IIEE UAE CHAPTER · · 2014-11-14IIEE UAE CHAPTER v INTRODUCTION ... o concerns the low-voltage...
Transcript of IIEE UAE CHAPTER · · 2014-11-14IIEE UAE CHAPTER v INTRODUCTION ... o concerns the low-voltage...
1
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir MachhiwalaBuilding a New Electric World
IIEE UAE CHAPTER
v INTRODUCTION v EVOLUTIONv FORMS OF CONSTRUCTIONv TYPE TESTINGv PRODUCTS
PDF created with pdfFactory Pro trial version www.pdffactory.com
2
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The low voltage electrical
switchboard
A vital link for electrical distribution
PDF created with pdfFactory Pro trial version www.pdffactory.com
3
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The low voltage switchboard
A vital link for electrical distribution
n and to provide a continual balance between:o the needs of safety and availabilityo and the constraints of reliability and maintenability of the installation.
n To satisfy the increasing needs of safety of people and equipment and availability of electrical power : its realization is not improvised…
Safety
Maintainability
Reliability
Availability
PDF created with pdfFactory Pro trial version www.pdffactory.com
4
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
DEFINITIONS:
WHAT IS SWITCHBOARD:
According to Institute of Electrical Engineers (IEE)
Is an assembly of switchgear with or without instruments. But the term does not apply to group of local switches on a final circuit.
PDF created with pdfFactory Pro trial version www.pdffactory.com
5
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
DEFINITIONS:
WHAT IS SWITCHBOARD:
According to Manufacturer
Is an assembly consisting of one or more vertical sections joined together to form a free-standing cubiclized, floor fixing assembly which is extensible at either ends
PDF created with pdfFactory Pro trial version www.pdffactory.com
6
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
DEFINITIONS:
WHAT IS SWITCHGEAR:
An assembly of a main and auxiliary apparatus for operation, regulation, protection or other control of electrical installation.
PDF created with pdfFactory Pro trial version www.pdffactory.com
7
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The principal types of distribution board is referred according to specific application and they are:
n Main (General) Distribution Board (MGDB)
n Local (General) Distribution Board
n Sub - Distribution Board
n Process-control Distribution Board (MCC)
n Final Distribution Board
The types of low voltage electricalswitchboardThe principal types of low voltage distribution board is referred according to the specific application
PDF created with pdfFactory Pro trial version www.pdffactory.com
8
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Low voltage network
Main LV switchboard
Sub distribution board
Final distribution board
Level 1a
Level 1b
Level 2
Level 3
Loads
PDF created with pdfFactory Pro trial version www.pdffactory.com
9
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
A complete L.V.Offer
n Main Switchboards
n Sub-Main Switchboards
n Final Distribution Boards
n Busways
n Intelligence & Services
PDF created with pdfFactory Pro trial version www.pdffactory.com
10
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Modular Switchboards
n This modular design brings much clearness to the switchboard :o incoming unito current distribution unitso feeder units o distribution units o connection unitso communication units
PDF created with pdfFactory Pro trial version www.pdffactory.com
11
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
BloksetHigh Dependability Switchboards and MCC’s upto 6300A
nA system for all your applications requiring a high level of dependabilityElectrical Distribution and MCC– Fixed and Withdrawable type for both incomer and outgoingTargeted at High Commercial, Industrial and Infrastructure Markets
nA modular structureFor low-voltage switchboards designed to meet local standards, practices and requirements.
nFully TYPE-TESTED Enclosure system complying with IEC 60439-1, IEC 60947-2, IEC 60947-4, IEC 60529, etc.n Tested for Internal Arc Containment to AS 3439-1.nSheet thickness - 2mm thick, up to Form-4b, IP54nColor : RAL 9002/ 7016
PDF created with pdfFactory Pro trial version www.pdffactory.com
12
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Local (General) Distribution Board, Sub-main Distribution Board, Process Control Distribution Board,
Functional Switchboards and MCC’s up to 3200AnFunctional system used to build Main & Secondary low voltage switchboards up to 3200A.
