KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max....

12
KN-2000W Series B-14 • High accuracy with 16bit ADC (±0.2% F.S.) • Max. display range: 19999 to 19999 • Multi-input : Thermometer 12 types, RTD 5 types, analog (mV, V, mA) 6 types • Auto display color change function (for error or alarm) • Various output options: 4EA or 2EA alarm output, 4-20 mA transmission output (isolated), RS485 communication output Full output option model is available. (alarm output 4EA + RS485 communication output +transmission output) • Various functions : High/Low peak monitoring, sensor break alarm output (burn-out), input correction, digital input (DI), user input range, display scale, transmission output scale, etc. • Built-in power supply for sensor (24 VDC) (unit:mm) Min. 116 92 +0.6 0 +0.6 0 46 Min. 52 W DIN W96×H48 mm KN-2 Multi Indicator 0 100-240 VAC 50 to 60 Hz 1 24 VDC 0 No option 1 Transmission output (4-20 mA) 4 RS485 communication output 5 Transmission output (4-20 mA) + RS485 communication output 0 No alarm output 2 2EA alarm output 4 4EA alarm output KN-2 0 0 0 W Power supply Option output Alarm output Item Size 10 90 91 44.8 ● Panel cut-out Please read “Caution for your safety” in operation manual before using this unit. Features Ordering information Dimensions 96 48 108

Transcript of KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max....

Page 1: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

KN-2000W Series

B-14

• Highaccuracywith16bitADC(±0.2%F.S.)• Max.displayrange: 19999to19999• Multi-input:Thermometer12types,RTD5types,analog(mV,V,mA)6types

• Autodisplaycolorchangefunction(forerrororalarm)• Variousoutputoptions:4EAor2EAalarmoutput,4-20mAtransmissionoutput(isolated),RS485communicationoutput

※Fulloutputoptionmodelisavailable.(alarmoutput4EA+RS485communicationoutput

+transmissionoutput)• Variousfunctions:High/Lowpeakmonitoring,sensorbreakalarmoutput(burn-out),inputcorrection,digitalinput(DI),userinputrange,displayscale,transmissionoutputscale,etc.

• Built-inpowersupplyforsensor(24VDC)

(unit:mm)

Min.116

92+0.60

+0.6

046

Min.52

W DINW96×H48mm

KN-2 MultiIndicator

0 100-240VAC50to60Hz1 24VDC

0 Nooption1 Transmissionoutput(4-20mA)4 RS485communicationoutput

5 Transmissionoutput(4-20mA)+RS485communicationoutput

0 Noalarmoutput2 2EAalarmoutput4 4EAalarmoutput

KN-2 0 0 0 W

Powersupply

Optionoutput

Alarmoutput

Item

Size

10

90

91

44.8

Panel cut-out

Please read “Caution for your safety” in operation manual before using this unit.

Features

Ordering information

Dimensions

96

48

108

Page 2: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

Multi Indicator

B-15

A.Recorder

B. Indicator

C.Converter

D.Controller

E.Thyristorunit

F.Pressuretransmitter

G.Temp.transmitter

H.Accessories

KN-1000B

KN-2000W

KN-20 W KN-24 W KN-22 W

Series KN-2000W

Powersupply

ACvoltage 100-240VAC50to60Hz

DCvoltage 24VDC

Allowablevoltagerange 90to110%ofratedvoltage

Powercon-sumption

ACvoltage Max.8VA

DCvoltage Max.3W

Displaymethod 41/2digit:7SegmentLEDDisplay(selectablered,green,yellow),charactersize:W10mm×H17mm

Inputtype

RTD JPt100Ω,DPt100Ω,DPt50Ω,Cu50Ω,Cu100Ω(5types)

Thermocouple K,J,E,T,R,B,S,N,C(W5),L,U,PLII(12types)

Analog ·Voltage:±1.0000V,±50.00mV,±200.0mV, 1.000V-10.000V(4types)·Current:4.00-20.00mA,0.00-20.00mA(2types)

Digitalinput·Contactinput:Max.2kΩinON,Max.90kΩinOFF·Non-contactinput:Residualvoltagemax.1.0VinON,Leakagecurrentmax.0.03mAinOFF·Outflowcurrent:Approx.0.2mA

Suboutput

Alarmoutput 2-point:Relaycontactcapacity250VAC3A1c,4-point:Relaycontactcapacity250VAC1A1a

Transmissionoutput ISOLATEDDC4-20mA(PVtransmission)loadresistancemax.600Ω(accuracy:±0.2%F.S.,resolution:8000)

Communicationoutput RS485(ModbusRTU)

