Installation - Bradley Corp · P.O. Box 309, Menomonee Falls, ... Pre-Installation Information...

8
P.O. Box 309, Menomonee Falls, WI USA 53052-0309 PHONE 800.BRADLEY (800.272.3539) FAX 262.251 5817 bradleycorp.com Installation 215-158E Rev. K; ECN 12-05-003C © 2012 Bradley Page 1 of 5 10/18/2012 E19-220 Wall-Mounted Eyewash with Plastic Bowl E19-220B Wall-Mounted Eyewash with Stainless Steel Bowl E19-220DC Wall-Mounted Eyewash with Dust Cover E19-220FW Wall-Mounted Eye/Face Wash with Plastic Bowl Table of Contents Pre-Installation Information ....................... 2 Installation Instructions .......................... 3 Dimensions ................................. 3–4 Components and Parts Lists .................... 5–8 E19-220 E19-220B E19-220DC E19-220FW

Transcript of Installation - Bradley Corp · P.O. Box 309, Menomonee Falls, ... Pre-Installation Information...

P.O. Box 309, Menomonee Falls, WI USA 53052-0309PHONE 800.BRADLEY (800.272.3539) FAX 262.251 5817bradleycorp.com

Installation

215-158E Rev. K; ECN 12-05-003C© 2012 BradleyPage 1 of 5 10/18/2012

E19-220Wall-Mounted Eyewash with Plastic Bowl

E19-220BWall-Mounted Eyewash with Stainless Steel Bowl

E19-220DCWall-Mounted Eyewash with Dust Cover

E19-220FWWall-Mounted Eye/Face Wash with Plastic Bowl

Table of ContentsPre-Installation Information . . . . . . . . . . . . . . . . . . . . . . . 2Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . 3Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–4Components and Parts Lists . . . . . . . . . . . . . . . . . . . . 5–8

E19-220

E19-220B

E19-220DC

E19-220FW

2

S19-210P Installation

10/18/2012 Bradley • 215-158E Rev. K; ECN 12-05-003C

IMPORTANT

Read this installation manual completely to ensure proper installation, then file it with the owner or maintenance department. Compliance and conformity to drain requirements and other local codes and ordinances is the responsibility of the installer.

Separate parts from packaging and make sure all parts are accounted for before discarding any packaging material. If any parts are missing, do not begin installation until you obtain the missing parts.

Flush the water supply lines before beginning installation and after installation is complete. Test the unit for leaks and adequate water flow. Main water supply to the eye/face wash should be “ON” at all times. Provisions shall be made to prevent unauthorized shutoff.

The ANSI Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley plumbed emergency fixtures require a minimum of 30 PSI (0.21 MPa) flowing pressure. Flushing fluid should be tepid per ANSI Z358.1.

The inspection and testing results of this equipment should be recorded weekly to verify proper operation. This equipment should be inspected annually to ensure compliance with ANSI Z358.1.

Workers who may come in contact with potentially hazardous materials should be trained regarding the placement and proper operation of emergency equipment per ANSI Z358.1.

For questions regarding the operation or installation of this product, visit www.bradleycorp.com or call 1-800-BRADLEY.

Product warranties and service parts information may also be found under ”Products” on our web site at www.bradleycorp.com.

Installation

THIS

SIDE

UP

Packing List

••••

P.O. B

ox 3

09, M

enom

onee F

alls

, WI 5

3051

R

TEST THIS U

NIT E

ACH WEEK

Test

-oper

ate

valv

e(s)

eac

h wee

k an

d sig

n bel

ow.

Report

any

mal

funct

ions

imm

edia

tely.

Ventil

(e) w

öchen

tlich

im Te

stbet

rieb p

rüfe

n, bes

tätig

t

durch U

nters

chrif

t. Je

gliche

Störu

ng sofo

rt m

elden

.

Date

Datum

Date

Signed

Unters

chrif

t

Signe

Date

DateDat

e

Signed

Signed

Signed

DIESES G

ERÄT 1ST W

ÖCHENTLICH Z

U PRÜFEN.

ESSAI HEBDOM

ADAIRE

Test

le fo

nctio

nnemen

t des

valv

es c

haque

sem

aine

et

signe

en b

as. S

'il y

à quel

que ch

ose q

ui ne

va p

as fa

it

un rapport

imm

édia

tem

ent.