Electrical Distribution and Motor Control – FixedTargeted at Buildings and Residential Markets.
nA modular structurePrisma Plus adopts a functional concept with standard configurations for Distribution Feeders and Motor Starters.
New cost effective solution evolved with the latest switchboard needs.
nFully TYPE-TESTED complying with IEC 60439-1, IEC 60947-2, IEC 60947-4, IEC 60529, etc.
n 1.5mm thick, Form-4b, IP55nColor : RAL 9001
PDF created with pdfFactory Pro trial version www.pdffactory.com
13
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Final Distribution BoardFinal Switchboards with Pan Assembly - suitable for incomer upto 250A
nFunctional system used for final switchboards Electrical Distribution with upto 54 ways of outgoing tp breakersTargeted at Buildings and Residential Markets.
Zinc coated metal sheet enclosure upto 1.2mm sheet thickness Available in both Flush and Surface mounted options Available in both Curved door and Flat door versions
Aesthetically designed enclosure – can be mounted in the main hall
Short circuit withstand upto 17KA rms for 200mS
nFully TESTED and ASTA certified, complying with IEC 60439-3.nIndex of Protection – IP31 as per IEC 60529nColor : RAL 9002
PDF created with pdfFactory Pro trial version www.pdffactory.com
14
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The 4 functions of an electrical
switchboard
For Groupprotectionand device control,
Inform the end-user on the status of the installations,
Protect the switchboard end-user against the risk of accidents (direct & indirect contact)
Research & Evolve with the activity.
PDF created with pdfFactory Pro trial version www.pdffactory.com
15
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
n Group Protection & Device Control (switchgear control)
o Relates to all switching operations in normal service conditions for energizing or de-energizing a part of the system or installation, or an individual equipment, etc.
PDF created with pdfFactory Pro trial version www.pdffactory.com
16
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
n Isolation - To inform the end-user on the state of its installation (verification of the contacts of the isolating device are in fact, open)
o All poles of the circuit
o It must be provided with a means of locking open with a key in order to avoid an unauthorized reclosure, inadvertent
o It must conforms to a recognized standard (e.g. IEC 60947-3)
PDF created with pdfFactory Pro trial version www.pdffactory.com
17
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
n Electrical Protection
o Protection of circuit elements against thermal and mechanical stresses to short-circuit currents;
o Protection of persons in the event of insulation failure (direct and indirect contact).
o Protection of appliance and apparatus being supplied
PDF created with pdfFactory Pro trial version www.pdffactory.com
18
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The minimum requirements to guarantee the reliability of a LV switchboard
First of all, it must comply with standards :
n Structural standards for incorporated switchgear :o IEC 60947-1 : general provisionso IEC 60947-2/3 : circuit-breakers/switcheso IEC 60269-1 : low voltage fuses.
n Switchboard construction standard :o IEC 60439-1 : low voltage switchgear assemblies.
n Installation standards :o IEC 60364 : buildings electrical installationo specific standards and rules to each country.
PDF created with pdfFactory Pro trial version www.pdffactory.com
19
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The IEC 60439-1 standard
n The IEC 60439-1 standard gives general rules for switchboards construction to meet with safety and availability needs required by the application
o guarantees the minimum level of safety of people and equipmento concerns the low-voltage switchgear and controlgear assemblies for the
power distribution and control.o states :
- the service conditions (temperature...)- the construction requirements (IP, IK, forms,...)- the tests requirements
n Conformity to the standard is, for the end user, an insurance on switchboard realization quality.
PDF created with pdfFactory Pro trial version www.pdffactory.com
20
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
DESIGN CRITERIA RELATING TO BUSBAR SIZES FOR SWITHCBOARD TO MEET REQUIREMENT OF BS EN 60439-1
n In any electrical circuit, some electrical energy is lost as heat, which if not kept within safe limits, may impair the performance of the system.
PDF created with pdfFactory Pro trial version www.pdffactory.com
21
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
BUS BARS
Like all other equipment in the system have to be able to withstand forces attributed from the big capacity of modern electrical plant and machinery that is controlled by the system
PDF created with pdfFactory Pro trial version www.pdffactory.com
22
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
It is essential that the material used in the switchboard to have the best possible mechanical properties and be designed to operate with the temperature limits laid down in BSEN G0439-1 and other (national or international) standards. The conductor material should therefore have the following properties, if it is to be produced efficiently and have low running costs from the point of view of energy consumption and maintenance.