Displayaccuracy

±0.2%F.S.±1digit(25±5)±0.3%F.S.±1digit( 10to20,30to50)Incaseofthermocoupleandbelow-100°Cinput,[±0.4%F.S.]±1digit※TC-T,TC-Uismin.±2.0

Settingmethod Setbyfrontkeys,orRS485communication

Alarmoutputhysteresis SetON/OFFinterval(1to999digit)

Samplingcycle Analoginput:100ms,Temperaturesensorinput:250ms

Dielectricvoltage 2000VAC50/60Hzfor1min.(betweeninputterminalandpowerterminal)

Vibration 0.75mmamplitudeatfrequencyof5to55Hz(for1min.)ineachofX,Y,Zdirectionsfor2hours

Relaylifecycle

2-point Mechanical:Min.10,000,000,Electrical:Min.100,000(250VAC3Aresistanceload)

4-point Mechanical:Min.20,000,000,Electrical:Min.500,000(250VAC1Aresistanceload)

Insulationresistance Min.100MΩ(at500VDCmegger)

Noiseresistance Squareshapednoisebynoisesimulator(pulsewidth1)±2kV

Memoryretention Approx.10years(non-volatilesemiconductormemorytype)

Environ-ment

Ambienttemperature 10to50,storage: 20to60Ambienthumidity 35to85%RH,storage:35to85%RH

Approval

Unitweight Approx.200g

※Environmentresistanceisratedatnofreezingorcondensation.

F.G.

RTD/TC/mV/±1V

-1to+10V

0to20mA

Connections

Specifications

Page 3: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

KN-2000W Series

B-16

①Displaypart(red)Runmode:Displayscurrentmeasurementvalue.Parametersetmode:DisplaysparameterandSV.②Unitindicator:Displaysthesetunit.③Alarmoutputindicator:TurnsONwhenthealarmisON.④(key:Usedtoenterparametersetmode,movetoparameters,saveSVandreturntoRUNmode.⑤1,4,3key:UsedtochangeparameterSV.⑥D.IN3:Pressthe4and3keyskeysfor3sec.atthesametime,itoperatesthesetfunction(alarmclear,displayhold,zero-pointadjustment)at[DI-K]atprogrammode.

Inputtype Parameter Inputrange() Inputrange()

Thermocouple

K(CA) TC-K 200.0 to1350.0 328 to2462

J(IC) TC-J 200.0 to800.0 328.0 to1472.0

E(CR) TC-E 200.0 to800.0 328.0 to1472.0

T(CC) TC-T 200.0 to400.0 328.0 to752.0

R(PR) TC-R 0.0 to1750.0 32 to3182

B(PR)* TC-B 400.0 to1800.0 752 to3272

S(PR)* TC-S 0.0 to1750.0 32 to3182

N(NN)* TC-N 200.0 to1300.0 328 to2372

C(W5)* TC-C 0 to2300 32 to4172

L(IC)* TC-L 200.0 to900.0 328.0 to1652.0

U(CC)* TC-U 200.0 to400.0 328.0 to752.0

PlatinelII* TC-P 0.0 to1390.0 32 to2534

RTD

Cu50Ω* Cu50 200.0 to200.0 328.0 to392.0

Cu100Ω* Cu10 200.0 to200.0 328.0 to392.0

JPt100Ω JPt1 200.0 to600.0 328.0 to1112.0

DPt50Ω DPt5 200.0 to600.0 328.0 to1112.0

DPt100Ω DPt1 200.0 to850.0 328.0 to1530.0

Analog

Current0.00 - 20.00mA aMA1

19999to19999(displayrangedependsonthedecimalpointposition)

4.00 - 20.00mA aMA2

Voltage

50.00 - 50.00mV aMV1

200.0 - 200.0mV aMV2

1.0000 - 1.0000V A-V1

1.000 - 10.000V A-V2

※Aboveinputtypeswhichhavethe*markarenotdisplayed.Todisplaytheaboveinputtypes,supplythepowerwithpressingthe(key.

٧٧ Input type selection switch

0-20mA:Selectitfor0(4)-20mAinput

1-10V:Selectitfor 1V-10Vinput

TD/TC/mV/±1V:SelectitforRTD,TCtemperaturesensoror±1V,mVinput

Thisunitismultiinputproduct.SelecttheproperinputwiththeinputtypeselectionswitchandselectthisinputtypeinIN-Pinprogrammode.ThesettingofinputtypeselectionswitchandtheinputtypeIN-Pparametershouldbesameanditcandisplaythepropermeasurementvalue.Factorydefaultis4-20mA.