P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USATEL: 1-800-BRADLEY FAX: (262-251-5817)

http://www.bradleycorp.com

114-051

3

Installation S19-210P

Bradley • 215-158E Rev. K; ECN 12-05-003C 10/18/2012

Installation

NOTICE! Avoid cleaners containing organic solvents, alcohols, and hydrocarbons. Rinse with water after cleaning.

Supplies Required:• (3) 8m wall fasteners and bolts

• Pipe sealant

• Piping to ½" BSP water supply inlet on unit

• Piping to 1¼"–11 BSP drain outlet for eyewash

• Sign-mounting hardware

Step 1: Secure base to floor The top of the eyewash heads should be

1067mm (42”) from the floor.

1. Position the inlet drain fitting over the 1¼” drain outlet pipe from wall.

2. Using the inlet drain fitting as template, mark bolt hole locations on the wall OR install three suitable fasteners (supplied by installer) for 8m bolts in the wall at marked hole locations (see illustrations on pages 3–4).

3. Bolt the inlet drain fitting to the wall or wall fasteners using 8m bolts (supplied by installer).

4. After the inlet drain is secured, assemble the flag handle, washer and nut.

Step 3: Connect water supply1. Connect the water supply piping (supplied by

installer) to the ½" BSP inlet on the eyewash.

2. Connect the drain piping (supplied by installer) to the 1¼–11 BSP drain outlet on the eyewash.

3. Mount the safety sign to the wall using sign-mounting hardware (supplied by installer).

4. Open the water supply lines. Test for leaks and adequate water flow.

394mm (15-1/2")

184mm(7-1/4")

57mm(2-1/4")

133mm(5-1/4")

Ø 8mm(5/16")

337mm(13-1/4")

Ø 254mm (10")

102mm(4")

210mm(8-1/4")

119mm(4-5/8")

1067mm (42")Suggested

HeightTo Floor

927mm(36-1/2")

SuggestedHeight

To Floor

Wall

E19-220

E19-220B

403mm (15-7/8")

187mm(7-3/8")

102mm(4")

346mm(13-5/8")

Ø 273mm (10-3/4")

927mm(36-1/2")

SuggestedHeight

To Floor

Wall

57mm(2-1/4")

133mm(5-1/4")

Ø 8mm(5/16")

119mm(4-5/8")

1067mm(42")

SuggestedHeight

To Floor

210mm(8-1/4")

4

S19-210P Installation

10/18/2012 Bradley • 215-158E Rev. K; ECN 12-05-003C

Ø 273mm (10-3/4")

184mm(7-1/4")

425mm(16-3/4")

222mm(8-3/4")

133mm(5-1/4")

346mm(13-5/8")

102mm(4")

Wall

508mm (20")

210mm(8-1/4")

119mm(4-5/8")

1067mm(42")

SuggestedHeight

To Floor57mm(2-1/4")

Ø 8mm(5/16")

927mm(36-1/2")

SuggestedHeight

To Floor

902mm(35-1/2")

SuggestedHeight

To Floor

394mm (15-1/2")

206mm(8-1/8")

57mm(2-1/4")

133mm(5-1/4")

102mm(4")

Ø 8mm(5/16")

210mm(8-1/4")

119mm(4-5/8")

Ø 254mm (10")

337mm(13-1/4")

1067mm(42")

SuggestedHeight

To Floor

Wall

E19-220DC E19-220FW

5

Installation S19-210P

Bradley • 215-158E Rev. K; ECN 12-05-003C 10/18/2012

Parts List

Assembly of Components - E19-220 (with Plastic Bowl)

Prepack S45-1785 includes Items 1.2, 1.4, 1.5, 1.6

Prepack S45-123 includes Items 2, 1.12, 1.111

Items 1.1-1.12 come preassembled as Item 1.

