V A A A a
(