Input type and range

Part descriptions

②③

④ ⑥

Page 4: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

Multi Indicator

B-17

A.Recorder

B. Indicator

C.Converter

D.Controller

E.Thyristorunit

F.Pressuretransmitter

G.Temp.transmitter

H.Accessories

KN-1000B

KN-2000W

Alarm [ AL-1, AL-2, AL-3, AL-4 ]Thisproducthas2or4alarmstooperateindividuallywhenthevalueistoohighorlow.Alarmfunctionissetbythecombinationofalarmmodeandalarmoption.Toclearalarm,usedigitalinputfunction(setting 야DI-T, DI-K as AlRE)orturnthepowerOFFandON.※Forthemodel(KN-20 W)withoutalarmoutput,theseparametersarenotdisplayed.

AT!A

Alarmoption

Alarmoperation

٧٧ Alarm operation

٧٧ Alarm option

Alarm output hysteresis [ Program mode: A-HY ]SettheintervalofON/OFFalarmoutput.ThesethysteresisisappliedtoAL1toAL4anditisasbelow.※Ex)A-HY:4,highlimitalarmvalue:800,lowlimitalarmvalue:200

Highlimitalarmvalue800

800ON

796OFF

A-HY:4

Lowlimitalarmvalue200

200ON

204OFF

A-HY:4

Error

High/Low peak monitoring [ Monitoring mode: H.PEK, L.PEK ]

Thisfunctionistosavehigh/lowpeaktochecktheinvisibleabnormalconditionofsystemat[hPEK]or[lPEK]inmonitoringmode.Whenthehigh/lowpeakisoutofthetemperaturerange,itdisplaysHHHHorLLLL.Toinitializehigh/lowpeak,pressthe3,4keysatthesametimefor3sec.at[hPEK]or[lPEK].Inthiscase,peakvalueisthepresentinputvalue.

Display Descriptions Troubleshooting

LLLLFlasheswhenmeasuredsensorinputislowerthanthetemperaturerange.

Wheninputismovedwithinthetemperaturerange,itiscleared.HHHH

Flasheswhenmeasuredsensorinputishigherthanthetemperaturerange

BURN Flasheswhenthesensorisbreakornotconnected.

Checktemperaturesensorconnection.

ERRFlasheswhenthereiserrortoSV

Checksetconditionsandre-setit.

ERR1FlasheswhenIN-P settingandinputtypeselectionswitchsettingarenotsame.

Checkinputtype.

Mode Name Alarmoperation Descriptions

AT)_ ㅡ ㅡ Noalarmoperation

AT! HighlimitalarmHighlimtalarmvalue:800

OFF ON

PV

HPV≥alarmtemperature,alarmisON

AT@ Lowlimitalarm

Lowlimtalarmvalue:200

OFFON

PV

HPV≤alarmtemperature,alarmisON

SBa_ Sensorbreakalarm ㅡ ItwillbeONwhenitdetectssensordisconnection.Sensorbreakalarmdoesnothavealarmoption.

Mode Name Descriptions

AT .A Standardalarm Ifitisanalarmcondition,alarmoutputisON.Unlessanalarmcondition,alarmoutputisOFF.

AT .B Alarmlatch Ifitisanalarmcondition,alarmoutputisON.Beforeclearingthealarm,anONconditionislatched.(Holdingthealarmoutput)

AT .C StandbysequenceFirstalarmconditionisignored.Fromthesecondalarmcondition,standardalarmoperates.WhenpowerisONanditisanalarmcondition,itisignored.Fromthesecondalarmcondition,standardalarmoperates.

AT .DAlarmlatchandstandbysequence

Ifitisanalarmcondition,itoperatesbothalarmlatchandstandbysequence.WhenpowerisONanditisanalarmcondition,itisignored.Fromthesecondalarmcondition,alarmlatchoperates.

※H:Alarmoutputhysteresis

Functions

Page 5: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

KN-2000W Series

B-18

Parameter initialization

Temperature unit [ Program mode : UNIT ]

Input and transmission output extension [ Program mode: ExIO ]

Front display unit [ Program mode : dUNT ]

User input range [ Program mode : L-RG, H-RG ]

Thisfunctionistoextendanaloginputand4to20mAtransmissionoutputto5%or10%range.

※Thisparameterisdisplayedonlyfortransmissionoutput(4-20mA)model.Butitisnotdisplayedwhenselectingtemperaturesensorinput.

Toinitializeallparameterasfactorydefault,supplythepowertotheproductwithpressingthe(and1keysatthesametimeanditentersinitializationparameter.