Item Part No. Qty. Description

1 S39-243 1 Europe Eyewash Assembly

1.1 111-061BSP 1 Inlet Drain Fitting

1.2 124-028 1 Gasket

1.3 154-058 1 Plastic Eyewash Bowl

1.4 173-025 1 Cup Strainer

1.5 S21-071 1 Supply Stem

1.6 113-1185 1 Spacer, Drain

1.7 S05-091 1 Eyewash Yoke Assembly

1.8 107-371 2 Dust Cover

Item Part No. Qty. Description

1.9 13-006LQ 1 Pipe ½” NPT x 89mm

1.10 169-025 1 Elbow

1.11 S27-282B 1 1/2” Ball Valve with nut

1.111 110-215 1 Nut only

1.12 142-002DA 1 Lockwasher

2 128-135 1 Plastic Handle

3 114-051E 1 Safety Sign

4 204-421 1 Emergency Tag

1.6

1.5Flow Control

This End

1.4

1.3

1.2

1.1

1-1/4" - 11 BSPDrain Outlet

1.8

1.71

1/2" BSP SupplyInlet (BSP threads

are noted withblack line on

threads)

1.9

1.101.11

1.111

2

1.12

P.O. Box 309, Menomonee Falls, WI 53051

R

TEST THIS UNIT EACH WEEK

Test-operate valve(s) each week and sign below.Report any malfunctions immediately.

Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt durch Unterschrift. Jegliche Störung sofort melden.

DateDatumDate

SignedUnterschriftSigne

DateDate

Date SignedSignedSigned

DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.ESSAI HEBDOMADAIRE

Test le fonctionnement des valves chaque semaine et signe en bas. S'il y à quelque chose qui ne va pas fait un rapport immédiatement.

P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USATEL: 1-800-BRADLEY FAX: (262-251-5817)

http://www.bradleycorp.com

114-051

3

4

6

S19-210P Installation

10/18/2012 Bradley • 215-158E Rev. K; ECN 12-05-003C

Parts List

Assembly of Components - E19-220B (with Stainless Steel Bowl)

Prepack S45-1782 includes Items 1.2, 1.4, 1.5, 1.6

Prepack S45-123 includes Items 2, 1.12, 1.1119

Items 1.1-1.12 come preassembled as Item 1.

Item Part No. Qty. Description

1 S39-246 1 Europe Eyewash Assembly

1.1 111-061BSP 1 Inlet Drain Fitting

1.2 124-028 1 Gasket

1.3 187-053 1 Stainless Steel Eyewash Bowl

1.4 173-009 1 Cup Strainer

1.5 S21-071 1 Supply Stem

1.6 113-1159 1 Spacer, Drain

1.7 S05-091 1 Eyewash Yoke Assembly

1.8 107-371 2 Dust Cover

Item Part No. Qty. Description

1.9 13-006LQ 1 Pipe 1/2” NPT x 89mm

1.10 169-025 1 Elbow

1.11 S27-282B 1 1/2” Ball Valve with nut

1.111 110-215 1 Nut only

1.12 142-002DA 1 Lockwasher

2 128-135 1 Plastic Handle

3 114-051E 1 Safety Sign

4 204-421 1 Emergency Tag

1.6

1.5Flow Control

This End

1.4

1.3

1.2

1.1

1-1/4" - 11 BSPDrain Outlet

1.8

1.71

1/2" BSP SupplyInlet (BSP threads

are noted withblack line on

threads)

1.9

1.101.11

1.111

2

1.12

P.O. Box 309, Menomonee Falls, WI 53051

R

TEST THIS UNIT EACH WEEK

Test-operate valve(s) each week and sign below.Report any malfunctions immediately.

Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt durch Unterschrift. Jegliche Störung sofort melden.

DateDatumDate

SignedUnterschriftSigne

DateDate

Date SignedSignedSigned

DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.ESSAI HEBDOMADAIRE

Test le fonctionnement des valves chaque semaine et signe en bas. S'il y à quelque chose qui ne va pas fait un rapport immédiatement.

P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USATEL: 1-800-BRADLEY FAX: (262-251-5817)

http://www.bradleycorp.com

114-051

3

4

7

Installation S19-210P

Bradley • 215-158E Rev. K; ECN 12-05-003C 10/18/2012

Parts List

Assembly of Components - E19-220DC (with Dust Cover)

Prepack S45-1782 includes Items 1.2, 1.4, 1.5, 1.6

Ball Valve Kit S30-072 includes Items 1.12, 1.13, 1.14, 1.121, 2

Prepack S30-087 includes Items 1.13, 1.14, 1.121, 2

Items 1.1-1.14 come preassembled as Item 1.

