CONTROL VALVES IN SPLIT RANGES
For certain control strategies some valve need to be operated in split range ,i.e, from 0 to 100 % signal two valves operate to maintain the parameter. Inthese cases valves may operate in either of following manner
% SIGNAL
The above figure shows opening of both valves as signal varies from 0 to 100 %
SIGNAL OPEN. OF VALVES% VALVE 1 VALVE 20 100 0
25 50 050 0 075 0 50100 0 100
Example LV - 5 A & B :LV - 5A is the condensate import valve of the carbamate condenser shell sideLV - 5B is the condensate export valve of the carbamate condenser shell side At 50 % output both valves are closedAt 0 % output LV - 5A valve is full open & LV - 5B full closedAt 100 % output LV - 5A valve is full closed & LV - 5B full open
CASE A
25 50 1000
VALVE 1 VALVE 2
CASE B
VALVE 1 VALVE 2
% SIGNAL
The above figure shows opening of both valves as signal varies from 0 to 100 %
SIGNAL OPEN. OF VALVES% VALVE 1 VALVE 20 0 0
25 50 050 100 075 100 50100 100 100
Example PV - 7 A & B .
PV - 5A is the condensate import valve of the carbamate condenser shell side& LV - 5B is the condensate export valve of the carbamate condenser shellside At 50 % output both valves are closedAt 0 % output LV - 5A valve is full open & LV - 5B full closedAt 100 % output LV - 5A valve is full closed & LV - 5B full open
TRIP LOGICS FOR UREA PLANT
The plant operates on fail safe principle which means that in case of an emergency orany undesirable event the plant should move to safe conditions.For this to happen all
critical equipments have been provided with tripping logics so that a particularequipment would be stopped automatically in case of an emergency
IS - 01 TRIP LOGIC FOR TK - 01 / K - 01
IS - 02 TRIP LOGIC FOR H.P SYNTHESIS LOOP
IS - 03 TRIP LOGIC FOR H.P AMMONIA PUMP , P - 01
25 50 1000
IS - 04 TRIP LOGIC FOR H.P CARBAMATE PUMP , P - 02
IS - 05 TRIP LOGIC FOR UREA MELT
IS - 06 TRIP LOGIC FOR INSTRUMENT AIR FAILURE
IS - 08 TRIP LOGIC FOR DRAIN RECOVERY PUMPS P-12A/B
IS - 09 TRIP LOGIC FOR HYDROLYZER TRIP CIRCUIT
IS - 10 TRIP LOGIC FOR HYDROLYZER FEED PUMP
IS - 11 TRIP LOGIC FOR COND. EXTACTION PUMP TRIP
IS - 12 TRIP LOGIC FOR PURIFIED WASTE WATER IS - 16 TRIP LOGIC FOR DEMISTER FLUSHING
TERMS ASSOCIATED WITH TRIP LOGICS
1
2for starting the M/C
3particular tripping cause so that actual tripping occurs onlywhen atleast 2 out of 3 switches for a particular reason actuatesimultaneously
4actuated will cause tripping whereas inactive switch will notcause tripping even on actuation of the switch
5than one tripping switches
6tripping even in case of actual actuation of switch
7knobs to bypass the trip switches
8
DESCRIPTION OF TRIP LOGICS
IS - 1
This trip logic relates to TK - 1/K - 1. All the trip reasons are listed below
PSXL 601
PSXL 02
PSXH 01LSXH 641 High level in surface condenser E - 28PSXH645 High extraction steam pressure
DELAY: Minimum time for which a switch has to remain actuated to cause tripping
READY TO RESET: Condition indicating fullfilment of certain requirements
VOTING LOGIC: Provision of more than one usually three switches for a
ACTIVE / INACTIVE: Indicates the state of switches. An active switch if
FIRST OUT: First reason (switch) on which a m/c trips on actuation of more
BYPASS: Physical condition of a trip cause which will not lead to
HARDWARE SWITCH : Switches provided on DCS consoles in form of
SOFTWARE SWITCH : Switches which can be bypassed from LM only
CO2 Compressor low suction pressure
CO2 Compressor low discharge pressure
CO2 Compressor high discharge pressure
PSXH 648 Turbine exhaust pressure very high
LSXH62ZSXH 650 Compressor,Turbine, Gear box high axial displacementXSXH 650 Compressor, Turbine, Gear box high vibrationSH 650 Turbine high speedPSXL677 Lube oil header pressure lowPSXL690 Lube control oil pressurePSXL 691 Low trip oil pressureLSXH606 High level in 1st interstage separator MV - 16LSXH 609 High level in 2nd interstage separator MV - 17LSXH 612 High level in 3rd interstage separator MV - 18IS 06 Emergency trip: instrument air failure.