Temperatureunit(/)isselectable.Whenchangingtemperatureunit,userinputrange,displayscale,outputscale,alarmSVareinitialized.Youshouldsettheparam-etersagainforyourpurpose.※Whenselectinganaloginput,temperatureunit[UNIT]

parameterisnotdisplayed.

Whenselectinganaloginput,selecttheunit(%,°C,°F,notdisplay)ofdisplayvalue.※Whennotdisplayingunit,setOFF anditturnsOFFall

indicators.※Whenselectingtemperaturesensorinput,thisparam-

eter[dUNT]isnotdisplayed.

Whenselectinganaloginput,youcansettheinputrangeforyourpurpose.Setlowlimitinputvalue[L-RG]andhighlimitinputvalue[H-RG]tolimittheinputrange.• Setconditions: Lowlimitinputvalue[L-RG]+20%F.S.<Highlimitinputvalue[H-RG]

Display scale [ Program mode : L-SC, H-SC ]Foranaloginput,thisfunctionistoset(-19999to19999)forparticularhigh/lowlimitvalueinordertodisplayhigh/lowlimitvalueofmeasurementinput.Ifmeasurementinputsare‘a’and‘b’andparticularvaluesare‘A’and‘B’,itwilldisplaya=A,b=Basbelowgraphs.

Displayscalefunctionisabletochangedisplayvalueformax./min.measuredinputbysettinghighlimitscale[H-SC]andlowlimitscale[L-SC]inprogrammode.※Ex)Sethigh/lowscalevalue(inputrangeis0to10V)

※Whenchanging input type,high/lowscale ischangedasfactorydefault.

• L-SC=)00

• H-SC=%00,1)00,1%00,`)00

• L-SC=1)00,H-SC=`)00

• L-SC=-%00,H-SC=%00

B

Displayvalue

Inputvalue

A

a b

BDisplayvalue

Inputvalue

A

a b

BDisplayvalue

Inputvalue

A

a b

Displayvalue

Inputvalue%00

0 10V

1)00

`)00

1%00

1)00

`)00

1%00

Displayvalue

Inputvalue0 10V

Mode Operation

0P Outputs4to20mAwithinanaloginputrange.

5POutputs3.2to20.8mAfor5%outoftheanaloginputrange.

10POutputs2.4to21.6mAfor10%outoftheanaloginputrange.

%00

1)00

1%00

Displayvalue

Inputvalue0 10V

-%00

CLR

NO YES

(

(

Pressthe(+1keysatthesametime.

Supplythepower.

Completesinitialization.

BDisplayvalue

Inputvalue

Aba

B

Displayvalue

Inputvalue

A

a b

B

Displayvalue

Inputvalue

Aba

Page 6: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

Multi Indicator

B-19

A.Recorder

B. Indicator

C.Converter

D.Controller

E.Thyristorunit

F.Pressuretransmitter

G.Temp.transmitter

H.Accessories

KN-1000B

KN-2000WParameter Functions Graph Applications

LINOutputsasinputvalue

Display

Input

Y=AX+B Standardcharacteristics.Inputforlinearity.

ROOT

Outputstherooted(√)inputvalue

Display

Input

Y=0(X<0)

Y=A(X)+B(X≥0)

Usedformeasuringflowsbypressuresignal.

SQAR

Outputsthesquaredinputvalue

Display

Input

Y=A(X)2+B(X>0)

Y=-A(X)2+B(X<0)

Usedforoutputtingdifferentialpressurebyflowsignal.

TUF Referto‘Twounitfunction’

Transmission output scale [ Program mode : lOUT, hOUT ]

For4-20mAcurrentoutput,thisfunctionistosetthedis-playvaluefor4mA[lOUT]andthedisplayvaluefor20mA[hOUT].TheintervalbetweenlOUT andhOUTis10%F.S.Ifitisbelow10%,itisfixedas10%ofSV.

Decimal point [ Program mode: dP ]

Itisabletochangedecimalpointpositionforhigh/lowlimitscalevalue.Itchangesdecimalpointpositionofdisplayvalue.

※Relationamonginputrange,userinputrange,displayscale,andtransmissionscale

Thebelowfigureistheexamplefor4to20mA.

Input special function [ Program mode: InSF ]

Whenselectinganaloginput,thisfunctionistodisplaythecalculatedactualvaluebysquare,root(√),ortwounitfunction(TUF)asdisplayvalue.

Whenconnectingapressuresensor,compoundpressurewhichisbelowatmosphericpressure(0)isforvacuumasmmHgandwhichisatmosphericpressureoroveritisforpositivepressureaskg/cm2.Atmosphericpressureis0kg/cm2.Whenthisunitdoesnotdisplay0kg/cm2,youcancorrectzero-pointadjustmentfunction.Whenusingtwounitfunction,L-SC isfixedas-760.L-SC parameterisdisplayedbutyoucannotsetthis.YoucansetH-SC within0to19999range.