PDF created with pdfFactory Pro trial version www.pdffactory.com
23
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
a. Low electrical and thermal resistanceb. High mechanical strength on tension, compression and shear.c. high resistance to fatigue failure.d. Low electrical resistance of surface films.e. Ease of fabricationf. High resistance to corrosion.
This combination is met best by copper.
The mechanical properties are:
PDF created with pdfFactory Pro trial version www.pdffactory.com
24
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
SAMPLE BUSBAR SIZE CALCULATION
PDF created with pdfFactory Pro trial version www.pdffactory.com
25
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
SAMPLE BUSBAR SIZE CALCULATION
PDF created with pdfFactory Pro trial version www.pdffactory.com
26
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
SAMPLE BUSBAR SIZE CALCULATION
PDF created with pdfFactory Pro trial version www.pdffactory.com
27
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
SAMPLE BUSBAR SIZE CALCULATION
PDF created with pdfFactory Pro trial version www.pdffactory.com
28
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
SAMPLE BUSBAR SIZE CALCULATION
PDF created with pdfFactory Pro trial version www.pdffactory.com
29
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Cont’d.
PDF created with pdfFactory Pro trial version www.pdffactory.com
30
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Figure 7.
Skin effect ratio
1.08
38.124
PDF created with pdfFactory Pro trial version www.pdffactory.com
31
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
GUIDE TO FOMS OF SEPARATION IEC 60 439-1
Low Voltage Switchgear and Controlgear Assemblies:BS EN 60439-1: 1994 (IEC 439-1)Including Amendment No. 1 : 1995
PDF created with pdfFactory Pro trial version www.pdffactory.com
32
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
EIEMA GUIDE TO FORMS OF SEPARATION
FUNDAMENTAS OF FORM OF SEPARATION
BS EN 60439 Part 1/IEC 60439-1 describes a system classifying the various forms of separation to be provided principally to:
n Protection against contact with live parts belonging to the adjacent functional units
n Limitation of the probability of initiating arcing faults.n Protection against the passage of solid foreign bodies from one unit of an
assembly to an adjacent unit.The standard includes definitions relating to Assemblies
PDF created with pdfFactory Pro trial version www.pdffactory.com
33
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
ACHIEVING SEPARATION
Separation can be achieved in several ways depending on application and requirements for maintenance:PVC sleeving, wrapping or plastic coating of conductors
a.Insulated terminal shields or PVC boots.
b.Rigid insulated barriers or partitions.
c.Compartments formed from earthed metal.
d.A device’s integral housing.
PDF created with pdfFactory Pro trial version www.pdffactory.com
34
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
In general, the price of the assembly will increase with increased level of separation and/or types of construction.
Manufacturer is likely to assume the most cost effective solution where specific requirements are not specified or identified.
PDF created with pdfFactory Pro trial version www.pdffactory.com
35
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Key Throughout
PDF created with pdfFactory Pro trial version www.pdffactory.com
36
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
37
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
38
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
39
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
40
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
41
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
42
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
43
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
44
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
45
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
46
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
47
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
48
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
49
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
50
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
51
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
52
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
53
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
SAFE WORKING WITH ADJACENT EQUIPMENT ENERGISED
PDF created with pdfFactory Pro trial version www.pdffactory.com
54
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
55
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Form-1 No internal separation
Internal separation of assemblies
PDF created with pdfFactory Pro trial version www.pdffactory.com
56
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Form-2 Separation of busbars from functional units
Form-2a Terminals not separated from busbars
Form-2b Terminals separated from busbars
Partition
Internal separation of assemblies
PDF created with pdfFactory Pro trial version www.pdffactory.com
57
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Form-3Separation of busbars from functional units +
Separation of functional units from one another +
Separation of terminals from functional units
Form-3a Terminals not separated from busbars
Form-3b Terminals separated from busbars
Internal separation of assemblies
PDF created with pdfFactory Pro trial version www.pdffactory.com
58
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Form-4 Separation of busbars from functional units +
Separation of functional units from one another +
Separation of terminals from functional units
Form-4a Terminals in same compartment as associated functional unit
Form-4b Terminals not in same compartment as associated functional unit
Internal separation of assemblies
PDF created with pdfFactory Pro trial version www.pdffactory.com
59
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
TTA & PTTA
n Type Tested Assembly (TTA)It is a LV switchgear and controlgear ASSEMBLY conforming to an established system without deviations, which are likely to significantly influence the performance, from the typical ASSEMBLY, verified to be in accordance with this standard.