On the trip , following actions will be taken by the system automatically.- ESV closes- passivation air flow control valve FV 61 closes- anti surge valve FV 602 opens- Interstage vent valve opens- HV 01 closes
Barring device gets permissive to start only after the following- Normal lube oil pressure- Turbine zero speed achieved- Trip oil pressure switch actuated (PXL 691)
IS 01 restting is permitted only after following :- All the trips switches are in healthy condition- Trip oil switch (PSXL 691) bypassed- Barring device disengaged- Interstage vent valve open indication switch bypassed- FV 602 open- HV 601 open- Overhead tank normal level
IS - 2
This trip logic relates to HP Loop. All the trip reasons are listed below
Trip actuation is on the following- PSXH 06 Reactor high pressure- IS 03 P 1 trip- IS 06 Emergency trip actuation
On the trip , following actions will be taken by the system automatically.- HV 02 closes- FV 34 opens- HV 06 closes- P 1 tripping
High level CO2 knock out drum MV -9
IS 02 restting is permitted only after following :All the trips switches are in healthy conditionP 1 running
IS -3
This trip logic relates to HP AMMONIA PUMP P-1. All the trip reasons are listed below
- PLL 98 Low lube oil pressure in torque convertor- PLL 97 Low lube oil pressure in Gear box- PLL 96 Low lube oil pressure in Crank case- PSXH 31 High dicharge pressure- WSXH 51 Crank case overload protection- IS 02 On the actuation of IS 02
On actuation of pump overspeed switch (SXH 51) , the pump return to minimumspeed. It can be restted only with the help of local hardware push button switchprovided.
IS - 4
This trip logic relates to HP CARBAMATE PUMP P-2. All the trip reasons are listed below
IXL 02 Low current consumptionZXH 501 High axial displacementXXH 501 High vibrationTH 509 High 1st stage thrust bearing temperatureTH 510 High first stage journal bearing tempTH 512 High first stage journal bearing tempTH 516 High second stage journal bearing tempTH 518 High second stage journal bearing tempTH 515 High second stage thrust bearing tempPLL 522 Low lube oil pressurePLL 527 Low seal flush suction pressurePLL 508 Low seal flush flow
IS 04 restting is permitted only after following :
All the trips switches are in healthy conditionPLL 508 Noramal seal flush flowPH521 Normal lube oil pressureTL 503 Normal lube oil tempLL 504 Normal level in lube oil console
IS - 5
This trip is actuated only when for following reasons
- Belt conveyors not running- Scrapper not running- Bucket not running
On the trip , following actions will be taken by the system automatically.
- 11 HS 132 11 Unit prilling diversion to V5- 21 HS 132 21 Unit prilling diversion to V5- HS 137 Flushing steam to bucket side will open
IS - 6
In case of instrument air failure PSXL 301 will actuate, the IS 06 will activate, and this will
IS - 8
The actuation of this trip will give start / off command to P 12 A/B.
IS - 9
This trip will be actuated only when hydrolyser temp goes very high (TXH 160 )And this will result in closing HS inlet to R 02 (FV 165)
IS - 10
This trip will be actuated on following:
IXL 14 Low current consumptionFXL 158 / 159 Low seal flush flow
This will result in the tripping of P 14.
IS - 11
The actuation of this trip will give start / off command to P 23 A/B.
IS - 12
This trip will actuate only when 11AH 161 A (high conc of urea in treated wastewater) actuate.The actuation of this trip will close HV 163 (condensate to DM plant) and open HV 162(recycle to V 6).
IS - 16
This opens the demister pad flushing water valve HV 173 after every 15 mins for aduration of 15 sec
result in the tripping of CO2 compressor (IS 01) and IS 02