Item Part No. Qty. Description

1 S39-312 1 Europe Dust Cover/Eyewash Assy

1.1 111-061BSP 1 Inlet Drain Fitting

1.2 124-028 1 Gasket

1.3 S90-009 1 Dust Cover Assembly

1.4 173-009 1 Cup Strainer

1.5 S21-071 1 Supply Stem

1.6 113-1159 1 Spacer, Drain

1.7 S05-091 1 Eyewash Yoke Assembly

1.8 269-447 1 Bumper

Item Part No. Qty. Description

1.9 161-025 1 Hex Nut

1.10 113-006LQ 1 Pipe 1/2” NPT x 89mm

1.11 169-025 1 Elbow

1.12 S27-282B 1 1/2” Ball Valve with nut

1.121 110-215 1 Nut only

1.13 153-372R 1 Ball Valve Adapter

1.14 142-002DA 1 Lockwasher

2 S08-056 1 Handle Assembly

3 114-051E 1 Safety Sign

4 204-421 1 Emergency Tag

P.O. Box 309, Menomonee Falls, WI 53051

R

TEST THIS UNIT EACH WEEK

Test-operate valve(s) each week and sign below.Report any malfunctions immediately.

Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt durch Unterschrift. Jegliche Störung sofort melden.

DateDatumDate

SignedUnterschriftSigne

DateDate

Date SignedSignedSigned

DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.ESSAI HEBDOMADAIRE

Test le fonctionnement des valves chaque semaine et signe en bas. S'il y à quelque chose qui ne va pas fait un rapport immédiatement.

P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USATEL: 1-800-BRADLEY FAX: (262-251-5817)

http://www.bradleycorp.com

114-051

1.9

1.5

Flow ControlThis End

1.4

1.3

1.2

1.1

1.10 1.12

6

1.14

17

1.11

1.8

HANDLE NOTE: Close the cover andput the pin through

the clip to keep closed.

1.6

1.7

1-1/4" - 11 BSPDrain Outlet

1/2" BSP SupplyInlet (BSP threads

are noted withblack line on

threads)

1.121

1.13

2

8

S19-210P Installation

10/18/2012 Bradley • 215-158E Rev. K; ECN 12-05-003C

Parts List

Assembly of Components - E19-220FW (with Eye/Face Wash)

Prepack S45-123 includes Items 2, 1.12, 1.111

Items 1.1-1.12 come preassembled as Item 1.

Item Part No. Qty. Description

1 S39-421 1 Europe Eye/Face Wash Assembly

1.1 111-061BSP

1 Inlet Drain Fitting

1.2 124-028 1 Gasket

1.3 154-058 1 Plastic Eyewash Bowl

1.4 173-025 1 Cup Strainer

1.5 113-1150 1 Supply Stem

1.6 S05-091P 1 Eyewash Yoke Assembly

1.7 S45-2453 1 Service Kit EFW - Black Sprayheads

Item Part No. Qty. Description

1.8 S53-063 2 Dust Cover

1.9 113-006LQ 1 Pipe 1/2” NPT x 89mm

1.10 169-025 1 Elbow

1.11 S27-282B 1 1/2” Ball Valve with nut

1.111 110-215 1 Nut only

1.12 142-002DA 1 Lockwasher

2 128-135 1 Plastic Handle

3 114-051E 1 Safety Sign

4 204-421 1 Emergency Tag

2

1.12

P.O. Box 309, Menomonee Falls, WI 53051

R

TEST THIS UNIT EACH WEEK

Test-operate valve(s) each week and sign below.Report any malfunctions immediately.

Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt durch Unterschrift. Jegliche Störung sofort melden.

DateDatumDate

SignedUnterschriftSigne

DateDate

Date SignedSignedSigned

DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.ESSAI HEBDOMADAIRE

Test le fonctionnement des valves chaque semaine et signe en bas. S'il y à quelque chose qui ne va pas fait un rapport immédiatement.

P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USATEL: 1-800-BRADLEY FAX: (262-251-5817)

http://www.bradleycorp.com

114-051

3

4

1.6

1.5

1.4

1.3

1.2

1.1

1-1/4" - 11 BSPDrain Outlet

1.8

1.71

1/2" BSP SupplyInlet (BSP threads

are noted withblack line on

threads)

1.9

1.101.11

1.111