A fully type tested assembly has to undergo a series of seven tests.
n Partially Type Tested Assembly (PTTA)A LV switchgear and controlgear ASSEMBLY containing both type tested and non type tested arrangements, provided that the latter are derived from type tested arrangements which have complied with the relevant tests.
PDF created with pdfFactory Pro trial version www.pdffactory.com
60
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Fully Type Tested Assemblies,complying with standard IEC 60 439-1
PDF created with pdfFactory Pro trial version www.pdffactory.com
61
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The tests of standard IEC 60439-1
n 7 type tests on the prototype:o n°1 - temperature rise limitso n°2 - dielectric propertieso n°3 - short-circuit withstando n°4 - protective circuit
effectivenesso n°5 - clearances and creepage
distanceso n°6 - mechanical operationo n°7 - degree of protection
n 3 routine tests :o n°8 - overall inspection :
cabling, electrical operationo n°9 - insulation/dielectric testo n°10 - protection measures .
They guarantee that the switchboard complies with standard and confirm its characteristics:
PDF created with pdfFactory Pro trial version www.pdffactory.com
62
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
7 type tests performed by the manufacturern The aim of these tests is to confirm the switchboard characteristics.
n The 7 type tests are carried out on most difficult and unfavourable system configurations. The assembled and cabled switchboards are made up of their usual components, connection system…, equipped with Merlin Gerin and Telemecanique switchgear and assemblied and installed according to inductrial standards
n The tests are conducted either in approved laboratories (Asefa, Kema, etc,…), which are independant laboratories.
PDF created with pdfFactory Pro trial version www.pdffactory.com
63
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Test n°1(8-2-1) :Temperature rise limits
n Guarantees the safety and reliability of the switchboard, by avoiding problems such as :
o connection damageso reduction in insulation performanceso risk of burn for maintenance operators o electronic components damageso faulty operation of the devices :
inopportune release
PDF created with pdfFactory Pro trial version www.pdffactory.com
64
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Test n°2(8-2-2) : dielectric properties
n Guarantees the switchboard safety and reliability , to avoid problems such as :
o electrical arc generationo insulation performance decreasingo connection damages
PDF created with pdfFactory Pro trial version www.pdffactory.com
65
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Test n°3(8-2-3) : short-circuit withstand
n This test simulates an incident which could occur on siten Withstanding the short-circuit currents is :
o to avoid danger (rupture and projections of components, arc generation and propagation outside the switchboard,...)
o it also means the installation can be quickly put back into operation after the incident
Complying limits :
the main conductors and the insulating parts must retain their insulation and mechanical withstand characteristics (lenght, cross-section, dielectric properties,…).
PDF created with pdfFactory Pro trial version www.pdffactory.com
66
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Test n°4(8-2-4) : effectiveness of the protective circuit
n The effectiveness of the protective circuit is verified by two tests :o resistance measurement of the connection between the exposed conductive
parts and the protective circuitso short-circuit withstand performed between the protective conductor and
the nearest phase conductor.
PDF created with pdfFactory Pro trial version www.pdffactory.com
67
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Test n°5(8-2-5) : clearance and creepage distances
n Clearance control : shortest distance between two conductive parts.
n Creepage distance control : shortest distance along the surface of an insulating material between two conductive parts.
PDF created with pdfFactory Pro trial version www.pdffactory.com
68
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
69
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
PDF created with pdfFactory Pro trial version www.pdffactory.com
70
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Test n°6(8-2-6) : mechanical operation
n Endurance of material, guaranteeing the longevity of the various mechanisms.