Ex)Whenpressurerangeis 760.0mmHgto3.000kg/cm2,andpressuretransmitteroutputs4-20mA,setthescaleasH-SC:3000,dP:)000.Thisunitdisplaysfor4mAinputas-76)0,andfor20mAinputas#000.

Two Unit Function [ Program mode: TUF ]

Input correction [ Program mode: IN-B ]

Thisfunctionistocorrecttheerroroccurringfromather-mocouple,aRTDoranaloginputoutofallowableerrorrangeofthisunit.Thisisalsoavailabletocorrecterrorwhenasensorcan-notcontactthesubjectpositionbycalculatingtheerrortemperature.Variabletemperaturesensorshaveaccuracylevel.Be-causehighaccuracytypeisexpansive,standardthermo-couplesaregenerallyused.Inthiscase,temperaturesensormayoccurerror.Byexecutingthisfunction,youcangetmoreaccuratetemperature.Whenexecutinginputcorrectionfunction,youshouldmeasuretheerrorfromasensoraccurately.Ifthemea-surederrorisnotcorrect,errormaybegreater.(IfInSF=TUF,IN-B asatmosphericpressureinputvaluenotasinputcorrectionfunction.RefertoTwounitfunc-tion.)Ex)Whenmeasuredtemperatureis4andactual

temperatureis0.SetIN-B as-4,andanddisplayvalueis0.

Display

Output

4mA

20mA

lOUT hOUTDisplay

Output

4mA

20mA

lOUT hOUT

※DisplayvalueandmAoutputvalueforSQAR:

※DisplayvalueandmAoutputvalueforROOT:

Displayvalue=()×(H-SC-L-SC)+L-SC(outputvalue)

Inputvalue-L-RG

H-RG- L-RG

Displayvalue=()×(H-SC-L-SC)+L-SC(outputvalue)

Inputvalue- L-RG

H-RG- L-RG

2

Display

Input

4mA 20mAInputrange

Userinputrange

Displayscale(displayvalue)

Transmissionoutputscale

L-RG=6 H-RG=16

L-SC=0 H-SC=1000LLLL HHHH

4mAtransmission

20mAtransmission

lOUT=100 hOUT=900

Page 7: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

KN-2000W Series

B-20

Digital input [ Program mode: DI-T, DI-K ]

Bydigitalinputterminal[DI-T](no.6,7terminals)ordigitalinputkey[DI-K](D.IN3:4+3for3sec.),oneofthreefunctionsexecutesasthebelowtable.

Display color [ Program mode: CLOR/ C-AL ]

Thisfunctionistochangedisplaycolorforoccurringerror,operatingalarmautomatically.Usercancheckthestatusofthisunitdirectly.※Colorofmonitoringmode,programmodeisred.

٧٧ RUN mode and error display color [ Program mode: CLOR ]

Parameter Displaycolor

SV RUN Error

RED Red Red

GRN Green Green

YELO Yellow Yellow

R--G Red Green

G--R Green Red

٧٧ Alarm display color[ Program mode: C-AL ]

Alarm output for disconnecting input sensor [ Program mode: BURN ]

Whendisconnectinginputsensor,youcansetthestatusoftransmissionoutput.

Parameter SVTransmissionoutput(4-20mA)

Alarmoutput

BURN

ON 20mA+5%output HighlimitalarmON

LowlimitalarmOFF

OFF 4mA-5%output HighlimitalarmOFF

LowlimitalarmON

Lock [ Program mode: LOCK ]Itlimitstocheckparametersetvalueandtochangeit.

OFF LOC1 LOC2

Programmode

Monitoringmode

:Enabletocheck/set :Enabletocheck,disabletoset, :Disabletocheck

※InLOC2,onlyLOCK parameterdisplaysinprogrammode.

• Whenalarmiscleared,ortwoalarmsoperateatthesametime,thelatestalarm’scolorisapplied.

• Whenerroroccurs[HHHH,LLLL,BURN,ERR,ERR1]duringalarm,thesetcolorofCLOR isapplied.

Digital filter [ Program mode: MAvF ]Movingaveragedigitalfilterisabletostablydisplayandoutputthenoisefrominputlineandirregularsignalsassoftware.•Filtersetrange:01to16(Whensettingas01,digitalfilterfunctiondoesnotrun.)※Displaycycleissamewhenexecutingmovingaveragedigitalfilter.

