Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

23
Slide 1 Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass Jim Braun Purdue University

description

Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass. Jim Braun Purdue University. Outline. Building Thermal Mass Concept Strategy Development and Evaluation Previous Work Objectives of Current Work. Control of Building Thermal Mass. - PowerPoint PPT Presentation

Transcript of Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Page 1: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 1

Introduction toLoad Shifting and Peak Load

Reduction using Building Thermal Mass

Jim BraunPurdue University

Page 2: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 2

Outline

Building Thermal Mass Concept

Strategy Development and Evaluation

Previous Work

Objectives of Current Work

Page 3: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 3

Control of Building Thermal Mass

Precool at night during off-peak hours

Adjust daytime setpoints to control discharge

Cooled structure reduces daytime, on-peak cooling loads

Savings due to » reduced on-peak energy and

demand usage» improved equipment performance» night ventilation

Page 4: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 4

Building Structural Storage Potential

Concrete Floor

Internal Gains~ 4 - 8 Watts/sq. ft.

Thermal Capacity ~ 2 - 4 Watts-Hours/sq. ft. - F

~ 0.25 - 1 hours of storage per 1 degree F temperature change

Page 5: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 5

Load Shifting

Types of StrategiesZ

one

Tem

pera

ture

Time of Day

Night Setup

Occupied Period Unoccupied Period

On-Peak Period

Demand Limiting

Lower Comfort Limit

Upper Comfort Limit76 F

70 F

Page 6: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 6

Load EffectsC

oolin

g Lo

ads

Time of Day

Occupied Period Unoccupied Period

On-Peak Period

Night Setup

Demand Limiting

Load Shifting

Page 7: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 7

Thermal Mass vs. Ice Storage

No additional costs (Structure

already exists!!)

Charging constraints due to

occupant comfort

Variable storage efficiency due to

coupling between building and

environment

Initial cost associated with ice tank(s),

piping, support equipment, &

installation.

No direct comfort constraints

Constant storage efficiency with easily

determined “state of charge”

Page 8: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 8

Strategy Development and Evaluation

Evaluate Maximum Savings

Potential

Develop and Evaluate Generic Control Strategies

SimulationControlled Testing –Validate Simulations

& Demonstrate Savings

Laboratory Testing

Evaluate Real-World Savings Potential

Field TestingImplementation

Issues

A Tool to Develop Site-Specific

Control Strategies

A Tool to Evaluate Field Savings

Page 9: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 9

Forward Simulation

System Physical Description

Weather Data& Schedules Utility RatesControl Strategy

Existing Modeling Tool

Performance Estimates

* use to evaluate savings potential & develop simple control strategies *

Page 10: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 10

Inverse Simulation

* use to develop site-specific control strategies & evaluate field savings *

System Training Data

SystemModel Structure Parameter Estimation

ModelValidationSystem Test Data

System Model

Weather Data& Schedules

Utility RatesControl Strategy

Performance Estimates

Page 11: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 11

Previous Studies

Simulation Work» Up to 30% HVAC energy & demand cost savings for large

commercial buildings (Braun (1990), Synder and Newell (1990), Rabl and Norford (1991), Andresen and Brandemuehl (1992))

» Cost savings very sensitive to control method, system parameters, utility rates, and weather

» Inverse modeling approach for developing and evaluating site-specific control strategies (Chaturvedi and Braun, 2002)

Laboratory Testing» Up to 50% load shifting & peak reduction for a lightweight internal

zone (Conniff (1991), Morris et. al (1994))» Good agreement between measured loads and load predictions

from TRNSYS building model (Morris et. al (1994))» Load shifting and peak load reduction very sensitive to control

strategy

Page 12: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 12

Previous Studies

Field Testing – Large Commercial Buildings» Small load shifting and peak reduction reported by Ruud et al.

(1990)» 100% shedding from 2 pm to 6:30 pm reported by Sukkhbir et al.

(1993)» ~25% peak cooling load reduction for side-by-side tests from 7

am to 6 pm reported by Keeney and Braun (1996)» Up to 40% HVAC cost savings predicted for large commercial

building by Braun et. al (2002)

Field Testing – Small Commercial Buildings» 23% load shifting for small commercial building reported Braun

et. al (2002)

Page 13: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 13

Simulated Load Shifting Cost Savings

(2-to-1 time-of-day rates)

90807060500

10

20

30

40

50

60

% DailyCooling Cost Savings

Average Daily Temperature (F)

Heavy ZoneGood Part-Load

Heavy ZoneFlat Part-Load

Light ZoneFlat Part-Load

Light ZoneBad Part-Load

* high sensitivity to building and plant *

Page 14: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 14

NIST Laboratory Test Facility

Zone Air

Handler

Guard Space

Air Handler

Guard Air Spaces

Plenum

Internal Gains

Concrete Slabs

Controlled to emulate internal zone within a multi-story building

Page 15: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 15

Demand-Limiting Test Results

0

500

1000

1500

2000

Cooling Load (Watts)

0 4 8 12 16 20 24

Time of Day (hours)

Night Setback

Minimum Demand

Page 16: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 16

Comfort Results – Demand Limiting

Page 17: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 17

Chicago Field Site Description

No Scale

Elevation View

North

OfficeSpace

OfficeSpaceReception

Area

1st Floor

2nd Floor

3rd Floor

4th FloorGroundLevel

Approx. 1280 ft.(390 m)

Approx. 512 ft.(156 m)

Plan View

1.4 million sq. ft., four 900-ton chillers, west of Chicago$0.052/kw-hr on-peak (9 am – 10 pm)

$0.023/kw-hr off-peak, $16.41 per peak kW

Page 18: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 18

Chicago Field Site

Page 19: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 19

Demand-Limiting Case Study

Page 20: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 20

HVAC Energy Cost Case Study

Created an inverse model from measured data

Used model to develop & evaluate control strategies

Cooling Plant

Evaporators

Condensers

AirHandlingUnit

AirHandlingUnit

Building

Test Site

Cooling Plant

Evaporators

Condensers

Evaporators

Condensers

Evaporators

Condensers

AirHandlingUnit

AirHandlingUnit

Building

Test Site

SimulateCosts

EvaluateSavings

Control StrategiesWeather DataUtility Rates

SimulateCosts

EvaluateSavings

Control StrategiesWeather DataUtility Rates

Building

model

AHU

model

Plant

model

Learn Building & Equip. Models

Building

model

AHU

model

Plant

model

Learn Building & Equip. Models

processed

data

AmbientConditions

processed

data

processed

data

AmbientConditionsAmbient

Conditions

Page 21: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 21

~ 5% difference in utility costs

113681

46748 43664

73265 70017

120013

0

20000

40000

60000

80000

100000

120000

140000

Actual Predicted

Costs ($)

Energy

Demand

Total

Model Validation

(HVAC utility costs, July 11 - August 8, 1997, field site data)

Page 22: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 22

3-Month Cost Savings for HVAC

StrategyEnergy

Costs($)Demand Costs($)

Total costs($) Savings(%)

Night Setup 90,802 189,034 279,836 0.0Load-Shifting Strategy 72,671 91,372 164,043 41.4

Page 23: Introduction to Load Shifting and Peak Load Reduction using Building Thermal Mass

Slide 23

Objectives of Current Work

Demonstrate peak load reduction potential in a

medium size commercial building

Further develop and validate inverse modeling tools » a tool for developing site-specific strategies and

evaluating field site savings

Evaluate peak load reduction potential for a small

commercial building