PDF created with pdfFactory Pro trial version www.pdffactory.com
71
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Test n°7(8-2-7) : degree of protection
n The tests carried out define the capacity of an equipped switchboard to :o protect persons against contact with live partso protect equipment against penetration of solid objects and liquidso protect equipment against external influences such as impacts (shocks).
PDF created with pdfFactory Pro trial version www.pdffactory.com
72
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
The IP degrees of protection :(IEC 60529/EN 60529)
n 1st digit : level of protection against penetration of solids
o protection of personso protection against solids.
n 2nd digit : level of protection against penetration of liquids
o protection against liquids.
PDF created with pdfFactory Pro trial version www.pdffactory.com
73
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
o The IK testing requirement is already included in standard IEC 62208 and IEC 62262.
o It will also be included in reference standard IEC 60439-1 in the.near future.
o It is also to be included in the next amendment of installation standard IEC.60364-5-551.
o It lays the correct foundation for judging the Real Strength of the LV.Switchboards rather than just the perceived strength,
– Real strength = technical criteria.– These criteria are the only objective ones because they can be quantified
and proven by tests.– Perceived strength = visual/tactile/audio criteria.
– These criteria are subjective and therefore subject to debate because they depend on the personal judgement of each person.
Impact Testing as per IEC Standards - The IK code becomes a standard reference
PDF created with pdfFactory Pro trial version www.pdffactory.com
74
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
3 routine tests performed by the panelbuildern The 3 routine tests, easily and rapidly performed, must be carried out by the
panelbuilder. :o overall inspection according to the mounting instructions and technical
documents (right device ratings, tightening torques)o insulation checking by a dielectric testo checking of protective measures and of the electrical continuity of the
protective circuits.
n They complete the 7 manufacturer type tests and guarantee professionalism and responsibility of panelbuilder.
PDF created with pdfFactory Pro trial version www.pdffactory.com
75
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Panelbuilder and manufacturer, together to offer maximum safety and reliabilityn Manufacturer :
o products tested in real configurations o detailed instructions for faultless construction.
n Installer :o it has to its disposal informations, by means of tools of switchboard
assembly and installation guide (catalogues, internet), software designso confidence in products and switchboards system, the result of many years
of experience
n A shared success :o this complementarity must fall under the duration to consolidate our
professionalism.
PDF created with pdfFactory Pro trial version www.pdffactory.com
76
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
IEC 60439-1 standard : an international influence
n IEC 60439-1 : the same standard for all the professionals of switchboards
UL
IEC
IEC
IEC
IEC
IEC
PDF created with pdfFactory Pro trial version www.pdffactory.com
77
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Category of Circuit Breaker
n Category A : Here the breakers have no deliberate delay in the operation of the “instantaneous”short circuit magnetic tripping device & are generally moulded-case type circuit breakers
n Category B :Here, in order to discriminate with other circuit breakers on a time basis, it is possible to delay the tripping of the CB, where the fault-current level is lower than that of the short-time withstand current rating (Icw) of the CB. This is generally applied to large open-type circuit breakers and to certain heavy-duty moulded-case types. Icw is the maximum current that the B category CB can withstand, thermally and electrodynamically, without sustaining damage, for a period of time given by the manufacturer
PDF created with pdfFactory Pro trial version www.pdffactory.com
78
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
OVER CURRENT PROTECTION
Fundamentals and Application:
n Costn Coordination Capabilityn Safety
Decisions rely on applications of available technology and solidunderstanding of overcurrent protection fundamentals.
PDF created with pdfFactory Pro trial version www.pdffactory.com
79
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Facts about Over Current:
n About the various types of high-and-low-level overcurrentn How overcurrent occurs in a typical systemn How often they can occur
Myth: Some believe that high-level bolted faults are common occurences, that there is a high probability of short circuits occuring in a given circuit .
Fact: The majority of overcurrents are over-load and low-level arcing faults. Only a fraction are high-level bolted fault.