Function Operaiton

AlRE Alarmclear

WhenalarmisONinRUNmode,itclearsalarmforcibly.(Itappliesonlyforalarmlatch,alarmlatchandstandbysequenceoptions.)Alarmclearoperatesonlywhenthevalueisoutofthealarmvaluerange.Afterclearingalarm,alarmoperatesitsoptionnormally.※Forthemodelwithoutalarmoutput(KN-20 W),thisparameterisnotdisplayed.

HOLDDisplayHOLD

Temporarilyindicatedvalueisstoppedinordertocheckindicatedvalueinunstableinput.

ZEROZero-pointadjustment

Setpresetdisplayvalueas0.Thisfunctionisrelatedwithinputcorrection[IN-B].Whenexecutingzeroadjustmentfunctionindisplayvalueas4,inputcorrectionvalue[IN-B]issetas-4automatically.

D4=S1+S2+S3+S4

4

D6=S3+S4+S5+S6

4

D8=S5+S6+S7+S8

4

D5=S2+S3+S4+S5

4

D7=S4+S5+S6+S7

4

D1=S1,D2=S2,D3=S3:Initialoperationbeforeaveraging4

Thisparameterisdisplayedonlyforthealarmoutputmodels(KN-22 W,KN24 W).• Thenumberofsetdigitissameasthenumberofalarmoutput.

[2alarmoutputs(KN-22 W)]S

[4alarmoutputs(KN-24 W)]S

• Setcolorforeachalarm.ItchangesasR→G→Y→Rinturn.

※Ex) S :Pressanyoneamongthe1,3,4keys.

S RUNmodecolorisgreen.

AL-4colorAL-3colorAL-2colorAL-1color

S

①AL-1isON,displayisgreen→yellow.②AL-2isON,displayisyellow→red.③AL-3isON,displayisred→green.④AL-4isON,displayisgreen→red.

S1

D1 D2 D3 D4 D5 D6 D7 D8

S2 S3

100ms

S4 S5 S6 S7 S8 S9

Sn:SamplingvalueDn:Displayvalue

Page 8: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

Multi Indicator

B-21

A.Recorder

B. Indicator

C.Converter

D.Controller

E.Thyristorunit

F.Pressuretransmitter

G.Temp.transmitter

H.Accessories

KN-1000B

KN-2000W

Communication set [ Program mode: ADDR, BAUD ]

Communication write enable/disable [ Program mode: COmW ]

Youcansetcommunicationaddress[ADDR]andcommu-nicationspeed[BAUD]forRS485communication.

Youcansettoenable[EnA]ordisable[DIsA]orwritingparametersettingbyRS485communication.

RefertocommunicationmanualforRS485communication.Visitourwebsite(www.autonics.com)todownloadcommunicationmanualandsoftware[Integrateddevicemanagementprogram:DAQMaster].

Communication specifications

Communication manual

Item Specifications

Communicationmethod RS4852-wirehalfduplex

Communicationspeed(BPS) 9600,4800,2400,1200

Converter ConverterbuiltinRS232

Max.connections 32units

Communicationdistance

Max.1200m(within700mrecommended)

Protocol MODBUS1.1RTU

Parity None

StopBit 1Bit

Datalength 8Bit

Communications

Integrated device management program ( DAQMaster)

DAQMasteristheintegrateddevicemanagementprogramtosetparametersandmanagemonitoringdata.Visitourwebsite(www.autonics.com)todownloadusermanualandintegrateddevicemanagementprogram.

<DAQMasterscreen>

<Computerspecificationforusingsoftware>

Item Minimumrequirements

System IBMPCcompatiblecomputerwithIntelPentiumⅢorabove

Operatingsystem MicrosoftWindows98/NT/XP/Vista/7

Memory 256MBormore

Harddisk Morethan1GBoffreeharddiskspace

VGA 1024×768orhigherresolutiondisplay

Others RS-232serialport(9-pin),USBport

Page 9: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

KN-2000W Series

B-22

※1. S :Pressanykeyamongthe1,3,4.※2.1:Movesdigits/4,3:ChangesSV.※3.Pressthe MODE keyafterchecking/changingSVineachparameter.Thevalueflashestwiceandissaved.Itmovestonextparameter.

※Afterenteringsettinggroup,pressthe MODE keyfor3sec.orthereisnoadditionalkeyoperationin30sec.,itreturnstoRUNmode.

※ :Thisparametermayormaynotappear,dependingontheotherparametersettings.