PDF created with pdfFactory Pro trial version www.pdffactory.com
80
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
OVER CURRENT PROTECTION DEVICES
Purpose of overcurrent device:
n To provide protection to service entrancen Feedern Branch circuit conductorsn Equipment
PDF created with pdfFactory Pro trial version www.pdffactory.com
81
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
BASIC TYPES OF OVERCURRENT DEVICES
n Fusible Switches - Protection of circuit by fusing / meltingopen its current-responding element.
PDF created with pdfFactory Pro trial version www.pdffactory.com
82
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
n Circuit Breaker - A mechanical switching device design to open and close a circuit by non-automatic means and to open a circuit automatically on a predetermined overcurrent without injury to itself when properly applied.
PDF created with pdfFactory Pro trial version www.pdffactory.com
83
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Kinds of Circuit Breaker
n Air Circuit Breaker A circuit breaker in which the contacts open and close in air at atmosphericpressure.
n Moulded Case Circuit Breaker
A circuit breaker having a supportinghousing of moulded insulating materialforming an integral part of the circuit breaker.
n Miniature Circuit Breaker
PDF created with pdfFactory Pro trial version www.pdffactory.com
84
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
4 Types of Molded Case Circuit Breaker
n Non Current Limiting Slower oparation due to large and heavy blades
PDF created with pdfFactory Pro trial version www.pdffactory.com
85
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
n Semi-current limiting Same basic component but the bladesare much thinner. Movable contacts are smaller and ligher. Move more freely.
PDF created with pdfFactory Pro trial version www.pdffactory.com
86
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
n Current limiting Limits current in less than one half cyle. Same basic component as semi-current limiting with the addition of‘O’ shape magnet or iron doughnut which completelysourrounds the movable and stationary contact areas where the current is flowing in opposite direction. This magnefies and intensifies the forces acting on theblades and arc to provide even more opening speed and force.
PDF created with pdfFactory Pro trial version www.pdffactory.com
87
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
n Electronic Circuit Breaker Delaying before trip to withstand high levels of current before tripping
PDF created with pdfFactory Pro trial version www.pdffactory.com
88
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
479
3953P : 7864P : 1016
3953P : 4414P : 556
439322
3P : 2884P : 358
278
The smallestin the world
Air Circuit Breaker
PDF created with pdfFactory Pro trial version www.pdffactory.com
89
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
5.0 P
6.0 H6.0 A 6.0 P
Type of current protection
2: Distribution L, I
5: Selective L, S, I
6: Selective and earth-fault protection L, S, I, G
7: Selective with earth-leakageprotection L, S, I, V
Micrologic 2. 0 A
type of measurementversion
type of current protection
A P H
2.0 A
5.0 A
7.0 P
5.0 H
7.0 H7.0 A
sans
2.0
5.0
The Micrologic Control Unit
PDF created with pdfFactory Pro trial version www.pdffactory.com
90
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Protection offer for houses
MCBs RCDs
n N
T
« Standard » design
n RCD 2P 63A
n N
T
n RCD 4P : 25, 40, 63 A
n3P+Nn 1P+N 3P
n
6 – 40 A , 6 KA , C curve Terminal Size upto 25²mm
As per IEC 60898
& 4P& 2P n1PRCD 2P
25A, 40A, 63A- 30, 100, 300mATerminal size upto 35²mm
As per IEC 61008
PDF created with pdfFactory Pro trial version www.pdffactory.com
91
Presentation EN
=SE= Gulf/Marketing/LV Equipment/Mudassir Machhiwala
Fundamental Characteristics of a Circuit Breaker
n Rated Operational voltage (Ue)n Rated current (In) – Maximum value of current the circuit breaker can carryn Frame-size rating – corresponds to the highest current settingn Over load trip-current setting (Im)n Rated Short-circuit breaking capacity (Icu) – Highest (prospective) value of
current the breaker is capable of breaking without damagen Rated Insulation Voltage (Ui) – dielectrical test voltage.n Category and rated short-time withstandn Rated making capacity (Icm) – Highest instantaneous value of current can
establish at rated voltagen Rated service short-circuit breaking capacity (Ics) – maximum fault-current
can successfully interrupt without being damage.
PDF created with pdfFactory Pro trial version www.pdffactory.com