AL1 09(9

AL2 09(9

AL3 00)1

AL4 00)1

hPEK ----

lPEK ----

MODE

S

S

S

S

S

S

MODE

MODE

MODE

MODE

MODE

MODE

Alarm1value

Alarm2value

Alarm3value

Alarm4value

Highpeakvalue

Lowpeakvalue

※1 ※2

※3

Displayshigh/lowpeakvalue.※High/Lowpeakvalueisavailableonlytocheckandinitializeit. (Referto‘High/Lowpeakmonitoring’forinitialization.)※Initialhigh/lowpeakissavedafter2sec.fromsupplyingthepower.

※Displayedonlyforalarmoutputmodels.

Seteachalarmvalue;[AL-1toAL-4]inprogrammode.•Setrange:Temperaturesensorinput→withintemperaturerangeAnaloginput→L-SCtoH-SC※Whenalarmmode[AL-1toAL-4]inprogrammodeisnoalarm[AT)_]orsensorbreakalarm[SBa_],theseparametersarenotdisplayed.

※For2EAalarmoutputmodel(KN-22 W),AL3,AL4 arenotdisplayed.

RUN mode

MODEPress key.

Monitoring mode

Program mode

※1. S :Pressanykeyamongthe1,3,4.※2.1:Movesdigits/4,3:ChangesSV.※3.Pressthe MODE keyafterchecking/changingSVineachparameter.Thevalueflashestwiceandissaved.Itmovestonextparameter.

※Afterenteringsettinggroup,pressthe MODE keyfor3sec.orthereisnoadditionalkeyoperationin30sec.,itreturnstoRUNmode.

※ :Thisparametermayormaynotappear,dependingontheotherparametersettings.

IN-P aMA2S

MODE

UNIT ?CS

MODE

dUNT ?/OS

MODE

L-RG 0$00S

MODE

H-RG 2)00S

MODE

Selectinputtype.(Referto「Inputtypeandrange」.)

Selecttemperatureunit.

Selectfrontdisplayunit.

※Displayedonlywhenselectinganaloginputtype.

?C ?F

?/O ?COFF ?F

Setlowlimitofinputrange.•Setrange:withinanaloginputtyperange

Sethighlimitofinputrange.•Setrange:withinanaloginputtyperange

Inputtype

Temperatureunit

Lowlimitinputvalue

Frontdisplayunit

Highlimitinputvalue

※1 ※2

MODE ※3

※Displayedonlywhenselectingtemperaturesensorinputtype.

RUN mode

MODEPress keyfor3sec.

Page 10: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

Multi Indicator

B-23

A.Recorder

B. Indicator

C.Converter

D.Controller

E.Thyristorunit

F.Pressuretransmitter

G.Temp.transmitter

H.Accessories

KN-1000B

KN-2000W

4mAoutputscalevalue

20mAoutputscalevalue

Inputandtransmissionoutputextension

AL1mode

AL2mode

AL3mode

AL4mode

EX.I0 SPS

MODE

AL-1 AT!AS

MODE

AL-2 AT!AS

MODE

lOUT 00)0S

MODE

AL-3 AT@AS

MODE

hOUT 10)0S

MODE

AL-4 AT@AS

MODE

※Displayedonlyfortransmissionoutputmodel.

※Displayedonlyforalarmoutputmodels.

Setoutputscalevaluefor4mA.•Setrange:Temperaturesensorinput→withintemperaturerange,Analoginput→L-SCtoH-SC

Setoutputscalevaluefor20mA.•Setrange:Temperaturesensorinput→withintemperaturerange,Analoginput→L-SCtoH-SC

Selectextensionrangeof4-20mAinputandtransmissionoutput.

S

MODE

MODE

MODE

MODE

MODE

Nextparameter

AL-1

AL-2

AL-3

AL-4

SetAL1toAL4alarmmodeandoption.

10PSP 0P

ALoutputhysteresis

Inputspecialfunction

Inputcorrection

InSF LINS

MODE

IN-B 0000S

MODE

A-HY 001S

MODE

Selectinputspecialfunction.

Setinputcorrectionvalue.•Setrange:-999to999

Setalarmoutputhysteresis.•Setrange:001to999

LIN SQARROOT TUF

dP )0MODE

L-SC 00)0MODE

H-SC 10)0MODE

S

S

S

Selectdecimalpointpositionofdisplayscalevalue.

)0 )000)00 0

Setlowlimitscalevalue.•Setrange:-19999to19999

Sethighlimitscalevalue.•Setrange:-19999to19999

Decimalpoint

Lowlimitscalevalue

Highlimitscalevalue

※Displayedonlywhenselectinganaloginputtype.

※Displayedonlywhenselectinganaloginputtype.

<Alarmmode> <Alarmoption>

AT!A

AT@A

SBa_

AT)_

AT!A

AT!B

AT!C

AT!D

※야 SVchangingmethodofAL-2toAL-4issameasAL-1’s.※For2EAalarmoutputmodel(KN-22 ٧W),AL3,AL4 arenotdisplayed.

※Noalarm[AT)_],sensorbreakalarm[SBa_]donothavealarmoption.※Setalarmvalue[AL1toAL4]inmonitoringmode.

※Whenalarmmode[AL-1toAL-4]inprogrammodeisnoalarm[AT)_]orsensorbreakalarm[SBa_],thisparameterisnotdisplayed.

※Displayedonlywhenselectinganaloginputtype.

Page 11: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

KN-2000W Series

B-24

COmW EnAS

LOCK OFFS

ADDR 01S

BAUD (6KS

※DisplayedonlyforRS485communicationoutputmodel.

Setcommunicationaddress.•Setrange:01to99

Selectcommunicationspeed(baudrate).

Selectlockfunction.

Selectenable/disabletocommunicationwrite.(EnA:enabletowrite,DIsA:disabletowrite)

BURN ONS Selectoutputstatuswhensensordisconnection.

Sensorbreakalarmoutput

Communicationaddress

Communicationspeed

Communicationwrite

Lock

ON OFF

EnA DIsA

LOC1OFF LOC2

(6K @4K!2K1(2K $8K

Digitalinputterminal

Digitalinputkey

Displaycolor

Alarmdisplaycolor

CLOR REDS

DI-T HOLDS

DI-K HOLDS

C-AL RRRRS

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

Selectdigitalinputfunctionbyno.6and7.※Forthemodelwithoutalarmoutput(KN-20 ٧W),AlRE isnotdisplayed.

Selectdigitalinputfunctionbyfrontkeys.※Pressthe4,3keysfor3sec.atthesametimeanditexecutestheselectedfunction.※Forthemodelwithoutalarmoutput(KN-20 ٧W),AlRE isnotdisplayed.

SelectdisplaypartcolorforRUNmodeanderror.※Referto「Displaycolor」.

Selectdisplaypartcolorforalarm.※Referto「Displaycolor」.

ZEROHOLD AlRE

ZEROHOLD AlRE

RED GRN YELO R--G G--R

Digitalfilter

MAvF 04S

MODE

Setthenumberofmovingaveragedigitalfilters.

•Setrange:01to16

※Displayedonlyforalarmoutputmodels.

※Displayedonlyforalarm,transmissionoutputmodels.

Page 12: KN-2000W Series · · Non-contact input : Residual voltage max. 1.0 V in ON, Leakage current max. 0.03 mA in OFF · Outflow current : Approx. 0.2 mA Sub output Alarm output 2-point

Multi Indicator

B-25

A.Recorder

B. Indicator

C.Converter

D.Controller

E.Thyristorunit

F.Pressuretransmitter

G.Temp.transmitter

H.Accessories

KN-1000B

KN-2000W

Parameter Default Parameter Default Parameter Default Parameter Default

IN-P aMA2 lOUT 00)0 InSF LIN ADDR 01

UNIT ?C hOUT 10)0 IN-B 0000 BAUD (6K

dUNT ?/O ExI0 5P MAuF 04 COMW EnA

L-RG 0$00 AL-1 AT!A DI-T HOLD LOCK OFF

H-RG 2)00 AL-2 AT!A DI-K HOLD

dP )0 AL-3 AT@A CLOR RED

L-SC 00)0 AL-4 AT@A C-AL RRRR

H-SC 10)0 A-HY 001 BURN ON

Parameter Default Parameter Default Parameter Default

AL1 09(9 AL3 00)1 hPEK ----

AL2 09(9 AL4 00)1 lPEK ----

Caution for using

Proper usage

• Forconnectingthepower,useacrimpterminal(M3.5,min.7.2mm).

• Theconnectionofthisunitshouldbeseparatedfromthepowerlineandhighvoltagelineinordertopreventinductivenoise.

• Installapowerswitchoracircuitbreakertosupplyorcutoffthepower.

• Switchorcircuitbreakershouldbeinstallednearbyusersforconvenientcontrol.

• Donotusethisunitnearthehighfrequencyinstruments(highfrequencyweldingmachine&sewingmachine,largecapacitySCRcontroller).

• Whensupplyinginput,ifHHHHorLLLLisdisplayed,measuredinputmayhaveproblem.Turnoffthepowerandchecktheline.

• Installationenvironment. ①Itshallbeusedindoor. ②PollutionDegree2 ③Altitudemax.2,000m ④InstallationcategoryⅡ• Itmaycausemalfunctionifaboveinstructionsarenotfollowed.

Factory default

Program mode

Monitoring mode